You are on page 1of 31

Universal Consultancy Services

EDG BUILDING HVAC CALCULATION


R0
05
04
03
02
01
00

25-02-2010
17-03-2010
22-02-2010
18-02-2010
11-02-2010
27-01-2010
17-01-2010

Rev.

Date

Released for construction


FTI comments
FTI comments
FTI changes due genset vendor requirements
FTI comments
FTI comments
Description

UCS
UCS
UCS
UCS
UCS
UCS
UCS

UCS
UCS
UCS
UCS
UCS
UCS
UCS

DSGN

CHKD

APPD

Project Title:

Al Qatrana Power Project


The Hashemite Kingdom of Jordan
The Ministry of Energy and Mineral Resources
Owner :

Owners Technical advisor :

EPC Contractor :

Engineering Company:

Sub-Vendors Name:

Project No.
3480870001
Document No.

Job No.
-

Scale
-

Sheet No.
-

KP-170-28-005

Sub-Contractor Document No.:


Sub-Supplier:

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 1 of 32

Universal Consultancy Services


CONTENTS
Section 1
i.
ii.
iii.
Section 2
i.
ii.
Section 3
i.
Section 4
i.
ii.
Section 5
i.
Section 6
i.
ii.
iii.
Section 7
i.
ii.
iii.
iv.
v.
vi.

General Information
General Project Information
Applicable Codes, Standards and References
Calculation Method
Design Parameters
Weather Data
Indoor Criteria
HVAC Systems Designation
System Definition
Overall Heat Transfer Coefficients (U Factors)
U Value Summary
U Value Detailed Calculations
Outdoor Air Sizing
Outdoor Air Sizing
Calculation Input Data
Space Input Data
Schedule Input Data
System Input Data
Calculation Results
Results Summary
Air System Sizing Summary
Zone Sizing Summary
Air System Design Load Summary
System Psychrometrics
Results Calculations

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 3 of 32

Universal Consultancy Services

SECTION 1

GENERAL INFORMATION

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 4 of 32

Universal Consultancy Services

i.

GENERAL PROJECT INFORMATION

ii.

: Al Qatrana Power Project


: Jordan - Qatrana
: Emergency Diesel Generator Building

APPLICABLE CODES, STANDARDS & REFERENCES

iii.

Project
Location
Building

ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers).


Jordanian National Code.

HVAC CALCULATION METHOD

Supplied air flow rate for a space is determined by the zone load requirements, any possible makeup
air need due to direct exhaust and pressurization requirements. Outdoor air quantity of spaces
are determined as per applicable standard to maintain acceptable indoor air quality in the space.
The software programs used for load calculation are Carrier E20-II / HAP V.4.4 & Carrier E20-II / Block Load V.3.05.

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 5 of 32

Universal Consultancy Services

SECTION 2

DESIGN PARAMETERS

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 6 of 32

Universal Consultancy Services

i.

WEATHER DATA
As per 2005 ASHRAE Fundamentals Handbook design condition for Amman
Latitude

: 31.98 N

Daily Range

: 11.3 C

Outdoor Design Conditions ( Air conditioning system ):


Summer Design Dry Bulb Temp: 35.4 C
Summer Design Wet Bulb Temp: 19.4 C
Relative Humidity: 21.1 %
Winter Design Dry Bulb Temp: 0.9 C
Winter Design Wet Bulb Temp: -2.26 C
Relative Humidity: 46.3 %
Indoor Design Conditions ( Air conditioning system ):
Summer: Minimum 1 C less than the design ambient temperature.
Winter: 20 C min
Relative Humidity: No humidity control.
Outdoor Design Conditions ( Ventilation system ):
The maximum outdoor temperature considered for design of ventilation system shall be 38.9

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 7 of 32

Universal Consultancy Services

Design Parameters:
City Name .......................................................................................................... Amman
Location .............................................................................................................. Jordan
Latitude .................................................................................................................... 32.0
Longitude ................................................................................................................ -36.0
Elevation ................................................................................................................ 773.0
Summer Design Dry-Bulb ........................................................................................ 35.4
Summer Coincident Wet-Bulb .................................................................................. 19.4
Summer Daily Range ............................................................................................... 11.3
Winter Design Dry-Bulb ............................................................................................. 0.9
Winter Design Wet-Bulb ............................................................................................ -2.3
Atmospheric Clearness Number .............................................................................. 1.00
Average Ground Reflectance ................................................................................... 0.20
Soil Conductivity .................................................................................................... 1.385
Local Time Zone (GMT +/- N hours) ......................................................................... -2.0
Consider Daylight Savings Time ................................................................................ No
Simulation Weather Data ................................................................................. none N/A
Current Data is ......................................................................................... User Modified
Design Cooling Months ............................................................... January to December

Deg.
Deg.
m
C
C
K
C
C
W/ (m-K)
hours

Design Day Maximum Solar Heat Gains


(The MSHG values are expressed in W/m)
Month
January
February
March
April
May
June
July
August
September
October
November
December
Month
January
February
March
April
May
June
July
August
September
October
November
December

