ABSTRACT

This experiment was conducted to perform energy and mass balance on the cooling
tower system and to observe the effects of one of the process variables on the exit
temperature of water. For water cooling tower experiment, there are several parameters that
can be adjusted to observe its effects on the evaporation of water. The parameters are
temperature and flow rate of water, relative humidity and flow rate of air and cooling load. In
this experiment, we choose the cooling load as variable while water flow rate and flow rate as
constant parameters. The steady flow equations which is energy and mass balances were
employed in order to provide an insight on the amount of energy transferred between phases
under different conditions. The energy transfer calculated from the experiment for cooling
load of 0.5 kJ/s , 1.0 kJ/s and 1.5 kJ/s.

INTRODUCTION
The laboratory cooling tower is a cooling tower unit from a commercial air
conditioning system used to study the principles of cooling tower operation. It is used in
conjunction with a residential size water heater to simulate a cooling tower used to provide
cool water to an industrial process. In the case of the laboratory unit, the cooling tower
process load is provided by the water heater. The laboratory cooling tower allows for
complete control of the speed of the fan used in cooling the warm return water and the pump
used to return the cooled water to the water heater.
Experiments can be conducted which study how adjustment of one or both of these
parameters affects the amount of heat removed from the water provided to the water heater.
The remainder of this report will explain the theory behind the operation of a cooling tower
and how the laboratory cooling tower is operated. An example of a mass and energy balance
on the laboratory cooling tower will be presented along with the results of experiments in
which the rate of heat dissipated by the tower was calculated at full capacity and when the
pump speed and fan speed were varied independently.

OBJECTIVE
To study the performance at different ranges cooling load and inlet temperature of
cooling tower.

THEORY
The cooling tower experiment operate according to the First Law of Thermodynamics
which is the conservation of energy. Energy can neither be created nor destroyed, just
transformed from one form to another. The energy that enter the system must exit the
systemas it can diffuse through the system. Energy that enters the cooling tower is in the form
of hot water. (Other energy contributions such as heat generation fromfriction of both air and
water, energy losses from pipes, etc. are ignored.) This hot water was cooled from
temperature T1to a temperature of T2. The cooling of the hot water was in the form of
forced convection 3 by which ambient air at T1 was blown over the hot water and exited the
cooling tower at some temperature T2. The data of both the enterence and the exit
temperature was recorded.
The main component of the energy balance is enthalpy which is defined as:
H = U + PV.
H = enthalpy
U = internal energy
P = pressure
V = is volume

This equation is related to the heat as it is use to calculate the enthalpy of the system.
Enthalpy can be calculated or referenced from tables of data for the fluid being used. In this
experiment we used the air and wateras the fluids in the cooling tower. Enthalpy values can
be obtained from a thermodynamics textbook. For example: Since both the initial and
finaltemperatures of the input hot water and the output cool water were measured, the
temperature T in can be referenced and the enthalpy (BTU/lbm, or KJ/kg) can be recorded.
The enthalpy of the output cooled water can be similarly referencedand an energy balance

can be conducted for the water.The equation below displays the general method to conduct an
energy balance:

in =

where

out

H = H in - H out.

The change in enthalpy for air can be determined form either of two methods. Since the air is
at low pressure, it can be treated as an ideal gas and the enthalpy change can be calculated
through the use of the following equation:
H = Cp
where

T (3)

H is the change in enthalpy,

T is the change in temperature, and Cp is the

specific heat with respect to constant pressure.


As water going into the cooling tower it loses energy. The enthalpy of the water going
into the tower can be determined by using the enthalpy of saturated liquid water in a steam
table. The enthalpy of the water coming out of the tower can be determined in the same way.
The data in steam tables are usually not given for every temperature so linear interpolation
must be performed to determine the enthalpy at the desired temperature. Then the enthalpy of
the water is multiplied by the mass flow rate. A basis of an operation of 1 minute was chosen
to make the calculation easier. The change in enthalpy for the water is determined by

.
The change in energy of the air can be determined using the same methodology as was used
for water. The enthalpy change is shown as

However, the determination of the enthalpy of air is more complicated than the
determination of the enthalpy values of the water stream. Now that the mass flow rate of dry
air is known, the enthalpy values of the in and out streams can be determined. The change in
enthalpy of the water should have a negative value, and the change in enthalpy of the air
should have a positive value. Theoretically, when the two values are added together, the result
should be zero. This can be shown by the first law of thermodynamics where

and

APPARATUS AND SET UP

Stopwatch
Deionized water
SOLTEQ Bench Top Cooling Tower Unit (Model: HE152)

1. Orifice
2. Water distributor
3. Packing column
4. Flow meter
5. Receiver tank
6. Air blower
7. Make-up tank
8. Differential Pressure Transmitter
9. Load Tank
10. Control Panel

PROCEDURE
1. Valves V1 and V6 were checked and ensured to be closed and valve V7 to be partially
opened.

