Professional Documents
Culture Documents
Terminal Unit
1stEdio
Edition
1
21/21N
PROTECTION
78
50HS
50/51
50/51N
67/67N
85/21
85/67N
27WI
46
79
25
62/62BF
43
APLICATION
The TPU L420 has been designed as a protection and terminal unit for supervision and
control of aerial lines, integrating the distance protection function, with a main application
in line feeders.
The TPU L420 performs a wide range of protection and automation functions. It has an
extensive range of user programming options, offering high accuracy regulation in
currents, voltages, temporisations and optional characteristics. All protection and
automation functions settings are independent among themselves, having 4 groups of
settings for each function.
There are 3 different versions of the TPU L420 which offer the user the flexibility to
choose the suitable relay for each application. The possibility to program logic
interlockings complementary to the existent control functions provides additional
protection configuration that can be used to adapt the unit to the users needs.
Programmable Logic
The local interface of the TPU L420 integrates a graphic display where is presented a
mimic with the state of all equipment of the bay, as well as its respective measurements.
In the front panel there are also several functional keys that allow an easy operation of
the protection in the most frequent operation situations.
As a terminal unit, the TPU L420 is capable of accurate measurements of all the values
of a line and several fault monitoring functions, including Oscillography and Event
Chronological Recorder. These functions allow its integration as a Remote Unit in
EFACECs Supervision Command and Control Systems, offering at the same time a
connection to a PC.
Together with the TPU L420 is supplied an integrated software package for PC interface
with the protection WinProt either locally or trough the local communication network.
This application allows, besides other functionalities, the access and modification of relay
settings and configurations and also the gathering and detailed analysis of the produced
records.
PROTECTION FUNCTIONS
Distance Protection
The distance protection offers complete
protection against all kind of faults in
systems where the neutral connection to
earth is solid or by means of a limiting
impedance. The TPU L420 has five
distance
protection
zones,
with
quadrilateral characteristic, working in
parallel and completely independent.
Zone 3
Zone 2
Zone 1
Zone 4
Zone 5
Zona 3
Overreach
Protection
of
Zone
Distance
Zona 2
Zona 1
Zona 4
Zona 5
Switch-Onto-Fault Protection
When energising a faulty line, the distance
protection may not offer adequate
equipment protection. This problem is
2/23
For the IEC complying option, the timecurrent functions follow the general
expression:
top [s ] =
aT
( Icc / I >)b 1
NI
a=0,14
b=0,02
A=16,86
VI
a=13,5
b=1
A=29,7
EI
a=80
b=2
A=80
LI
a=120
b=1
A=264
For the IEEE complying option, the timecurrent functions follow the general
expression:
c
+ e TIEEE
top [s ] =
( Icc / I >) d 1
NI
c=0,103
d=0,02
e=0,228
A=9,7
VI
c=39,22
d=2
e=0,982
A=43,2
EI
c=56,4
d=2
e=0,243
A=58,2
LI c=56,143
d=1
e=21,8592 A=133,1
with
Low
Set
Overcurrent
definite/inverse time
U0
I0
3/23
Teleprotection
Schemes
Distance Protection
for
When
associated
to
teleprotection
schemes, the distance protection provides
instantaneous clearance time for faults
occurring anywhere in the protected line.
The TPU L420 has several types of
schemes associated to the distance
protection DUTT, PUTT, POTT,
POTT+DCUB and DCB, which are adapted
to several network characteristics. These
schemes are prepared for feeders with 2 or
3 terminals and have elements to lock due
to operation direction change.
Remote Tripping
The remote tripping function allows the
TPU L420 to trip upon reception of an
external order. It is possible to associate a
time delay between the signal reception
and the send of the trip.
Phase Balance
The TPU L420 also features a directional
phase fault overcurrent protection, which
runs independently from the directional
earth fault overcurrent protection.
UR
IR
UST
UT
US
Teleprotection
Schemes
for
Directional Earth Fault Protection
Relay non-operation zone
(direction: front)
Fault Locator
Complementing the protection functions,
the fault locator gives very accurate
information on the distance to the
eliminated short circuits. The start signals
of the functions of distance protection and
of earth fault directional overcurrent
protection are only used to define the fault
loop or loops and the fault locator function
operates independently of those functions.
4/23
5/23
Automatic Reclosing
The TPU L420 executes the automatic
reclosing
automatism,
allowing
the
execution of up to five reclosing cycles,
completely configurable. The main purpose
of this function is the service restoration of
a line after the elimination of temporary or
intermittent faults, common in aerial
networks.
