You are on page 1of 14

CHAPTER 6

DUCT SYSTEMS

601.0 Scope. Exhaust ducts under positive pressure and


601.1 Ducts and plenums that are portions of a venting systems shall not extend into or pass
heating, cooling, absorption or evaporative cooling, through ducts or plenums. For appliance vents and
or product-conveying system shall comply with the chimneys, see Chapter 8.
requirements of this chapter. 602.2 Combustibles Within Ducts or Plenums.
601.2 Sizing Requirements. Duct systems used Materials exposed within ducts or plenums shall be
with blower-type equipment that are portions of a noncombustible or shall have a flame spread index
heating, cooling, absorption, evaporative cooling, or not greater than twenty-five (25) and a smoke devel-
outdoor-air ventilation system shall be sized in oped index not greater than fifty (50), when tested as
accordance with Chapter 17, or by other approved a composite product in accordance with one of the
methods. following test methods: NFPA 255, Method of Test of
Surface Burning Characteristics of Building Materials,
ASTM E84, Surface Burning Characteristics of Building
602.0 Material. Materials, or UL 723, Test for Surface Burning Charac-
602.1 General. Supply air, return air, and outside air teristics of Building Materials, except as indicated
for heating, cooling, or evaporative cooling systems below.
shall be conducted through duct systems constructed Exceptions:
of metal as set forth in Tables 6-1, 6-2, 6-3, 6-4, 6-7, 6-
8, 6-9, and 6-10, or metal ducts complying with UMC (1) Return-air and outside-air ducts, plenums,
Standard No. 6-2 or the referenced HVAC duct or concealed spaces that serve a dwelling
construction standard in Chapter 17. Rectangular unit shall be permitted to be of combustible
ducts in excess of two (2) inches w.g. shall comply construction.
with UMC Standard No. 6-2 or the referenced HVAC (2) Air filters meeting the requirements of
duct construction standard in Chapter 17. Ducts, Sections 311.2 and 503.3.
plenums, and fittings may be constructed of (3) Water evaporation media in an evaporative
concrete, clay, or ceramics when installed in the cooler.
ground or in a concrete slab, provided the joints are
(4) Charcoal filters when protected with an
tightly sealed.
approved fire suppression system.
Corridors shall not be used to convey air to or
(5) Electrical wiring in plenums shall comply
from rooms if the corridor is required to be of fire-
with NFPA 70, National Electrical Code. Elec-
resistive construction per the Building Code.
trical wires and cables and optical fiber
Concealed building spaces or independent cables shall be listed and labeled as suitable
construction within buildings may be used as ducts for use in plenums and shall have a flame
or plenums. spread distance not greater than five (5) feet
When gypsum products are exposed in ducts or (1,524 mm), an average optical density not
plenums, the air temperature shall be restricted to a greater than 0.15, and a peak optical density
range from 50ºF (10ºC) to 125ºF (52ºC), and moisture not greater than 0.5, when tested in accor-
content shall be controlled so that the material is not dance with NFPA 262, Flame Travel and
adversely affected. For the purpose of this section, Smoke of Wires and Cables for Use in Air-
gypsum products shall not be exposed in ducts Handling Spaces.
serving as supply from evaporative coolers, and in (6) Nonmetallic fire sprinkler piping in
other air-handling systems regulated by this chapter plenums shall be listed and labeled as suit-
when the temperature of the gypsum product will be able for use in plenums and shall have a
below the dew point temperature. flame spread distance not greater than five
See Chapter 8 for limitations on combustion (5) feet (1,524 mm), an average optical
products venting systems extending into or through density not greater than 0.15 and, a peak
ducts or plenums. optical density not greater than 0.5, when
See Chapter 5 for limitations on environmental tested in accordance with UL 1887, Fire Test
air systems exhaust ducts extending into or through of Plastic Sprinkler Pipe for Visible Flame and
ducts or plenums. Smoke Characteristics.

