You are on page 1of 6

17528 Federal Register / Vol. 72, No.

67 / Monday, April 9, 2007 / Notices

should be electronically mailed to 9507; E-mail: reports from manufacturers. With


ICDocketMgr@ed.gov. Individuals who Francine.Pinto@hq.doe.gov. respect to test procedures, both parts
use a telecommunications device for the SUPPLEMENTARY INFORMATION: In generally authorize the Secretary of
deaf (TDD) may call the Federal accordance with Title 10, Code of Energy to prescribe test procedures that
Information Relay Service (FIRS) at Federal Regulations Parts 430.27(l) and are reasonably designed to produce
1–800–877–8339. 431.401(f)(4), notice is hereby given of results which reflect energy efficiency,
the issuance of a Decision and Order energy use and estimated operating
[FR Doc. E7–6618 Filed 4–6–07; 8:45 am]
granting MEUS a Waiver from the costs, and that are not unduly
BILLING CODE 4000–01–P
applicable Department of Energy burdensome to conduct. (42 U.S.C.
residential and commercial package air 6293(b)(3), 6314(a)(2))
The test procedure for residential
conditioner and heat pump test
DEPARTMENT OF ENERGY central air conditioning and heat pump
procedures for its R410A CITY MULTI
products is contained in 10 CFR Part
Office of Energy Efficiency and Variable Refrigerant Flow Zoning
430, Subpart B, Appendix M. For
Renewable Energy (‘‘VRFZ’’) products, subject to a commercial package air conditioning
condition requiring MEUS to test and and heating equipment, EPCA provides
[Docket No. EERE–2006–WAV–0147] rate its R410A CITY MULTI products that the test procedures shall be those
pursuant to the alternate test procedure generally accepted industry testing or
Energy Conservation Program for described in this notice. Today’s rating procedures developed or
Consumer Products: Decision and decision requires that any recognized by the Air-Conditioning and
Order Granting a Waiver From the representations concerning the energy Refrigeration Institute (‘‘ARI’’) or by the
Department of Energy (DOE) efficiency of these products are made American Society of Heating,
Residential and Commercial Package consistent with the provisions and Refrigerating and Air Conditioning
Air Conditioner and Heat Pump Test restrictions in the alternate test Engineers (‘‘ASHRAE’’), as referenced in
Procedures to Mitsubishi Electric, and procedure. ASHRAE/IES Standard 90.1 and in
Modification of a 2004 Waiver Granted The waiver granted for MEUS’s R22 effect on June 30, 1992. (42 U.S.C.
to Mitsubishi Electric From the Same CITY MULTI VRFZ products on August 6314(a)(4)(A)) This section also provides
DOE Test Procedures (Case No. CAC– 27, 2004, is hereby amended to prohibit for the Secretary of Energy to amend the
012) MEUS from making energy efficiency test procedure for a product if the
representations regarding its R22 CITY industry test procedure is amended,
AGENCY: Office of Energy Efficiency and MULTI products unless such
Renewable Energy, Department of unless the Secretary determines that
representations are made consistent such a modified test procedure does not
Energy. with the provisions set forth in the meet the statutory criteria. (42 U.S.C.
ACTION: Decision and Order. alternate test procedure described in 6314(a)(4)(B))
this notice. On December 8, 2006, DOE published
SUMMARY: Today’s notice publishes a
Decision and Order (Case No. CAC–012) Issued in Washington, DC, on April 2, a final rule adopting test procedures for
granting a Waiver to Mitsubishi Electric 2007. commercial package air conditioning
and Electronics USA, Inc. (‘‘MEUS’’) Alexander A. Karsner, and heating equipment, effective
from the existing Department of Energy Assistant Secretary, Energy Efficiency and January 8, 2007. 71 FR 71340. DOE
(DOE) residential and commercial Renewable Energy. adopted ARI Standard 210/240–2003 for
package air conditioner and heat pump commercial package air conditioning
Decision and Order and heating equipment with capacities
test procedures for specified R410A
CITY MULTI products. MEUS shall be In the Matter of: Mitsubishi Electric <65,000 Btu/h and ARI Standard 340/
required to test and rate the R410A and Electronics USA, Inc. (‘‘MEUS’’) 360–2004 for commercial package air
CITY MULTI VRFZ products according (Case No. CAC–012). conditioning and heating equipment
to the alternate test procedure set forth with capacities ≥65,000 Btu/h and
Background
in this notice. DOE is also amending the <240,000 Btu/h. Id. at 71371. The[MR1]
Title III of the Energy Policy and capacities of MEUS’s CITY MULTI
waiver granted to MEUS for its R22
Conservation Act (‘‘EPCA’’) sets forth a VRFZ products fall in the ranges
CITY MULTI products in August 2004
variety of provisions concerning energy covered by ARI Standard 340/360–2004
to explicitly prohibit MEUS from
efficiency. Part B of Title III (42 U.S.C. and the DOE test procedure for
making energy efficiency
6291–6309) provides for the ‘‘Energy residential products referred to above.
representations regarding these products
Conservation Program for Consumer DOE’s regulations contain provisions
unless such representations are
Products other than Automobiles.’’ Part allowing a person to seek a waiver from
consistent with the alternate test
C of Title III (42 U.S.C. 6311–6317) the test procedure requirements for
procedure.
provides for an energy efficiency covered consumer products. These
FOR FURTHER INFORMATION CONTACT: Dr. program entitled ‘‘Certain Industrial provisions are set forth in 10 CFR
Michael G. Raymond, U.S. Department Equipment,’’ which is similar to the 430.27. The waiver provisions for
of Energy, Building Technologies program in Part B, and which includes commercial equipment are substantively
Program, Mailstop EE–2J, Forrestal commercial air conditioning equipment, identical to those for covered consumer
Building, 1000 Independence Avenue, packaged boilers, water heaters, and products and are found at 10 CFR
SW., Washington, DC 20585–0121. other types of commercial equipment. 431.401.
Telephone: (202) 586–9611, E-mail: Today’s notice involves residential The waiver provisions allow the
Michael.Raymond@ee.doe.gov; or products under Part B, and commercial Assistant Secretary for Energy Efficiency
sroberts on PROD1PC70 with NOTICES