Reclosing sequence starts with the
disconnection of the faulty line, followed by
the reclosing command, after the dead time
defined for the current cycle.
After the closing command, the automatism
waits a configurable time to confirm fault
absence. If the fault is still present after the
reclosing attempts, a definitive trip signal is
generated.
The logic conditions for automatic reclosing
operation are configurable through the
programmable logic of the TPU L420. By
default, they correspond to the first stage
trip of the distance protection and the
teleprotection schemes
Supervision of VTs
6/23
Programmable Logic
Supervision scheme of the circuit breaker trip
Distributed Automation
The complete integration of the TPU L420
in Supervision Command and Control
Systems allows the definition of control
functions that take advantage of their
connection to the local area network (LAN).
This means that, besides the vertical
communication with the control centre, fast
communication mechanisms among the
several units are available.
Operation Modes
The TPU L420 allows the specification of
several operation modes, which affect the
operation of the control and protection
functions.
In the front panel there are two operation
modes, configurable by the user. They are
usually associated with the bay operation
mode, specifically with the control and
supervision functions performed by the
relay. Current status of each mode is
signalised by LEDs and may be directly
changed through the associated functional
keys.
Besides theses modes, the TPU L420 also
includes a menu to access other operation
modes that may be required.
The Local/Remote operation mode defines
the relay behaviour concerning the
received information from the Supervision
Command and Control System. When in
Local Mode all remote operations are
inhibited.
The Manual/Automatic mode concerns the
control functions executed by the TPU
L420. When in Manual Mode all control
functions are locked. This mode is
fundamental to perform maintenance tasks,
with the system in service.
The Normal/Emergency mode refers to the
systems special operation. When in
Emergency mode all logical interlockings of
circuit breaker commands are inhibited.
The
Special
Operation
mode
is
characterised,
by
default,
by
the
instantaneous operation of the phase and
the earth overcurrent protections. However,
other logical conditions can be configured.
7/23
MONITORING
Measurements
The TPU L420 accurately measures, in
almost stationary state, the following
values:
RMS value of the three phase currents
th
and the zero sequence current (4
current input and virtual sum of the three
phase currents);
RMS value of the inverse current;
RMS value of phase to earth and phase
to phase voltages and zero sequence
voltage, obtained by virtual sum of the
th
three phase voltages and the 4 voltage
input;
Line frequency and bus frequency;
Differences of magnitude, phase and
frequency between the line voltage and
the bus voltage;
Active and reactive power and power
factor;
Active and reactive energy counting
(values stored in flash memory) supplied
and received;
Resistance and reactance per loop.
Based on the measurements made, the
TPU L420 calculates and registers, with
date of occurrence, the
following
information:
Load Diagram
The TPU L420 permanently calculates and
registers the daily load diagram. This
information is based on the calculation of
the 15 minute average of each of the
power measurements. All daily diagrams
can be stored for a full month.
Each diagram may be accessed locally or
through the software interface WinProt.
Data gathering is done through a serial port
or through the LAN.
Oscillography
The TPU L420 registers and stores in flash
memory a large number of oscillographies
of currents and voltages (about 60
seconds).
The length of each oscillography, the prefault and post-fault times are variable and
configurable by the user. By default, the
recording starts 0.1 second before the
protection start and ends 0,1 second after
the reset of all virtual relays of the several
functions. The maximum length is 1
second. The sampling frequency of the
analogue values is 1000 Hz.
Analogue Comparators
Additionally to all protection and measure
functions, TPU L420 has a set of
configurable comparators for analogue
values, acquired and calculated in the
protection.
Event Recorder
The TPU L420 monitors the relays inputs
and outputs, as well as all defined internal
logical variables. Any state change or
event is registered, with precise time
tagging (1ms resolution).
Each event may be configured to be
presented, or not, in the event recorder,
according to the desired level of detail, as
well as the associated description and the
Event time-tagging
The event time-tagging done by the TPU
L420 is always made in the local time zone
of the country where it is installed. For this,
it is necessary to set the deviation of the
timezone relative to the reference given by
the GMT time, as well as the day and hour
of start and end of the daylight saving
period, according to the legal regulations.
The TPU L420 receives periodically a time
synchronisation signal through the local
area network. In the absence of this signal,
an internal real time clock allows the
updating of the protection date and time
when the protection is disconnected.