75
602.2 – 603.0 UNIFORM MECHANICAL CODE

(7) Nonmetallic pneumatic tubing in plenums Joints and seams for flat oval ducts and round
shall be listed and labeled as suitable for use ducts in other than single-dwelling units shall be as
in plenums and shall have a flame spread specified in Table 6-8.
distance not greater than five (5) feet (1,524 Joints and seams and all reinforcements for
mm), an average optical density not greater factory-made air ducts and plenums shall meet with
than 0.15, and a peak optical density not the conditions of prior approval in accordance with
greater than 0.5, when tested in accordance
the installation instructions that shall accompany the
with UL 1820, Fire Test of Pneumatic Tubing
product. Closure systems for rigid air ducts and
for Flame and Smoke Characteristics.
plenums shall be listed in accordance with UL 181A,
(8) Loudspeakers and recessed lighting fixtures, Standard for Closure Systems for Use with Rigid Air
including their assemblies and accessories, in Ducts and Air Connectors. Closure systems for flexible
plenums shall be listed and labeled as suit- air ducts shall be listed in accordance with UL 181B,
able for use in plenums and shall have a peak Standard for Closure Systems for Use with Flexible Air
rate of heat release not greater than 100 kilo- Ducts and Air Connectors.
watts, an average optical density not greater
602.5 Metal. Every duct, plenum, or fitting of metal
than 0.15, and a peak optical density not
shall comply with Table 6-1 or 6-8.
greater than 0.5, when tested in accordance
with UL 2043, Fire Test for Heat and Visible Exceptions:
Smoke Release for Discrete Products and their (1) Ducts, plenums, and fittings for systems
Accessories Installed in Air-Handling Spaces. serving single-dwelling units may comply
(9) Smoke detectors. with Table 6-9.
(10) Duct insulation, coverings, and linings and (2) Duct systems complying with UMC Stan-
other supplementary materials complying dard No. 6-2 or the referenced HVAC duct
with 605.0. construction standard in Chapter 17, with
prior approval, or duct systems complying
(11) Materials in a Group H, Division 6, fabrica-
with UL 181, Standard for Factory-Made Air
tion area including the areas above and
Ducts and Air Connectors.
below the fabrication area sharing a
common air recirculation path with the (3) Duct systems complying with the UMC
fabrication area. Standard No. 6-2 or the referenced HVAC
602.3 Factory-Made Air Ducts. Factory-made air duct construction standard in Chapter 17,
ducts shall be approved for the use intended or shall with prior approval.
conform to the requirements of the referenced stan- 602.6 Tin. Existing tin ducts may be used when
dard for air ducts in Chapter 17. Each portion of a cooling coils are added to a heating system, provided
factory-made air duct system shall be identified by the first ten (10) feet (3,048 mm) of the duct or
the manufacturer with a label or other suitable iden- plenum measured from the cooling coil discharge
tification indicating compliance with the referenced are constructed of metal of the gauge thickness set
standard for air ducts in Chapter 17 and its class forth in Tables 6-1, 6-8, or 6-9 of this chapter or are of
designation. These ducts shall be listed and shall be approved material and construction. Tin ducts
installed in accordance with the terms of their listing completely enclosed in inaccessible concealed areas
and the requirements of UMC Standard No. 6-5. need not be replaced. All accessible ducts shall be
Flexible air connectors are not permitted. insulated to comply with Table 6-6 of this chapter.
602.4 Joints and Seams of Ducts. Joints of duct For the purpose of this subsection, ducts shall be
systems shall be made substantially air-tight by considered accessible where the access space is thirty
means of tapes, mastics, gasketing, or other means. (30) inches (762 mm) or greater in height.
Crimp joints for round ducts shall have a contact 602.7 Vibration Isolators. Vibration isolators
lap of at least 1-1/2 inch (38 mm) and shall be installed between mechanical equipment and metal
mechanically fastened by means of at least three (3) ducts (or casings) shall be made of an approved
sheet-metal screws equally spaced around the joint, material and shall not exceed ten (10) inches (254
or an equivalent fastening method. mm) in length.
Joints and seams for 0.016 inch (0.41 mm) (No. 28
gauge) and 0.013 inch (0.33 mm) (No. 30 gauge) resi- 603.0 Quality of Material.
dential rectangular ducts shall be as specified in Table Galvanized steel shall be of lock-forming quality
6-1 for 0.019 inch (0.48 mm) (No. 26 gauge) material. with a minimum coating of 1.25 ounces of zinc per
Joints and seams for rectangular duct systems square foot (0.04 kg/m3) conforming to the require-
shall be as specified in Table 6-1. ments of UMC Standard No. 2-2.

