Professional Documents
Culture Documents
(Per unit reactances (or impedances) remain unchanged whether referred to the high
voltage or the low voltage side of a transformer. As a result of this, the turns ratio is not
included in the impedance diagram representation of the power system. The above
example illustrates this point.)
Problem#4
A Y-connected synchronous generator rated 100 MVA, 13.2 kV has a rated impedance of
R = 5% and XS = 80% per unit. It is connected to a j10 transmission line through a
13.8/120 kV, 100 MVA, -Y transformer with a rated impedance of R = 2% and X = 8%
per unit. The base for the power system is 200 MVA, 120 kV at the transmission line.
(a) Sketch the one-line diagram of this power system.
(b) Find per unit impedance of the generator on the system base.
(c) Find per unit impedance of the transformer on the system base.
(d) Find per unit impedance of the transmission line on the system base.
(e) Find the per-phase, per unit equivalent circuit of this power system.
Problem#5
Draw the single line diagram for the system whose description is as follows:
Generator G1 is connected to Bus 1 through transformer T1. Line 1 from Bus 1 connects
Bus 2, to which is connected generator G2 through transformer T2. Line 2 from Bus 1
connects Bus 3, to which is connected a motor M and another Load through transformer
T3. Further, Line 3 connects Bus 2 and Bus 3.
Hence draw its impedance diagram with all ratings in per unit. Choose 100 MVA as the
three-phase base apparent power. Select 161 kV as the base voltage of Line 1.
Data for the system is:
G1 : 50 MVA, 13.8 kV, X=0.15 pu
G2 : 20 MVA, 14.4 kV, X=0.15 pu
M : 20 MVA, 14.4 kV, X=0.15 pu
T1 : 60 MVA, 13.2 kV/161 kV, X=0.10 pu
T2 : 25 MVA, 13.1 kV/161 kV, X=0.10 pu
T3 : 25 MVA, 13.2 kV/160 kV, X=0.10 pu
(Note the voltage rating on LV side of T2 and HV side of T3!)
Line 1: 20+80
Line 2: 10+j40
Line 3: 10+j40
Load: 20+j15 MVA at 12.63 kV