N
74.0
86.0
99.3
112.1
120.8
151.3
126.0
117.3
102.9
88.8
75.3
68.8
SSW
794.0
734.8
615.0
444.2
312.7
260.2
301.4
428.0
596.1
706.7
776.7
794.8

NNE
74.0
86.0
108.4
252.6
350.2
383.2
345.1
247.2
109.3
88.8
75.3
68.8
SW
790.6
785.9
714.5
589.6
486.7
436.7
469.7
568.1
688.1
747.8
776.9
774.1

NE
95.4
220.1
356.1
458.9
532.6
548.5
527.0
455.0
321.9
187.4
88.6
68.8
WSW
716.1
756.1
759.1
691.9
629.5
597.8
615.6
667.0
718.5
741.5
706.2
688.2

ENE
318.4
450.4
578.1
635.3
657.0
661.8
651.7
617.8
545.8
450.8
331.5
252.8
W
547.0
660.3
717.0
714.3
693.0
673.1
674.2
689.0
677.3
620.6
550.1
508.6

E
563.3
652.2
706.0
715.3
694.6
678.3
680.2
688.3
679.6
628.7
536.8
515.0
WNW
340.8
460.3
564.5
628.0
652.9
653.7
640.6
607.5
546.7
443.2
310.0
273.9

ESE
711.9
769.1
757.8
686.2
627.9
594.1
606.9
656.6
715.1
731.4
708.5
683.1
NW
79.5
209.1
356.7
468.2
537.3
560.9
535.0
455.6
326.8
209.0
95.6
68.8

SE
793.4
777.9
713.1
591.2
488.3
442.0
476.6
570.0
688.7
759.1
769.3
779.7
NNW
74.0
86.0
112.2
252.0
350.1
383.6
347.3
249.9
108.2
88.8
75.3
68.8

SSE
792.2
729.5
612.2
444.5
313.2
261.3
303.2
428.2
596.7
712.9
778.8
797.4
HOR
553.5
680.6
793.5
854.1
872.7
870.7
859.8
836.2
769.1
670.6
552.2
499.4

S
775.1
692.9
552.6
362.5
232.7
190.4
225.4
349.6
540.1
676.0
765.8
794.1
Mult
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

Mult. = User-defined solar multiplier factor.

Location: Amman, Jordan


(Dry and Wet Bulb temperatures are expressed in C)