76
DUCT SYSTEMS 604.0 – 605.0

604.0 Installation of Ducts. Factory-made air ducts shall not be used for
604.1 General Ducts Under Floor or Crawl Space. vertical risers in air-duct systems serving more than
Air ducts installed under a floor in a crawl space two stories. Such ducts shall not penetrate construc-
shall be installed as follows: tion where fire dampers are required.
(A) Shall not prevent access to any area of the crawl Factory-made air ducts shall be installed with at
space. least four (4) inches (102 mm) of separation from
earth, except when installed as a liner inside of
(B) Where it is required to move under ducts for
concrete, tile, or metal pipe; they shall be protected
access to areas of the crawl space a minimum
from physical damage.
vertical clearance of eighteen (18) inches (457
mm) shall be provided. The temperature of the air to be conveyed in any
of these classes of ducts shall not exceed 250ºF
604.2 Metal Ducts. Ducts shall be securely fastened
(122ºC).
in place at each change of direction and as set forth
in Table 6-7. Vertical rectangular ducts and vertical 604.4 Protection of Ducts. Ducts installed in loca-
round ducts shall be supported as set forth in Table tions where they are exposed to mechanical damage
6-7, Part A. Riser ducts shall be held in place by by vehicles or from other causes shall be protected
means of metal straps or angles and channels to by approved barriers.
secure the riser to the structure. 604.5 Support of Ducts. Installers shall provide the
Metal ducts shall be installed with at least four manufacturer’s field fabrication and installation
(4) inches (102 mm) separation from earth. Metal instructions.
ducts when installed in or under a concrete slab shall In the absence of specific supporting materials
be encased in at least two (2) inches (51 mm) of and spacing, approved factory-made air ducts may
concrete. be installed as set forth in Table 6-10.
Ducts shall be installed in a building with 604.6 Protection Against Flood Damage. In flood
adequate clearance so as to permit retaining the full hazard areas, ducts shall be located above the design
thickness of fireproofing on structural members. flood elevation or shall be designed and constructed
Supports for rectangular ducts as set forth in to prevent water from entering or accumulating
Table 6-7, when suspended from above, shall be within the ducts during floods up to the design flood
installed on two opposite sides of each duct and shall elevation. If the ducts are located below the design
be riveted, bolted, or metal screwed to each side of flood elevation, the ducts shall be capable of resisting
the duct at not more than the intervals specified. hydrostatic and hydrodynamic loads and stresses,
including the effects of buoyancy, during the occur-
Horizontal round ducts forty (40) inches (1,016 rence of flooding to the design flood elevation.
mm) or less in diameter when suspended from above
shall be supported at intervals not more than as set
forth in Table 6-7 with one hanger installed to 605.0 Insulation of Ducts.
comply with the requirements listed below: Supply-, return-air ducts and plenums of a heating
604.2.1 Ducts shall be equipped with tight- or cooling system shall be insulated to achieve the
fitting circular bands extending around the minimum thermal (R) value as set forth in Tables 6-6
entire perimeter of the duct at each specified A and B.
support interval. Exceptions:
604.2.2 Circular bands shall be not less than one (A) Factory-installed plenums, casings, or duct-
(1) inch (25 mm) wide nor less than equivalent to work furnished as a part of HVAC equip-
the gauge of the duct material it supports. ment tested and rated in accordance with
Exception: Ducts ten (10) inches (254 mm) approved energy efficiency standards.
and less in diameter may be supported by (B) Ducts or plenums located in conditioned
No. 18 gauge galvanized steel wire. spaces.
604.2.3 Each circular band shall be provided (C) For runouts less than ten (10) feet (3,048
with a suitable means of connecting to the mm) in length to air terminals or air outlets,
suspending support. the rated R value of insulation need not
604.2.4 Ducts shall be braced and guyed to exceed R-3.5 (R-0.6).
prevent lateral or horizontal swing. (D) Backs of air outlets and outlet plenums
604.3 Factory-Made Air Ducts. Listed Class 0 or exposed to unconditioned or indirectly
Class 1 factory-made air ducts may be installed in conditioned spaces with face areas exceeding
any occupancy covered by this code. five (5) square feet (0.5 m2) need not exceed

77
605.0 – 606.7 UNIFORM MECHANICAL CODE

R-2 (R-0.4); those five (5) square feet (0.5 m2) Chapter 17, and shall be installed in accordance with
or smaller need not be insulated. the approved manufacturer’s installation instruc-
(E) Ducts and plenums used exclusively for tions when required by the Building Code. Fire
evaporative cooling systems. dampers shall have been tested for closure under
airflow conditions and shall be labeled for both
Approved materials shall be installed within
maximum airflow permitted and direction of flow.
ducts and plenums for insulating, sound deadening,
or other purposes. Materials shall have a mold, When more than one damper is installed at a point in
humidity, and erosion-resistant surface that meets a single air path, the entire airflow shall be assumed
the requirements of the referenced standard for air to be passing through the smallest damper area. Fire
ducts in Chapter 17. Duct liners in systems operating dampers shall be labeled by an approved agency.
with air velocities exceeding 2,000 feet per minute Ductwork shall be connected to damper sleeves
(10.16 m/s) shall be fastened with both adhesive and or assemblies in accordance with the fire damper
mechanical fasteners, and exposed edges shall have manufacturer’s installation instructions.
adequate treatment to withstand the operating 606.3 Ceiling Radiation Dampers. Ceiling radiation
velocity. dampers shall comply with the standard for ceiling
Insulation applied to the surface of ducts, radiation dampers referenced in Chapter 17, and
including duct coverings, linings, tapes, and adhe- shall be installed in accordance with the manufac-
sives, located in buildings shall have a flame-spread turer’s approved installation instructions in the fire-
index not greater than twenty-five (25) and a smoke resistive ceiling element of floor-ceiling and roof-
developed index not greater than fifty (50), when ceiling assemblies when required by the Building
tested in accordance with NFPA 255, Method of Test of Code. Fire dampers not meeting the temperature
Burning Characteristics of Building Materials, or in limitation of ceiling radiation dampers shall not be
accordance with ASTM E 84, Surface Burning Charac-
used as a substitute. Ceiling radiation dampers shall
teristics of Building Materials, or in accordance with
be labeled by an approved agency.
the provisions of UL 723, Test for Surface Burning
Characteristics of Building Materials. The specimen 606.4 Multiple Arrangements. When size requires
preparation and mounting procedures of ASTM E the use of multiple dampers, the installation shall be
2231, Specimen Preparation and Mounting of Pipe and framed in an approved manner to ensure that the
Duct Insulation Materials to Assess Surface Burning dampers remain in place.
Characteristics, shall be used. Air duct coverings and 606.5 Access and Identification. Dampers shall be
linings shall not flame, glow, smolder, or smoke provided with an approved means of access large
when tested in accordance with ASTM C 411, Hot- enough to permit inspection and maintenance of the
Surface Performance of High-Temperature Thermal Insu- damper and its operating parts. The access shall not
lation, at the temperature to which they are exposed impair fire-resistive construction. Access shall not
in service. In no case shall the test temperature be require the use of tools, keys, or special knowledge.
below 250ºF (121ºC). Access points shall be permanently identified on the
Factory-made air ducts and faced insulations exterior by a label with letters not less than 1/2 inch
intended for installation on the exterior of ducts shall (12.7 mm) in height reading: SMOKE DAMPER or
be legibly printed with the name of the manufac- FIRE DAMPER. Access doors in ducts shall be tight
turer, the thermal resistance (R) value at installed fitting and suitable for the required duct construction.
thickness, and the flame-spread index and smoke 606.6 Freedom from Interference. Dampers shall be
developed index of the composite material. installed in a manner to ensure positive closing or
opening as required by function. Interior liners or
606.0 Smoke Dampers, Fire Dampers, and Ceiling insulation shall be held back from portions of a
Dampers. damper, its sleeve, or adjoining duct that would
606.1 Smoke Dampers. Smoke dampers shall interfere with the damper’s proper operation. Exte-
comply with the standards for leakage-rated rior materials shall be installed so as to avoid interfer-
dampers referenced in Chapter 17, and shall be ence with the operation or maintenance of external
installed in accordance with approved manufac- operating devices needed for proper function.
turer’s installation instructions when required by the 606.7 Temperature Classification of Operating
Building Code. Smoke dampers shall be labeled by Elements. Fusible links, thermal sensors, and pneu-
an approved agency. matic or electric operators shall have a temperature
606.2 Fire Dampers. Fire dampers shall comply rating or classification as required by the Building
with the standard for fire dampers referenced in Code.

