Catalogue2013
Source
changeover
systems
Compact NSX100-630, Compact NS630b-1600,
Compact INS/INV, Masterpact
Efficient energy
management and
continuity of service with
source-changeover system
To ensure continuity of service for critical applications,
LV electrical installations need to be connected to
at least two independent power sources:
1
2
A normal
The source-changeover
source (N)
And a replacement
between these
two sources.
source (R)*
> A source-changeover
a main power source to system comprises
a replacement source circuit breakers,
can be performed
either manually or
automatically.
switch-disconnectors
or contactors.
* The replacement source (R) can be: a second power source (with possibly different
characteristics from the normal source) or an electrical generator
I
ways
System
Applications
System
Applications
System
II
Applications
Compact INS
From 40 A to 630 A
Maximum continuity
of service
Masterpact NT / NW
From 630 A to 6300 A
Maximum safety
Optimized energy
management
UA Controller
Compact NSX
From 100 A to 630 A
III
IV
Managing
energy
efciently
Power Cost
Safety
Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Compact INS/INV, Masterpact
General content
Presentation
A-1
Dimensions
B-1
Electrical diagrams
C-1
Catalogue numbers
and order forms
D-1
Presentation
Db101543.eps
PB105109.eps
Currents
From 630 to 6300 A.
PD390385_SE_R_35.eps
Power distribution
Currents
From 250 to 3200 A.
PB111556.eps
Loads
Currents
From 40 to 400 A.
QN
0
1
0
QR
QS1
QC
QS2
0
0
0
1
0
1
1
1
0
0
1
1
1
0
0 (1)
0
0
1 (1)
(1) possible by forcing
operation.
0
0
1
2 normal sources
1 replacement source
Db101540.eps
Db101539.eps
Db101538.eps
1 normal source
1 replacement source
QN1
0
1
0
1
0
QN2
QR
0
1
0
0
1
0
0
1
0
0
Generator or permanent
source
Db101541.eps
QN
0
1
0
0
0
1
Typical applications:
b continuous production processes
b operating rooms
b computer rooms...
Generator or permanent
source
Db101544.eps
Db101541.eps
Generator or permanent
source
QR
QN
0
1
0
QR
0
0
1
Typical applications:
b large electrical installations (e.g. airports)
b refrigeration units
b special electricity tariffs
b pumping stations...
TOOLS
Ecodial
Ecodial software is dedicated to LV electrical installation
calculation in accordance with the IEC60364
international standard or national standards.
This 4th generation, "Ecodial Advance Calculation 4",
offers a new ergonomic and new features:
p operating mode that allows easy calculation in case
of installation with different type of sources
(parallel transformers, back-up generators)
p discrimination analysis associating curves checking
and discrimination tables
p direct access to protection settings including residual
current protections
p easy selection of alternate solutions or manual
selection of a product.
Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Compact INS/INV, Masterpact
Presentation
Overview of solutions
Manual source-changeover systems Compact INS/INV 40 to 630 A,
Compact NSX100/630
Manual source-changeover systems Compact NS
and Masterpact NT/NW 630 A to 6300 A
Remote-operated source-changeover systems
Compact NSX100/630, Compact NS630b/1600 A
Remote-operated source-changeover systems
Masterpact NT/NW 630 A to 6300 A
A-2
A-3
A-4
A-5
A-6
A-10
A-11
A-12
A-13
A-14
A-15
A-16
$
Associated controllers
Controller selection
Controller installation
BA controller
BA controller, Operating sequences
UA controller
UA controller, Operating sequences, Forced operation mode
UA controller, Operating sequences, Special-tariff mode
UA controller, Operating sequences , Test mode and automatic operation
A-18
A-19
A-20
A-21
A-22
A-23
A-24
A-25
Operating sequences
IVE unit
%$8$FRQWUROOHU
A-26
$
A-28
B-1
C-1
D-1
A-1
Functions
and characteristics
Range
Overview of solutions
Manual source-changeover systems
Compact INS/INV 40 to 630 A, Compact
NSX100/630
Compact
Models
Compact
INS40 to INS80
INS100 to INS160
40 to 160
Switch-disconnectors with
extended handles
Rating (A)
Type of device
INS250 to INS630
INV250 to INV630
100 to 630
Switch-disconnectors
NSX100 to NSX250
NSX400 to NSX630
100 to 630
N/H/L circuit breakers
NA switch-disconnectors
DB126589.eps
2 devices side-by-side.
3 devices side-by-side.
Db101548.eps
'EHSV
Db101546.eps
.4
DB126590.eps
ON
I
O
OFF
2 devices side-by-side.
O
OFF
Db101550.eps
Db101549.eps
DB126588.eps
Db101551.eps
'%HSV
2 devices side-by-side.
DB126586.eps
'%HSV
2 devices side-by-side.
A-2
Compact
Masterpact
NS630b to NS1600
630 to 1600
N/H/L circuit breakers
NA switch-disconnectors
NT06 to NT16
630 to 1600
H1/L1 circuit breakers
HA switch-disconnectors
NW08 to NW63
800 to 6300
N1/H1/H2/H3/L1 circuit
breakers
NA/HA/HF switchdisconnectors
DB126590.eps
2 devices side-by-side.
I ON
OOFF
push
push
discharged
O OFF
Db101556.eps
Db101555.eps
Db101554.eps
DB126588.eps
I ON
OOFF
push
push
discharged
O OFF
sup
degr
ahcs
id
Db101559.eps
NO h
Db101562.eps
hsup
Db101558.eps
FFO
FFO
Db101561.eps
'EHSV
DB126585.eps
FFO
hsup
NO h
sup
FFO
O
degr
ahcs
id
Db101560.eps
DB126584.eps
DB126583.eps
(1)
2 or 3 devices side-by-side.
(2)
DB126580.eps
A-3
Functions
and characteristics
Overview of solutions
Range
Compact
Models
Rating (A)
Type of device
Remote-operated source-changeover
systems Compact NSX100/630,
Compact NS630b/1600 A
NSX100 to NSX630
100 to 630
N/H/L circuit breakers
NA switch-disconnectors
NS630b to NS1600
630 to 1600
N/H/L circuit breakers
NA switch-disconnectors
Db101563.eps
'EHSV
DB126585.eps
FFO
hsup
NO h
s
up
FFO
O
degr
a
hcsi
d
FFO
hsup
NO h
sup
FFO
O
degr
a
hcsi
d
Db101560.eps
DB126581.eps
DB126582.eps
(1)
DB404439.eps
BA controller
DB404440.eps
DB126582.eps
A-4
Remote-operated source-changeover
systems Masterpact NT/NW
630 A to 6300 A
Range
Masterpact
Models
Rating (A)
Type of device
NT06 to NT16
630 to 1600
H1/L1 circuit breakers
HA switch-disconnectors
NW08 to NW63
800 to 6300
N1/H1/H2/H3/L1 circuit breakers
NA/HA/HF switch-disconnectors
DB126585.eps
Db101558.eps
Db101562.eps
Db101561.eps
DB126584.eps
DB126583.eps
BA controller
DB404440.eps
DB126582.eps
DB126581.eps
A-5
Functions
and characteristics
Manual source-changeover
systems
Possible combinations
Complete
assembly
Compact switch-disconnectors
Keylock
Direct rotary
handle
Extended
rotary handle
INS40 to INS160
b
INS250-100 to INS630
INV100 to 630
b r
b r
b r
b rr
b
INS/INV630b to 2500
Legend:
r Possible but visible break function disabled.
r 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.
