Technical specification
CALL US TODAY
1-888-POWER-58
NOTES
1. With 4% engine governing.
2. After 10 minutes.
3. Generator de-rate may apply. Check with factory.
4. User adjustable.
5. Any device connected to the analogue input must be fully
floating (galvanically isolated from ground), with an
insulation strength of 500V ac.
6. The CT phase position should be the same as the droop
CT.
7. Non condensing.
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
Design Detail
Stator Voltage
Sensing
PMG
Droop
Hand
Trimmer
Potential
Divider &
Rectifier
Low Hz
Detection
Synchronising
Circuit
Reference
Voltage
Analogue
Input
Mixer
OR
Current
Limit
Input
Amp
Power
supply
Ramp
Generator
Level
Detector &
Driver
Power
Control
Devices
Over
Excitation
Detector
Stability
Circuit
Exciter
Field
The Current Limit input and the output from the Stator
Voltage Sensing circuit are applied to the OR circuit. This
determines which sensed input should be used for control.
The highest input takes priority.
CALL US TODAY
1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
P4 XX X 3
Trim
K1-K2
Power isolation link
(normally fitted)
A1
A2
S1
S2
Droop
Volts
MX342
-2
EXC.
TRIP
HZ CAL
2 2 1
I Lim
1
2
3
4
5
6
7
Sensing links
Current Limit
CT Input
(VS1 VS2)
Stability Selection Switch
0 = < 90kW
1 = 90-550kW
2 = 550-2000kW
3 = > 2000kW
LED
Stability
UFRO
FUNCTION
DIRECTION
VOLTS
STABILITY
UFRO
DROOP
VTRIM
EXC TRIP
I LIM
HZ CAL
WARNING!
CALL US TODAY
1-888-POWER-58
REQUEST A QUOTE
parts@genpowerusa.com
SHOP ONLINE
www.genpowerusa.com
STABILITY ADJUSTMENT