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 8 of 32

Universal Consultancy Services

Hr

January

February

March

April

May

June

DB

WB

DB

WB

DB

WB

DB

WB

DB

WB

DB

WB

0000

17.1

10.1

18.2

11.0

20.7

13.5

22.0

14.4

24.3

15.3

25.6

16.5

0100

16.6

9.8

17.7

10.7

20.1

13.3

21.5

14.2

23.7

15.1

25.0

16.3

0200

16.0

9.6

17.1

10.5

19.6

13.1

20.9

14.0

23.1

14.9

24.5

16.1

0300

15.5

9.4

16.7

10.3

19.1

12.9

20.5

13.8

22.7

14.7

24.0

16.0

0400

15.2

9.3

16.3

10.2

18.8

12.8

20.1

13.7

22.3

14.6

23.7

15.9

0500

15.1

9.2

16.2

10.1

18.7

12.7

20.0

13.6

22.2

14.5

23.6

15.8

0600

15.3

9.3

16.4

10.2

18.9

12.8

20.2

13.7

22.4

14.6

23.8

15.9

0700

15.9

9.5

17.0

10.5

19.4

13.0

20.8

13.9

23.0

14.8

24.4

16.1

0800

16.9

10.0

18.0

10.9

20.5

13.4

21.8

14.3

24.0

15.2

25.4

16.4

0900

18.4

10.6

19.5

11.5

21.9

13.9

23.3

14.8

25.5

15.7

26.8

16.9

1000

20.1

11.3

21.2

12.1

23.6

14.6

25.0

15.4

27.2

16.3

28.5

17.5

1100

22.0

12.0

23.1

12.9

25.5

15.2

26.9

16.1

29.1

16.9

30.4

18.1

1200

23.8

12.7

24.9

13.5

27.3

15.8

28.7

16.7

30.9

17.5

32.3

18.6

1300

25.1

13.2

26.2

14.0

28.7

16.3

30.0

17.1

32.3

17.9

33.6

19.0

1400

26.0

13.6

27.1

14.4

29.6

16.6

30.9

17.4

33.2

18.2

34.5

19.3

1500

26.4

13.7

27.5

14.5

29.9

16.7

31.3

17.5

33.5

18.3

34.8

19.4

1600

26.0

13.6

27.1

14.4

29.6

16.6

30.9

17.4

33.2

18.2

34.5

19.3

1700

25.2

13.3

26.4

14.1

28.8

16.3

30.2

17.1

32.4

17.9

33.7

19.1

1800

24.0

12.8

25.1

13.6

27.6

15.9

28.9

16.7

31.1

17.5

32.5

18.7

1900

22.5

12.3

23.6

13.1

26.1

15.4

27.4

16.2

29.7

17.1

31.0

18.2

2000

21.1

11.7

22.2

12.5

24.6

14.9

26.0

15.7

28.2

16.6

29.5

17.8

2100

19.8

11.2

20.9

12.0

23.4

14.5

24.7

15.3

27.0

16.2

28.3

17.4

2200

18.7

10.7

19.8

11.6

22.3

14.1

23.6

14.9

25.8

15.8

27.2

17.0

2300

17.8

10.4

18.9

11.2

21.4

13.7

22.7

14.6

24.9

15.5

26.3

16.7

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 9 of 32

Universal Consultancy Services

Hr

July

August

September

October

November

December

DB

WB

DB

WB

DB

WB

DB

WB

DB

WB

DB

WB

0000

26.2

16.5

26.2

16.5

25.0

15.9

23.1

14.6

20.1

13.1

17.7

11.3

0100

25.6

16.3

25.6

16.3

24.5

15.7

22.6

14.4

19.6

12.9

17.1

11.1

0200

25.0

16.1

25.0

16.1

23.9

15.5

22.0

14.2

19.0

12.7

16.5

10.9

0300

24.6

16.0

24.6

16.0

23.5

15.3

21.6

14.1

18.6

12.5

16.1

10.7

0400

24.2

15.9

24.2

15.9

23.1

15.2

21.2

13.9

18.2

12.4

15.8

10.6

0500

24.1

15.8

24.1

15.8

23.0

15.2

21.1

13.9

18.1

12.3

15.6

10.5

0600

24.3

15.9

24.3

15.9

23.2

15.3

21.3

14.0

18.3

12.4

15.9

10.6

0700

24.9

16.1

24.9

16.1

23.8

15.5

21.9

14.2

18.9

12.6

16.4

10.8

0800

25.9

16.4

25.9

16.4

24.8

15.8

22.9

14.6

19.9

13.0

17.4

11.2

0900

27.4

16.9

27.4

16.9

26.3

16.3

24.4

15.1

21.4

13.6

18.9

11.8

1000

29.1

17.5

29.1

17.5

28.0

16.9

26.1

15.7

23.1

14.2

20.6

12.5

1100

31.0

18.1

31.0

18.1

29.9

17.5

28.0

16.3

25.0

14.9

22.5

13.2

1200

32.8

18.6

32.8

18.6

31.7

18.0

29.8

16.9

26.8

15.5

24.3

13.9

1300

34.2

19.0

34.2

19.0

33.0

18.5

31.1

17.3

28.1

16.0

25.7

14.4

1400

35.1

19.3

35.1

19.3

34.0

18.7

32.1

17.6

29.0

16.3

26.6

14.7

1500

35.4

19.4

35.4

19.4

34.3

18.8

32.4

17.7

29.4

16.4

26.9

14.8

1600

35.1

19.3

35.1

19.3

34.0

18.7

32.1

17.6

29.0

16.3

26.6

14.7

1700

34.3

19.1

34.3

19.1

33.2

18.5

31.3

17.4

28.3

16.0

25.8

14.4

1800

33.0

18.7

33.0

18.7

31.9

18.1

30.0

17.0

27.0

15.6

24.6

14.0

1900

31.6

18.2

31.6

18.2

30.5

17.7

28.6

16.5

25.5

15.1

23.1

13.4

2000

30.1

17.8

30.1

17.8

29.0

17.2

27.1

16.0

24.1

14.6

21.6

12.9

2100

28.9

17.4

28.9

17.4

27.7

16.8

25.8

15.6

22.8

14.1

20.4

12.4

2200

27.7

17.0

27.7

17.0

26.6

16.4

24.7

15.2

21.7

13.7

19.3

12.0

2300

26.8

16.7

26.8

16.7

25.7

16.1

23.8

14.9

20.8

13.4

18.4

11.6

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 10 of 32

Universal Consultancy Services


Location: Amman, Jordan

Design Temperature Profiles for July


Dry Bulb

Wet Bulb

36
34
32
Temperature ( C )

30
28
26
24
22
20
18
16
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour

ii.

INDOOR CRITERIA
OUTDOOR
AIR

INDOOR CONDITIONS
ITEM

1
2

SPACE

SWITCH
GEAR
ROOM
DG SET
ROOM

Tel. + 962.6. 55 29 476

SUMMER

WINTER

TEMP
DB
(C)

RH
(%)

TEMP
DB
(C)

RH
(%)

34.4

NA

20

NA

53.9

NA

NA

INDOOR
PRESS.
(Pa)

INTERNAL HEAT GAINS


EQUIP DISSIP

REQ.

PEOPLE
(No.)

LIGHTS
2
(W/m )

(+)

1ACH

(-)

30ACH

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

SENS.
(W)

LAT.
(W)

21.5

2000

21.5

200000

Email: info@ucs-jo.com
Page 11 of 32

Universal Consultancy Services

SECTION 3

HVAC SYSTEMS DESIGNATION

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 12 of 32

Universal Consultancy Services


i.

SYSTEM DEFINITION:

SYSTEM-1

EQUIPMENT

NO.