78
DUCT SYSTEMS 607.0 – 609.0

607.0 Ventilating Ceilings. 608.7 A noncombustible receptacle shall be placed


607.1 General. Perforated ceilings may be used for below each floor opening into the air chamber, and
air supply within the limitations of this section. Exit such receptacle shall conform to the following:
corridors, when required to be of fire-resistive 608.7.1 The receptacle shall be securely
construction by the Building Code, shall not have suspended from the floor members and shall be
ventilating ceilings. not more than eighteen (18) inches (457 mm)
607.2 Requirements. Ventilating ceilings shall below the floor opening.
comply with the following provisions: 608.7.2 The area of the receptacle shall extend
607.2.1 Suspended ventilating ceiling material three (3) inches (76 mm) beyond the opening on
shall have a Class I flame-spread classification all sides.
on both sides, determined in accordance with 608.7.3 The perimeter of the receptacle shall
the Building Code. Suspended ventilating have a vertical lip at least one (1) inch (25.4 mm)
ceiling supports shall be of noncombustible high at the open sides if it is at the level of the
materials. bottom of the joists, or three (3) inches (76 mm)
607.2.2 Lighting fixtures recessed into venti- high if the receptacle is suspended.
lating ceilings shall be of a type approved for 608.8 Floor registers shall be designed for easy
that purpose. removal in order to give access for cleaning the
receptacles.
608.0 Use of Under-Floor Space as Supply 608.9 Exterior walls and interior stud partitions shall
Plenum for Dwelling Units. be fire-stopped at the floor.
An under-floor space may be used as a supply 608.10 Each wall register shall be connected to the
plenum, provided: air chamber by a register box or boot.
608.1 The use of under-floor space shall be limited to 608.11 A duct conforming with Section 602.0 shall
dwelling units not more than two stories in height. extend from the furnace supply outlet at least six (6)
Except for the floor immediately above the under- inches (152 mm) below combustible framing.
floor plenum, supply ducts shall be provided
608.12 The entire ground surface of the under-floor
extending from the plenum to registers on other
space shall be covered with a vapor barrier having a
floor levels.
minimum thickness of four (4) mils (0.1016 mm) and
Exception: In flood hazard areas, under-floor a flame-spread index of 200 or less.
spaces shall not be used as supply plenums
unless the flood opening requirements in the 608.13 Fuel-gas lines and plumbing waste cleanouts
Building Code are satisfied. are not located within the space.
608.2 Such spaces shall be cleaned of all loose
combustible scrap material and shall be tightly and 609.0 Automatic Shutoffs.
substantially enclosed. Air-moving systems supplying air in excess of 2,000
608.3 The enclosing material of the under-floor cubic feet per minute (944 L/s) to enclosed spaces
space, including the sidewall insulation, shall be not within buildings shall be equipped with an auto-
more flammable than one (1) inch (25 mm) (nominal) matic shutoff. Automatic shutoff shall be accom-
wood boards (flame-spread index of 200). Installa- plished by interrupting the power source of the air-
tion of foam plastics is regulated by the Building moving equipment upon detection of smoke in the
Code. main supply-air duct served by such equipment.
608.4 Access shall be through an opening in the floor Smoke detectors shall be labeled by an approved
and shall be not less than twenty-four (24) inches by agency for air duct installation and shall be installed
twenty-four (24) inches (610 mm x 610 mm). in accordance with the manufacturer’s approved
608.5 A furnace supplying warm air to under-floor instructions. Such devices shall be compatible with
space shall be equipped with an automatic control the operating velocities, pressures, temperatures,
that will start the air-circulating fan when the air in and humidities of the system. Where fire-detection
the furnace bonnet reaches a temperature not higher or alarm systems are provided for the building, the
than 150ºF (66ºC). Such control shall be one that smoke detectors required by this section shall be
cannot be set higher than 150ºF (66ºC). supervised by such systems.
608.6 A furnace supplying warm air to such space Exceptions:
shall be equipped with an approved temperature (1) When the space supplied by the air-moving
limit control that will limit outlet air temperature to equipment is served by a total coverage
200ºF (93ºC). smoke-detection system complying with the

