Professional Documents
Culture Documents
Approvals
Characteristics
Monitoring of DC and AC voltages from 3-600 V
TRMS measuring principle
One device includes 4 measuring ranges
Over- or undervoltage monitoring configurable
Hysteresis adjustable from 3-30%
Tripping delay TV adjustable 0; 0.1-30 s
3 supply voltage versions
2 c/o contacts
22.5 mm (0.89 in) width
3 LEDs for indication of operational states
GL
GOST
CB Scheme
CCC
RMRS
(pending)
Marks
CE
C-Tick
Order data
Voltage monitoring relays
Type
Measuring ranges
Order code
CM-ESS.2
24-240 V AC/DC
110-130 V AC
220-240 V AC
Type
Description
Order code
ADP.01
MAR.02
COV.01
Accessories
Functions
Operating controls
1 Adjustment of the hysteresis
2 Adjustment of the threshold value
3 Indication of operational states
U/T: green LED control supply voltage, timing
R: yellow LED relay status
3
4
5
6
Application
Depending on the configuration, the voltage monitoring relays CM-ESS.2 can be used for over- d or undervoltage
monitoring c in single-phase AC and/or DC systems. The devices work according to the open-circuit principle.
Operating mode
The voltage monitoring relay CM-ESS.2 has 2 c/o contacts. One device includes 4 measuring ranges:
3-30 V, 6-60 V, 30-300 V, and 60-600 V.
The unit is adjusted with potentiometers and switches on the top of the unit. The selection of over- d or undervoltage
monitoring c is made with a DIP switch . Potentiometers, with direct reading scale, allow the adjustment of the threshold
value U, of the hysteresis % and of the tripping delay TV. The hysteresis % is adjustable within a range of 3 to 30% of the
threshold value, and the tripping delay TV over a range of instantaneous to a 30 s delay.
The voltage to be monitored (measured value) is applied to terminals B-C. The supply voltage applied to terminals A1-A2 is
displayed by the glowing green LED.
If the measured value exceeds the adjusted threshold value, the tripping delay TV starts and the red LED (overvoltage)
glows. Timing of TV is displayed by the flashing W green LED. When TV is complete and the measured value still
exceeds the threshold value minus the adjusted hysteresis, the output relays energize and the yellow LED (relay energized)
glows.
If the measured value drops below the threshold value minus the adjusted hysteresis, the output relays de-energize and the
red and yellow LEDs turn off.
A1-A2
Threshold
Hysteresis
Measured value
< TV
TV
11-14 (15-18)
11-12 (15-16)
21-24 (25-28)
21-22 (25-26)
green LED
red LED
yellow LED
The voltage to be monitored (measured value) is applied to terminals B-C. The supply voltage applied to terminals A1-A2 is
displayed by the glowing green LED.
If the measured value decreases below the adjusted threshold value, the tripping delay TV starts and the red LED
(undervoltage) flashes W . Timing of TV is displayed by the flashing W green LED. When TV is complete and the
measured value is still below the threshold value plus the adjusted hysteresis, the output relays energize and the yellow LED
(relay energized) glows.
If the measured value exceeds the threshold value plus the adjusted hysteresis, the output relays de-energize and the red
and yellow LEDs turn off.