DESCRIPTION

TYPE

UNIT TAG

SERVED AREA

AIR CONDITIONING
SYSTEM

SPLIT AIR
CONDITIONING UNIT/
HEAT PUMP

10SAD01AH003,4

SWITCH GEAR
ROOM

SYSTEM-3

EQUIPMENT

NO.

DESCRIPTION

TYPE

UNIT TAG

SERVICE

SMOKE EXTRACTION

AXIAL WALL
MOUNTED EXHAUST
FANS*

10SAD03AN002

SWITCH GEAR
ROOM

NOTES

DUTY-2x50%

NOTES

DUTY-100%

*All smoke control fans installation is pending, client & CDD requirements & approvals

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 13 of 32

Universal Consultancy Services

SECTION 4

OVERALL HEAT TRANSFER COEFFICIENTS

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 14 of 32

Universal Consultancy Services

i.

U VALUE SUMMARY:

ITEM

DESCRIPTION

HEAT TRANSFER
COEFFICIENT
U
(W/m2.K)

1
2
3
4
5
6

EXTERIOR WALLS
INTERIOR WALLS
ROOFS
FLOORS
EXTERIOR DOORS
WINDOWS

0.37
2.92
2.5
2.79
5.8
3.5

ii.

NOTES

U VALUE DETAILED CALCULATION:

- EXTERIOR WALLS
THICKNESS
(mm)

HEAT
TRANSFER
FILM COEFF.
(h)
(W/m2.K)

THERMAL
CONDUCTIVITY
(k)
(W/m.K)

THERMAL
RESISTANCE
(R)
(m2.K/W)

REFERENCES/NOTES

0.12

JORDANIAN NATIONAL
CODES

ITEM

DESCRIPTION

EXTERIOR WALLS

1.1

INDOOR AIR FILM


HEAT FLOW

1.2

PLASTER

15

1.2

0.0125

JORDANIAN NATIONAL
CODE

1.3

SOLID BLOCK

100

1.2

0.0833

JORDANIAN NATIONAL
CODE

1.4

THERMAL
INSULATION

85

0.038

2.2368

JORDANIAN NATIONAL
CODE

1.5

HOLLOW BLOCK

150

0.15

JORDANIAN NATIONAL
CODE

1.6

PLASTER

15

1.2

0.0125

JORDANIAN NATIONAL
CODE

1.7

OUTDOOR AIR FILM


HEAT FLOW,
18 km/h WIND

0.06

JORDANIAN NATIONAL
CODE

8.333

16.666

OVERALL THERMAL
RESISTANCE
(R)
(m2.K/W)

2.68

OVERALL HEAT
TRANSFER COEFF.
(U)
(W/ m2.K)

Tel. + 962.6. 55 29 476

0.37

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 15 of 32

Universal Consultancy Services


- INTERIOR WALLS
THICKNESS
(mm)

HEAT
TRANSFER
FILM COEFF.
(h)
(W/m2.K)

THERMAL
CONDUCTIVITY
(k)
(W/m.K)

THERMAL
RESISTANCE
(R)
(m2.K/W)

ITEM

DESCRIPTION

INTERIOR WALLS

2.1

INDOOR AIR FILM


HEAT FLOW

2.2

PLASTER

15

1.2

0.0125

2.3

Concrete Hollow
Block

200

1.2

0.1667

2.4

PLASTER

15

1.2

0.0125

6.667

0.15

OVERALL THERMAL
RESISTANCE
(R)
(m2.K/W)

REFERENCES/NOTES

JORDANIAN NATIONAL
CODE
JORDANIAN NATIONAL
CODE
JORDANIAN NATIONAL
CODE
JORDANIAN NATIONAL
CODE

0.3417

OVERALL HEAT
TRANSFER COEFF.
(U)
(W/ m2.K)

2.92

-ROOFS
ITEM

DESCRIPTION

ROOFS

THICKNESS
(mm)

HEAT
TRANSFER
FILM COEFF.
(h)
(W/m2.K)

THERMAL
CONDUCTIVITY
(k)
(W/m.K)

THERMAL
RESISTANCE
(R)
(m2.K/W)

3.1

ROOF-1

3.1.1

INDOOR AIR FILM


HEAT FLOW

3.1.2

RCC

200

1.2

0.1667

3.1.3

PLASTER

15

1.2

0.0125

3.1.4

OUTDOOR AIR FILM


HEAT FLOW,
18 km/h WIND
OVERALL THERMAL
RESISTANCE
(R)
(m2.K/W)

6.25

16.667

0.06

JORDANIAN NATIONAL
CODE
JORDANIAN NATIONAL
CODE
JORDANIAN NATIONAL
CODE
JORDANIAN NATIONAL
CODE

0.399

OVERALL HEAT
TRANSFER COEFF.
(U)
(W/ m2.K)

Tel. + 962.6. 55 29 476

0.16

REFERENCES/NOTES

2.5

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 16 of 32

Universal Consultancy Services


- FLOORS
ITEM

DESCRIPTION

FLOORS

4.1

INDOOR AIR FILM


HEAT FLOW

4.2

RCC

THICKNESS
(mm)

HEAT
TRANSFER
FILM COEFF.
(h)
(W/m2.K)

THERMAL
CONDUCTIVITY
(k)
(W/m.K)