Francine Pinto, Esq., U.S. Department of equipment under Part C. Both parts and Renewable Energy (‘‘Assistant
Energy, Office of General Counsel, Mail specifically provide for definitions, test Secretary’’) to temporarily waive test
Stop GC–72, Forrestal Building, 1000 procedures, labeling provisions, energy procedures for a particular basic model
Independence Avenue, SW., conservation standards, and the when a petitioner shows that the basic
Washington, DC 20585–0103, (202) 586– authority to require information and model contains one or more design

VerDate Aug<31>2005 18:21 Apr 06, 2007 Jkt 211001 PO 00000 Frm 00054 Fmt 4703 Sfmt 4703 E:\FR\FM\09APN1.SGM 09APN1
Federal Register / Vol. 72, No. 67 / Monday, April 9, 2007 / Notices 17529

characteristics that prevent testing the Application for Interim Waiver.2 the new R410A refrigerant, MEUS
according to the prescribed test DOE also published for comment an requested a waiver from the test
procedures, or when the prescribed test alternate test procedure for MEUS. DOE procedures for its new CITY MULTI
procedures may evaluate the basic stated that if it specified an alternate test models. The MEUS petition requested
model in a manner so unrepresentative procedure for MEUS in the subsequent that DOE grant a waiver from existing
of its true energy consumption as to Decision and Order, DOE would test procedures until such time as a
provide materially inaccurate consider applying the procedure to representative test procedure is
comparative data. 10 CFR 430.27(a)(1), similar waivers for residential and developed and adopted for this class of
10 CFR 431.401(a)(1). commercial central air conditioners and products. MEUS did not include an
The Assistant Secretary may grant the heat pumps, including such waivers alternate test procedure in its petition
waiver subject to conditions, including that previously have been granted.3 DOE and noted that it knows of no test
adherence to alternate test procedures. solicited comments, data, and procedure that could evaluate its
10 CFR 430.27 (l), 10 CFR 431.401 (f)(4). information respecting the petition and products in a representative manner.
Petitioners are to include in their the proposed alternate test procedure. However, MEUS is actively working
petition any alternate test procedures DOE received written comments from with ARI to develop test procedures that
known to evaluate the basic model in a seven companies—Rheem Heating and accurately reflect the operation and
manner representative of its energy Cooling, Lennox International Inc., energy consumption of these types of
consumption. 10 CFR 430.27(b)(1)(iii), Daikin AC (Americas), Inc, Samsung units.
10 CFR 431.401(b)(1)(iii). Waivers and Quietside, Sanyo Fisher Company, MEUS’s petition presented several
generally remain in effect until final test United Mechanical and MEUS—in arguments in support of its claim.
procedure amendments resolving the response to the March 24th Notice. Only MEUS stated that the design
problem that is the subject of the waiver one commenter expressed opposition to characteristics of the R410A CITY
become effective. the MEUS petition.4 Additionally, most MULTI VRFZ systems prevent testing
The waiver process also allows the of the commenters responded favorably according to the currently prescribed
Assistant Secretary to grant an Interim to DOE’s proposed alternate test test procedures for the same reasons that
Waiver from test procedure procedure.5 Commenters generally its R22 models were previously granted
requirements to manufacturers that have agreed that an alternate test procedure is a waiver. The R410A CITY MULTI
petitioned DOE for a waiver of such necessary while a final test procedure systems, like the R22 models, can
prescribed test procedures. 10 CFR for these types of products is being connect more indoor units than the test
430.27(a)(2), 10 CFR 431.401(a)(2). An developed.6 laboratories can physically test at one
Interim Waiver remains in effect for a time. Because of the inability to test
Assertions and Determinations
period of 180 days or until DOE issues products with so many indoor units,
its determination on the Petition for MEUS’s Petition for Waiver testing laboratories will not be able to
Waiver, whichever is sooner, and may DOE previously granted MEUS a test many of the R410A system
be extended for an additional 180 days, waiver from test procedures in 2004 for combinations. Furthermore, MEUS
if necessary. 10 CFR 430.27(h), 10 CFR similar CITY MULTI VRFZ models asserted that the current DOE test
431.401(e)(4). which use R22 as a refrigerant.7 Given procedures do not provide direction for
On November 7, 2005, MEUS filed an product adjustments to accommodate determining what combinations of
Application for Interim Waiver and outdoor and indoor units should be
Petition for Waiver from the test 2 Energy Conservation Program for Consumer tested in the circumstance where a
procedures applicable to the R410A Products: Publication of the Petition for Waiver and multitude of different combinations are
models of its CITY MULTI VRFZ line of Granting of the Application for Interim Waiver of possible. Also, the test procedures
Mitsubishi Electric From the DOE Residential and provide no mechanism for sampling
residential and commercial package air Commercial Package Air Conditioner and Heat
conditioning and heating equipment. Pump Test Procedures (Case No. CAC–012), 71 FR component combinations. In addition,
MEUS’s petition requested a waiver 14858 (March 24, 2006) (hereinafter, March 24th MEUS asserted that it is not practical to
from both the residential and Notice). On April 11, 2006, MEUS submitted a test all of the potentially available
Corrected Petition for Waiver of Test Procedure and combinations of indoor and outdoor
commercial test procedures. In Application for Interim Waiver (‘‘Corrected
particular, MEUS requested a waiver Petition’’) to DOE. The Corrected Petition noted five units, which could number in the
from the residential test procedures minor errors in the list of model numbers for which billions.
contained in 10 CFR Part 430, subpart the waiver and the interim waiver had been MEUS stated that the R410A CITY
requested. MEUS requested that the interim waiver MULTI system is designed to be
B, Appendix M, and a waiver from the granted apply to the corrected list of model
commercial test procedures contained numbers, and that DOE use the corrected list of flexible, with numerous combinations
in ARI Standard 210/240–2003 and in model numbers in any future actions regarding the possible. According to MEUS, each of
ARI Standard 340/360–2000.1 MEUS Petition for Test Procedure Waiver. In a letter dated the 108,000 Btu/h rated outdoor units is
June 1, 2006, DOE granted MEUS’s request. designed to be connected with up to 18
seeks a waiver from the applicable test 3 March 24th Notice, 71 FR 14861.

