Features

o
o

Temperature control for 2-pipe, 4-pipe HVAC


systems.
-H version: Humidity control with integrated
humidity sensor
Universal PID and binary control for any
analog input/output signal and range
4 independent PID sequences, 12
independent binary sequences
1 modulating output for DC 0...10V or 020
mA actuators with 10 bit resolution.
1 Input for DC 05V, 010V or 020 mA
sensors with 10 bit resolution
1 internal temperature sensor and 1 external
sensor input
Multiple functions on external input: auto
changeover, remote control
Monitoring of low and high limits on all inputs.
Programmable reaction in case of alarm.
Feedback function for internal sensors and
set points.
Special functions for dehumidifying, set point
shift and VAV control
Transformation of display value according to
analog sensor range
Password protected programmable user and
control parameters
Blue backlight
Deluxe Version only:
Power Cap protected real time clock with 24h
power backup
16 switching times, grouped in 4 time
schedules.
o
Infrared remote control

Applications

Air Only
o
o
o
o

Systems: Constant or Variable Air Volume systems for single or dual duct systems with options of:
up to two reheat stages
supply air, extract air cascade control
humidity control
Control for variable speed fans

Air/Water Systems:
o
Fan Coil units for 2-pipe or 4-pipe systems with options of:

Humidity control

Pressure control
o
radiator control, chilled ceiling

Water Only Systems: Radiator, floor heating or chilled ceilings

Individual room control for hotel rooms, meeting rooms, etc.

General Description
The TCY3 is a stand-alone electronic universal controller with two autonomous control loops. Each control loop may use up
to 2 PID sequences and 6 binary sequences. The TCY3-T0121R features 1 NTC temperature sensor and 1 analog input, 2
binary outputs and one analog output. The outputs need to be assigned to the control sequences by parameters. A
detailed configuration is possible by following a simple setup routine. The TCY3 can be configured using the standard
operation terminal. No special tool or software is required.

Doc: 70-000002 V1.0, 20100420


Subject to alteration

Vector Controls GmbH, Switzerland

Page 1

TCY3-T0121R Technical Data

Name

T C Y 3 - T 0 1 2 1 R (- H ) (- U ) (- D )
Deluxe version
2 x 4 housing
Integrated Humidity sensor
Relays for binary outputs
Number of analog outputs (AO) = 1
Number of binary output (DO) = 2
Number of analog inputs (AI) = 1
Number of binary inputs (DI) = 0
With external temperature input (RT)
Series (TCY3)

Ordering
Model

Stock code

Variant

TCY3-T0121R
TCY3-T0121R-D
TCY3-T0121R-U
TCY3-T0121R-U-D
TCY3-T0121R-H
TCY3-T0121R-H-D
TCY3-T0121R-H-U
TCY3-T0121R-H-U-D

40-10
40-10
40-10
40-10
40-10
40-10
40-10
40-10

Standard
Deluxe
Standard
Deluxe
Standard
Deluxe
Standard
Deluxe

0021
0022
0023
0024
0025
0026
0027
0028

Mounting size
88mm x 88mm
2 x 4
88mm x 88mm
2 x 4

Type

Key-data

No humidity
sensor

Compact PI controller
with:
1 TI int or ext
1 AI
2 DO (Relay)
1 AO

With humidity
sensor

Dimensions [mm] (inch)


32 (1.2)

21
(0.8)

88 (3.5)

58 (2.3)

88 (3.5)

Doc: 70-000002 V1.0, 20100420


Subject to alteration

32 (1.2)

15
(0.6)

58 (2.3)

112 (4.4)

73 (2.9)

Vector Controls GmbH, Switzerland

Page 2

TCY3-T0121R Technical Data

Technical specifications
Power Supply

Signal inputs

Operating Voltage

24 V AC/DC 10 %, 5060 Hz

Power Consumption

Max. 3 VA

Electrical Connection

Terminal Connectors,
wire 0.342.5 mm2 (AWG 2412)

Internal rectification:
Signal ground = power ground

Half wave rectified


Security transformer required

Clock backup

24 hours (Deluxe version only)