79
609.0 UNIFORM MECHANICAL CODE

Fire Code, interconnection to such system


may be used to accomplish the required
shutoff.
(2) Automatic shutoff is not required when all
occupied rooms served by the air-handling
equipment have direct exit to the exterior
and the travel distance does not exceed 100
feet (30,480 mm).
(3) Automatic shutoff is not required for Group
R, Division 3 and Group U Occupancies.
(4) Automatic shutoff is not required for
approved smoke-control systems or where
analysis demonstrates shutoff would create
a greater hazard, such as may be encoun-
tered in air-moving equipment supplying
specialized portions of Group H Occupan-
cies. Such equipment shall be required to
have smoke detection with remote indica-
tion and manual shutoff capability at an
approved location.
(5) Smoke detectors that are factory installed in
listed air-moving equipment may be used in
lieu of smoke detectors installed in the main
supply-air duct served by such equipment.

80
2” w.g TABLE 6-1 Duct Construction for 4 Feet Duct Lengths
[SMACNA HVAC Duct Construction Standards; Second Edition - 1995] INTERMEDIATE
STATIC
REINFORCEMENT
POS. OR NEG. TRANSVERSE JOINT REINFORCEMENT
DUCT SYSTEMS

81
Table 6-1
2” w.g TABLE 6-2 Duct Construction for 5 Feet Duct Lengths
INTERMEDIATE

82
STATIC [SMACNA HVAC Duct Construction Standards; Second Edition - 1995]
REINFORCEMENT
POS. OR NEG. TRANSVERSE JOINT REINFORCEMENT
Table 6-2
UNIFORM MECHANICAL CODE
DUCT SYSTEMS Table 6-3 – Table 6-5

RECTANGULAR ALUMINUM DUCT


ADAPTED FROM 3” W.G. (750 Pa) or LOWER
TABLE 6-3
THICKNESS ADJUSTMENTS
Galv. Steel Ga (mm) 28 (0.48) 26 (0.55) 24 (0.70) 22 (0.78) 20 (1.00) 18 (1.31) 16 (1.61)
nominal
Min. Alum. equivalent1 (mm) 0.023 0.027 0.034 0.043 0.052 0.067 0.083
(0.58) (0.69) (0.86) (1.09) (1.32) (1.70) (2.11)
Commercial size (mm) 0.025 0.032 0.04 0.05 0.063 0.071 0.09
(0.60) (0.80) (1.00) (1.27) (1.60) (1.80) (2.29)
Lbs wt/Sf. Alum. Consult Appendix-5 for Weights
Note:
1
Alloy 3003-H-14.

TABLE 6-4
DIMENSION ADJUSTMENTS
Galv. Rigidity Class A B C D E F G H I J K L
Alum. dim. per Galv. Class C E E F H I I K 1 1 1 1

Note:
1
Calculate an effective Ix= 3x that used for steel.

