GB50263-2007
GB50263-2007 Code for installation and acceptance of gas
extinguishing system
2000
Safety inspection regulations for gas cylinders (2000 version)
-2-
Contents
........................................................................ - 7 I. System introduction............................................................. - 7 ................................................... - 11II. Structure and working principle........................................- 112.1 ................................................................. - 112.1 System classification.............................................. - 11 2.2 ........................................................ - 12 2.2 Working principle................................................... - 12 2.3 ............................ - 12 2.3 Control modes and operating regulations...............- 12 2.4 ................................................ - 18 -3-
2.4 Cabinet HFC-227ea fire extinguishing equipment.- 18 2.5 ........................ - 21 2.5 Hanging System (wall-hanging type)..................... - 21 2.6 ............................................ - 23 2.6 System with a piping system.................................. - 23 .......................................... - 26 III. Main parts and data of the System with a piping system- 26 3.1 ........................................................... - 26 3.1 Extinguishant storage cylinder group..................... - 26 3.2 ....................................................................... 27
3.2 Starting gas cylinder group............................................ 27
3.3
........................................................................ 29
3.5 .......................................... 32
3.5 High-pressure metal hose (connecting hose)................. 32
3.6 ................................................................... 33
3.6 Liquid flow check valve................................................ 33
3.7 ........................................................................... 33
3.7 Safety valve................................................................... 33
3.8 ........................................................................... 34
3.8 Header............................................................................34
3.9 ............................................................................. 35
3.9 Nozzles....................................................................... 35
3.10 ................................................................. 35
3.10 Pressure signal device..................................................35
3.11 ................................................................. 36
3.11 Gas flow check valve................................................... 36
......................................... 37
-5-
-6-
I. System introduction
HFC-227ea
13011211
HFC-227ea is a colorless, almost tasteless and
non-conductive gas without secondary pollution. It is
characterized by high cleanliness, no toxicity, high fire
extinguishing efficiency, small space occupation, low piping
system pressure, etc. Particularly, without damage for the ozone
layer and with short time of stay in the atmosphere, it is much
more environment friendly than alkyl halides. It is now a most
successful clean gas extinguishant and an optimal product for
substituting alkyl halides 1301 and 1211 as well.
DBJ15-23-1999HFC-227ea
ISO14520-9-
/
The System essentially consists of a storage cylinder group,
a storage cylinder group rack, drive cylinders, a liquid flow
check valve, a gas flow check valve, a header, selector valves,
tees, bends, flanges, pipe reducers, safety valves, a pressure
signal feedback device, high-pressure metal hoses, a nozzle, a
HFC-227ea extinguishant, a smoke detector, a gas fire
extinguishing controller, an audible and visual alarm, an alarm
bell, a gas discharge indicator and an E-start/stop button.
-8-
1
(1) Chemicals and mixtures
(1) Electrical fires;
including oxidants such as
2 nitrocellulose and sodium nitrate;
2
(2) Fires of liquid surfaces
of meltable solids;
(2) Active metals such as K, Na,
3
Mg, Ti, Zr and U;
(3) Fire of solid surfaces;
3
4
-9-
- 10 -
II. Structure and working principle
2.1
2.1 System classification
2.2
2.2 Working principle
H+OH-O2
2.3
2.3 Control modes and operating regulations
/
30s
- 13 -
(1) Automatic control: The gas fire extinguishing controller is
provided with a smoke detector and a heat detector. It has a
control mode selection lock. When the lock is put in the AUTO
position, the gas fire extinguishing controller will enter the
automatic control mode. After either of the detectors sends a fire
signal, the gas fire extinguishing controller will send an alarm
bell alarm signal to inform relevant persons of the abnormality
and not start the fire extinguishing device for releasing the
extinguishant. (Note: When it is necessary to start the fire
extinguishing device for fire extinguishing, press the E-start
button. After that, the fire extinguishing device will start and
release the extinguishant for fire extinguishing.) After both the
detectors send a fire signal, the gas fire extinguishing controller
will send an audible and visual alarm signal to inform relevant
persons of the fire and reminding relevant persons of evacuating
from the scene and sending an online command for stopping
linkage devices such as the fan and the fire damper. After a
delay of thirty seconds, the gas fire extinguishing controller will
send a fire extinguishing command for turning on the solenoid
valve, starting the gas source, turning on the cylinder valves and
releasing the extinguishant for fire extinguishing. If it is found in
the delay that the fire extinguishing device does not need to be
started, press the E-stop button on the controller operation panel
out of the protected area to terminate sending of the fire
extinguishing command. After that, the fire extinguishing device
will not be started and the automatic control mode of the System
will be terminated.
2
- 14 -
1.2.
3.
- 15 -
Fire alarm
Fire detector
Evacuation of persons
Electrical manual
Relay
- 17 -
Fire extinguishing
Device linkage (cut off the power supply, stop the fan
Injection display
2.4
2.4 Cabinet HFC-227ea fire extinguishing
equipment
DC24V 1.2A
1. 2. 3. 4.
5. 6. / 7.
