Datasheet

MGE G3 SA (With Analog Outputs)


Multimeter

Multimeter for three or single phase mains with more


than 50 electrical variables, nonvolatile bulk storage
memory, digital and analog outputs. The instrument
has three alphanumeric LCD displays with easy
visualization. Furthermore, there are harmonic
th
measurement, up to 127 order, THD for current and
voltage and waveform capture. All parameters can be
configured through keyboard or software, which
follows the instrument and allows view all variables,
harmonics spectrum and waveform.

Characteristics
Three alphanumeric LCD displays with easy visualization
Waveform capture in the Modbus buffer for all three phases (current and voltage)
Free included configuration and monitoring software with the instrument
Easy configuration through keyboard or software
Universal three phase connection, balanced and unbalanced load, or single phase.
Serial communication RS 485 protocol Modbus RTU and RS 232 for local configuration
th

THD measurement for current and voltage. Harmonics (up to 127 ) measurements, which can be viewed
through software in form of table or histogram
Nonvolatile Bulk storage memory, supports up to 48 hours without power supply with correct time register.
This functionality register the date, time and the variables configured (e.g. if it was chosen 12 variables,
sampling time 15 minutes, it is possible to store 40 days). Through the configuration software it is possible
read, salve and configure the bulk memory.
Universal auxiliary supply 85...265VAC/90...300VDC
Protection degree IP50 (housing) and IP20 (connectors)
7 digital outputs configurable though software + 1 for Failure Signaling.
4 analog outputs configurable through software
Accuracy class 0,5%

Electrical Tests

Technical data
Input
Voltage (Vn)
Current (In)

0500VAC phase-phase
1A , 5A

Signal limit

U = 10120%
I = 10...120%

Consumption

Input signal voltage:


Input signal voltage:

Nominal
frequency
Overload

Auxiliary supply

Mechanical tests
1mA.
0,2VA.

Analog outputs

Permanent: 1,5 x Un ; 2 x In
Short time: 4 x U/1s; 50 x I/1s
Maximum: 250A /1s
85 265VAC/90300VDC
Consumption ~ 6VA

8 digital outputs (open collector):


2 ative energy pulse
(1...5000 pulses / h)
5 for alarm configurable though
software
1 fail resume

Construction and mounting


Housing

Plastic anti-flame UL94-VO.

Fastening

Pair of clamps

Protection degree

IP50 housing
IP20 connectors

Weight

~ 0,45 kg

Climatic conditions
-20...+60C
-40...+80C

Maximum voltage: 24Vcc


Maximum current: 20mA

Relative humidity

75%

4 analog outputs
0 20mA RC 500 Ohm
0 10V RC 100 kOhm

Connections diagrams Input signal

Input:
Frequency:
Additional error input 1,2xI
or 1,2xU

Auxiliary supply

Acceleration 2g frequency 5..150Hz

Storage temperature

Error limit

Temperature error

Acceleration 30g duration 11ms

Vibration

Operating temperature

Influence variables

Linearity deviation

Impact

50; 60 Hz 10%

Outputs
Digital outputs

2,5kV/1 min 60 Hz between all


circuits

Test voltage

0,5%
I = 10%...100%;
U = 10%...100%
U = 10120%
I = 10...120%
0,2%
0,2%
(included in the error limit)
0,2%/10 K;
Nominal Temperature 25C
85 265VAC/90300VDC

Connections diagrams Auxiliary supply and


RS 485

Mounting Instructions
The installation must regard the climatic conditions. It is
important verify the vibration, dust, temperature and
humidity, which must be in the specified limit. The
mechanical fastening in the panel door is done through a
pair of clamps, which is included with the instrument. The
connection of the input voltage, auxiliary supply and RS 485
should be done though pin terminal. The connections of the
input current should be done though lug terminal.

User guide
Caution
Be sure that all connected voltage and current are
compatible with the technical specification and if the
connection are in accordance with the connections
diagrams.

Dimensional (mm)

Verify the connection diagrams and user manual to


configure the instrument. Configure the PT ratio and the CT
primary, connection, and communication (address, baud
rate and byte are according to the local installation

Product specification
MGE G3 SA

N 0 0 4 0 3

Nominal frequency
50 Hz
60Hz
Connection (Universal)
Monofsica
Current signal
1A
5A
Voltage signal
63V (fase/neutral) / 110V (phase/phase)
127V (fase/neutral) / 220V (phase/phase)
254V (fase/neutral) / 440V (phase/phase)
Auxiliary supply
85265VAC e 90300VDC
Analog outputs
4 outputs 0....10V
4 outputs 0/4.....20mA
Additional information
Standard configuration:
Default configuration, class 0,5%.
Special configuration
Inform a special configuration

1
2
4
1
2
1
2
4
3
1
2
1
C

Example:
Frequency:60Hz
Input current: 5A
Input voltage: 0440Vca (phase-phase)
Auxiliary supply:
85265VAC/90300VDC
Analog output: 0.20mA
Standard Configuration
Code: N004032424321

Contact
ABB Ltda.
Avenida dos Autonomistas, 1496
Osasco So Paulo - Brazil
Zip code 06020-902
Telephone 0800 014 9111
Email: abbatende@br.abb.com

Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. W ith regard to purchase orders,
the agreed particulars shall prevail. ABB BR
does not accept any responsibility whatsoever
for potential errors or possible lack of
information in this document.
CopyRight 2012
All rights reseverd

You might also like