TABLE 6-5
REINFORCEMENTS
Steel Angle Size, Equivalent Alumn,1
Inches (mm) Cod Angle Size, Inches Steel Bar Aluminum Bar1
1 x 1 x16 Ga. C 1-1/4 x 1-1/4 x 1/8 1 x 1/8 1-1/2 x 1/8 or 1-1/4 x 3/16
(25 x 25 x 1.61) (31.8 x 31.8 x 3.2) (25 x 3.2) (38.1 x 3.2 or 31.8 x 4.8)
1 x 1 x 1/8 D 1-1/2 x 1-1/2 x 1/8 1-1/2 x 1/8 1-1/2 x 1/8 x or 1-1/4 x 3/16
(25 x 25 x 3.2) (38.1 x 38.1 x 3.2) (38.1 x 3.2) (38.1 x 3.2 or 38.1 x 4.8)
1-1/4 x 1-1/4 x 1/8 F 1-3/4 x 1-3/4 x 1/8
(31.8 x 31.8 x 3.2) (44.5 x 44.5 x 3.2)
1-1/2 x 1-1/2 x 1/8 G 2-1/2 x 2-1/2 x 1/8
(38.1 x 38.1 x 3.2) (63.5 x 63.5 x 3.2)
2 x 2 x 1/8 H 2-1/2 x 2-1/2 x 3/16
(51 x 51 x 3.2) (63.5 x 63.5 x 4.8)
2 x 2 x 3/16 I 2-1/2 x 2-1/2 x 3/8 or 3 x 3 x 1/4
(51 x 51 x 4.8) (63.5 x 63.5 x 9.5 or 76.2 x 76.2 x 6.4)
2 x 2 x 1/4 J 2-1/2 x 2-1/2 x 3/8 or 3 x 3 x 1/4
(51 x 51 x 6.4) (63.5 x 63.5 x 7.9 or 76.2 x 76.2 x 6.4)
2-1/2 x 2-1/2 x 3/16 K 3 x 3 x 3/8 or 3-1/2 x 3-1/2 x 1/4
(63.5 x 63.5 x 4.8) (76.2 x 76.2 x 9.5 or 88.9 x 88.9 x 6.4)

Notes:
1
Alloy 6061-T6 Strength normally.
Any aluminum shape substitute must have a moment of inertia three times that of steel and have 30,000 psi minimum yield
strength.

83
Table 6-6 A UNIFORM MECHANICAL CODE

TABLE 6-6 A (I-P Units)


Minimum Duct Insulation R Value Cooling and Heating Only Supply Ducts and Return Ductsd, e
a

Climate Zone Duct Location

Envelope HDD65 CDD50 Exterior Ventilated Unvented Unvented Uncon- Indirectly Buried
Criteria Table Attic Attic w/ Attic w/ ditioned Con-
Backloaded Roof Spaceb ditioned
Ceiling Insulationa Spacec

Heating-Only Ducts

5-1 to 5-7 0–1,800 all none none none none none none none
5-8 to 5-12 1,801–3,600 all R-3.5 none none none none none none
5-13 to 5-15 3,601–5,400 all R-3.5 none none none none none none
5-16 to 5-18 5,401–7,200 all R-6 R-3.5 none none none none R-3.5
5-19 to 5-20 7,201–9,000 all R-6 R-6 R-3.5 none none none R-3.5
5-21 to 5-22 9,001–10,800 all R-8 R-6 R-6 none R-3.5 none R-3.5
5-23 10,801–12,600 all R-8 R-6 R-6 none R-6 none R-6
5-24 12,601–16,200 all R-8 R-8 R-6 none R-6 none R-6
5-25 16,201–19,800 all R-10 R-8 R-8 none R-6 none R-6
5-26 19,801+ all R-10 R-10 R-8 none R-8 none R-6

Cooling-Only Ducts

5-15, 18, 20, all 0–1,800 R-1.9 R-1.9 R-1.9 R-1.9 R-1.9 none none
22 to 26
5-12, 14, 17, all 1,801–3,600 R-3.5 R-1.9 R-3.5 R-1.9 R-1.9 none none
19, 21
5-7, 9, 11, 13, all 3,601–5,400 R-3.5 R-3.5 R-6 R-1.9 R-1.9 none none
16
5-4, 6, 8, 10 all 5,401–7,200 R-6 R-6 R-6 R-3.5 R-1.9 none none
5-3, 5-5 all 7,201–9,000 R-6 R-6 R-6 R-3.5 R-3.5 none R-3.5
5-2 all 9,001–10,800 R-6 R-6 R-8 R-3.5 R-3.5 none R-3.5
5-1 all 10,801+ R-8 R-8 R-8 R-3.5 R-3.5 none R-3.5

Return Ducts

5-15 to 5-26 all climates R-3.5 R-3.5 R-3.5 none none none none none

Notes:
a
Insulation R-values, measured in (h·ft2·ºF)/Btu, are for the insulation as installed and do not include film resistance. The
required minimum thicknesses do not consider water vapor transmission and possible surface condensation. Where exterior
walls are used as plenum walls, wall insulation shall be as required by the most restrictive condition. Insulation resistance
measured on a horizontal plane in accordance with ASTM C518 at a mean temperature of 75ºF (24ºC) at the installed thickness.
b
Includes crawl spaces, both ventilated and nonventilated.
c
Includes return-air plenums with or without exposed roofs above.
d
Vapor retarders shall be installed on supply ducts in spaces vented to the outside in geographic areas where the average
summer dewpoint temperature based on the 2-1/2 percent column of dry-bulb and mean coincident wet-bulb temperature
exceeds 60ºF (16ºC).
e
Insulation shall have an approved weatherproof barrier.