Type of device
Keylock
Direct rotary
handle
Extended rotary
handle
On base plate
On base plate
(toggle or direct extended (motor mechanism)
rotary control)
&RPSDFW[HGRUZLWKGUDZDEOHFLUFXLWEUHDNHUV
NSX100 to 250
bb
bbp
bb
bb
bbb
bbb
NSX400 to NS630
bb
bbp
bb
bb
bbb
bbb
bbp
bbp
bbp
bbbp
bbbp
NSX100 to 630
bb
NS630b to 1600 with
bbp
rotary handle
Legend:
b Fixed devices only.
b Fixed or withdrawable devices.
b 'HYLFHVPXVWEHHLWKHUERWK[HGRUERWKZLWKGUDZDEOH
p With NSX400/630 rotary handle interlocking system.
p Possible with NSX400/630 base plate + NSX100-250 adaptation kit.
p Devices equipped with rotary handles.
Type of device
bb
7\SHRILQWHUORFNLQJIRUHLWKHUDOO[HGRUDOOZLWKGUDZDEOHGHYLFHV
Cable-type,
Cable-type,
Cable-type,
2 devices one
3 devices
2 devices
above the other
side-by-side
side-by-side
&RPSDFW[HGRUZLWKGUDZDEOHFLUFXLWEUHDNHUVRUVZLWKGLVFRQQHFWRUVZLWKPRWRUPHFKDQLVP
Keylock
Cable-type,
3 devices one
above another
b
b
b
NS630b to 1600
0DVWHUSDFW[HGRUZLWKGUDZDEOHFLUFXLWEUHDNHUVRUVZLWKGLVFRQQHFWRUVPDQXDORSHUDWLRQRUZLWKPRWRUPHFKDQLVP
NT06 to 16
NW08 to 63
NT06 to NW63
A-6
b
b
b
b
Rod-type,
3 devices one
above another
b
b
Possible combinations
Complete source-changeover assembly for two switch-disconnectors
All possibilities for manual source-changeover systems
'%HSV
Normal N
Replacement R
INS250-100
INS250-100
Ratings 100 A
INS250-160
Ratings 160 A
INS200-200
Ratings 200 A
INS250-250
Ratings 250 A
INS320
Ratings 320 A
INS400
Ratings 400 A
INS500
Ratings 500 A
INS630
Ratings 630 A
INS250-160
INS200-200
INS250-250
INS320
INS400
INS500
INS630
b
b
b
b
b
b
b
b
Two devices can be interlocked using this system. Two identical interlocking systems
can be used to interlock three devices installed side by side, in which case one
device is in the ON position and the two others are in the OFF position. Devices must
DOOKDYHWKHVDPHFRQJXUDWLRQLH[HGSOXJLQZLWKGUDZDEOHRUGUDZRXW
The system is locked using one or two padlocks (shackle diameter 5 to 8 mm).
Two interlocking system models are available for:
b Compact NSX100 to 250
b Compact NSX400 to 630.
Normal N
NSX100
Ratings 16... 100 A
NSX160
Ratings 80...160 A
NSX250
Ratings 125...250 A
NSX400
Ratings 150... 400 A
NSX630
Ratings 630 A
Replacement R
NSX100
NSX160
NSX250
NSX400
NSX630
$
Functions
and characteristics
Manual source-changeover
systems
Possible combinations
The direct or extended rotary handles are padlocked with the devices in the OFF
position. The mechanism prevents simultaneous closing of the devices, but allows
them to be opened.
ON
I
ON
I
O
OFF
O
OFF
Normal N
Compact NSX100/630 (1)
Replacement R
NSX100
NSX160
NSX250
NSX400
NSX630
NSX100
Ratings 16... 100 A
b
b
b
v
v
NSX160
Ratings 80...160 A
b
b
b
v
v
NSX250
Ratings 125...250 A
b
b
b
v
v
NSX400
Ratings 160... 400 A
v
v
v
b
b
NSX630
Ratings 630 A
v
v
v
b
b
v 250 A and 630 A ratings can be mixed by using NSX400/630 rotary handle interlocking
system.
Normal N
Replacement R
NS800
Compact NS630b/1600 (1) NS630b
NS1000
NS1200
NS1600
NS630b
Ratings 250... 630 A
b
b
b
b
b
NS800
Ratings 320... 800 A
b
b
b
b
b
NS1000
Ratings 400... 1000 A
b
b
b
b
b
NS1200
Ratings 480... 1200 A
b
b
b
b
b
NS1600
Ratings 640... 1600 A
b
b
b
b
b
(1) When mixing NSX100/250 and NSX400/630 circuit breakers, use the NSX400/630
interlocking system.
A-8
Possible combinations
Interlocking of two devices with rotary handles
Possible combinations of Normal and Replacement source switch-disconnectors
'%HSV
The direct or extended rotary handles are padlocked with the devices in the OFF
position. The mechanism prevents simultaneous closing of the devices, but allows
them to be opened.
Normal N
Compact INS (1)
Replacement R
INS40
INS63
INS80
INS100
INS40
Ratings 40 A
b
b
b
b
INS63
Ratings 63 A
b
b
b
b
INS80
Ratings 80 A
b
b
b
b
INS100
Ratings 100 A
b
b
b
b
INS125
Ratings 125 A
b
b
b
b
INS160
Ratings 160 A
b
b
b
b
(1) With extended rotary handles only.
(2) 3RVVLEOHZLWK,19EXWYLVLEOHEUHDNIXQFWLRQLVVLJQLFDQWO\LPSDLUHG
Normal N
Compact INS /INV (2)
INS125
INS160
Replacement R
INS250-100/
INV100
INS250-160/
INV160
INS250-200/
INV200
INS250-250/
INV250
INS250-100/INV100
Ratings 100 A
b
b
b
b
INS250-160/INV160
Ratings 160 A
b
b
b
b
INS250-200/INV200
Ratings 200 A
b
b
b
b
INS250-250/INV250
Ratings 250 A
b
b
b
b
INS320/INV320
Ratings 320 A
v
v
INS400/INV400
Ratings 400 A
INS500/INV500
Ratings 500 A
INS630/INV630
Ratings 630 A
v
v
v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.
INS320/
INV320
INS400/
INV400
INS500/
INV500
INS630/
INV630
Replacement R
NSX100
NSX160
NSX250
NSX400
NSX630
Interlocking uses two identical keylocks with a single key. This solution enables
LQWHUORFNLQJEHWZHHQWZRGHYLFHVWKDWDUHSK\VLFDOO\GLVWDQWRUWKDWKDYHVLJQLFDQWO\
different characteristics.
A-9
Functions
and characteristics
Remote-operated
source-changeover systems
Mechanical interlocking Compact NSX,
Compact NS or Masterpact NT/NW
PB105106_50.eps
Normal N
DB126268.eps
NSX100
Ratings 12,5... 100 A
NSX160
Ratings 12,5...160 A
NSX250
Ratings 12,5...250 A
NSX400
Ratings 160... 400 A
NSX630
Ratings 250... 630 A
Replacement R
NSX100
NSX160
NSX250
NSX400
NSX630
Normal N
Replacement R
NS630b to
NS1600
A-10
NS630b to NS1600
Ratings 250... 1600 A
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A
NT06 to NT16
NW08 to
NW40
NW40b to
NW63
PB100842_68_SE.eps
Mechanical interlocking
Compact NS or Masterpact NT/NW
Interlocking of two Compact NS630b to 1600 or two Masterpact
NT/NW or up to three Masterpact NW devices using cables
For cable interlocking, the circuit breakers may be mounted one above the other or
side-by-side.
7KHLQWHUORFNHGGHYLFHVPD\EH[HGRUGUDZRXWWKUHHSROHRUIRXUSROHDQGKDYH
different ratings and sizes.