1. Fire extinguishing device 2.Fire detector 3. Fire
extinguishing controller 4. Injection indicator 5. Audible and
visual alarm 6. E-start/stop button 7. Alarm bell
- 19 -
Main technical data of a cabinet System:
Model
20
(Kg)
Maximum
(MPa)
filling
Filling
capacity of
pressure
the
at 20
extinguish
( MPa)
(S)
Time
of
injectio
()
Operation
temperatur
n (s)
e ()
(M3)
Maximum
protective
volume
External
dimensions
( M3)
ant (kg)
GQQ-40
44.8
49
1450*450*400
GQQ-70
78.4
84
1550*450*400
GQQ-100
112
123
1700*500*450
GQQ-120
134.4
148
1900*500*450
GQQ-150
168
185
1900*550*500
GQQ-180
201.6
222
1700*720*620
2.5
10
- 20 -
0~50
2.5
2.5 Hanging System (wall-hanging type)
68
- 22 -
Electromagnetic hanging System
Supporting foot
Solenoid valve
Cylinder valve
Piping system
Nozzle
Pressure gauge
Extinguishant outlet
Heat-sensing element
2.6
2.6 System with a piping system
- 23 -
- 24 -
1./
6.
11.
16
21.
2.
7.
3.
8.
13.
12.
17.
18.
22.
4.
9.
14.
19.
5.
10.
15.
20.
- 25 -
III. Main parts and data of the System with a
piping system
3.1
3.1 Extinguishant storage cylinder group
1.
(1) Application: It is the main component for storing and
releasing the extinguishant.
2.
3.
(3) Main technical data
- 26 -
Kg/m
MPa
MPa
Maximum
Storage
Maximum
pressure
operating
mm
mm
Diameter
Height
(mm)
(mm)
QMQ-40
300
766
QMQ-70
350
940
QMQ-100
350
1280
QMQ-120
400
1430
QMQ-150
400
1590
QMQ-180
400
1650
Model
filling
950
4.2
6.7
3.2
3.2 Starting gas cylinder group
1)
(1) Application: It is used for storing and releasing the starting gas
(nitrogen).
2)
-27-
Model
QQP4/6
QQP7/6
Mpa
Design pressure
(Mpa)
6.0
(L)
Volume
(L)
Mpa
Operating pressure of
the safety pressure
relief device (MPa)
Medium
8.80.44
Nitrogen
-28-
3.3
3.3 Cylinder valves
Drive valve
-29-
20
Cylinder valve
Model
Operating pressure
Detector
below 20
HQF37/4.2
5.3MPa
HQF50/4.2
Pressure gauge
cylinder group
Drive valve
ECF6/6
6.6MPa
Pressure gauge
Technical data:
1
-30-
3.4
3.4 Selector valves
Technical data:
QXZ/4.2
Model: QXZ/4.2
5.3MPa(20)
Operating pressure:
5.3MPa (20)
70N~150N
Manual starting force: 70N~150N
300mm
Manual operation displacement: 300mm
-31-
3.5
3.5 High-pressure metal hose (connecting
hose)
1
3.6
3.6 Liquid flow check valve
1
3.7
3.7 Safety valve
1
the driving gas cylinder group and 7.22MPa for the safety
valve on the header.
3.8
3.8 Header
1
2
(2) Structure: It mainly includes a seamless steel pipe, joints,
flanges and safety valves, etc.
3QJG50/4.2
(3) Model: QJG50/4.2
-34-
3.9
3.9 Nozzles
3.10
3.10 Pressure signal device
1):
Main performance data of the pressure signal feedback
device:
Model
QXFO.16/4.2
Operating
Working
pressure
pressure
5.3MPa
0.16MPa
Voltage
Current
DV24
1.2A
3.11
3.11 Gas flow check valve
1):
IV. Instructions for installation, debugging and
maintenance
Install the System in line with the design drawing and the
Code for design of gas fire extinguishing systems.
Adjustment must be done in the installation according to actual
conditions of the site. A simple installation flow is as below:
1.
GB50193-93
3. The piping system must be installed in strict line the
engineering design requirements. Its material, diameter, length,
surface treatment, route and nozzle specification should be
determined by the engineering design personnel in line with
GB50193-93 and not be changed without permission in
-37-
installation or construction.
4.
-38-
System with a piping system
1.
1. Determine the cylinder positions and assemble the storage
cylinder group rack.
2.
6. Mount and fix the other selector valves and outlet flanges
and mount and tighten the starting gas cylinders.
7.
7. Mount and fix the copper hoses delivered with the System
according to the design specification.
8.
8. Finally, mount and start the solenoid.
-39-
Cabinet System
1.
-40-
V. Maintenance
1.
(1) All parts of the System, such as the storage cylinders, the
-41-
-43-
5. The new safety diaphragms for replacement must be us. Do
not use any untested diaphragms.
6.
6. In dismantling and mounting, keep appearance of the System
from handling marks.
7.
2. Unplug the safety pin above the solenoid of the starter and
press the E-start button of the electromagnetic drive above the
corresponding drive cylinder group with a great force to release
the extinguishant for fire extinguishing.
3