THERMAL
RESISTANCE
(R)
(m2.K/W)

6.67

REFERENCES/NOTES

JORDANIAN NATIONAL
CODE
JORDANIAN NATIONAL
CODE

0.15

250

1.2

0.21

OVERALL THERMAL
RESISTANCE
(R)
(m2.K/W)

0.36

OVERALL HEAT
TRANSFER COEFF.
(U)
(W/ m2.K)

2.79

-EXTERIOR DOORS
ITEM

DESCRIPTION

EXTERIOR DOORS

THICKNESS
(mm)

HEAT
TRANSFER
FILM
COEFF. (h)
(W/m2.K)

THERMAL
CONDUCTIVITY
(k)
(W/m.K)

THERMAL
RESISTANCE
(R)
(m2.K/W)

REFERENCES/NOTES

DOUBLE SKINNED PRESSED


STEEL DOOR
OVERALL THERMAL
RESISTANCE
(R)
(m2.K/W)

0.17

OVERALL HEAT
TRANSFER COEFF.
(U)
(W/ m2.K)

Tel. + 962.6. 55 29 476

5.8

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 17 of 32

Universal Consultancy Services


- WINDOWS
ITEM

DESCRIPTION

WINDOWS

THICKNESS
(mm)

HEAT
TRANSFER
FILM
COEFF. (h)
(W/m2.K)

THERMAL
CONDUCTIVITY
(k)
(W/m.K)

THERMAL
RESISTANCE
(R)
(m2.K/W)

REFERENCES/NOTES

Double glazing, 6mm air


space, vertically installed,
operable, aluminum frame
OVERALL THERMAL
RESISTANCE
(R)
(m2.K/W)

0.29

OVERALL HEAT
TRANSFER COEFF.
(U)
(W/ m2.K)

Tel. + 962.6. 55 29 476

3.5

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 18 of 32

Universal Consultancy Services

SECTION 5

OUTDOOR AIR SIZING

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 19 of 32

SGR.
ROOM

SGR.
ROOM

SGR.
ROOM

SGR.
ROOM

EQUIPMENT

10SAD
01AH0
03,4

10SAD
02AA00
9

10SAD
02AA01
0

10SAD
03AN0
02*

SYSTEM

3.6

8.55

8.55

(-)

(-)

(+)

(+)

Fax. + 962.6. 55 22 476

166

889

889

166

ACH

15

L/S/
per.

RATE

L/s/
2
m

48672

166

AIR
FLOW
3
(m /h)
REF.

12

ACH

L/S/
per

RATE

L/s/
2
m

Page 20 of 32

1987

108774

AIR
FLOW
3
(m /h)

AS PER
DESIGN REQ.

VENDOR REQ.

REF.

MINIMUM EXHAUST AIR REQUIREMENTS

Email: info@ucs-jo.com

VENDOR
REQ.

ASHRAE
STD. 62

MINIMUM OUTDOOR AIR


REQUIREMENTS

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Tel. + 962.6. 55 29 476

46

104

104

CEILING
HEIGHT
(m)

3.6

SPACE
VOLUME
3
(m )

*PENDING

SPACE

PRESSURE
(Pa)

46

OUTDOOR AIR SIZING:

FLOOR AREA
2
(m )

i.

Universal Consultancy Services

PEOPLE
(no.)

166

HIGHEST
OUTDOOR
AIR
(m3/h)

HIGHEST
EXHAUST
AIR
3
(m /h)

1987

108774

48672

ARE USED

N/A AS
SPLIT UNITS

OUTDOOR
AIR
ADOPTED
IN CALC'S
3
(m /h)

Universal Consultancy Services

SECTION 6

CALCULATION INPUT DATA

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 21 of 32

Universal Consultancy Services


i.

SPACE INPUT DATA

SWITCH GEAR
1. General Details:
Floor Area ............................................................ 46.1
Avg. Ceiling Height ................................................ 3.6
Building Weight .................................................. 341.8
1.1. OA Ventilation Requirements:
Space Usage ......................................... User-Defined
OA Requirement 1 ................................................ 46.1
OA Requirement 2 ................................................ 0.00
Space Usage Defaults .......... ASHRAE Std 62.1-2004
2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Unvented)
Wattage .............................................................. 21.50
Ballast Multiplier ................................................... 1.10
Schedule .................................................... LIGHTING
2.4. People:
Occupancy ............................................................ 1.0
Activity Level ........................................... Office Work
Sensible ............................................................... 71.8
Latent ................................................................... 60.1
Schedule ...................................................... PEOPLE
2.2. Task Lighting:
Wattage ................................................................ 0.00
Schedule ............................................................ None
2.5. Miscellaneous Loads:
Sensible ................................................................... 0
Schedule ............................................................ None
Latent ....................................................................... 0
Schedule ............................................................ None
2.3. Electrical Equipment:
Wattage ............................................................ 2000.0
Schedule ............................................... EQUIPMENT

m
m
kg/m
L/s
L/(s-m)

W/m

Person
W/person
W/person

W/m
W
W
Watts

3. Walls, Windows, Doors:


Exp.