Interlocking between two devices (Compact NS630b to 1600 or Masterpact NT
and NW)
This function requires:
b DQDGDSWDWLRQ[WXUHRQWKHULJKWVLGHRIHDFKGHYLFH
b a set of cables with no-slip adjustments.
7KHPD[LPXPGLVWDQFHEHWZHHQWKH[LQJSODQHVYHUWLFDORUKRUL]RQWDOLVPP
Normal N
Replacement R
NS630b to
NS1600
NS630b to NS1600
Ratings 250... 1600 A
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A
NT06 to NT16
NW08 to
NW40
NW40b to
NW63
Normal N
Replacement R
NS630b to
NS1600
NS630b to NS1600
Ratings 250... 1600 A
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A
NT06 to NT16
NW08 to
NW40
NW40b to
NW63
A-11
Remote-operated
source-changeover systems
Functions
and characteristics
General characteristics
Compact NSX
Range
Compact NSX
Types of devices
Types of circuit breakers
Switch-disconnector version
Mixing possibilities
NSX100 to NSX250
N/H/L
NA
all devices
NS100 to NS250
N/H/L/NA
[HGRUSOXJLQ
NSX400 to NSX630
N/H/L
NA
all devices
NS100 to NS630
N/H/L/NA
[HGRUSOXJLQ
Rating
Insulating voltage Ui (V AC)
Positive break indication
Number of poles
(N and R devices must have the same number of poles)
15 to 250 A
b
3, 4
15 to 630 A
b
Electrical durability
Operating temperature
Electrical characteristics
Control characteristics
Control voltage
AC
Maximum consumption
DC
AC
DC
48 V - 50 Hz
110/130, 220/240, 380/440 V - 50/60 Hz
24-250 V
500 VA
500 W
800 ms
48 V - 50 Hz
110/130, 220/240, 380/440 V - 50/60 Hz
24-250 V
500 VA
500 W
800 ms
b
b
1 OF + 1 SDE
b
b
1 OF + 1 SDE
b
b
b
b
b
b
b
b
b
OF + SD (+ SDV)
b
b
b
b
b
b
3 OF + SD (+ SDV)
b
b
b
b
b
b
Interlocking
Mechanical (see page A-10)
Electrical
by diagram (without IVE)
with IVE unit
auxiliary contacts used by circuit breaker
long time
short time
instantaneous
by Vigi module
by control unit
by add-on Vigirex relay
Current measurements
Voltage, frequency, power measurements, etc.
Source-changeover controller
With permanent replacement source
With standby generator set
b BA controller
b UA controller
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
A-12
b
b
b
General characteristics
Compact NS, Masterpact NT/NW
Compact NS
Masterpact
NS630b to NS1600
N/H/L
NA
all devices
NS630b to 1600
N/H/L/NA
[HGRUSOXJLQ
NT06 to 16
N1 / H1 / H2 / H3 / L1
NA / HA / HF
all mixing possibilities
[HGGUDZRXWRU[HGGUDZRXW
N1/H1/H2/H3/L1/NA/HA/HF
NW08 to 63
N1 / H1 / H2 / H3 / L1
NA / HA / HF
all mixing possibilities
[HGGUDZRXWRU[HGGUDZRXW
N1/H1/H2/H3/L1/NA/HA/HF
250 to 1600 A
600 to 1600 A
1000
b
3, 4
800 to 6300 A
1000
b
24-250 V
180 VA
180 W
800 ms
48 to 415 V - 50/60 Hz
440 V - 60 Hz
24-250 V
180 VA
180 W
800 ms
24-250 V
180 VA
180 W
800 ms
b
b
1 OF + 1 CE (+ SDE)
b
only with UA or BA
1 OF + 1 CE + 1 PF
b
only with UA or BA
1 OF + 1 CE + 1 PF
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
2 OF + SD
b
b
2 OF + SD
b
b
b
b
b
b
2 OF + SD
b
b
b
b
b
b
b BA controller
b UA controller
b
b
b
b
b
b
b
b
b
b
b (vertical or horizontal)
b (drawout)
b (vertical or horizontal)
b (drawout)
b (vertical or horizontal)
b (drawout)
b
b
b
b
b
b
b
b
b
b
b
A-13
Remote-operated
source-changeover systems
Functions
and characteristics
Durability (category A)
(ON-CR-OR-CN cycles)
Number of poles
Conventional thermal current (A)
Rated operational current (A)
Durability (category A)
(ON-CR-OR-CN cycles)
lth at 60 C
Ie Electrical AC, 50/60 Hz
440-480 V
660-690 V
Mechanical
Electrical AC, 50/60 Hz
440-480 V
660-690 V
lth
Ie
at 60 C
Electrical AC, 50/60 Hz
440-480 V
660-690 V
Mechanical
Electrical AC, 50/60 Hz
440-480 V
660-690 V
3, 4
100
AC22A
100
100
15000
AC22A
1500
1500
AC23A
100
100
AC23A
1500
1500
3, 4
160
AC22A
160
160
15000
AC22A
1500
1500
AC23A
160
160
AC23A
1500
1500
3, 4
200
AC22A
200
200
15000
AC22A
1500
1500
AC23A
200
200
AC23A
1500
1500
INS250
3, 4
250
AC22A
250
250
15000
AC22A
1500
1500
INS320
INS400
INS500
INS630
3, 4
320
AC22A
320
320
10000
AC22A
1500
1500
3, 4
400
AC22A
400
400
10000
AC22A
1500
1500
3, 4
500
AC22A
500
500
10000
AC22A
1500
1500
3, 4
630
AC22A
630
630
10000
AC22A
1500
1500
AC23A
320
320
AC23A
1500
1500
AC23A
400
400
AC23A
1500
1500
AC23A
500
500
AC23A
1500
1500
AC23A
250
250
AC23A
1500
1500
AC23A
630
630
AC23A
1500
1500
3, 4
100 to 250
20000 - 40000 50000
3, 4
400 to 630
15000
3, 4
630 to 1600
8000
4000 - 6000
2000
2000 - 3000
1500
3, 4
630 to
1600
8000
3, 4
1250 to
1600
8000
3, 4
800 to
1600
10000
3, 4
2000
10000
3, 4
2500 to
4000
10000
3, 4
5000 to
6300
5000
10000
8000
5000
1500
6000
Electrical durability at In 6000
NT16:
(ON-CR-OR-CN cycles)
for y 440 V and 480 V
3000
NEMA (2)
Electrical durability at In 3000
10000
6000
2500
1500
2000
(ON-CR-OR-CN cycles)
NT16:
(2)
for U = 500 V to 690 V
1000
(1) Mechanical and electrical durability not applicable to Masterpact H3 and L versions.
(2) Electrical durability tests carried out with a power factor of 0.8 as per IEC 947-2.
Note:
ON: opening of Normal source
CR: closing of Replacement source
OR: opening of Replacement source
CN: closing of Normal source
A-14
DB413568.eps
7KHFRXSOLQJDFFHVVRU\FDQEHWWHGZLWKWKHVDPHFRQQHFWLRQDQGLQVXODWLRQ
accessories as the circuit breakers and switch-disconnectors.
Possible uses
Downstream coupling
Possible
mounting
Outgoing pitch
(mm)
b
b
b
b
b
b
35
35
35
45
45
45
b
b
35
45
b
b
35
45
1
2
3
4
A-15
Remote-operated
source-changeover systems
Functions
and characteristics
Electrical interlocking
Electrical interlocking is used with a mechanical
interlocking system.
An automatic controller may be added to take into
account information from the distribution system.
'EHSV
IVE unit.
Necessary equipment
For Compact NSX100 to 630, each circuit breaker must be equipped with:
b a motor mechanism
b an OF contact
b an SDE contact.
The components are supplied ready for assembly and the circuit breakers prewired.