Analog Input
Input Signal
Resolution

AI1
0...10 V or 0...20 mA
9.76 mV or 0.019 mA (10 bit)

Temperature Input

Signal outputs

Environment

Standards

Range

Int. NTC: 050 C (32122 F)


Ext. NTC (Sxx-Tn10 sensor): -40140 C (-40284 F)

Accuracy

-400 C (-4032 F): 0.5 K


050 C (32122 F): 0.2 K
50100 C (122212 F): 0.5 K
> 100 C (> 212 F): 1 K

Humidity Input: (-H Version only)


Range
Accuracy at 55 % r.H.
Hysteresis
Repeatability
Stability

H1 Thermoset Polymer-Based Capacity


0100 % r.H.
3.0 % at 25 C (77 F)
3 % between 1590 % r.H.
0.5 %
0.5 % / year if used within 050 C (32122 F)

Analog Outputs
Output Signal
Resolution
Maximum Load in voltage mode

AO1
DC 0...10 V or 0...20 mA (250 max.)
9.76 mV resp. 0.019 mA (10 bit)
10 mA

Relays Outputs
AC Voltage
DC Voltage

DO1, DO2
0250 VAC, 2 (1.2) A max. each output
030 VDC, 2 (1.2) A max. each output

Operation
Climatic Conditions
Temperature
Humidity

To IEC 721-3-3
class 3 K5
050 C (32122 F)
<95 % r.H. non-condensing

Transport & Storage


Climatic Conditions
Temperature
Humidity
Mechanical Conditions

To IEC 721-3-2 and IEC 721-3-1


class 3 K3 and class 1 K3
-2570 C (-13158 F)
<95 % r.H. non-condensing
class 2M2

conform according to
EN 61 000-6-1/ EN 61 000-6-3
EMC Standard
89/336/EEC
EMEI Standard 73/23/EEC
Product standards
Automatic electrical controls for
household and similar use
Special requirement on
temperature dependent controls
Degree of Protection

General

EN 60 730 1
EN 60 730 2 9
IP30 to EN 60 529

Safety Class

III (IEC 60536)

Cover, back part


Mounting Plate

Fire proof ABS plastic (UL94 class V-0)


Galvanized Steel

Dimensions (H x W x D)

Front part: 88 x 88 x 21 mm (3.5 x 3.5 x 0.8)


Power case: 58 x 32 mm ( 2.3 x 1.3)

Dimensions (H x W x D), U-version Front part: 112 x 73 x 15 mm (4.4 x 2.9 x 0.6)


Power case: 58 x 32 mm ( 2.3 x 1.3)

Doc: 70-000002 V1.0, 20100420


Subject to alteration

Weight (controller only)

180 g (6.3 oz)

Weight (including package)

260 g (9.2 oz)

Vector Controls GmbH, Switzerland

Page 3

TCY3-T0121R Technical Data

Selection of actuators and sensors


Temperature Sensors:
Use only our approved NTC sensors to achieve maximum accuracy. Recommended is SDB-Tn10-20 as Duct sensor, SRATn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.

Modulating Actuators:
Choose actuators with an input signal type of 0-10 V DC or 4-20 mA. Minimum and maximum signal limitations may be
set in software.

Floating Actuators:
Actuators with constant running time are recommended. Observe power limits on binary devices.

Binary auxiliary devices:


E.g. pumps, fans, on/off valves, humidifiers, etc. Do not directly connect devices that exceed 250 VAC, 2(1.2) A. Observe
startup current on inductive loads.

Connection diagram

Description:
YB1
YB2
XA1
YM1
RT

Binary output 1:
Binary output 2:
Analog input 1:
Analog output 1:
Temperature input 1:
*

0250 VAC or 030 VDC


0250 VAC or 030 VDC
05 V, 010 V or* 020 mA
010 V or* 020 mA
NTC 10k @ 25C (77F)

) selectable by jumper

!
U

WARNING:
Power supply is half-wave rectified:
Signal ground = Power ground
Connect through a safety isolation transformer

Doc: 70-000002 V1.0, 20100420


Subject to alteration

Vector Controls GmbH, Switzerland