Wall Gross Area (m)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

NNW

44.0

ESE

14.0

WNW

14.0

3.1. Construction Types for Exposure NNW


Wall Type ....................................................................... U-1
1st Window Type ........................................................ U=3.5
3.2. Construction Types for Exposure ESE
Wall Type ....................................................................... U-1
1st Window Type ........................................................ U=3.5
3.3. Construction Types for Exposure WNW
Wall Type ....................................................................... U-1
Door Type .................................................................. U=5.8
4. Roofs, Skylights:
Exp.

Roof Gross Area (m)

Roof Slope (deg.)

Skylight Qty.

46.1

4.1. Construction Types for Exposure H


Roof Type ................................................................... U=2.5
5. Infiltration:

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 22 of 32

Universal Consultancy Services


Design Cooling ..................................................... 0.00 L/s
Design Heating ..................................................... 0.00 L/s
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ......................................... Slab Floor On Grade
Floor Area ............................................................ 46.1
Total Floor U-Value ............................................ 2.790
Exposed Perimeter ............................................... 19.8
Edge Insulation R-Value ....................................... 0.00

m
W/ (m-K)
m
(m-K)/W

7. Partitions:
7.1. 1st Partition Details:
(No partition data).
7.2. 2nd Partition Details:
Partition Type ....................................... Wall Partition
Area ..................................................................... 44.0
U-Value .............................................................. 2.920
Uncondit. Space Max Temp .................................. 53.9
Ambient at Space Max Temp ................................ 35.4
Uncondit. Space Min Temp ................................... 15.9
Ambient at Space Min Temp .................................. 0.9

m
W/ (m-K)
C
C
C
C

WINDOW INPUT DATA


U=3.5
Window Details:
Detailed Input ......................................................... No
Height ................................................................... 1.00 m
Width .................................................................... 1.00 m
Overall U-Value .................................................. 3.500 W/(m-K)
Overall Shade Coefficient ................................... 0.500
DOOR INPUT DATA
U=5.8
Door Details:
Gross Area ............................................................ 3.8 m
Door U-Value ...................................................... 5.800 W/(m-K)

ii.

SCHEDULE INPUT DATA:

EQUIPMENT (Fractional)
Hourly Profiles:
1: Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2: Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3: Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4: Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 23 of 32

Universal Consultancy Services


Assignments:
Design
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Holiday

Jan
1
2
2
2
2
2
3
4
4

Feb
1
2
2
2
2
2
3
4
4

Mar
1
2
2
2
2
2
3
4
4

Apr
1
2
2
2
2
2
3
4
4

May
1
2
2
2
2
2
3
4
4

Jun
1
2
2
2
2
2
3
4
4

Jul
1
2
2
2
2
2
3
4
4

Aug
1
2
2
2
2
2
3
4
4

Sep
1
2
2
2
2
2
3
4
4

Oct
1
2
2
2
2
2
3
4
4

Nov
1
2
2
2
2
2
3
4
4

Dec
1
2
2
2
2
2
3
4
4

LIGHTING (Fractional)
Hourly Profiles:
1: Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2: Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3: Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4: Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Assignments:
Design
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Holiday

Jan
1
2
2
2
2
2
3
4
4

Feb
1
2
2
2
2
2
3
4
4

Mar
1
2
2
2
2
2
3
4
4

Apr
1
2
2
2
2
2
3
4
4

May
1
2
2
2
2
2
3
4
4

Jun
1
2
2
2
2
2
3
4
4

Jul
1
2
2
2
2
2
3
4
4

Aug
1
2
2
2
2
2
3
4
4

Sep
1
2
2
2
2
2
3
4
4

Oct
1
2
2
2
2
2
3
4
4

Nov
1
2
2
2
2
2
3
4
4

Dec
1
2
2
2
2
2
3
4
4

LOAD (Fractional)
Hourly Profiles:
1: Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2: Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3: Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 24 of 32

Universal Consultancy Services


4: Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Assignments:
Jan
1
2
2
2
2
2
3
4
4

Design
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Holiday

Feb
1
2
2
2
2
2
3
4
4

Mar
1
2
2
2
2
2
3
4
4

Apr
1
2
2
2
2
2
3
4
4

May
1
2
2
2
2
2
3
4
4

Jun
1
2
2
2
2
2
3
4
4

Jul
1
2
2
2
2
2
3
4
4

Aug
1
2
2
2
2
2
3
4
4

Sep
1
2
2
2
2
2
3
4
4

Oct
1
2
2
2
2
2
3
4
4

Nov
1
2
2
2
2
2
3
4
4

Dec
1
2
2
2
2
2
3
4
4

PEOPLE (Fractional)
Hourly Profiles:
1: Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2: Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3: Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4: Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Assignments:
Jan
1
2
2
2
2
2
3
4
4

Design
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Holiday

Feb
1
2
2
2
2
2
3
4
4

Mar
1
2
2
2
2
2
3
4
4

Apr
1
2
2
2
2
2
3
4
4

May
1
2
2
2
2
2
3
4
4

Jun
1
2
2
2
2
2
3
4
4

Jul
1
2
2
2
2
2
3
4
4

Aug
1
2
2
2
2
2
3
4
4

Sep
1
2
2
2
2
2
3
4
4

Oct
1
2
2
2
2
2
3
4
4

Nov
1
2
2
2
2
2
3
4
4

Dec
1
2
2
2
2
2
3
4
4

THERMOSTAT (Fan / Thermostat)


