Professional Documents
Culture Documents
o
o
Applications
Air Only
o
o
o
o
Systems: Constant or Variable Air Volume systems for single or dual duct systems with options of:
up to two reheat stages
supply air, extract air cascade control
humidity control
Control for variable speed fans
Air/Water Systems:
o
Fan Coil units for 2-pipe or 4-pipe systems with options of:
Humidity control
Pressure control
o
radiator control, chilled ceiling
General Description
The TCY3 is a stand-alone electronic universal controller with two autonomous control loops. Each control loop may use up
to 2 PID sequences and 6 binary sequences. The TCY3-T0121R features 1 NTC temperature sensor and 1 analog input, 2
binary outputs and one analog output. The outputs need to be assigned to the control sequences by parameters. A
detailed configuration is possible by following a simple setup routine. The TCY3 can be configured using the standard
operation terminal. No special tool or software is required.
Page 1
Name
T C Y 3 - T 0 1 2 1 R (- H ) (- U ) (- D )
Deluxe version
2 x 4 housing
Integrated Humidity sensor
Relays for binary outputs
Number of analog outputs (AO) = 1
Number of binary output (DO) = 2
Number of analog inputs (AI) = 1
Number of binary inputs (DI) = 0
With external temperature input (RT)
Series (TCY3)
Ordering
Model
Stock code
Variant
TCY3-T0121R
TCY3-T0121R-D
TCY3-T0121R-U
TCY3-T0121R-U-D
TCY3-T0121R-H
TCY3-T0121R-H-D
TCY3-T0121R-H-U
TCY3-T0121R-H-U-D
40-10
40-10
40-10
40-10
40-10
40-10
40-10
40-10
Standard
Deluxe
Standard
Deluxe
Standard
Deluxe
Standard
Deluxe
0021
0022
0023
0024
0025
0026
0027
0028
Mounting size
88mm x 88mm
2 x 4
88mm x 88mm
2 x 4
Type
Key-data
No humidity
sensor
Compact PI controller
with:
1 TI int or ext
1 AI
2 DO (Relay)
1 AO
With humidity
sensor
21
(0.8)
88 (3.5)
58 (2.3)
88 (3.5)
32 (1.2)
15
(0.6)
58 (2.3)
112 (4.4)
73 (2.9)
Page 2
Technical specifications
Power Supply
Signal inputs
Operating Voltage
24 V AC/DC 10 %, 5060 Hz
Power Consumption
Max. 3 VA
Electrical Connection
Terminal Connectors,
wire 0.342.5 mm2 (AWG 2412)
Internal rectification:
Signal ground = power ground
Clock backup
Analog Input
Input Signal
Resolution
AI1
0...10 V or 0...20 mA
9.76 mV or 0.019 mA (10 bit)
Temperature Input
Signal outputs
Environment
Standards
Range
Accuracy
Analog Outputs
Output Signal
Resolution
Maximum Load in voltage mode
AO1
DC 0...10 V or 0...20 mA (250 max.)
9.76 mV resp. 0.019 mA (10 bit)
10 mA
Relays Outputs
AC Voltage
DC Voltage
DO1, DO2
0250 VAC, 2 (1.2) A max. each output
030 VDC, 2 (1.2) A max. each output
Operation
Climatic Conditions
Temperature
Humidity
To IEC 721-3-3
class 3 K5
050 C (32122 F)
<95 % r.H. non-condensing
conform according to
EN 61 000-6-1/ EN 61 000-6-3
EMC Standard
89/336/EEC
EMEI Standard 73/23/EEC
Product standards
Automatic electrical controls for
household and similar use
Special requirement on
temperature dependent controls
Degree of Protection
General
EN 60 730 1
EN 60 730 2 9
IP30 to EN 60 529
Safety Class
Dimensions (H x W x D)
Page 3
Modulating Actuators:
Choose actuators with an input signal type of 0-10 V DC or 4-20 mA. Minimum and maximum signal limitations may be
set in software.
Floating Actuators:
Actuators with constant running time are recommended. Observe power limits on binary devices.
Connection diagram
Description:
YB1
YB2
XA1
YM1
RT
Binary output 1:
Binary output 2:
Analog input 1:
Analog output 1:
Temperature input 1:
*
) selectable by jumper
!
U
WARNING:
Power supply is half-wave rectified:
Signal ground = Power ground
Connect through a safety isolation transformer
Page 4