Optionally, the TPU L420 can be
synchronised through an IRIG-B signal,
having a specific interface for that purpose,
or trough a SNTP server, according to the
RFC 2030 standard (in versions with
Ethernet communications board).
System Information
The TPU L420 has available in real time a
large set of system information. This
information reflects the protections internal
status, at both hardware and software
level.
In terms of hardware it is possible to
access the status of several electronic
components, which are permanently
monitored. The information associated to
the software contains all the data regarding
the relay identification, namely relay type,
relay version, serial number, relay name,
network address, etc.
All this information can be accessed locally
or visualised in a PC, through WinProt. It
may also be reported in real time to the
Supervision Command and Control System
through the communication network.
8/23
INTERFACES
Inputs
Outputs
5+1
Type 1 Expansion
Type 2 Expansion
16
Type 3 Expansion
15
Main Board
Functional Keys
Through functional keys it is possible to
change the operation mode of the
protection, to select a specific device and
command it, or to acknowledge an alarm.
Alarms
Next to the graphic display the TPU L420
has 8 configurable alarms. For each alarm
it is possible to define an associated logical
variable, choose the alarm type and the
text presented in the display.
Serial Communication
The TPU L420 has available 3 serial ports
for communication, two in the back panel
and one in the front panel.
The front panel serial port is only used to
communicate with the WinProt application.
In the TPU L420 version with the DNP 3.0
serial protocol, both rear ports may be
used for communication with the WinProt,
and COM1 rear port may serve as support
Graphic Display
The TPU L420 has a graphic display where
a variety of information can be presented,
namely: mimic, parameterization menus
and records menus. The mimic presents
logical information with the equipment
state,
alarms
description,
analogue
measurements and static information.
Security
Any user can access all information in the
local interface. However, for security
reasons, without the correct password the
settings can not be accessed.
SCADA Integration
The integration of the TPU L420 in SCADA
systems can be done through serial
communication protocols or through
dedicated communication boards, namely:
Serial Interface supporting the DNP 3.0
protocol, with communication speeds up
to 19200 baud.
Lonworks Board, using the LONTALK
communication
protocol,
with
a
communication speed of 1.25 Mbps.
Redundant 100 Mbps Ethernet Board,
supporting the IEC 60870-5-104 and
IEC 61850 protocols. This board also
provides the TCP/IP communication
protocol for direct connection with
WinProt.
9/23
Remote Access
WinProt allows local access by serial port
through a modem and remote access
through the local communication network
(LAN) or even through an Ethernet network
directly connected to the units. It is
possible to configure the settings
associated to each type of communication
and each specific unit.
The use of a LAN has an advantage
regarding the serial communication by
allowing the access to any of the
protections in the network without having
to change physical configurations. Thus,
any
operation
of
maintenance,
configuration or simply the system
monitoring can be remotely done from the
Supervision Command and Control
System. It also can be done through
intranet, if available.
Parameterisation Module
The parameterisation of each protection is
done through a specific module
WinSettings where is possible to
configure function by function, to copy data
from one relay to another, to compare
settings from the database to those
existing in the relay or simply to compare
settings among different relays.
The user has a set of tools that help him
performing the parameterisation task, such
as
graphics
with
time-current
characteristics, default settings, print
configurations, comparisons list, etc.
10/23
11/23
General Information
The main page presents all units general data,
namely, the order code, the application, the
version and the serial number. From this page,
it is possible to reach pages with more
specialized data (parameters, registers,
measures, etc.). There is also available an
access counter, a map of the accessible pages
in the server and a page with useful links
(technical support, EFACEC Web site,
e-mail, etc.).
Parameters
Through the WebProt, the user can visualize
and change several functional parameters
defined in the unit. Besides, this is subject to a
previous password insertion, for changing
purposes. It is also possible to print and export
the complete data.
Records
WebProt allows the collection and analysis of
the different records existing in the unit
(oscillographies,
event
recording,
load
diagrams, etc.). Concerning more complex
records, such as oscillographies, analysis tools
are downloaded directly from the server,
avoiding the need for high level specific
applications.
Schematic Diagrams
Remote monitoring of the units schematic
diagram and alarm data is another feature,
available in order to allow an easy and efficient
access to the equipment state, as performed
locally.