2. The load tank was filled with deionized water. Firstly, the make-up tank was removed
and deionized water was poured through the opening at the top of the load tank. The
make-up tank was replaced onto the load tank and the nuts were lightly tightened.
3.
4.
5.
6.

Then, the tank was filled with deionized water up to the zero mark and the scale.
Deionized water was added to the wet bulb sensor reservoir to the fullest.
All appropriate tubing was connected to the differential pressure sensor.
The appropriate cooling tower packing was installed for the experiment.
Temperature set point of temperature controller was set to 45 o-C. The 1.0kW water

heater was switch on and water was heated up to 40oC.


7. The pump was switched on and the control valve V1 was slowly opened and the water
flow rate was set to 2LPM.
8. The damper was fully opened and the fan was switched on.
9. Blower switch was switched on after the water already went through the cooling
tower.
10. The unit was run for 20 minutes to ensure float valve correctly adjusted the level in
the load tank. The make-up tank was refilled as required.
11. The damper and the flow rate were set to be constant.
12. The 1.0kW water heater was switched off to set the power as 0kW.
13. Record all the data required after 10 minute to ensure the unit stabilized for first trial
and another 10 minutes for second trial.
14. To measure the differential pressure across the orifice , valves V4 and V5 were
opened while valves V3 and V6 were closed.
15. To measure the differential pressure across the column, valves V3 and V6 were
opened while V4 and V5 were closed.
16. The water heater then was set to 0.5kW, 1.0kW and 1.5kW.
17. After all the experiments were done, the heaters were switched off and the water was
let to circulate through the cooling tower system for 3-5 minutes until the water
cooled down.
18. The fan was switched off and the fan damper was closed fully
19. The pump and power supply were switched off.
RESULT

Heater
Column B
Water flow rate : 1.0 LPM
Blower: fully opened

Heater (kW)
Air inlet dry bulb, T1(C)
Air inlet wet bulb, T2(C)
Air outlet dry bulb, T3(C)
Air outlet wet bulb, T4(C)
Water inlet temperature,

0.5
26.8
27.5
25.6
25.9
36.6

1.0
26.7
27.3
26.1
26.6
38.7

1.5
26.9
27.3
27.4
28.0
44.9

T5(C)
Water outlet temperature,

25.1

25.6

26.1

T6(C)
Heater power (W)
Dp orifice
Dp column

425
108
0

801
108
0

1232
108
0

Water flow rate


Column B
Heater: 1.0 KW
Water flow rate (LPM)
Air inlet dry bulb, T1(C)
Air inlet wet bulb, T2(C)
Air outlet dry bulb, T3(C)
Air outlet wet bulb, T4(C)
Water inlet temperature,
T5(C)
Water outlet

0.8
27.3
27.8
28.1
29.7
48.2

temperature, 26.9

T6(C)
Heater power (W)
Dp orifice, (Pa)
Dp column, (Pa)
Blower : fully opened

829
111
0

1.0
27.6
28.0
26.8
26.7
39.9

1.2
27.9
28.1
26.1
23.3
30.1

1.4
27.4
27.9
26.2
21.5
26.0

1.6
27.2
27.5
26.0
20.2
23.5

25.9

24.8

23.5

22.9

812
109
0

801
107
0

796
105
0

784
102
0

CALCULATION
Experiment 1
Water flow rate constant = 1.0LPM
Variable : heater
Change in temperature for each power supply, T (cooling range)
= water inlet temperature,T5 water outlet temperature, T6
Power = 0.5 kW
T =T 5T 6
36.625.1
11.5

Power =1.0 kW
T =T 5T 6
38.725.6

13.1
Power =1.5 kW
T =T 5T 6
44.926.1

18.8

Experiment 2
At water flow rate 0.8 LPM = 0.013 kg/s
Cooling range, T

= water inlet temperature,T5 water outlet temperature,T6


= 48.2 26.9
=21.3C

Heat load Q

= mCpT
= 0.013kg/s x 4.186 x 21.3C
= 1.1591kW

Water flow rate (LPM)