7KHSUHZLULQJPXVWQRWEHPRGLHG
For Compact NS630b to 1600, each circuit breaker must be equipped with:
b a motor mechanism
b an available OF contact
b a CE connected-position contact (carriage switch) on withdrawable circuit breakers
b an SDE contact.
For Masterpact NT and NW, each circuit breaker must be equipped with:
b a remote-operation system made up of:
v MCH gear motor
v MX or MN opening release
v XF closing release
v PF ready to close contact
b an available OF contact
b one to three CE connected-position contacts (carriage switches) on drawout
circuit breakers (depending on the installation).
A-16
Standard configurations
Diagram no.
'EHSV
2 devices
QN
QR
51201177
v with EPO by MN
51201178
v with EPO by MX
51201179
51201183
51201184
51201185
51201142
51201143
51201144
51156904
51156905
51156903
Masterpact NW only
Types of mechanical interlocking
Diagram no.
'EHSV
QN2
QR
b electrical interlocking:
51156906
51156907
'EHSV
QN2
QR
51156908
51156909
QS1
QS2
QS3
b electrical interlocking:
51156910
51156911
QS1
QC
QS2
b electrical interlocking:
51156912
51156913
51156914
(1)
(1)
'EHSV
'EHSV
$
Functions
and characteristics
Associated controllers
Controller selection
Controller
BA
UA
4-position switch
Automatic operation
Forced operation on Normal source
Forced operation on Replacement source
Stop (both Normal and Replacement sources off)
b
b
b
b
b
b
b
b
b
b
b
b
b
Automatic operation
Monitoring of the Normal source and automatic transfer
Generator set startup control
Delayed shutdown (adjustable) of generator set
Load shedding and reconnection of non-priority circuits
Transfer to the Replacement source if one of the phases
of the Normal phase is absent
Test
DB403809.eps
b
b
Indications
Circuit breaker status indication on the front of the controller:
on, off, fault trip
Automatic mode indicating contact
Other functions
BA controller.
b
b
b
b
DB403810.eps
Options
Communication option
Power supply
Control voltages (2)
110 V
220 to 240 V 50/60 Hz
380 to 415 V 50/60 Hz
and 440 V 60 Hz
b
b
b
b
b
b
b
b
b
Operating thresholds
Undervoltage
Phase failure
Voltage presence
UA controller.
Front
Side
Connectors
Front
IP40
IP30
IP20
,.
b
b
b
b
b
b
b
b
3%B6(HSV
Controller installation
'%HSV
A-19
Functions
and characteristics
The BA controller is used to create simple sourcechangeover systems that switch from one source to
another depending on the presence of voltage UN on
the Normal source.
It is generally used to manage two permanent sources
and can control Compact NS, Compact NSX and
Masterpact NT/NW circuit breakers and switchdisconnectors.
Associated controllers
BA controller
Operating modes
A four-position switch may be used to select:
b automatic operation
b forced operation on the Normal source
b forced operation on the Replacement source
b stop (both Normal and Replacement sources off).
DB403841.eps
Test
DB403838.eps
BA Controller
A-20
BA controller
Operating sequences
'%HSV
DB126548.eps
DB126549.eps
Key
UN : Normal source voltage
UR : Replacement source voltage
N : Normal source circuit breaker
R : Replacement source circuit breaker
WAITING 7KHV\VWHPH[LWVWKLVPRGHZKHQWKHRSHUDWLQJPRGHLVPRGLHGRU
when an external event occurs (e.g. failure or return of UN).
1
1 The number sends to the indicated step when
the condition is true.
A-21
Functions
and characteristics
DB403842.eps
The UA controller is used to create a sourcechangeover system integrating the following automatic
functions:
b transfer from one source to another depending on
the presence of voltage UN on the Normal source
b startup of an engine generator set
b shedding and reconnection of non-priority circuits
b transfer to the Replacement source if one of the
phases on the Normal source fails.
The UA controller can control Compact NS,
Compact NSX and Masterpact NT/NW devices.
Associated controllers
UA controller
Operating modes
A four-position switch may be used to select:
b automatic operation
b forced operation on the Normal source
b forced operation on the Replacement source
b stop (both Normal and Replacement sources off, then manual operation).
'%HSV
Distribution-system settings
UA Controller
Test
A pushbutton on the front of the controller may be used to test transfer from the
Normal source to the Replacement source, then the return to the Normal source.
The test lasts approximately three minutes.
A-22
Using the internal bus protocol, this option may be used to remote the following
information:
b circuit breaker status (ON, OFF, fault trip)
b presence of the Normal and Replacement voltages
b presence of an order for forced operation (e.g. special tariffs)
b VHWWLQJVDQGFRQJXUDWLRQLQIRUPDWLRQ
b status of non-priority circuits (loads shed or not)
b position of the switch (stop, auto, forced operation on the Normal source, forced
operation on the Replacement source).
UA controller
Operating sequences
Forced operation mode
Switch set to the N position (forced operation on
the Normal source)
DB126552.eps
DB126551.eps
DB126553.eps
A-23
Functions
and characteristics
DB126554.eps
Key
UN : Normal source voltage
UR : Replacement source voltage
N : Normal source circuit breaker
R : Replacement source circuit breaker
B : Penalties accepted (N ON), i.e. B = 1
A-24
Associated controllers
UA controller
Operating sequences
Special-tariff mode
UA controller
Operating sequences
Test mode and automatic operation
DB126555.eps
Switch set to the Auto position (automatic operation and test mode).
A-25
Functions
and characteristics
Operating sequences
IVE unit
Db126594.eps
IVE unit
Symbols
QN : Normal Compact circuit breaker equipped
for remote operation (motor mechanism)
QR : Replacement Compact circuit breaker
equipped for remote operation (motor
mechanism)
ON : Circuit breaker QN opening order
OR : Circuit breaker QR opening order
IN : Circuit breaker QN closing order
IR : Circuit breaker QR closing order
L1 : Faulty Normal indication LED
L2 : Faulty Replacement indication LED
Key
O: OFF (circuit open)
I: ON (circuit closed
: either ON or OFF.
A-26
Note: following all trips (overload, short-circuit, earth-leakage fault, voluntary trip), a manual
reset on the front of the motor mechanism is required.
BA/UA controller
Db126595.eps
BA controller
Inputs
UN : Normal source voltage
UR : Replacement source voltage
KT : order for forced-operation on R
KR : additional check before transfer
Outputs
QN : Normal source circuit breaker
QR : Replacement source circuit breaker
Db126599.eps
UA controller
Inputs
UN : Normal source voltage
UR : Replacement source voltage
KT : order for forced-operation on R
KR : additional check before transfer
Outputs
KG : order to the genset
SH : load-shedding order
QN : Normal source circuit breaker
QR : Replacement source circuit breaker
Key
O: OFF (circuit open)
I: ON (circuit closed
: either ON or OFF.
Important
If UR is not ON when the transfer order is issued (KT or UN), the sequence is not carried out.
If KR status is not ON when the transfer order is issued (KT or UN), the transfer sequence is
carried out later when KR status becomes I.
$
'%HSV
Functions
and characteristics
Electrical-installation management
Communication
interface
RS 232, Ethernet
RS 485
Communication bus
ON / OFF
Fault trip
Connected / disconnected position
BBus
JBus
OK
com.
com.
error
24V
error
9600
19200
3
N1
N2
1
15
3
9
13
5
1
15
N1
7
9
13
N2
b
b
b
N
DC150
DC150 data
concentrator
ON / OFF
Fault trip
Connected / disconnected position
b
b
b
b
b
Devices
N
R
IVE
A-28
Masterpact
Masterpact
Modbus
Measurement
Current
A
E
P
Voltages, power...