12/23
CONNECTION DIAGRAM
T2
C B
L420
GND 10
GND 9
UA
4
3
UB
2
1
UC
O1
Expansion Card
Type I
9 Inputs
6 Outputs
T1
C B
8
7
IN
6
5
IA
4
3
IB
2
1
IC
8
9
O3
Binary
Out puts
10
11
O4
IN4
9
10
IN5
11
12
IN6
13
14
IN7
IN8
17
18
IN9
1
2
Binary
Inputs
Expansion Card
Type II
16 Inputs
IN8
15
16
IN9
3
4
I O3
I O5
Binary
Inputs
...
15
16
IN1
...
7
8
16
17
...
IN3
O6
...
IN2
5
6
13
14
18
...
IN1
3
4
O5
...
1
2
I O4
I O6
12
15
Currents
IO1
6
7
O2
A
A
I O3
I O5
17
18
IN9
Voltages
...
6
5
1
2
IN1
Binary
Inputs
...
UD
...
8
7
I O4
I O6
17
18
IN16
Main Card
1
O4
13
14
18
O5
16
17
WD
Binary
Out puts
Binary
Outputs
Expansion Card
Type III
15 Outputs
Auxiliary
Power Supply
1, 2
3
1
2
6
O11
4
5
9
O12
7
8
12
O13
10
11
15
O14
13
14
18
O15
16
17
IRIG-B
2
1
I O3
I O5
18
O10
IO2
...
O9
12
15
17
O3
10
11
...
...
O2
8
9
IO2
O1
O1
6
7
IO4
IO6
Galvanic
Isolation
Piggy-back
COM1
Piggy-back
COM2
Communication Card
Lonworks
Ethernet
Galvanic
I solation
Galvanic
Isolation
1 2
3,4,5,6
P1
FO1
COM4
RS232 Gate
For WINPROT
Galvanic
Isolation
Galvanic
Isolation
COM1
COM2
Galvanic
I solation
COM3
Frontal
G ate
13/23
DIMENSIONS
14/23
TECHNICAL SPECIFICATIONS
Burden
50 Hz / 60 Hz optional
1A/5A
5 A / 15 A Continuous
100 A / 500 A for 1 s
5 A / 1 A / 0,2 A / 0,04 A
15 A / 5 A / 1,5 A / 0,5 A Continuous
500 A / 100 A / 20 A / 4 A for 1 s
< 0,25 VA @ In
Frequency
Rated Voltage (Phase-to-Phase)
Overvoltage
Burden
50 Hz / 60 Hz optional
100 / 110 / 115 / 120 V
1,5 Un Continuous; 2,5 Un for 10 s
< 0,25 VA @ Un
Power Supply
Voltage Range
24 Vdc
(19 - 72 Vdc)
48 Vdc
(19 - 72 Vdc)
110 / 125 Vac/dc
(88 - 300 Vdc/80 - 265 Vac)
220 / 240 Vac/dc
(88 - 300 Vdc/80 - 265 Vac)
12 to 30 W / 20 to 60 VA
< 12%
Frequency
Rated Current
Thermal Withstand
4th Input Rated Current
Thermal Withstand
Power Consumption
Ripple at DC Auxiliary Power Supply
Binary Inputs
24 V
48 V
110/125 V
220/250 V
24 V
48 V
110/125 V
220/250 V
1 .. 128 ms
1 .. 255
1 .. 60 s
Power Consumption
Debounce Time
Chatter Filter
Validation Time of double inputs
Binary Outputs
Rated Voltage
Rated Current
Making Capacity
Breaking Capacity
250 V ac / dc
5A
1 s @ 10 A; 0,2 s @ 30 A
dc : 1/0,4/0,2 A @ 48/110/220 V; L/R < 40 ms
ac : 1250 VA (250 V / 5 A); cos > 0,4
1 kV rms 1 min
Pulsed / Latched
0,02 .. 5 s
Communication Interfaces
Lonworks
Fibre Type
Ethernet
Wavelength
Connector
Max. Distance
Fibre Type
Wavelength
Connector
Max. Distance
Fibre Type
Wavelength
Connector
Max. Distance
Fibre Type
Wavelength
Max. Distance
15/23
Insulation Tests
IEC 60255-5
IEC 60255-5
IEC 60255-5
Electrostatic Discharge
Electromagnetic field
Fast Transient Disturbance
2,5 kV ac 1 min 50 Hz
3 kV dc 1 min (power supply)
5 kV 1,2/50 s, 0,5 J
> 100 M @ 500 V dc
2,5 kV common mode
1 kV differential mode
8 kV contact; 15 kV air
80 MHz1000 MHz; 10 V/m; 80% AM
900 5 MHz; 10V/m; 50%; 200Hz
4 kV 5/50 ns
EN 61000-4-4
IEC 60255-22-4 Class IV
EN 61000-4-5
EN 61000-4-6
EN 61000-4-8
EN 61000-4-11
IEC 60255-11