84
DUCT SYSTEMS Table 6-6 B

TABLE 6-6 B (I-P Units)


Minimum Duct Insulation R Valuea Combined Heating and Cooling Ductsd, e

Climate Zone Duct Location

Envelope HDD65 CDD50 Exterior Ventilated Unvented Unvented Uncon- Indirectly Buried
Criteria Attic Attic w/ Attic w/ Roof ditioned Conditioned
Table Backloaded Insulationa Spaceb Spacec
Ceiling
5-1 0–900 10,801+ R-8 R-6 R-8 R-3.5 R-3.5 none R-3.5
5-2 0–900 9,001–10,800 R-6 R-6 R-8 R-3.5 R-3.5 none R-3.5
5-3 0–900 7,201–9,000 R-6 R-6 R-6 R-3.5 R-3.5 none R-3.5
5-4 0–900 0–7,200 R-6 R-3.5 R-6 R-3.5 R-1.9 none R-3.5
5-5 901–1,800 7,201+ R-6 R-6 R-6 R-3.5 R-3.5 none R-3.5
5-6 901–1,800 5,401–7,200 R-6 R-6 R-6 R-3.5 R-3.5 none R-3.5
5-7 901–1,800 0–5,400 R-3.5 R-3.5 R-6 R-1.9 R-1.9 none R-1.9
5-8 1,801–2,700 5,401+ R-6 R-6 R-6 R-3.5 R-3.5 none R-3.5
5-9 1,801–2,700 0–5,400 R-6 R-3.5 R-6 R-1.9 R-1.9 none R-1.9
5-10 2,701–3,600 5,401+ R-6 R-6 R-6 R-3.5 R-3.5 none R-3.5
5-11 2,701–3,600 3,601–5,400 R-6 R-6 R-6 R-3.5 R-3.5 none R-1.9
5-12 2,701–3,600 0–3,600 R-3.5 R-3.5 R-3.5 R-1.9 R-1.9 none R-1.9
5-13 3,601–5,400 3,601+ R-6 R-6 R-6 R-3.5 R-3.5 none R-3.5
5-14 3,601–5,400 1,801–3,600 R-6 R-3.5 R-6 R-1.9 R-3.5 none R-1.9
5-15 3,601–5,400 0-1,800 R-3.5 R-3.5 R-3.5 R-1.9 R-1.9 none R-1.9
5-16 5,401–7,200 3,601+ R-6 R-6 R-6 R-3.5 R-3.5 none R-3.5
5-17 5,401–7,200 1,801–3,600 R-6 R-6 R-6 R-1.9 R-3.5 none R-3.5
5-18 5,401–7,200 0–1,800 R-6 R-3.5 R-3.5 R-1.9 R-3.5 none R-3.5
5-19 7,201–9,000 1,801+ R-8 R-6 R-6 R-1.9 R-3.5 none R-3.5
5-20 7,201–9,000 0–1,800 R-6 R-6 R-6 R-1.9 R-3.5 none R-3.5
5-21 9,001–10,800 1,801+ R-8 R-6 R-6 R-1.9 R-6 none R-3.5
5-22 9,001–10,800 0–1,800 R-8 R-6 R-6 R-1.9 R-3.5 none R-3.5
5-23 10,801–12,600 all R-8 R-6 R-6 R-1.9 R-6 none R-6
5-24 12,601–16,200 all R-8 R-8 R-8 R-1.9 R-6 none R-6
5-25 16,201–19,800 all R-10 R-8 R-8 R-3.5 R-6 none R-6
5-26 19,801+ all R-10 R-10 R-8 R-3.5 R-8 R-3.5 R-6
Notes:
a
Insulation R-values, measured in (h·ft2·˚F)/Btu, are for the insulation as installed and do not include film resistance. The required
minimum thicknesses do not consider water vapor transmission and possible surface condensation. Where exterior walls are
used as plenum walls, wall insulation shall be as required by the most restrictive condition. Insulation resistance measured on a
horizontal plane in accordance with ASTM C518 at a mean temperature of 75˚F (24ºC) at the installed thickness.
b
Includes crawl spaces, both ventilated and nonventilated.
c
Includes return air plenums with or without exposed roofs above.
d
Vapor retarders shall be installed on cooling supply ducts in spaces vented to the outside in geographic areas where the average
summer dewpoint temperature based on the 2-1/2 percent column of dry-bulb and mean coincident wet-bulb temperature
exceeds 60°F (16°C).
e
Insulation shall have an approved weatherproof barrier.

85
Table 6-7 UNIFORM MECHANICAL CODE

TABLE 6-7
Duct Support

A. Vertical Ducts

Maximum Maximum
Side of Diameter
Rectangular Metal Strap or of Round Strap
Duct Angle Bracket Ducts

24" 1" x 1/8" strap1 10" 0.047" (No. 18 gauge)


galvanized steel 2" wide1

36" 1" x 1" x 1/8" angle1 20" 0.058" (No. 16 gauge)


galvanized steel 2" wide1

48" 1-1/8" x 1-1/8" x 1/8" angle1 40" 1/8" steel x 1-1/2"1

60" 1-1/2" x 1-1/2" x 1/8" angle1 60" 1/8" steel x 2"1

Over 60" 2" x 2" x 1/8" angle1 Over 60" 3/16" steel x 2"1

B. Horizontal Ducts

18" 1" x 18 gauge2 Same gauge as galvanized steel duct,


10" 1" wide or (No. 18 gauge galvanized
30" 1" x 18 gauge 2
steel wire) on 10’ centers

