Rev 3
SAIC NUMBER
SAIC-K-4002
PROJECT TITLE
WBS / BI / JO NUMBER
EQUIPMENT ID NUMBER(S)
EQUIPMENT DESCRIPTION
REV. NO.
30-Jun-08
DATE APPROVED
QR NUMBER
15-Dec-09
HVAC
CONTRACTOR / SUBCONTRACTOR
EQPT CODE
SYSTEM ID.
PLANT NO.
MH's SPENT
TRAVEL TIME
ITEM
No.
ACCEPTANCE CRITERIA
REFERENCE
A1
SAES-K-001
Para 4.8.9.1
A2
SAES-K-001
Para 4.8.9.1
A3
All exhaust fans shall have back draft dampers which shall close when
fan is off.
SAES-K-001
Para 4.8.9.2
A4
SAES-K-001
Para 4.8.14.3
A5
SAES-K-001
Para 5.1.4
A6
SAES-K-001
Para 4.4.10.3
A7
Exhaust fan used for ventilating the Battery Room shall have their
exhaust point (air outlet) located in the ceiling or its upper edge flush
with ceiling if it is located in a wall.
SAES-K-002
Para 6.4
A8
Fans and their Motors shall be accessible for servicing and maintenance
(UMC Para 503.1)
SAES-K-100
Section 1
PASS
FAIL
N/A
RE-INSP DATE
REMARKS:
REFERENCE DOCUMENTS:
1-SAES-K-001 -- Heating, Ventilating and Air Conditioning (HVAC), 25 November, 2006
2-SAES-K-002 -- Air Conditioning System for Essential Operating Facilities 31 May , 2004
3- Uniform Mechanical Code (UMC), 1997
4-SAES-K-100 -- Saudi Aramco Mechanical (HVAC) Code, 31 May , 2004
Contractor / Third-Party
Saudi Aramco
Construction Representative*
PMT Representative
QC Inspector
QC Record Reviewed
Work Verified
T&I Witnessed
QC Record Reviewed
Work Verified
T&I Witnessed
QC Record Reviewed
Work Verified
PID Representative
Performed Inspection
QC Supervisor
T&I Witnessed
Name, Initials and Date:
Name, Organization,
Initials and Date:
Page 1 of 2
Y = YES
Page 2 of 2
N = NO F = FAILED