Hourly Profiles:
1: Profile One
Hour 00 01
Value O
O

02
O

03
O

04
O

05
O

06
O

07
O

08
O

09
O

10
O

11
O

12
O

13
O

14
O

15
O

16
O

17
O

18
O

19
O

20
O

21
O

22
O

23
O

2: Profile Two
Hour 00 01
Value O
O

02
O

03
O

04
O

05
O

06
O

07
O

08
O

09
O

10
O

11
O

12
O

13
O

14
O

15
O

16
O

17
O

18
O

19
O

20
O

21
O

22
O

23
O

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 25 of 32

Universal Consultancy Services


3: Profile Three
Hour 00 01
Value O
O

02
O

03
O

04
O

05
O

06
O

07
O

08
O

09
O

10
O

11
O

12
O

13
O

14
O

15
O

16
O

17
O

18
O

19
O

20
O

21
O

22
O

23
O

4: Profile Four
Hour 00 01
Value O
O

02
O

03
O

04
O

05
O

06
O

07
O

08
O

09
O

10
O

11
O

12
O

13
O

14
O

15
O

16
O

17
O

18
O

19
O

20
O

21
O

22
O

23
O

O = Occupied; U = Unoccupied
Assignments:
Design
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Holiday

iii.

Jan
1
2
2
2
2
2
3
4
4

Feb
1
2
2
2
2
2
3
4
4

Mar
1
2
2
2
2
2
3
4
4

Apr
1
2
2
2
2
2
3
4
4

May
1
2
2
2
2
2
3
4
4

Jun
1
2
2
2
2
2
3
4
4

Jul
1
2
2
2
2
2
3
4
4

Aug
1
2
2
2
2
2
3
4
4

Sep
1
2
2
2
2
2
3
4
4

Oct
1
2
2
2
2
2
3
4
4

Nov
1
2
2
2
2
2
3
4
4

Dec
1
2
2
2
2
2
3
4
4

SYSTEM INPUT DATA:

1. General Details:
Air System Name .................................................................................. SWGR
Equipment Type ..................................................................... Terminal Units
Air System Type ................................................................. Split DX Fan Coil
Number of zones ........................................................................................... 1
Ventilation .......................................................................... Direct Ventilation
2. Ventilation System Components:
(Common Ventilation System not used: no inputs)
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
SWITCH GEAR

x1

Thermostats and Zone Data:


Zone ........................................................................................................... All
Cooling T-stat: Occ. .................................................................................. 34.4
Cooling T-stat: Unocc. .............................................................................. 34.4
Heating T-stat: Occ. .................................................................................. 20.0
Heating T-stat: Unocc. .............................................................................. 20.0
T-stat Throttling Range ............................................................................. 0.83

C
C
C
C
K

Thermostat Schedule .............................................................. THERMOSTAT


Unoccupied Cooling is .............................................................. Not Available
Common Terminal Unit Data:
Cooling Coil:
Design Supply Temperature ..................................................................... 12.8 C
Coil Bypass Factor ................................................................................. 0.100
Cooling Source ........................................................................ Air-Cooled DX
Schedule ............................................................................ JFMAMJJASOND
Heating Coil:
Design Supply Temperature ..................................................................... 43.3 C
Heating Source ........................................................... Air Source Heat Pump
Schedule ............................................................................ JFMAMJJASOND
Fan Control .......................................................................................... Fan On
Ventilation Sizing Method ................................... Sum of Space OA Airflows

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 26 of 32

Universal Consultancy Services

Terminal Units Data:


Zone ........................................................................................................... All
Terminal Type ................................................................................... Fan Coil
Minimum Airflow ....................................................................................... 0.00 L/s/person
Fan Performance ........................................................................................... 0 Pa
Fan Overall Efficiency .................................................................................. 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ................................................................................. 7.0 K
Hot Water Delta-T ..................................................................................... 10.0 K
Safety Factors:
Cooling Sensible .......................................................................................... 10 %
Cooling Latent ............................................................................................. 10 %
Heating ........................................................................................................ 10 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................ Sum of space airflow rates
Space Airflow Sizing Method ............................ Individual peak space loads

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 27 of 32

Universal Consultancy Services

SECTION 7

CALCULATION RESULTS

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 28 of 32

SGR.
ROOM

SGR.
ROOM
SGR.
ROOM

SPACE

166

166

166

10SAD03AN002*

3.6

10SAD01AH003,4

3.6

3.6

INDOOR
COND.