0.8
1.0
1.2
1.4
1.6

Heat load, kW
1.1591
0.9962
0.4526
0.1494
0.3302

Cooling range, C
21.3
14.0
5.3
2.5
0.6

DISSCUSSION
From this experiment, the instrument was used in this experiment is Water Cooling
Tower HE152 unit. All cooling towers operate on the principle of removing heat from water
by evaporating a small portion of the water that is recirculated through the unit. The heat that
is removed is called the latent heat of vaporisation. This experiment consist of three
experiment. Experiment 1: Investigation of the effect of different the power of heater toward
cooling range of cooling tower. Experiment 2: Investigation of the effect of cooling range
toward different water flow rate.
There are several term in principle of cooling tower need to be focused when conducting
this experiment as a basic knowledge to perform experiment perfectly. First, cooling range.
The difference in temperature between the hot water entering the tower and the cold water
leaving the tower is the cooling range. Second is approach. The difference between the
temperature of the cold water leaving the tower and the wet-bulb temperature of the air is
known as the approach. Establishment of the approach fixes the operating temperature of the
tower and is a most important parameter in determining both tower size and cost. Others is
heat load and wet-bulb temperature. Heat Load is the amount of heat to be removed from the
circulating water within the tower. Heat load is equal to water circulation rate (gpm) times the
cooling range times 500 and is expressed in BTU/hr. Heat load is also an important parameter

in determining tower size and cost. Wet-Bulb Temperature is the lowest temperature that
water theoretically can reach by evaporation. Wet-Bulb temperature is an extremely important
parameter in tower selection and design and should be measured by a psychrometer.
For experiment 1, Investigation of the effect of different the power of heater toward
cooling range of cooling tower based on three different value of power of heater which is 0.5
kW, 1.0 kW and 1.5 kW give the result of three different cooling range. When we used the
value of heater power above it will resulting the value of cooling range 11.5C, 13.1C, and
18.8C respectively. It show that increasing the value of heater power will increase the
temperature of cooling range in cooling tower by constant of air blower and constant water
flow rate which is 1.0 LPM (liter per minute).
For experiment 2, we have investigate of the effect of cooling range toward different
water flow rate. We choose to investigate the relationship between the flow rate and the
cooling effect at 0.8 (LPM), 1.0 (LPM), 1.2(LPM), 1.4(LPM) and 1.6(LPM). From the
calculation, the value of cooling range where T5-T6 will show the decresing value which is
21.3C, 14.0C, 5.3C, 2.5C and 0.6C respectively. From this data we can conclude that the
faster water flow rate will give small value of mass transfer which in this term of heat transfer
in this cooling system. In this experiment also we can calculate the value of heat load based
on different water flow rate. From calculation, the heat load show the value 1.1591 kW,
0.9962 kW, 0.4526 kW, 0.1492 kW and 0.3302 kW respectively. It prove that the heat that
released is become decrease when the water flow rate is increase.

CONCLUSION
For the conclusion of this experiment, we can said that this experiment was
successfully conducted because the objective of the experiment had achieved. This
experiment consist of two part which is experiment 1 and 2. For experiment 1 we can
conclude that if the value of heater power is increasing the temperature of the cooling range
in the cooling tower will increase. In experiment 2, based on the result obtain, we can
conclude that the higher the water flowrate , the lower the energy in the form of heat transfer
or released and the higher the power the lower the energy transfer.

RECOMMENDATION
In order to obtain better results, there are a few methods or recommendations that may be
considered.
1. The auxiliary heaters always be used during experiments in order to increase the
temperature difference between the return water from the water heater and the cool
supply water. This increase in temperature difference will allow for a larger enthalpy
difference and will decrease the possibility of the enthalpy difference being negligible.
2. The humidity recording devices were not working properly. So,be recalibrated or
3.
4.
5.
6.

replaced so that more accurate and timely measurements of humidity can be made.
Use appropriate safety PPE when conducting the experiment
Make consultation with lab assistance before run the experiment
Make sure student know how to use the equipment.
Avoid any of mistake and error when conducting the experiment to get best result. Stay
alert to the time taken of every ten minutes running.