Professional Documents
Culture Documents
Surachai Chaitusaney
I.
INTRODUCTION
c
978-1-4577-2119-9/12/$26.00 2011
IEEE
1645
I pd ,ref
d
1
V pq
2 Vp
3 V pq V pd
Pref
Qref
d
Iinv
, ref
d
Iinv
I dp
I qp ,ref
q
Iinv
, ref
q
Iinv
abc
U PWM
, ref
I qp
dq
I inv
, ref ,lim
dq
I inv
,ref
dq
I inv
, ref
dq
Iinv
,ref ,lim
dq
Iinv
, sat
abc
I inv
, ref
Power controller
By using the set point of output power and the feedback
voltage, the reference current is computed in the Synchronous
Reference Frame (SRF) as shown in Fig. 2.
In the SRF, the reference current is calculated from the
reference three-phase complex power by (1).
I dp ,ref
q
I p ,ref
2
=
3 Vd
V pd
V pq
( ) ( )
2
+ V pq
V pq Pref
V pd Qref
(1)
q
I inv , ref
I dp , ref
=
I qp , ref
I d I pd
+ inv
q
I inv
I qp
2 f c
=
+
s
2 f c
I dp ,ref
q
I p ,ref
I d I dp
+ inv
q
I inv
I qp
(3)
1646
V pabc
(2)
q
I inv,ref
abc
I inv
GPR = k p +
2ki
s + 2
2
(4)
abc
U PWM
, ref
V pabc
, ref
V pabc
I abc
p
abc
I inv
, ref
abc
I inv
, ref ,lim
-Ithres
abc
Iinv
, sat
abc
Iinv
, ref
abc
I inv
, ref , lim
L
N
Reset
I inv,ref =
Pref jQref
3V p*
+ jC f
Vp
3
(5)
1647
Va1
Va0
Va2
Phase B Phase C
Fault
instant
Pp jQ p
V p*
= V pYpp +
q =1, p q
YpqVq
p = 1, n q p (6)
k=k+1
Bus count p=1
PV bus?
Yes
Q kp +1 = imag V p*
( )
I abc = AI 012
(7)
a ,
a2
1
3
a= + j
2
2
(8)
1648
n
k
k
V p Y pp + Y pqVq
q =1
p q
slack bus?
Yes
No
Yes
n
1 Pp jQ p p 1
YpqVqk +1 YpqVqk
V pk +1 =
Y pp V * k
q =1
q = p +1
( )
Calculate change in
voltage of bus p?
V pk = V pk +1 V pk
V pk +1 =
V pk > max V k ?
p 1
n
1
I inv, sat YpqVqk +1 YpqVqk
Y pp
q =1
q = p +1
Yes
Set max V k = V pk
No
p=p+1
The end bus?
p > n?
Yes
No
Replace V pk by V pk +1
p = 1, n p s
Yes
No
1 1
A = 1 a 2
1 a
Yes
Q p = Q pk +1
PQ bus?
VApositive p.u.
Bus 2
0.820.02
I Apositive
I Azero
0.472.99
Bus 3
rad
rad
4.48 0.98
Bus 4
0.42 0.06
rad
I Anegative
rad
0.81 0.39rad
IF
4.182.08
rad
1.412.99rad
ing IBDG. However, the increases are small (48.8 (A) in phase
B and 48.15 (A) in phase C) because the power of IBDG is
small and the contributed current is limited due to the current
limiter in the control system of the IBDGs inverter. The peak
values of fault currents after installing IBDG are 1090 (A) in
phase B and 945 (A) in phase C.
It is noted that during the unbalanced fault, phase currents
contributed by IBDG are still symmetrical with the peak phase
value of 2300 (A) as shown in Fig. 13. This is because the
inverter responses to only the positive-sequence component of
the voltage at Bus 4. Additionally, the inverter current is
limited in the SRF.
B. Results from using the proposed algorithm
The equivalent negative and zero-sequence impedances of
the system viewed from Bus 3 are identical to (0.05+j0.08)
p.u. According to the sequence network connection in Fig. 9,
these two impedances and three times of the fault impedance
(3ZF) can be replaced by an equivalent impedance of
(0.06+j0.07) p.u. It is connected to the faulted bus (Bus 3) in
the positive-sequence network for applying the algorithm in
Fig. 10. To easily compare with the results from the simulation
in Subsection IV.A, the load is also modeled as a constant
impedance with respect to the nominal voltage. Results
obtained from the program, that uses the proposed algorithm,
are tabulated in Table I.
CONCLUSION
1649
APPENDIX
Parameters of the simple system in Section 4:
1650