Professional Documents
Culture Documents
164
Power Conductor
Current
Transformer
Current Relay
Termination
Polarity Mark
Internal Panel Wiring
Panel to Panel Cable
Figure10.1
Simplified current elementary diagramone relay, one CT.
Power
Conductor 1
Power
Conductor 2
CT 1
Current Relay
CT 2
CT 1
CT 2
Termination
Polarity Mark
Internal Panel Wiring
Panel to Panel Cable
Figure10.2
Simplified current elementary diagramone relay, two CTs.
diagrams. Note also that the power conductor between the CT and the VT
must be continuous; otherwise the relationship between current and voltage cannot be maintained.
Figure10.6 illustrates redundant current transformers installed on both
sides of a transmission-class circuit breaker. One set of CTs would be provided on the bus side for each of two sets of transmission-line relays and
one set of CTs would be provided on the line side for each of two sets of
bus differential relays. The CTs are connected so that the circuit breaker is
included in overlapping zones of protection.
Figure 10.7 illustrates how redundancy is achieved for voltage transformers installed for transmission system protection. A voltage transformer with one primary winding and multiple secondary windings is
connected to each phase. One secondary winding would be connected
2009 by Taylor & Francis Group, LLC
165
Power Conductor
Voltage
Transformer
Voltage Relay
Termination
Polarity Mark
Internal Panel Wiring
Panel to Panel Cable
Figure10.3
Simplified voltage elementary diagramone relay, one VT.
Power Conductor 2
Power Conductor 1
VT 1
Voltage Relay
VT 2
Termination
Polarity Mark
Internal Panel Wiring
Panel to Panel Cable
Figure10.4
Simplified voltage elementary diagramone relay, two VTs.
166
Power
Conductor
VT
Impedance Relay
CT
Termination
Polarity Mark
Internal Panel Wiring
Panel to Panel Cable
Figure10.5
Simplified current and voltage elementary diagram for an impedance relay.
Substation Bus
Scheme I
Line Prot
CTs
Scheme II
Line Prot
CTs
Power
Circuit
Breaker
Scheme I
Bus Di CTs
Scheme II
Bus Di CTs
Transmission
Line Conductor
Protective
Relays
Figure10.6
Simplified current elementary diagram showing redundant CTs.
The fuse can be placed in the positive leg, the negative leg, or both the
positive and negative legs of the DC power supply. (All DC circuits at a
substation must be fused the same.)
Figure 10.9 illustrates a simplified close circuit for a circuit breaker
that can be closed by local control switch, reclosing relay, and a remotely
controlled device (supervisory control). The close coil can be energized
via AC or DC power. Like a trip coil, a close coil is a small solenoid that
releases energy stored in a spring, pneumatic, or hydraulic actuator. The
2009 by Taylor & Francis Group, LLC
167
Power Conductor
Sec. Winding 1
Scheme I Relay
Sec. Winding 2
Scheme II Relay
Voltage
Transformer
Termination
Polarity Mark
Internal Panel Wiring
Panel to Panel Cable
Figure10.7
Simplified voltage elementary diagram showing redundant VTs.
Fuse
Control
Switch
Protective
Relay(s)
DC Power
Trip
Coil
Remote
Control
Device
Trip
Signals
CB
Closed
Indicator
Solid Link
Termination
Figure10.8
Simplified circuit-breaker trip circuit.
168
Fuse
Control
Switch
AC PowerDistr CBs
DC PowerTrans CBs
Remote
Control
Device
Reclosing
Relay
Initiate
Closing
CB Open
Indicator
Protective
Relay
Block
Closing
Interlocks
Local
Remote
CB
Close
Circuitry
Anti-pumping
Logic and other
Permissives
52 b
(Circuit Breaker Position Switch)
Solid Link
Termination
Figure10.9
Simplified circuit-breaker close circuit.
169
for circuit-breaker closing when AC power must be available before specific circuit breakers can be closed.
Usually, for simple control schemes, such as those for a 12-KV circuit
breaker that feeds a distribution line, the current elementary diagram,
voltage elementary diagram, circuit-breaker trip circuit, and circuitbreaker close circuit are shown on one drawing. More complex schemes,
such as those for transmission lines with redundant relaying, are shown
on several drawingsone for current elementary diagrams, one for voltage elementary diagrams, one for the Scheme I relaying, and one for the
Scheme II relaying. Wiring is usually shown on separate drawings.
When working with electromechanical and solid-state equipment, auxiliary relays, timers, interposing relays, and interlocks are used to set
up desired control scheme action. When working with microprocessorbased equipment, program instructions are used to set up desired control scheme action. In either case, drawings are used to illustrate control
scheme logic. An important consideration when developing elementary
diagrams is the inclusion of legends in the database. Otherwise, elementary diagrams may be misinterpreted. Interlocks can be manual or automatic, electromechanical or program instructions.