48" 1" x 1/8"2 20" Same gauge as galvanized steel


duct, 1" wide or (No. 8 gauge
60" 1" x 1/8"2 galvanized steel wire) tied to
40" 1" galvanized steel band
80" 1" x 1/8"2 around duct on 10’ centers

60" Same gauge as galvanized steel


duct, 1-1/2" wide on 6' centers

Over 60" Same gauge as galvanized steel


duct, 1-1/2" wide on 4' centers

C. Horizontal Ducts –– Trapeze-Type Supports

Maximum
Diameter of Round Horizontal
Duct or Side of Support Hanger
Rectangular Duct Angle3

36" 1-1/2" x 1-1/2" x 1/8" 1/4" round rod or 1" x 1" x 1/8" angle

48" 2" x 2" x 1/8" 1/4" round rod or 1" x 1" x 1/8" angle

60" 2" x 2" x 1/8" 5/16" round rod or 1" x 1" x 1/8" angle

84" 2" x 2" x 1/8" 3/8" round rod or 1" x 1" x 1/8" angle

Notes:
1
Spaced vertically not more than 12 feet on centers.
2
Spaced horizontally not more than 10 feet on centers.
3
Spaced not more than 8 feet on centers.
1 in. = 25.4 mm, 1 ft. = 0.305 m

86
DUCT SYSTEMS Table 6-8 – Table 6-9

TABLE 6-8
Construction Details for Round and Flat-Oval Ducts

Aluminum STEEL –– THICKNESS IN INCHES


B. & S. Gage (STEEL –– GALVANIZED SHEET GAUGE) GIRTH JOINTS1
2
Duct Diameter Pressure < 2" W.C. Pressure < 2" W.C. Pressure > 2" < 10" W.C. Minimum Girth
Max. Width Spiral Longitudinal Welded Reinforcing, Maximum
(In Inches) Round Round Flat-Oval Seam Seam Fittings Pressure > 2" < 10" W.C. Spacing and Angle Size

Up to 9 24 0.019 0.024 0.019 0.024 0.030 2" Slip None


(26) (24) (26) (24) (22)
Over 9 24 0.019 0.024 0.024 0.030 0.036 4" Slip None
Up to 14 (26) (24) (24) (22) (20)

Over 14 22 0.024 0.030 0.024 0.030 0.036 4" Slip None


Up to 23 (24) (22) (24) (22) (20)

Over 23 20 0.030 0.036 0.030 0.036 0.036 4" Slip None


Up to 37 (22) (20) (22) (20) (20)

Over 37 18 0.036 0.047 0.036 0.036 0.047 1-1/4" x 1-1/4" x 1/8" 1-1/4" x 1-1/4" x 1/8"
Up to 51 (20) (18) (20) (20) (18) Flange on 72"
Over 51 16 0.047 0.058 X 0.047 0.047 1-1/4" x 1-1/4" x 1/8" 1-1/4" x 1-1/4" x 1/8"
Up to 61 (18) (16) (18) (18) Flange on 72"

Over 61 14 0.058 0.070 X 0.058 0.058 1-1/2" x 1-1/2" x 1/8" 1-1/2" x 1-1/2" x 1/8"
Up to 84 (16) (14) (16) (16) Flange on 48"

Notes:
1
For pressure < 2 inches W.C., any of the following joints are acceptable: butt slip; pipe slip; pipe lock; roll slip; snap slip; plenum
lock; and companion flange.
2
Acceptable longitudinal seams for pressure < 2 inches W.C.: Acme (grooved); snap lock; standing; and spiral.
1 in. = 25.4 mm, 1 in. W.C. = 0.249 kPa

TABLE 6-9
Thickness of Metal Ducts and Plenums Used for Heating or Cooling for a Single-Dwelling Unit

GALVANIZED STEEL

Minimum Equivalent Approximate


Thickness, Galvanized Sheet Aluminum
Inches (mm) Gauge No. B.&S. Gauge

Round ducts and enclosed


rectangular ducts
14" (356 mm) or less 0.013 (0.33) 30 26
Over 14" (356 mm) 0.016 (0.41) 28 24
Exposed rectangular ducts
14" (356 mm) or less 0.016 (0.41) 28 24
Over 14" (356 mm) 0.019 (0.48) 26 22

87
Table 6-10 UNIFORM MECHANICAL CODE

TABLE 6-10
Alternate Supports for Factory-Made Air Ducts

Maximum Support
Class 1 Duct Material Minimum Support Material Spacing, Feet

Rigid round fibrous No. 26 gauge x 5/8" 6


wide galvanized iron strap

Corrugated metal No. 18 gauge galvanized 6


iron wire

Flexible No. 26 gauge x 1-1/2" 4


wide galvanized iron strap
Note: 1 in. = 25.4 mm, 1 ft. = 0.305 m

88

You might also like