34.4

34.4

34.4

NA

NA

NA

Fax. + 962.6. 55 22 476

(-)

(+)

(+)

PRESS.
RELATED
TO
ADJUST.
SPACES
(Pa)
COOLING
LOAD

3.6

3.6

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Tel. + 962.6. 55 29 476

46

46

46

SPACE
VOLUME
(m3)

DB
(C)

CEILING
HEIGHT
(m)

RH
(%)

FLOOR
AREA
(m2)

SEN.
(kW)
-

569

569

SUPPLY
AIRFLOW
(m3/h)

1987

EXHAUST
AIRFLOW
(m3/h)

Page 29 of 32

OUTDOOR
AIR
(m3/h)

Email: info@ucs-jo.com

RETURN
AIRFLOW
(m3/h)

INDOOR
COND.

DB
(C)
-

20

20

2.95

2.95

HEATING
LOAD
(KW)

LOAD CALCULATION/
WINTER

RH
(%)

LOAD CALCULATION/ SUMMER

COOLING
CAPACITY
(KW)

3.96

3.96

3.96

3.96

HEATING
CAPACITY
(KW)

SELECTED EQUIPMENT
WITH 10% EXTRA

SEN.
(kW)

RESULTS SUMMARY:

*Pending

i.

LAT.
(kW)

Universal Consultancy Services

LAT.
(kW)

SYSTEM

Universal Consultancy Services


ii.

Air System Sizing Summary:

Air System Information

Air System Name ............................................. SWGR


Equipment Class .............................................. TERM
Air System Type ........................................... SPLT-FC

Number of zones .......................................................... 1


Floor Area ................................................................ 46.1 m
Location ................................................ Amman, Jordan

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s ......................... Sum of space airflow rates


Space L/s ..................... Individual peak space loads

iii.

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Zone Sizing Summary:

Air System Information

Air System Name ............................................. SWGR


Equipment Class .............................................. TERM
Air System Type ........................................... SPLT-FC

Number of zones .......................................................... 1


Floor Area ................................................................ 46.1 m
Location ................................................ Amman, Jordan

Zone and Space Sizing Method:


Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Sizing Calculation Information

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
7.5

Design
Air
Flow
(L/s)
316

Minimum
Air
Flow
(L/s)
316

Time
of
Peak
Load
Jul 1700

Maximum
Heating
Load
(kW)
5.2

Total
Coil
Load
(kW)
7.2

Sens
Coil
Load
(kW)
7.2

Coil
Entering
DB / WB
(C)
35.0 / 19.6

Coil
Leaving
DB / WB
(C)
14.3 / 12.7

Water
Flow
@ 7.0 K
(L/s)
-

Heating
Coil
Ent/Lvg
DB
(C)
16.7 / 33.6

Htg Coil
Water
Flow
@10.0 K
(L/s)
-

Fan
Design
Airflow
(L/s)
316

Fan
Motor
(BHP)
0.000

Zone
Floor
Area
(m)
46.1

Zone
L/(s-m)
6.85

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Heating
Coil
Load
(kW)
5.9

Fan
Motor
(kW)
0.000

OA Vent
Design
Airflow
(L/s)
46

Space Loads and Airflows


Zone Name /
Space Name
Zone 1
SWITCH GEAR

Tel. + 962.6. 55 29 476

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

7.5

Jul 1700

316

5.2

46.1

6.85

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 30 of 32

Universal Consultancy Services

iv.

Air System Design Load Summary:

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Exhaust Fan Load
Ventilation Load
Ventilation Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Terminal Unit Cooling
Terminal Unit Heating
>> Total Conditioning
Key:

Tel. + 962.6. 55 29 476

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1700
HEATING DATA AT DES HTG
COOLING OA DB / WB 34.3 C / 19.1 C
HEATING OA DB / WB 0.9 C / -2.3 C
Sensible
Latent
Sensible
Latent
Details
(W)
(W)
Details
(W)
(W)
12 m
891
12 m
56 m
46
56 m
401
46 m
678
46 m
2201
12 m
-65
12 m
802
0 m
0
0 m
0
4 m
-34
4 m
421
46 m
0
46 m
363
44 m
2145
44 m
527
0 m
0
0 m
0
1090 W
1090
0
0
0W
0
0
0
2000 W
2000
0
0
1
72
60
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
682
6
10%
471
0
7506
66
5186
0
7234
66
4929
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
0 L/s
0
0 L/s
0
46 L/s
-43
-67
46 L/s
939
0
0 L/s
0
0 L/s
0
0
0
0%
0
0%
0
7191
-1
5868
0
7191
0
0
0
0
5868
7191
0
5868
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 31 of 32

Universal Consultancy Services

v.

Exhaust Air Louver Sizing

As per EDG vendor requirements, the exhaust louver shall be 2100x2100mm


vi.

Fresh Air Louver Sizing

As per OFR requirements & standards, the fresh velocity is 2 m/s across Louver. As per vendor requirements the
flow is
Flow: 13520 L/s
Hence, area is:
2
Total Area= 13520/(2x1000) = 6.76 m
This area is higher than that suggested by vendor.
Hence, a louver of area 2600x2600mm in lieu of 2300x2300 mm suggested by the vendor

Tel. + 962.6. 55 29 476

Fax. + 962.6. 55 22 476

P:\U00-238-03\calcs\mech\EDG\EDG HVAC REP-27-2-2010.rtf

Email: info@ucs-jo.com
Page 32 of 32

You might also like