procedures because the design 4 The only commenter that objected to MEUS’s
indoor units, while each of the 234,000
characteristics of the R410A systems Petition was Lennox International Inc.
Btu/h rated outdoor units can be
prevent testing according to the 5 See Comments submitted by Sanyo Fisher configured with up to 32 indoor units.
currently prescribed test procedures. Company, Samsung and Quietside, United MEUS offers 58 different indoor models
On March 24, 2006, DOE published
Mechanical, Daikin AC (Americas), Inc., and Rheem that can be used in the different
Heating and Cooling. combinations. Given the above, MEUS
MEUS’s Petition for Waiver and granted 6 See Comments submitted by MEUS, Sanyo

Fisher Company, Samsung and Quietside, Daikin


asserts the current test procedures
1 In its petition, MEUS also requested a waiver AC (Americas), Inc., and Rheem Heating and cannot practically be applied to the
CITY MULTI VRFZ systems.
sroberts on PROD1PC70 with NOTICES

from ARI Standard 210/240–2003. Based on a Cooling.


review of the products listed by MEUS in its 7 Energy Conservation Program for Consumer MEUS claims that many of the
petition, DOE has determined that none of the Products: Decision and Order Granting a Waiver benefits of its systems’ characteristics,
products have the combined features (i.e., 3-phase From the DOE Commercial Package Air Conditioner
power and rated capacity less than 65,000 Btu/h) and Heat Pump Test Procedure to Mitsubishi
including variable refrigerant control
that would require a waiver from ARI Standard 210/ Electric (Case No. CAC–008), 69 FR 52660, at 52662 and distribution, zoning diversity, part-
240–2003. (Aug. 27, 2004) (hereinafter, ‘‘2004 Waiver’’). load operation and simultaneous

VerDate Aug<31>2005 18:21 Apr 06, 2007 Jkt 211001 PO 00000 Frm 00055 Fmt 4703 Sfmt 4703 E:\FR\FM\09APN1.SGM 09APN1
17530 Federal Register / Vol. 72, No. 67 / Monday, April 9, 2007 / Notices