E
P
Frequency
P
Power quality: fundamental, harmonics
Programming of demand metering
E
P
Fault readings
Type of fault
A
E
P
Interrupted current
P
Waveform capture
On faults
On demand or programmed
Histories and logs
Trip history
E
P
Alarm history
P
Event logs
P
Indicators
Counter operation
A
E
P
Contact wear
P
Maintenance register
P
Note: see the description of the Micrologic control units for further details on protection and
alarms, measurements, waveform capture, histories, logs and maintenance indicators.
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
Controller
UA150
Status indications
Normal source
ON / OFF
Circuit breaker ON
Fault trip (SDE)
Voltage presence
Replacement source
Circuit breaker ON
Fault trip (SDE)
Voltage presence
Status of R voltage contact
Controller
Automatic mode
Normal mode
Replacement mode
Stop mode
Testing
Replacement engine generator set
Genset failure
Genset OFF
Genset ON
Shedding of non-priority circuits
Reconnection of non-priority circuits
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
'%HSV
Settings
Time delay t1 for validation of UN absence
b
b
b
b
b
b
N
DC150
BBus
JBus
OK
com.
com.
error
24V
error
9600
19200
3
N1
N2
1
15
3
9
13
5
1
15
N1
Main characteristics
b Power supply:
110 V AC to 240 V AC
115 V DC to 125 V DC.
b Weight: 1.5 kg.
b Installation: on panel with the DC150 box which must be earthed on metal part of
the installation.
b Over dimensions H x W x D (mm): 138.5 x 100 x 192.8.
7
9
N2
13
A-29
TOOLS
schneider-electric.com
Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Compact INS/INV, Masterpact
Dimensions
Presentation
Functions and characteristics
2
A-1
B-2
B-3
B-5
B-6
%
B-9
B-13
B-15
B-20
C-1
D-1
B-1
Manual source-changeover
systems
Dimensions
DB404483.eps
Front-panel cutout
DB126608.eps
Dimensions
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
A
325
416
B
90
115
C
100
D
200
F
156
210
G
133
H
9.25
5
J
9
24.6
K
295
386
L
100
M
150
N
P
155
Front-panel cutout
Db101610.eps
Db101609.eps
Dimensions
Dimensions (mm)
Type
A
B
C
INS/INV250 - 100/160/200/250 325
90
INS/INV320/400/500/630
416
115
100
Note: X and Y are the symmetry planes for a 3-pole device.
B-2
D
200
F
156
210
G
106
130
H
22.5
K
295
386
L
100
M
150
N
P
131
160.4
Front-panel cutout
DB126608.eps
DB126610.eps
Dimensions
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
A
325
416
B
90
115
C
100
D
200
F
156
210
G min
195
G max
600
600
H
9.25
5
J
9
24.6
P
25.5
30.8
Q
25.5
30.8
Front-panel cutout
Db101615.eps
Db101614.eps
Dimensions
Dimensions (mm)
Type
INS40/63/80
INS100/125/160
INS/INV250 - 100/160/200/250
INS320/400/500/630
A
325
325
325
416
B
90
90
90
115
C
100
D
200
F
156
156
156
210
G min
155
200
185
204
G max
396
441
600
600
H
0
0
22.5
P
25.5
25.5
25.5
30.8
Q
25.5
25.5
25.5
30.8
B-3
Manual source-changeover
systems
Dimensions
DB101618.eps
Dimensions
Db101619.eps
Front-panel cutout
Dimensions (mm)
Type
NS630b/800/1000/1200/1600
B-4
A
411
B
63.5
C
98
D
F
280
G min
218
G max
605
H
25
J
24
P
25.5
Q
25.5
R
64
Interlocking of toggles
Compact NSX100 to 630
4 poles
4 poles on left
Db101624.eps
3 poles on left
Db101623.eps
Front-panel cutout
DB126614.EPS
3 poles
DB126613.EPS
DB126612.EPS
Dimensions
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
C2
54
92.5
C3
108
182
L
52.5
L16
140
185
L17
245
325
L18
280
R2
54
R18
89
116.5
R19
140
185
P5
83
P
120
150
B-5
Manual source-changeover
systems
Dimensions
Db101625.eps
Dimensions
'EHSV
Front-panel cutout
Dimensions (mm)
Type
INS250 - 100/160/200/250
INS320/400/500/630
A
60.4
82.5
B
130.4
C
296
395
D
68
102.5
E
136
205
F
131
155
G
61.8
H
I
42
64
J
84
128
K
156
210
L
186.5
213
M
5.5
8
N
50
50
'%HSV
Db101650.eps
Db101651.eps
Dimensions (mm)
Type
A
INS250 - 100/160/200/250 60.4
INS320/400/500/630
82.5
B
130.4
C
295
395
E
136
205
K
156
210
L
138.5
162.5
Dimensions (mm)
Type
P
INS250 - 100/160/200/250 100
INS320/400/500/630
150
Mmax Mmin
195
593
220.5
Q
64
64
B-6
M
631
658
N
50
DB413282.eps
Dimensions
DB413569.eps
Connection
DB413280.eps
Dimensions
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
G2
118
165.9
G3
181.5
G28
244.5
G29
96
143.5
G30
152.5
220.5
G52
K1
35
45
K2
35
45
K3
51
K4
156
210
K8
113.5
K9
K16
8
15
L28
320
425
L29
99.5
130
L30
300
400
L31
89.5
L32
5.15
L33
130.5
L34
139.5
L35
98.5
L36
19.5
26
L37
115
L39
9.5
9.85
L40
140
T
6
6
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
Note: FRXSOLQJDFFHVVRU\RQO\IRUFKDQJHRYHUV\VWHPVXVLQJ[HGYHUVLRQVRI&RPSDFW16;FLUFXLWEUHDNHUV
%
Manual source-changeover
systems
Dimensions
DB413283.eps
DB413286.eps
Dimensions
Connection
DB413284.eps
'%HSV
Dimensions
Dimensions (mm)
Type
INS250-100/160/200/250
INS320/400/500/630
G2
105.5
141
G3
169
G28
232
313
G29
83.5
119
G30
140
195.6
G52
165.5
240
K1
35
45
K2
35
45
K3
51
K4
156
210
K8
88.5
K9
K16
25.5
L28
320
425
L29
83
L30
300
400
L31
95
L32
12.8
L33
130.5
L34
139.5
L35
98.5
L36
21.5
26
L37
92.5
L39
8.5
12.65
L40
140
T
6
6
Dimensions (mm)
Type
INS250-100/160/200/250
INS320/400/500/630
B-8
Remote-operated
source-changeover systems
Interlocking on a base plate
Compact NSX100 to 250
Fixed device
Withdrawable device
DB126619.EPS
'%HSV
DB413288.eps
Dimensions, 3 or 4 poles
Horizontal mounting
Db101638.eps
'EHSV
Vertical mounting
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
G50
180
G51
285
360
H20
62.5
100
H21
152
H22
45.5
83
H23
123
H42
60
60
H43
120
120
H44
144.5
189
H45
300
H46
K25
156
210
K35
210.5
282.5
L31
110.5
150.5
L32
354
466
P7
25
25
P8
45
45
P9
100
P32
182
256
P33
143
215
P50
25
25
P52
99.5
123
P54
21
21
T9
9
9
T10
6
6
U
y 32
y 32
K36
300
400
Dimensions (mm)
Type
NSX100/160/250
NSX400/630
Note: FRXSOLQJDFFHVVRU\RQO\IRUFKDQJHRYHUV\VWHPVXVLQJ[HGYHUVLRQVRI&RPSDFW16;FLUFXLWEUHDNHUV
B-9
Remote-operated
source-changeover systems
Dimensions
Fixed device
DB413289.eps
Dimensions, 3 or 4 poles
DB126622.EPS
Withdrawable device
Note: FRXSOLQJDFFHVVRU\RQO\IRUFKDQJHRYHUV\VWHPVXVLQJ[HGYHUVLRQVRI&RPSDFW16;
circuit breakers.