EN 61000-4-11
IEC 60255-11
Radiated Emission
Conducted Emission
EN 55011; EN 55022
EN 55011; EN55022
CE Marking
EMC Immunity
EMC - Emission
Low Voltage Directive
EN 61000-6-2 : 2001
EN 50263 : 1999
EN 61000-6-4 : 2001
EN 50263 : 1999
EN 60950-1 : 2001
IEC 60255-5 : 2000
Mechanical Tests
Environmental Tests
- 10C to + 60C
- 25C to + 70C
- 10C, 72h
+ 60C, 72h
96h
+ 40C, 93% RH, 96h
- 25C
+ 70C
IP54
Relative humidity
Temperature
10 to 90%
- 10 C to 60 C, 40C damp
Environmental Conditions
Weight
Line settings
IP20
8 Kg
Impedance Values
Length Unit
Line Length
Line Reactance
Line Angle
Ko Magnitude (forward, reverse and zone 1)
Ko Angle (forward, reverse and zone 1)
Primary / Secondary
Kilometer / Mile
1,0 .. 1000,0 (km) / 0,65..650,0 (mile)
0,05 .. 500,00 (In=1 A) / 0.01 .. 100.00 (In=5 A)
30,0 .. 90,0
0,0 .. 4,0 (independent settings)
-180,0 .. 180,0 (independent settings)
16/23
Distance Protection
5 independent
Quadrilateral
Under-impedance / Overcurrent
0,05 .. 500,00 (In=1 A) / 0.01 .. 100.00 (In=5 A)
0,05 .. 500,00 (In=1 A) / 0.01 .. 100.00 (In=5 A)
0,05 .. 500,00 (In=1 A) / 0.01 .. 100.00 (In=5 A)
0,05 .. 500,00 (In=1 A) / 0.01 .. 100.00 (In=5 A)
0,05 .. 500,00 (In=1 A) / 0.01 .. 100.00 (In=5 A)
0,05 .. 500,00 (In=1 A) / 0.01 .. 100.00 (In=5 A)
0,0 .. 60,0 s (independent for each zone)
0,0 .. 60,0 s (independent for each zone)
30,0 .. 90,0
30,0 .. 90,0
0,0 .. 60,0
0,05 .. 500,00 (In=1 A) / 0.01 .. 100.00 (In=5 A)
10.0 .. 60.0
0,20 .. 4,0 pu
0,10 .. 4,00 pu
0,005 .. 0,80 pu
0,20 .. 10,00 pu
0,00 .. 60,00 s
< 35 ms (with SIR =1 and Xdef < 0,75 Xop)
3%10ms
5% of Zn
1,05
0,96
0,96
0,96
Switch-On-To-Fault Protection
Activation Time
Operacional current
Current Accuracy
Min. Operating Time
Reset Ratio
0,04 .. 60,0 s
0,20 .. 40,0 pu
3% (minimum 3% In)
< 30 ms
0.96
Operational Current
Time Delay
Min. Operating Time
Timer Accuracy
Current Accuracy
Reset Ratio
Max. Reset time
0,2 .. 40 pu
0 .. 60 s
30 ms (with I 2 Iop)
10 ms
5% (minimum 3% In)
0,95
30 ms
Curves
Current Accuracy
Start Value of Inverse Time Protection
Reset Ratio
Max. Static Reset Time
Operational Current
Time Delay
Timer Accuracy
Current Accuracy
Reset Ratio
Max. Reset Time
0,2 .. 40 pu
0,04 .. 300 s
10 ms
3% (minimum 3% In)
0,96
30 ms
Operational Current
Temporisation
TM regulation
Timer Accuracy
17/23
Operational Current
Time Delay
Min. Operating Time
Timer Accuracy
Current Accuracy
Reset Ratio
Max. Reset Time
0,1 .. 40 pu
0 .. 60 s
30 ms (with I 2 Iop)
10 ms
5% (minimum 3% In)
0,95
30 ms
Curves
Current Accuracy
Start Value of Inverse Time Protection
Reset Ratio
Max. Static Reset Time
Operational Current
Time Delay
Timer Accuracy
Current Accuracy
Reset Ratio
Max. Reset Time
0,1 .. 40 pu
0,04 .. 300 s
10 ms
3% (minimum 3% In)
0,96
30 ms
30 .. 60 (forward/reverse)
2,5 s
-90 .. 90 (forward/reverse)
0,005.. 0,8 pu
Remote Tripping
Time Delay
Timer Accuracy
0,0 .. 10,0 s
10 ms
Schemes
Line Configuration
Send Time