heating and cooling, are not credited covered by EPCA. (42 U.S.C. 6293(c), 42 which disadvantages these products
under the current test procedures. For U.S.C. 6314(d)). The ability of a because they are optimized for best
residential systems, there are some manufacturer to make representations efficiency when operating with less than
deficiencies in the current DOE test about the energy efficiency of its full loads. In fact, these products
methods and calculation algorithms products is important, for instance, to normally operate at part-load
when applied to multi-split systems. determine compliance with state and conditions. Therefore, as explained in
With regard to commercial systems, local energy codes and regulatory the March 24th Notice, the alternate test
MEUS asserts that the current test requirements. Energy efficiency procedure will provide a conservative
procedure for the energy efficiency ratio representations also provide valuable basis for assessing the energy efficiency
(‘‘EER’’) does not capture the energy consumer purchasing information. for such products.10
savings of VRFZ products. The same Therefore, to provide a basis from which The alternate test procedure applies to
issue was raised by MEUS in its petition manufacturers covered by a test both residential and commercial multi-
for waiver for its R22 CITY MULTI procedure waiver for VRFZ products split products. However, some
products. As DOE stated in the waiver can make valid energy efficiency provisions are specific to residential or
granted in August 2004, ‘‘while this representations, DOE proposed an commercial products. Section (A) of the
assertion is true, it is irrelevant because alternate test procedure for MEUS in the alternate test procedure has different
the full load EER energy efficiency March 24th Notice. provisions for residential and
descriptor is one mandated by EPCA for The alternate test procedure has two commercial products. Section (B),
these products (42 U.S.C. 6313(a)(1)(c)), basic components. First, it permits which defines the combinations of
and the relevant energy performance is indoor and outdoor units to test, and
MEUS to designate a ‘‘tested
the peak load efficiency, not the section (C), which sets forth the
combination’’ for each model of outdoor
seasonal energy savings.’’ 8 A waiver can requirements for making
unit. The indoor units designated as
only be granted if a test procedure does representations, are the same for both
part of the tested combination must
not fairly represent the peak load energy residential and commercial products.
meet specific requirements. For Section (A) distinguishes between
consumption characteristics which EER example, the tested combination must
measures. Therefore, the basis for this residential and commercial products for
have from two to five indoor units so two reasons. First, 10 CFR part 430.24,
waiver, as was the case for the 2004
that it can be tested in available test used for residential products, already
Waiver, is the problem of being
facilities. The tested combination must has requirements for selecting split-
physically unable to test most of the
be tested according to the applicable system combinations based on the
complete systems in a laboratory, the
DOE test procedure. Second, it permits highest sales volume. Part 431 of 10
regulatory requirement to test the
MEUS to represent the energy efficiency CFR, which applies to commercial
highest-sales-volume combination, and
for a non-tested combination in two products, has no comparable
the lack of a method for predicting the
ways. MEUS may represent the energy requirements. Section (A) modifies the
performance of untested combinations.
Lennox International Inc. argued that efficiency of a non-tested combination: residential and commercial CFR
waivers for VRFZ systems should not be (1) At an energy efficiency level requirements so that both residential
granted because the existing DOE test determined under a DOE-approved and commercial products can use the
procedures are available to rate these alternative rating method; or, if method same definition of a ‘‘tested
systems. DOE agrees that the existing (1) Is not available, (2) at the efficiency combination,’’ which definition is set
test procedures can be used, but only level of the tested combination utilizing forth in section (B). Second, section (A)
after clarifications are made and the same outdoor unit. Until an requires several test procedure revisions
deficiencies are addressed. alternative rating method is developed, to determine the SEER and HSPF for the
In August 2004, DOE granted a all combinations with a particular tested combination of residential
Petition for Waiver to MEUS relating to outdoor unit may use the rating of the products. No test procedure revisions
its R22 CITY MULTI VRFZ products, combination tested with that outdoor are introduced for commercial products.
finding that ‘‘the basic model contains unit. DOE believes that allowing MEUS [P3] The changes for residential
one or more design characteristics to make energy efficiency products relate to: (1) The requirement
which * * * prevent testing of the basic representations for non-tested that all indoor units operate during all
model according to the prescribed test combinations as described above is tests, (2) the restriction on using only
procedures.’’ 9 MEUS’s November 2005 reasonable because the outdoor unit is one indoor test room, (3) the selection
Petition for Waiver for its R410A CITY the principal efficiency driver. The of the modulation levels (maximum,
MULTI VRFZ products presents current test procedure tends to rate minimum, and a specified intermediate
virtually the same issues, and thus we these products conservatively. This is speed) used when testing, and (4) the
find that waiver of the test procedures because the current test procedure does algorithm for estimating performance
is appropriate. To enable MEUS to make not account for the product’s over the intermediate speed operating
energy efficiency representations for the simultaneous heating and cooling range. These changes are proposed in a
specified CITY MULTI products, DOE capability, which is more efficient than July 20, 2006, DOE notice of proposed
adopts the alternate test procedure requiring all zones to be either heated or rulemaking. 71 FR 41320. For today’s
described below. cooled. Further, the multi-zoning Decision and Order, the July 20, 2006,
feature of these products, which enables proposed changes to test procedure
DOE’s Alternate Test Procedure them to cool only those portions of the sections 2.1, 2.2.3, 2.4.1, 3.2.4
As explained in DOE’s March 24th building that require cooling, can use (including Table 6), 3.6.4 (including
Notice, manufacturers face restrictions less energy than if the unit is operated Table 12), 4.1.4.2, and 4.2.4.2 constitute
with respect to making representations to cool the entire home or a mandatory elements of the alternate test
sroberts on PROD1PC70 with NOTICES

about the energy consumption and comparatively larger area of a procedure. These changes allow indoor
energy consumption costs of products commercial building in response to a units to cycle off, allow the
single thermostat. Additionally, the manufacturer to specify the compressor
8 69 FR 52662 (Aug. 27, 2004). current test procedure for commercial
9 Ibid. equipment requires full load testing, 10 71 FR 14862 (March 24, 2006).