Horizontal mounting
Db101638.eps
'EHSV
Dimensions
Vertical mounting
B-10
DB413291.eps
DB404134.eps
Dimensions
95
95
47.5
47.5
77
29.5
NSX100
to
NSX250
156
NSX100
to
NSX250
145
177
Front-panel cutout
DB413300.eps
Dimensions
127
127
63.5
63.5
127
42
NSX400
to
NSX630
210
NSX400
to
NSX630
217
249
B-11
Remote-operated
source-changeover systems
Dimensions
DB126623.EPS
Dimensions
NSX400
to
NSX630
B-12
NSX100
to
NSX250
'%HSV
Fixed devices
Db101656.eps
Fixed devices
B-13
Dimensions
Remote-operated
source-changeover systems
Interlocking using connecting rods
'%HSV
Fixed devices
B-14
Db101661.eps
Db101662.eps
Fixed devices
Db101663.eps
Fixed devices
Db101664.eps
Fixed devices
B-15
Dimensions
Remote-operated
source-changeover systems
Interlocking using cables
Db101666.eps
Fixed devices
Fixed devices
Db101669.eps
Drawout devices
B-16
'%HSV
Fixed devices
'EHSV
Fixed devices
%
Dimensions
Remote-operated
source-changeover systems
Interlocking using cables
'%HSV
Fixed devices
'%HSV
Fixed devices
B-18
Dimensions
Remote-operated
source-changeover systems
Interlocking using cables
'%HSV
Fixed devices
B-19
Remote-operated
source-changeover systems
Dimensions
'EHSV
Db101681.eps
Db101680.eps
DB101683.eps
'EHSV
IVE unit
B-20
Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Compact INS/INV, Masterpact
Electrical diagrams
Presentation
Functions and characteristics
Dimensions
2
A-1
B-1
C-2
C-5
C-6
&
C-8
C-9
C-12
&
C-26
D-1
C-1
Electrical diagrams
Remote-operated
source-changeover systems
2 Compact NSX100/630 devices
Diagram no. 51201177
Db401805.eps
Db101659.eps
Db101660.eps
Automatic reset
(1)3UHIDEULFDWHGZLULQJFDQQRWEHPRGLHG
Legends
QN Normal source Compact NSX equipped with motor mechanism
QR Replacement source Compact NSX equipped with motor
mechanism
SDE fault-trip indication contact
IVE electrical interlocking and terminal block unit
MT motor mechanism
OF2 breaker ON/OFF indication contact
RN reset order for breaker QN
RR reset order for breaker QR
C-2
Electrical diagrams
Remote-operated
source-changeover systems
2 Compact NSX100/630 devices
Diagram no. 51201178
KA5
KA5
Automatic reset
KA5
KA5
Legends
QN Normal source Compact NSX equipped with
motormechanism
QR Replacement source Compact NSX equipped with motor
mechanism
MN undervoltage release
OF2 breaker ON/OFF indication contact
SDE fault-trip indication contact
MT motor mechanism
IVE electrical interlocking and terminal block unit
BP emergency off button with latching
KA5 auxiliary relay
F1 auxiliary power supply circuit breaker
C-3
Electrical diagrams
Remote-operated
source-changeover systems
2 Compact NSX100/630 devices
Diagram no. 51201179
Automatic reset
C-4
Remote-operated
source-changeover systems
Electrical diagrams
DB415112.eps
CN CR
CN CR
Closure order to
"Replacement" source (1)
KA1
KA1
Closure order to
"Normal" source (1)
KA2
KA3
Opening order to
"Replacement" source
KA4
KA1
KA1
KA2
KA2
KA2
Opening order to
"Normal" source
KA3
KA4
IMPORTANT
The relays controlling the closing order to the Normal and Replacement circuit breakers must be mechanically and/or electrically
interlocked to prevent them from giving simultaneous closing commands.
It is recommended to use Tesys K relays from Schneider Electric reference LC2-K06010pp. These relays are mechanically and electrically
interlocked.
Legends
ON Normal source opening order
OR Replacement source opening order
CN Normal source closing order
CR Replacement source closing order
KA1 auxiliary relay
KA2 auxiliary relay
KA3 auxiliary relay
KA4 auxiliary relay
L1
Normal source fault-trip signal
L2
Replacement source fault-trip signal
N
Normal source auxiliary wiring connector
R
Replacement source auxiliary wiring connector
C-5
Electrical diagrams
Source-changeover systems
with automatic controllers
2 Compact NSX100/630, NS630b/1600
or Masterpact NT/NW devices
'%HSV
'%HSV
Transfer conditions
'%HSV
Legends
Q1
circuit breaker supplying and protecting the automaticcontrol circuits for the Normal source
Q2
circuit breaker supplying and protecting the automaticcontrol circuits for the Replacement source
ACP control plate
UA
automatic controller
IVE
electrical interlocking and terminal block unit
C-6
Source-changeover systems
with automatic controllers
Electrical diagrams
Controller settings
Source changeover system with UA controller
Using communication functions
'%HSV
'%HSV
Controller settings
&
Electrical diagrams
Source-changeover systems
with automatic controllers
2 Compact NSX100/630, NS630b/1600
or Masterpact NT/NW devices
'%HSV
Coupling
'%HSV
Transfer conditions
Legends
Q1
circuit breaker supplying and protecting the automaticcontrol circuits for the Normal source
Q2
circuit breaker supplying and protecting the automaticcontrol circuits for the Replacement source
ACP control plate
BA
automatic controller
IVE
electrical interlocking and terminal block unit
C-8
Remote-operated
source-changeover systems
Electrical diagrams
DB415209.eps
IVE
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
Legends
QN
Normal source Compact NS630b to 1600
QR
Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
IVE
electrical interlocking and terminal block unit
ON
Normal source opening order
OR
Replacement source opening order
CN
Normal source closing order (0.25 second delay)
CR
Replacement source closing order (0.25 second delay)
MT
Motor Mechanism
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
(1)1RWWREHZLUHGRQ[HGYHUVLRQ
(2) Prefabricated wiring supplied.
C-9
Remote-operated
source-changeover systems
Electrical diagrams
DB415210.eps
KA5
CN CR
KA5
KA5
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
Legends
QN
Normal source Compact NS630b to 1600
QR
Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
IVE
electrical interlocking and terminal block unit
MX
shunt release
BP
emergency off button with latching
KA5 auxiliary relay
ON
Normal source opening order
OR
Replacement source opening order
Normal source closing order (0.25 second delay)
CN
CR
Replacement source closing order (0.25 second delay)
MT
Motor Mechanism
GN
BK
VT
YE
red
green
black
violet
yellow grey
C-10
GY
WH
BN
white
brown
(1)1RWWREHZLUHGRQ[HGYHUVLRQ
(2) Prefabricated wiring supplied.
Remote-operated
source-changeover systems
Electrical diagrams
DB415211.eps
KA5
CN CR
KA5
KA5
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
Legends
QN
Normal source Compact NS630b to 1600
QR
Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
IVE
electrical interlocking and terminal block unit
MN
undervoltage release
BP
emergency off button with latching
KA5 auxiliary relay
ON
Normal source opening order
OR
Replacement source opening order
CN
Normal source closing order (0.25 second delay)
CR
Replacement source closing order (0.25 second delay)
MT
Motor Mechanism
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
(1)1RWWREHZLUHGRQ[HGYHUVLRQ
(2) Prefabricated wiring supplied.