An example of an automatic interlock would be the interlock used with
low-set instantaneous overcurrent relays on overhead distribution lines
shown in Figure10.10.
Low-set instantaneous overcurrent relays are set at a relatively low
value, such as two or three times maximum circuit load. The theory is
that most overhead distribution line faults are transient and that if a fault
is detected and isolated quickly, the distribution line can be returned to
service without a significant outage to customers served by that line. An
interlock in the control scheme blocks the low-set instantaneous overcurrent relays from tripping the associated circuit breaker unless the circuit
breaker has remained closed for some predetermined time. The reset of
this type of interlock is hardwired, whether the protective relays are electromechanical, solid-state, or microprocessor-based, since reset is based
on circuit breaker status and the duration that a circuit breaker is closed.
An example of a manual interlock would be a blocking switch that prevents underfrequency relays from tripping selected feeder breakers at distribution substations as shown in Figure10.11.
One underfrequency relay cabinet is used for all feeders in a substation.
Blocking switches, which are manually opened or closed in individual
feeder circuit-breaker trip and close schemes, determine whether or not
the underfrequency relaying scheme is permitted to trip specific feeder
circuit breakers at the substation.
Auxiliary relays do not receive the attention given to protective relays
because their operation is predetermined (individual settings are not
170
Fuse
50 (Inst.)
Control
Switch
51
CBX
CBX
CB
Closed
Timer
DC Power
Trip
Coil
52 a
(Circuit Breaker Position Switch)
Solid Link
Termination
Figure10.10
Instantaneous overcurrent relay, block tripping circuitry.
developed for each application). Nevertheless, auxiliary relay characteristics and auxiliary relay response need to be properly addressed in order to
ensure that protection and control schemes meet design intent.
Usual practice is to minimize the use of low-voltage fuses in power
circuit-breaker trip circuits. This minimizes the possibility that a lowvoltage DC fuse opens inadvertently and removes control power from a
circuit-breaker trip coil.
Low-voltage fuses, when used in trip circuits, are sized as large as possible in order to further minimize the possibility of inadvertent fuse opening. Fuses are sized to protect wire from damage in the event that a trip
coil fails.
The use of timers can be illustrated by discussing the application of
phase distance relays. The phase distance relay that is used to provide
instantaneous detection and isolation of phase faults on the first 90% of a
transmission line (Zone 1) is identical to the phase distance relay that is
used to provide detection and isolation of phase faults on the last 10% of
a transmission line (Zone 2). Both relays are bipolar devices; that is, their
output contacts are either open or closed.
171
Fuse
Control
Switch
81
MT
51
81
BLK
(Manual)
DC Power
Trip Coil
52 a
(Circuit Breaker
Position Switch)
Solid Link
Figure10.11
Underfrequency relay, block tripping circuitry.
The Zone-1 relay is allowed to trip its associated circuit breaker directly
because it is known that any time the Zone-1 relay actuates, there must be
a fault on the protected line.
The Zone-2 relay, on the other hand, will overreach the protected line.
This is necessary so that when inaccuracies are taken into account, there
is an assurance that line-end faults can be detected and isolated. Since the
Zone-1 and Zone-2 relays are identical devices, the difference in circuitbreaker opening time is due to control scheme interlocks. Specifically, the
Zone-2 relay actuates a timer, usually set for about 0.4 seconds, and the
timerwhen it times outtrips the circuit breaker.
Zone-1 and Zone-2 circuit-breaker trip circuits are shown in
Figure10.12.
172
Fuse
Control
Switch
Z2T
21
Z1
DC Power
21
Z2
Z2T
Timer
Trip Coil
52 a
(Circuit Breaker Position Switch)
Solid Link
Figure10.12
Zone-1 and Zone-2 relays and circuit-breaker trip circuit.
173
DC Power 1
DC Power 2
DC Power3
Relay 1
Relay 2
Relay 3
Relay 2
Relay 3
Relay 1
Trip Coil 1
Trip Coil 2
Trip Coil 3
Scheme 1
Scheme 3
Scheme 2
Figure10.13
Two-of-three voting logic.
DC Power 1
DC Power 2
DI-SI
DI-SII
DI-SI
DI-SII
DII-SI
DII-SII
DII-SI
DII-SII
Trip Coil 1
Trip Logic 1
Trip Coil 2
Trip Logic 2
Figure10.14
One-of-two, taken twice logic.
taken twice logic is used when the consequences of an incorrect trip far exceed the cost of the additional protective relay
schemes.