VerDate Aug<31>2005 18:21 Apr 06, 2007 Jkt 211001 PO 00000 Frm 00056 Fmt 4703 Sfmt 4703 E:\FR\FM\09APN1.SGM 09APN1
Federal Register / Vol. 72, No. 67 / Monday, April 9, 2007 / Notices 17531

speed used during certain tests, and alternate test procedure. As explained in B, Appendix M, and[P9] ARI Standard
introduce a new algorithm for the March 24th Notice, the alternate test 340/360–2000. After reviewing and
estimating power consumption. procedure adopts a conservative considering all of the comments
With regard to the laboratory testing approach for rating VRFZ products submitted regarding the proposed
of both residential and commercial based on the tested results of a simple alternate test procedure, DOE believes
products, some of the difficulties are system configuration. In the proposed that the proposed alternate test
avoided by the requirements for alternate test procedure, DOE would procedure, with the clarifications
choosing the indoor units to be used in allow manufacturers to make efficiency discussed above, should be adopted.
the manufacturer-specified tested representations for non-tested DOE will also consider applying the
combination. For example, in addition combinations at the DOE-prescribed same alternate test procedure to similar
to limiting the number of indoor units, minimum efficiency level for the waivers for residential and commercial
another requirement is that all of the product class only if the tested central air conditioners and heat pumps.
indoor units must be subject to meeting combination with the same outdoor unit
the same minimum external static met or exceeded the minimum MEUS Waiver for R22 Products
pressure. This requirement allows the efficiency level. 71 FR 14862, March 24, In the previous paragraph, DOE stated
test lab to manifold the outlets from 2006. DOE is eliminating this option its intention to consider applying the
each indoor unit into a common plenum because, as explained below, there is no alternate test procedure to similar
that supplies air to a single airflow need for it. waivers. Such a similar waiver was
measuring apparatus. This requirement Rheem suggested that third party granted to MEUS for its R22 CITY
eliminates situations in which some of testing, or on-site witness testing, is the MULTI VRFZ products on August 27,
the indoor units are ducted and some preferred method to verify system 2004 (the ‘‘2004 Waiver’’, see footnote
are non-ducted. Without this performance.13 Additionally, Rheem 7). As discussed previously, the R22
requirement, the laboratory must requested that, in order to provide fair products are quite similar to the R410A
evaluate the capacity of a subgroup of and equitable test methods and ratings products that are the subject of this
indoor coils separately, and then sum to the consumer, the heating test points waiver. Therefore, today’s notice
the separate capacities to obtain the and laboratory operating conditions amends the 2004 Waiver to prohibit
overall system capacity. This would remain consistent.14 DOE’s alternate test MEUS from making energy efficiency
require that the test lab must be procedure would specify certain representations regarding its R22 CITY
equipped with multiple airflow parameters for the testing of VRFZ MULTI products unless such
measuring apparatuses (which is products, but would otherwise retain representations are made consistent
unlikely), or that the test lab connect its the existing test procedure protocols on with the provisions of the alternate test
one airflow measuring apparatus to one issues such as where products are procedure.
or more common indoor units until the tested, test points, and laboratory DOE consulted with the Federal Trade
contribution of each indoor unit has operating conditions. Thus, in these Commission (‘‘FTC’’) concerning the
been measured. respects, VRFZ systems would be tested
MEUS petition. The FTC did not have
DOE stated that if it specified an as other products are tested under the
any objections to the issuance of the
alternate test procedure for MEUS, it existing test procedures.
Lennox suggested that DOE bar sales waiver to MEUS. Thus, DOE is granting
would consider applying the procedure MEUS’s petition.
to waivers for similar residential and of non-tested combinations with an
commercial central air conditioners and evaporator capacity of less than 95% of Conclusion
heat pumps produced by other the nominal outdoor unit capacity
unless an approved ARM (alternative After careful consideration of all the
manufacturers. Most of the comments material that was submitted by MEUS,
received by DOE favored the proposed rating method) simulation is available to
demonstrate conformance to the the comments received, the review by
alternate test procedure. Commenters NIST, and consultation with the FTC, it
generally agreed that an alternate test minimum efficiency requirement.15 No
data was provided to justify this is ordered that:
procedure is appropriate for an interim
proposed indoor-to-outdoor sizing (1) The ‘‘Petition for Waiver’’ filed by
period while a final test procedure for
limitation and so DOE is inclined not to Mitsubishi Electric and Electronics
these products is being developed.11
impose such a regulatory limitation on USA, Inc. (MEUS) (Case No. CAC–012)
Sanyo and Daikin raised concerns
VRFZ configurations at this time. is hereby granted as set forth in the
regarding DOE’s proposal to allow
Moreover, DOE expects the paragraphs below.
manufacturers to represent the energy
efficiency of non-tested combinations at development of an alternative rating (2) MEUS shall not be required to test
the DOE-prescribed minimum efficiency method that is applicable to multi-split or rate its R410A CITY MULTI Variable
level for the product class. They systems like the MEUS CITY MULTI Refrigerant Flow Zoning (‘‘VRFZ’’)
suggested that allowing such ratings products will follow, and not precede, products listed below on the basis of the
without testing the product may allow the work by ARI members to develop a currently applicable test procedures, but
low efficiency products to be installed multi-split test procedure. shall be required to test and rate such
even though equipment that meets or Based on the discussion above, DOE products according to the alternate test
exceeds the minimum requirements is believes that the testing problems procedure as set forth in Paragraph
available.12 DOE believes these described above do prevent testing of (3): 16
commenters misread the proposed the R410A CITY MULTI basic model CITY MULTI Variable Refrigerant
according to the test procedures Flow Zoning System R–2 Series Outdoor
11 See Comments submitted by Sanyo Fisher prescribed in 10 CFR Part 430, Subpart Equipment:
• PURY–P72TGMU–*, 72,000 Btu/h
sroberts on PROD1PC70 with NOTICES