C-11
Remote-operated
source-changeover systems
Electrical diagrams
2 Masterpact NT or NW devices
Diagram no. 51201142
DB415212.eps
IVE
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
Legends
QN
Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
F1
auxiliary power supply circuit breaker
ON
Normal source opening order
OR
Replacement source opening order
CN
Normal source closing order (0.25 second delay)
CR
Replacement source closing order (0.25 second delay)
C-12
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
(1) Not to be wired for the without lockout after a fault solution.
(2) 1RWWREHZLUHGRQ[HGYHUVLRQ
(3) Prefabricated wiring supplied.
Remote-operated
source-changeover systems
Electrical diagrams
2 Masterpact NT or NW devices
Diagram no. 51201143
DB415213.eps
Electrical interlocking by IVE unit with lockout after a fault and emergency off by shunt release
KA5
CN CR
KA5
KA5
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
Legends
Normal source Masterpact NT or NW
QN
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
KA5 auxiliary relay
F1
auxiliary power supply circuit breaker
BP
emergency off button with latching
ON
Normal source opening order
OR
Replacement source opening order
CN
Normal source closing order (0.25 second delay)
CR
Replacement source closing order (0.25 second delay)
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
(1) Not to be wired for the without lockout after a fault solution.
(2) 1RWWREHZLUHGRQ[HGYHUVLRQ
(3) Prefabricated wiring supplied.
BN
brown
C-13
Remote-operated
source-changeover systems
Electrical diagrams
2 Masterpact NT or NW devices
Diagram no. 51201144
DB415214.eps
Electrical interlocking by IVE unit with lockout after a fault and emergency off by undervoltage release
KA5
CN CR
KA5
KA5
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
Legends
QN
Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
KA5 auxiliary relay
F1
auxiliary power supply circuit breaker
BP
emergency off button with latching
ON
Normal source opening order
OR
Replacement source opening order
CN
Normal source closing order (0.25 second delay)
CR
Replacement source closing order (0.25 second delay)
C-14
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
(1) Not to be wired for the without lockout after a fault solution.
(2) 1RWWREHZLUHGRQ[HGYHUVLRQ
(3) Prefabricated wiring supplied.
Remote-operated
source-changeover systems
Electrical diagrams
2 Masterpact NT or NW devices
Diagram no. 51156904
DB414899.eps
Automatic-control system for permanent replacement source with lockout after a fault (with MN)
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
(1) Not to be wired for the without lockout after a fault solution.
(2) 1RWWREHZLUHGRQ[HGYHUVLRQ
(3) Prefabricated wiring supplied.
IMPORTANT
The relays controlling the closing order to the Normal and Replacement circuit breakers must be mechanically and/or electrically
interlocked to prevent them from giving simultaneous closing commands.
It is recommended to use Tesys K relays from Schneider Electric reference LC2-K06010pp. These relays are mechanically and electrically
interlocked.
Legends
QN
Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
F1
auxiliary power supply circuit breaker
F2
circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relays
KA2 auxiliary relays
KA3 auxiliary relays
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
C-15
Remote-operated
source-changeover systems
Electrical diagrams
2 Masterpact NT or NW devices
Diagram no. 51156905
DB414900.eps
Automatic-control system for replacement source generator set with lockout after a fault (with MN)
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
(1) Not to be wired for the without lockout after a fault solution.
(2) 1RWWREHZLUHGRQ[HGYHUVLRQ
(3) Prefabricated wiring supplied.
IMPORTANT
The relays controlling the closing order to the Normal and Replacement circuit breakers must be mechanically and/or electrically
interlocked to prevent them from giving simultaneous closing commands.
It is recommended to use Tesys K relays from Schneider Electric reference LC2-K06010pp. These relays are mechanically and electrically
interlocked.
Legends
QN
Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
F1
auxiliary power supply circuit breaker
F2
circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relay
KA2 time delay for genset startup order to avoid starting
the genset for transient UN disturbances
KA3 auxiliary relay
C-16
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156906
'EHSV
2 normal sources and 1 replacement source: electrical interlocking without lockout after a fault
Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE
connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
order for transfer from R to N1 + N2
(QN1 and QN2 closing time delay = 0.25 sec. minimum)
t2
order for transfer from N1 + N2 to R
(QR closing time delay = 0.25 sec. minimum)
&
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156907
'EHSV
2 normal sources and 1 replacement source: electrical interlocking with lockout after a fault
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
S1
control switches
S2
source selection switches
KA1 auxiliary relay
KA2 auxiliary relays with 10 to 180 sec. time delay
t1
order for transfer from R to N1 + N2
(QN1 and QN2 closing time delay = 0.25 sec. minimum)
t2
order for transfer from N1 + N2 to R
(QR closing time delay = 0.25 sec. minimumm)
C-18
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156908
'EHSV
2 normal sources and 1 replacement source: automatic-control system for generator set without lockout
after a fault (with MN)
Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
S2
source selection switches
KA1 auxiliary relay
KA2 auxiliary relays with 10 to 180 sec. time delay
KA3 auxiliary relays with 0.1 to 30 sec. time delay
KA4 auxiliary relay
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay
C-19
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156909
'EHSV
2 normal sources and 1 replacement source: automatic-control system for generator set with lockout
after a fault (with MN)
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
S2
source selection switches
KA1 auxiliary relay
KA2 auxiliary relays with 10 to 180 sec. time delay
KA3 auxiliary relays with 0.1 to 30 sec. time delay
KA4 auxiliary relay
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay
KA7 auxiliary relay
KA8 auxiliary relay
C-20
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156910
'EHSV
3 sources with only 1 device closed: electrical interlocking without lockout after a fault
Legends
QS... Source Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
order for transfer to Source 1
(QS1 closing time delay = 0.25 sec. minimum)
t2
order for transfer to Source 2
(QS2 closing time delay = 0.25 sec. minimum)
t3
order for transfer to Source 3
(QS3 closing time delay = 0.25 sec. minimum)
C-21
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156911
'EHSV
3 sources with only 1 device closed: electrical interlocking with lockout after a fault
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QS... Source Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
order for transfer to Source 1
(QS1 closing time delay = 0.25 sec. minimum)
t2
order for transfer to Source 2
(QS2 closing time delay = 0.25 sec. minimum)
t3
order for transfer to Source 3
(QS3 closing time delay = 0.25 sec. minimum)
KA1 auxiliary relays
KA2 auxiliary relays
KA3 auxiliary relays
C-22
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156912
'EHSV
Legends
QS... Source Masterpact NW
QC
Coupling Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
coupling order for Source 1 failure
(QC closing time delay = 0.25 sec. minimum)
t2
coupling order for Source 2 failure
(QC closing time delay = 0.25 sec. minimum)
t3
coupling order for Source 1 restored
(QS1 closing time delay = 0.25 sec. minimum)
t4
coupling order for Source 2 restored
(QS2 closing time delay = 0.25 sec. minimum)
C-23
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156913
'EHSV
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QS... Source Masterpact NW
QC
Coupling Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
coupling order for Source 1 failure
(QC closing time delay = 0.25 sec. minimum)
t2
coupling order for Source 2 failure
(QC closing time delay = 0.25 sec. minimum)
t3
coupling order for Source 1 restored
(QS1 closing time delay = 0.25 sec. minimum)
t4
coupling order for Source 2 restored
(QS2 closing time delay = 0.25 sec. minimum)
KA1 auxiliary relays
KA2 auxiliary relays
KA3 auxiliary relays
C-24
Electrical diagrams
Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156914
'EHSV
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QS... Source Masterpact NW
QC
Coupling Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
S2
source selection switches
KA1 auxiliary relays with 10 to 180 sec. time delay
KA2 auxiliary relays with 0.1 to 30 sec. time delay
KA3 auxiliary relays with 10 to 180 sec. time delay
KA4 auxiliary relays with 0.1 to 30 sec. time delay
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay
KA7 auxiliary relays with 0.25 sec. time delay
C-25
Source-changeover systems
with automatic controllers
Electrical diagrams
2 Masterpact NT or NW devices
Diagram no. 51156903
DB415120.eps
ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.
