Professional Documents
Culture Documents
Chapter
10
he transformer is one of the most important hardware in the electrical power system.
An
important consideration in transformer protection is the high cost of the transformer and the
relative long outage time that occurs when a transformer fails.
transformer protection is differential protection, whose zone of protection is bounded by the location of the
protection current transformers (CTs) between the transformers high voltage and low voltage terminals.
The differential protection should operate for a fault within the zone of the CT and should not operate for a
fault outside the zone of the CT. The major advantage of the differential protection is the fast speed of
operation to detect a fault as compared to transformer
PowerGrid
The use of
300MVA
Yd 11, 230/19kV
19kV
CT1
58/23/35MVA
19/6.6/22kV
G
CT2
CT3
19kV
250MW
6.6kV
22kV
impedance between any pairs of windings with the third winding in open circuit. Therefore we will have:
Zps
Zpt
Zst
Primary
19kV
Primary
19kV
Ip
However the
Ip
The values of
It
Zt= 25%
Zs= 37%
Is = 40% x Ip
Secondary Tertiary
6.6kV
22kV
It = 60% x Ip
Secondary
6.6kV
Tertiary
22kV
Table 10.1 shows the nameplate data and the normalized values of impedance for
Capacity
Primary
58MVA
Nameplate
Impedance
Impedance at
58MVA Base
Zps = 31%,
Voltage
Primary
= 19kV
Secondary 23MVA
Secondary = 6.6kV
Zpt = 19%,
Tertiary
Tertiary
Zst = 62%,
35MVA
= 22kV
Zps
Z p + Zs
31%
Zpt
Z p + Zt
19%
Zst
Z s + Zt
62%
Phase angle
Difference
Primary to
Secondary = 30o
Primary to
o
Tertiary = 30
Secondary to
Tertiary = 0o
Commissioning
An external 3 phase, 400 volts diesel generator was connected at the 19kV side with three different
combinations of open/short circuit at the 6.6kV and 22kV.
The three combinations were ;
Connection
19kV
6.6kV
22kV
Figure 10.3A
Generator connection
Short circuit
Open circuit
Figure 10.3B
Generator connection
Open circuit
Short circuit
Figure 10.3C
Generator connection
Short circuit
Short circuit
The KVA rating of the external generator was calculated using the impedance data of the three
winding transformer of Table 10.1.
The required KVA rating of the external generator for the three
Percentage of
Full Load Current
Figure 10.3A
3 x 400 x 119
= 82 KVA
7%
Figure 10.3B
3 x 400 x 195
= 135 KVA
11%
Figure 10.3C
3 x 400 x 416
= 288 KVA
23%
A 3 phase, 400 volts, 300KVA generator was selected for the commissioning test. The calculated
value of 416A at the 19kV winding is about 23% of the full load current and so considered high enough to
commission the differential protection relay. Table 10.2 is the summary of the measured values for Figure
10.3A, Figure 10.3B and Figure 10.3C under external fault conditions. Incorrect CT polarity at the 22kV CT
was suspected because ;
High value of differential current for the case of Figures 10.3B and 10.3C
The star point of the 22kV CT was reversed to rectify the incorrect CT polarity. Table 10.3 is the
summary of the measured values with the correct CT polarity. The differential protection was considered
stable for the out of zone fault because the differential current was zero. The short circuit at the 22kV side
was relocated to create an in-zone fault and the differential current was non-zero and of high value. The
differential relay was considered commissioned.
Conclusion
In this case study, the polarity of the 22kV CT was incorrect and fortunately discovered during the
commissioning test.
If such a commissioning test was not done, the differential relay will operate under
I yellow
162 A
105 A
344 A
I blue
162 A
105 A
344 A
I red
0A
289 A
421 A
I yellow
0A
289 A
421 A
I blue
0A
289 A
421 A
I red
137 A
0A
169 A
I yellow
137 A
0A
169 A
I blue
137 A
0A
169 A
I red
91 mA
59 mA
197 mA
I yellow
91 mA
59 mA
197 mA
I blue
91 mA
59 mA
197 mA
I red
183 mA
0A
226 mA
I yellow
183 mA
0A
226 mA
I blue
183 mA
0A
226 mA
External Generator
Connected to
19 kV Side
I red
19kV
6.6kV
22kV
Bias
Diff.
In-Zone Fault
In-Zone Fault
In-Zone Fault
Short Circuit
at 22kV
Short Circuit
at 6.6kV
Short Circuit at
22kV and 6.6kV
Short Circuit at
22kV and 6.6kV
Open Circuit
(Fig. 10.3B)
Short Circuit at
6.6kV and 22kV
Open Circuit
(Fig. 10.3A)
Short Circuit at
22kV and 6.6kV
(Fig. 10.3C)
I red
344A
344 A
I yellow
344A
344 A
344A
162A
105A
344A
344A
162A
105A
I blue
344A
344A
344 A
344A
162A
105A
344A
I red
I yellow
421A
0A
0A
0A
289A
421A
421A
0A
0A
0A
289A
421A
I blue
421A
0A
0A
0A
289A
421A
I red
0A
169A
0A
137A
0A
169A
I yellow
0A
169A
0A
137A
0A
169A
I blue
0A
169A
0A
137A
0A
169A
I red
140mA
154mA
97mA
91mA
59mA
197mA
I yellow
140mA
154mA
97mA
91mA
59mA
197mA
I blue
140mA
154mA
97mA
91mA
59mA
197mA
I red
113mA
81mA
194mA
0A
0A
0A
I yellow
113mA
81mA
194mA
0A
0A
0A
I blue
113mA
81mA
194mA
0A
0A
0A
External Generator
Connected to 19kV
Side
19kV
6.6kV
22kV
Bias
Diff.
400V
3 Generator
400V
3 Generator
~
i
Ip
Zp = -6%
Z = 31%
i=
Is
Zs= 37%
Zt= 25%
0.4
0.31 x 19
x Full load
Current
= 6.79% x 1762
= 119A
400V
3 Generator
400V
3 Generator
~
i
Ip
Zp = -6%
Z = 19%
i=
It
Zs= 37%
Zt= 25%
0.4
0.19 x 19
x Full load
Current
= 11.08% x 1762
= 195A
400V
3 Generator
400V
3 Generator
~
i
Ip
Zp = -6%
Z = 8.9%
i=
Is
Zs= 37%
It
Zt= 25%
0.4
x Full load
0.089 x 19
Current
= 23.65% x 1762
= 416A
-- END --