Company (Sanyo, No. 7), Samsung and Quietside


(Samsung, No. 8), Daikin AC (Americas), Inc. 13 See Comments submitted by Rheem Heating
208/230–3–60 split-system variable-
(Daikin, No. 3), and Rheem Heating and Cooling and Cooling, (Rheem, No. 5 at page 2).
(Rheem, No. 5). 14 See Comments submitted by Rheem Heating
speed heat pump.
12 See Comments submitted by Sanyo Fisher and Cooling, (Rheem, No. 5 at page 2).
Company, (Sanyo, No.7 at page 1) and Daikin AC 15 See Comments submitted by Lennox 16 The * denotes engineering differences in the

(Americas), Inc., (Daikin, No. 3 at pages 1–2). International Inc., (Lennox, No. 6 at page 2). models.

VerDate Aug<31>2005 18:21 Apr 06, 2007 Jkt 211001 PO 00000 Frm 00057 Fmt 4703 Sfmt 4703 E:\FR\FM\09APN1.SGM 09APN1
17532 Federal Register / Vol. 72, No. 67 / Monday, April 9, 2007 / Notices

• PURY–P96TGMU–*, 96,000 Btu/h system variable-capacity air conditioner that are listed in the July 20, 2006
208/230–3–60 split–system variable- or heat pump. Federal Register Notice. 71 FR 41320,
speed heat pump. • PCFY Series—Ceiling Suspended— July 20, 2006. These designated changes
• PURY–P108TGMU–*, 108,000 Btu/ PCFY–P12/18/24/30/36***–*. are with respect to the following test
h 208/230–3–60 split-system variable- • PDFY Series—Ceiling Concealed procedure sections: 2.1, 2.2.3, 2.4.1,
speed heat pump. Ducted—PDFY–P06/08/12/15/18/24/30/ 3.2.4 (including Table 6), 3.6.4
• PURY–P126TGMU–*, 126,000 Btu/ 36/48***–*. (including Table 12), 4.1.4.2, and
h, 208/230–3–60 split-system variable- • PEFY Series—Ceiling Concealed 4.2.4.2.
speed heat pump. Ducted (Low Profile)—PEFY–P06/08/ (iii) For products covered by 10 CFR
• PURY–P144TGMU–*, 144,000 Btu/ 12***–*. Part 431 (commercial products), MEUS
h, 208/230–3–60 split-system variable- • PEFY Series—Ceiling Concealed shall test a ‘‘tested combination’’
speed heat pump. Ducted (Alternate High Static Option)— selected in accordance with the
• PURY–P168TGMU–*, 168,000 Btu/ PEFY–P15/18/24/27/30/36/48/54/72/ provisions of subparagraph (B) of this
h, 208/230–3–60 split-system variable- 96***–*. paragraph. For every other system
speed heat pump. • PEFY–F Series—Ceiling Concealed combination using the same outdoor
• PURY–P192TGMU–*, 192,000 Btu/ Ducted (100% OA Option)—PEFY–P unit as the tested combination, MEUS
h, 208/230–3–60 split-system variable- 30/54/72/96***––*. shall make representations concerning
speed heat pump. • PFFY Series—Floor Standing the R410A CITY MULTI products
• PURY–P204TGMU–*, 204,000 Btu/ (Concealed)—PFFY–P06/08/12/15/18/ covered in this waiver according to the
h, 208/230–3–60 split-system variable- 24***–*. provisions of subparagraph (C) below.
speed heat pump. • PFFY Series—Floor Standing
• PURY–P216TGMU–*, 216,000 Btu/ (B) Tested combination. The term
(Exposed)—PFFY–P06/08/12/15/18/
h, 208/230–3–60 split-system variable- ‘‘tested combination’’ means a sample
24***–*.
basic model comprised of units that are
speed heat pump. • PKFY Series—Wall-Mounted—
• PURY–P234TGMU–*, 234,000 Btu/ production units, or are representative
PKFY–P06/08/12/18/24/30***–*.
h, 208/230–3–60 split-system variable- • PLFY Series—4-Way Airflow of production units, of the basic model
speed heat pump. Ceiling Cassette—PLFY–P12/18/24/30/ being tested. For the purposes of this
CITY MULTI Variable Refrigerant 36***–*. waiver, the tested combination shall