Lock Time DCB
Security Time DCUB
Lock Time DCUB
Failure Time DCUB
Confirmation Time Transient Lock
Lock Time Transient Lock
Timer Accuracy
Schemes
Line Configuration
Send Time
Lock Time DCB
Security Time DCUB
Lock Time DCUB
Failure Time DCUB
Confirmation Time Transient Lock
Lock Time Transient Lock
Timer Accuracy
Operating mode
Confirmation time
Echo emission time
Operational voltage (distance)
Operational voltage (earth directional)
Voltage precision
Time precision
Operational Current
Time Delay
TM regulation
Timer Accuracy
18/23
Operational Current
Time Delay
Min. Operating Time
Timer Accuracy
Current Accuracy
Reset Ratio
Max. Reset Time
0,1 .. 10 pu
0 .. 60 s
30 ms (with I 2 Iop)
10 ms
5% (minimum 3% In)
0,95
30 ms
Curves
Current Accuracy
Start Value of Inverse Time Protection
Reset Ratio
Max. Static Reset Time
Automatic Reclosing
5
0,1 .. 60 s
1 .. 60 s
0,05 .. 60 s
Operation Mode
Closing Mode
Bus Voltage Selection
Bus/Line Voltage Ratio
-180,0 .. 180,0
0,05 .. 0,80 pu
0,20 .. 1,20 pu
0,50 .. 1,50 pu
Min. Frequency
Voltage Difference
Frequency Difference
Phase Difference
Operational Current
Time Delay
TM Regulation
Timer Accuracy
Max. Frequency
Command Time
Confirmation Time
Timer Accuracy
Voltage Accuracy
Frequency Accuracy
Angle Accuracy
10 ms
0,5%
20 mHz
2
19/23
Time Delay
Confirmation Time of Trip Circuit Failure
0,05 .. 10 s
0,05 .. 10 s
Detection Criteria
Min. Operational Current
Min. Operational Voltage
Confirmation Time
Current Accuracy
Voltage Accuracy
Timer Accuracy
0,05 .. 60 s
0,05 .. 60 s
Measurement Accuracy
Currents
Voltages
Power
Frequency
Impedances
0,5 % In
0,5 % Vn
1 % Sn
0,05 % fn
1 % Zn
Fault Locator
Accuracy
Resolution
Maximum Number of Events per Register
Number of Recorded Events
1 ms
256
> 28000
Oscillography
Sampling Frequency
Total Time Recorded
Analogue Comparators
Configurable Settings
Timer Accuracy
Load Diagram
Measurements
Total Time Recorded
P, Q
1 month
SNTP Synchronization
2
1 .. 1440 min
1 .. 1000 ms
1 .. 25
1 .. 3600 s
Multicast/Unicast
20/23
VERSIONS
VERSION
AVAILABLE FUNCTIONS
Distance Protection (21/21N)
L420 D
L420 R
L420 S
Remote Tripping
VT Supervision
Programmable Logic
Distributed Automation
Oscillography
Fault Locator
Analogue Comparators
Load Diagram
The TPU L420-D is suitable for less integrated applications, with specific equipment for execution of automatic reclosing and synchronism
check functions. These functions are available in other two TPU L420 versions.
21/23
ORDERING FORM
TPU L420 Ed1 Version
TPU L420 D
TPU L420 R
TPU L420 S
D
R
S
1A
5A
0,04A
0,2A
1A
5A
100V
110V
115V
120V
100V
110V
115V
120V
50Hz
60Hz
A
B
C
D
0
1
2
3
0
1
2
3
0
DNP
LON1
LON2
LON3
LON4
ETH1
ETH2
850T
850F
0
1
2
3
0
1
2
3
PT
UK
FR
ES
22/23
NOTES
Main Address
EFACEC Engenharia, S.A.
Rua Eng. Frederico Ulrich, 4471-907 Moreira Maia, Portugal | Tel. +351 22 940 20 00 | Fax +351 22 940 33 09 | E-mail: ase.eng@efacec.com | Web: www.efacec.com
23/23