A1-A2
Measured value
TV
< TV
Hysteresis
Threshold
21-24 (25-28)
21-22 (25-26)
green LED
red LED
yellow LED
11-14 (15-18)
11-12 (15-16)
Connection diagram
A1
B
B
1115
1115
2125
2125
A1-A2
B-C
1216
2226
C
A2
ON
Undervoltage monitoring
OFF
Overvoltage monitoring
OFF = Default
Technical data
Data at Ta = 25 C and rated values, unless otherwise indicated
Input circuit
Supply circuit
A1-A2
110-130 V AC
-15...+10%
Rated frequency
Current / power consumption
220-240 V AC
50/60 Hz
24 V DC
24-240 V AC/DC
50/60 Hz or DC
30 mA / 0.75 W
115 V AC
24 mA / 2.6 VA
17 mA / 1.9 VA
230 V AC
12 mA / 2.6 VA
11 mA / 2.6 VA
On-period
100%
20 ms
varistors
Measuring circuit
B-C
Monitoring function
Measuring method
Measuring inputs
terminal connection
measuring range
input resistance
B-C
3-30 V, 6-60 V, 30-300 V, 60-600 V
600 k
800 V
continous capacity
660 V
Threshold value
3-30% adjustable
DC / 15 Hz - 2 kHz
DC / 50-60 Hz
AC
80 ms
DC
120 ms
U 0.5%
U 0.06% / C
varistors
Timing circuit
Delay time TV
0 or 0.1-30 s adjustable
t 0.5%
t 0.06% / C
Measured value
Relay status
U: red LED
R: yellow LED
Output circuits
Kind of output
11-12/14
21-22/24
Operating principle
AgNi
250 V
24 V / 10 mA
250 V AC / 4 A AC
AC12 (resistive) at 230 V
4A
3A
DC12 (resistive) at 24 V
4A
DC13 (inductive) at 24 V
2A
B 300
300 V AC
5A
3600/360 VA
(Make/Break) at B 300
Mechanical lifetime
n/c contact
10 A fast-acting
short-circuit protection
n/o contact
10 A fast-acting
General data
MTBF
Dimensions (W x H x D)
available on request
product dimensions
packaging dimensions
Weight
net weight
gross weight
Material of enclosure
PA 6
Mounting
Mounting position
Degree of protection
any
enclosure
IP50
terminals
IP20
Electrical connection
Wire size
Stripping length
7 mm (0.28 in)
Tightening torque
Environmental data
Ambient temperature
operation
-20...+60 C
storage
-40...+85 C
55 C, 6 cycle
class 2
class 2
Isolation data
Rated insulation voltage
600 V
250 V
6 kV 1.2/50 s
4 kV 1.2/50 s
2.0 kV, 50 Hz
(routine test)
2.5 kV, 50 Hz
III
Standards
Product standard
IEC/EN 60255-6
2006/95/EC
EMC Directive
2004/108/EC
RoHS Directive
2002/95/EC
Electromagnetic compatibility
Interference immunity to
IEC/EN 61000-6-2
electrostatic discharge
IEC/EN 61000-4-2
Level 3
IEC/EN 61000-4-3
Level 3
IEC/EN 61000-4-4
Level 3
surge
IEC/EN 61000-4-5
Level 3
IEC/EN 61000-4-6
Level 3
radio-frequency fields
Interference emission
IEC/EN 61000-6-3
high-frequency radiated
Class B
high-frequency conducted
Class B
Technical diagrams
V
300
V 200
V 200
100
80
60
50
40
30
100
80
60
50
40
30
20
10
0.1
0.2
0.5
2
I
10
A
V
300
AC load (resistive)
10
0.1
0.2
0.5
2
I
10
A
DC load (resistive)
Switching cycles
1.0
0.9
0.8
0.7
0.5
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos
Contact lifetime
250 V
resistive load
0.6
20
Dimensions
in mm and inches
109.5 4.31
22.5
0.886
1
0.155
100 3.94
78
3.07
102 4.02
5.5
0.216
CM-ESS.2
front-to-back
size 107
18 0.709
21 0.827
8
0.314
60 2.362
70 2.756
4T22
7 0.275
3.5 0.138
68.5 2.70
11.5
0.453
62.5 2.461
10
0.394
20
0.787
6.5
0.256
22.5
0.886
Further documentation
Document title
Document type
Document number
Technical catalogue
CM-ESS.1, CM-ESS.2
Instruction manual
You can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products ->
Electronic Relays and Controls -> Single Phase Monitors.
Contact us
Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.
We reserve all rights in this document and in
the subject matter and illustrations contained
therein. Any reproduction, disclosure to third
parties or utilization of its contents in whole
or in parts is forbidden without prior written
consent of ABB AG.
Copyright 2012 ABB
All rights reserved