Flow Zoning System Y-Series Outdoor • PMFY Series—1-Way Airflow have the following features:
Equipment: Ceiling Cassette—PMFY–P06/08/12/ (i) The basic model of a variable
• PUHY–P72TGMU–*, 72,000 Btu/h 15[MR12]***–*. refrigerant flow system used as a tested
208/230–3–60 split-system variable- (3) Alternate test procedure. combination shall consist of an outdoor
speed heat pump. (A) MEUS shall be required to test the unit that is matched with between 2 and
• PUHY–P96TGMU–*, 96,000 Btu/h products listed in Paragraph (2) above 5 indoor units.
208/230–3–60 split-system variable- according to those test procedures for (ii) The indoor units shall—
speed heat pump. central air conditioners and heat pumps (a) Represent the highest sales volume
• PUHY–P108TGMU–*, 108,000 Btu/ prescribed by DOE at 10 CFR Parts 430 type models;
h 208/230–3–60 split-system variable- and 431, except that: (b) Together, have a capacity between
speed heat pump. (i) For products covered by 10 CFR 95% and 105% of the capacity of the
• PUHY–P126TGMU–*, 126,000 Btu/ Part 430 (consumer products), MEUS outdoor unit;
h, 208/230–3–60 split-system variable- shall not be required to comply with: (1) (c) Not, individually, have a capacity
speed heat pump. The first sentence in 10 CFR greater than 50% of the capacity of the
• PUHY–P144TGMU–*, 144,000 Btu/ 430.24(m)(2), which refers to ‘‘that outdoor unit;
h, 208/230–3–60 split-system variable- combination manufactured by the (d) Have a fan speed that is consistent
speed heat pump. condensing unit manufacturer likely to with the manufacturer’s specifications;
• PUHY–P168TGMU–*, 168,000 Btu/ have the highest volume of retail sales;’’ and
h, 208/230–3–60 split-system variable- and (2) the third sentence in 10 CFR (e) All have the same external static
speed heat pump. 430(m)(2) and the provisions of 10 CFR pressure[MR15].
• PUHY–P192TGMU–*, 192,000 Btu/
430(m)(2)(i) and (ii). Instead of testing (C) Representations. MEUS may make
h, 208/230–3–60 split-system variable-
the combinations likely to have the representations about the energy
speed heat pump.
highest volume of retail sales, MEUS efficiency of CITY MULTI VRFZ
• PUHY–P204TGMU–*, 204,000 Btu/
may test a ‘‘tested combination’’ products, for compliance, marketing, or
h, 208/230–3–60 split-system variable-
selected in accordance with the other purposes, only to the extent that
speed heat pump
• PUHY–P216TGMU–*, 216,000 Btu/ provisions of subparagraph (B) of this such representations are made
h, 208/230–3–60 split–system variable- paragraph. Additionally, instead of consistent with the provisions outlined
speed heat pump. following the provisions of 10 CFR below:
• PUHY–P234TGMU–*, 234,000 Btu/ 430(m)(2)(i) and (ii) for every other (i) For CITY MULTI VRFZ
h, 208/230–3–60 split-system variable- system combination using the same combinations tested in accordance with
speed heat pump. outdoor unit as the tested combination, this alternate test procedure, MEUS may
CITY MULTI Variable Refrigerant MEUS shall make representations make representations based on these test
Flow Zoning System S-Series Outdoor concerning the R410A CITY MULTI results.
Equipment: products covered in this waiver (ii) For CITY MULTI VRFZ
• PUMY–P48NHMU–*, 48,000 Btu/h, according to the provisions of combinations that are not tested, MEUS
208/230–1–60 split-system variable- subparagraph (C) below. may make representations which are
sroberts on PROD1PC70 with NOTICES

speed heat pump (ii) For products covered by 10 CFR based on the testing results for the
CITY MULTI Variable Refrigerant Part 430 (consumer products), MEUS tested combination and which are
Flow Zoning System Indoor Equipment: shall be required to comply with 10 CFR consistent with either of the two
• P*FY models, ranging from 6,000 to 430 Appendix M as amended in following methods, except that only
96,000 Btu/h, 208/230–1–60 split- accordance with designated changes method (a) may be used, if available:

VerDate Aug<31>2005 18:21 Apr 06, 2007 Jkt 211001 PO 00000 Frm 00058 Fmt 4703 Sfmt 4703 E:\FR\FM\09APN1.SGM 09APN1
Federal Register / Vol. 72, No. 67 / Monday, April 9, 2007 / Notices 17533

(a) Representation of non-tested Electric and Electronics USA, Inc. According to 10 CFR 1004.11, any
combinations according to an (MEUS). This Petition for Waiver person submitting information that he
Alternative Rating Method (‘‘ARM’’) (hereafter ‘‘MEUS Petition’’) requests a or she believes to be confidential and
approved by DOE. waiver of the Department of Energy exempt by law from public disclosure
(b) Representation of non-tested (‘‘DOE’’) test procedures applicable to should submit two copies: one copy of
combinations at the same energy commercial package water source heat the document including all the
efficiency level as the tested pumps. DOE is soliciting comments, information believed to be confidential,
combination with the same outdoor data, and information with respect to and one copy of the document with the
unit. the MEUS Petition. Today’s notice also information believed to be confidential
(4) The waiver granted for MEUS’s grants an Interim Waiver to MEUS, with deleted. DOE will make its own
R22 CITY MULTI VRFZ products on an alternate test procedure, from the determination about the confidential
August 27, 2004 17 is hereby amended to existing DOE test procedure applicable status of the information and treat it
prohibit MEUS from making energy to commercial package water source according to its determination.
efficiency representations regarding its heat pumps. Docket: For access to the docket to
R22 CITY MULTI products unless such DATES: DOE will accept comments, data,
read the background documents
representations are made consistent and information regarding this Petition relevant to this matter, go to the U.S.
with the provisions set forth in for Waiver until, but no later than May Department of Energy, Forrestal
Paragraph (3) above. 9, 2007. Building, Room 1J–018 (Resource Room
(5) This waiver shall remain in effect of the Building Technologies Program),
ADDRESSES: Please submit comments,
from the date of issuance of this Order 1000 Independence Avenue, SW.,
identified by case number [CAC–015], Washington, DC, (202) 586–2945,
until DOE prescribes final test by any of the following methods:
procedures appropriate to the model between 9 a.m. and 4 p.m., Monday
• Mail: Ms. Brenda Edwards-Jones, through Friday, except Federal holidays.
series manufactured by MEUS and U.S. Department of Energy, Building
listed above. Available documents include the
Technologies Program, Mailstop EE–2J, following items: this notice; public
(6) This waiver is conditioned upon Forrestal Building, 1000 Independence
the presumed validity of statements, comments received; the Petition for
Avenue, SW., Washington, DC 20585– Waiver and Application for Interim
representations, and documentary 0121. Telephone: (202) 586–2945.
materials provided by the petitioner. Waiver; prior Department rulemakings
Please submit one signed original paper regarding commercial central air
This waiver may be revoked or modified copy.
at any time upon a determination that conditioners and heat pumps; the prior
• Hand Delivery/Courier: Ms. Brenda MEUS Petition for Waiver, DOE’s notice
the factual basis underlying the petition Edwards-Jones, U.S. Department of
is incorrect, or DOE determines that the of the prior MEUS Petition for Waiver
Energy, Building Technologies Program, and the DOE Decision and Order (D&O)
results from the alternate test procedure Room 1J–018, Forrestal Building, 1000
are unrepresentative of the basic regarding the prior MEUS Petition,
Independence Avenue, SW., which is being published today. Please
models’ true energy consumption Washington, DC 20585–0121.
characteristics. call Ms. Brenda Edwards-Jones at the
• E-mail: above telephone number for additional
Issued in Washington, DC, on April 2, Michael.raymond@ee.doe.gov. Include information regarding visiting the
2007. either the case number [CAC–015], and/ Resource Room. Please note: DOE’s
Alexander A. Karsner, or ‘‘MEUS Petition’’ in the subject line Freedom of Information Reading Room
Assistant Secretary, Energy Efficiency and of the message. (formerly Room 1E–190 at the Forrestal
Renewable Energy. • Federal eRulemaking Portal: http:// Building) is no longer housing
[FR Doc. E7–6608 Filed 4–6–07; 8:45 am] www.regulations.gov. Follow the rulemaking materials.
BILLING CODE 6450–01–P instructions for submitting comments.
FOR FURTHER INFORMATION CONTACT: Dr.
Instructions: All submissions received
Michael G. Raymond, U.S. Department
must include the agency name and case
of Energy, Office of Energy Efficiency
DEPARTMENT OF ENERGY number for this proceeding. Submit
and Renewable Energy, Building
electronic comments in WordPerfect,
Office of Energy Efficiency and Technologies Program, Mail Stop EE–2J,
Microsoft Word, PDF, or text (ASCII) file
Renewable Energy Forrestal Building, 1000 Independence
format and avoid the use of special
Avenue, SW., Washington, DC 20585–
characters or any form of encryption.
Energy Conservation Program for 0121, (202) 586–9611; e-mail:
Wherever possible, include the
Consumer Products: Publication of the Michael.Raymond.ee.doe.gov; or
electronic signature of the author.
Petition for Waiver and Granting of the Francine Pinto, Esq., U.S. Department of
Absent an electronic signature,
Application for Interim Waiver of Energy, Office of General Counsel, Mail
comments submitted electronically
Mitsubishi Electric From the DOE Stop GC–72, Forrestal Building, 1000
must be followed and authenticated by
Commercial Water Source Heat Pump Independence Avenue, SW.,
submitting the signed original paper
Test Procedure [Case No. CAC–015] Washington, DC 20585–0103, (202) 586–
document. DOE does not accept
9507; e-mail:
AGENCY: Office of Energy Efficiency and telefacsimiles (faxes). Any person
Francine.Pinto@hq.doe.gov.
Renewable Energy, Department of submitting written comments must also
send a copy of such comments to the SUPPLEMENTARY INFORMATION:
Energy.
petitioner. 10 CFR 431.401(d)(2). The I. Background and Authority
ACTION: Notice of petition for waiver, II. Petition for Waiver
granting of application for interim name and address of the petitioner of III. Application for Interim Waiver
today’s notice is: William Rau, Senior
sroberts on PROD1PC70 with NOTICES

waiver, and request for comments. IV. Alternate Test Procedure


Vice President and General Manager, V. Summary and Request for Comments
SUMMARY: Today’s notice publishes a HVAC Advanced Products Division,
Petition for Waiver from Mitsubishi Mitsubishi Electric & Electronics USA, I. Background and Authority
Inc., 4300 Lawrenceville-Suwanee Road, Title III of the Energy Policy and
17 71 FR 14858 (March 24, 2006). Suwanee, GA 30024. Conservation Act (EPCA) sets forth a

VerDate Aug<31>2005 18:21 Apr 06, 2007 Jkt 211001 PO 00000 Frm 00059 Fmt 4703 Sfmt 4703 E:\FR\FM\09APN1.SGM 09APN1

You might also like