Legends
QN
Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
C-26
GN
green
BK
black
VT
violet
YE
GY
yellow grey
WH
white
BN
brown
(1) Not to be wired for the without lockout after a fault solution.
(2) 1RWWREHZLUHGRQ[HGYHUVLRQ
(3) Prefabricated wiring supplied.
Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Compact INS/INV, Masterpact
Catalogue numbers
and order forms
Presentation
Functions and characteristics
Dimensions
Electrical diagrams
2
A-1
B-1
C-1
D-2
D-3
D-5
'
D-8
D-10
D-12
D-14
D-16
D-18
D-1
Catalogue numbers
and order forms
Source-changeover systems
for 2 devices
Compact INS40 to INS2500
and INV100 to INV2500
'%HSV
5...8
31073
31074
'%HSV
'%HSV
'%HSV
3P
With Compact INS250-100A
31140
With Compact INS250-160A
31144
With Compact INS250-200A
31142
With Compact INS250
31146
With Compact INS320
31148
With Compact INS400
31150
With Compact INS500
31152
With Compact INS630
31154
Locking for INS complete source changeover assembly
Handle locking by 1 to 3 padlocks (in OFF position)
By keylock
Keylocking device
+ Ronis 1351B.500 keylock
or + Profalux KS5 B24 D4Z keylock
4P
31141
31145
31143
31147
31149
31151
31153
31155
Built in
31097
41940
42888
Rotary handle
Extended front control for complete source changeover assembly
31055
Manual source-changeover systems Compact INS250 to INS2500 and INV250 to INV2500 by keylock
DB404080.eps
Db101549.eps
Interlocking
Locking device for Ronis/Profalux keylocks
on INS250-100 to INS250/INV100 to INV250
Locking device for Ronis/Profalux keylocks
on INS/INV320 to INS/INV630
2x
3/4P
31087
2x
31088
2x
31291
41950
42878
Connection accessories
Downstream coupling accessories
DB101062.eps
DB413292.eps
3/4P
LV429359
LV432620
INS250/INS250
INS320 to INS630/INS320 to INS630
Db403921.eps
LV429518
LV432594
LV432596
DB115652.eps
Terminal extensions
Spreaders
D-2
52.5 mm
4P
LV432491
Source-changeover systems
for 2 devices
Catalogue numbers
and order forms
NSX100...250
NSX400...630
LV429354
LV432614
DB404084.eps
Mechanical interlocking
NSX100...250
NSX400...630
LV429369
LV432621
41950
42878
24 to 250 V DC
48 to 415 V AC 50/60 Hz
440 V 60 Hz
29351
29349
29356
4 x 29450
29365
29350
29349
29352
4 x 29450
29365
(2)
(2)
(2)
(2)
32611
32609
29356
4 x 29450
29365
32610
32609
29352
4 x 29450
29365
(2)
(2)
(2)
(2)
1 x 32618
1 x 32618
'%HSV
GERIN
MERLIN
multi
0 . OFF
220/240 V AC 50/60 Hz
29470
29363
29376
29472
29363
29378
29474
29363
29379
380/415 V AC 50/60 Hz
440 V 60 Hz
29471
29364
29377
29473
29364
29380
29475
29364
29381
29368
29368
0 . OFF
P25M
660V
AC3-IEC292-1
P25M
660V
AC3-IEC292-1
Test
Test
Communication module
DB403922.eps
50823
N
DC150
com.
OK
error
BBus
com.
error
24V
JBus
9600
19200
N 1
N 2
3 5 7
N1
15 13
3 5 7
1
9 N2
15 13
(1) The supply voltages BA/UA controller, ACP plate, IVE unit and the remote control must be identical whatever the source changeover type.
(2) See products pages.
D-3
Source-changeover systems
for 2 devices
Catalogue numbers
and order forms
'%HSV
4P
LV429359
LV432620
Db403921.eps
3/4P
LV429518
LV432594
LV432596
DB115652.eps
Terminal extensions
Spreaders
52.5 mm
4P LV432491
D-4
Catalogue numbers
and order forms
Source-changeover systems
for 2 devices
Compact NS630b to NS1600
circuit breakers and switch-disconnectors
Mechanical interlocking
For 2 devices with extended rotary handles
33890
&RPSOHWHDVVHPEO\ZLWKDGDSWDWLRQ[WXUHVURGV
&RPSDFW[HGGHYLFHV
2 Compact withdrawable devices
33910
33913
FFO
hsu p
NO h
FFO
sup
O
degr
ahcs
i
F FO
hsup
NO h
sup
FFO
O
degr
ahcs
i
&RPSOHWHDVVHPEO\ZLWKDGDSWDWLRQ[WXUHVFDEOHV
&RPSDFW[HGGHYLFHV
2 Compact withdrawable devices
&RPSDFW[HG&RPSDFWZLWKGUDZDEOHGHYLFH
FFO
hsup
NO h
FFO
33911
33914
33915
sup
O
degr
ah
csid
F FO
hsup
NO h
sup
FFO
O
degr
ah
csid
D-5
Catalogue numbers
and order forms
Source-changeover systems
for 2 devices
Compact NS630b to NS1600 circuit
breakers and switch-disconnectors (cont.)
Associated controller
The automatic-control option includes:
b an IVE electrical-interlocking unit
b an ACP control plate
b a BA or UA controller, depending on the required functions
b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.
24 to 250 V DC
DB404093.eps
For 2 devices
29356
:LULQJNLWIRUFRQQHFWLRQRI[HGZLWKGUDZDEOHGHYLFHVWRWKH,9(XQLW
'%HSV
GERIN
MERLIN
multi
110/127 V AC 50/60 Hz
ACP + controller BA (1)
Plate ACP
Controller BA
29448
ACP + controller UA (1)
Plate ACP
29447
Controller UA
29446
ACP + controller UA150 (1) (communication option)
Plate ACP
Controller UA150
0 . OFF
P25M
GERIN
MERLIN
multi
0 . OFF
660V
AC3-IEC292-1
P25M
660V
AC3-IEC292-1
Test
Test
48/415 V AC 50/60 Hz
440 V 60 Hz
29352
54655
220/240 V AC 50/60 Hz
380/415 V AC 50/60 Hz
440 V 60 Hz
29470
29363
29376
29472
29363
29378
29474
29363
29379
29471
29364
29377
29473
29364
29380
29475
29364
29381
DB403922.eps
Communication module
DC150 data concentrator
110-240 V AC / 115-125 V DC
50823
N
DC150
com.
OK
error
BBus
com.
error
24V
JBus
9600
19200
N1
N2
3 5 7
N1
15 13
3 5 7
1
9 N2
15 13
(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of sourcechangeover system.
D-6
Catalogue numbers
and order forms
Source-changeover systems
for 2 devices
Masterpact NT circuit breakers
and switch-disconnectors
&RPSOHWHDVVHPEO\ZLWKDGDSWDWLRQ[WXUHVURGV
0DVWHUSDFW17[HGGHYLFHV
2 Masterpact NT drawout devices
33912
33913
33200
33201
33209
Associated controller
The automatic-control option includes:
b an IVE electrical-interlocking unit
b an ACP control plate
b a BA or UA controller, depending on the required functions
b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.
DB404093.eps
'%HSV
GERIN
MERLIN
multi
110/127 V AC 50/60 Hz
ACP + controller BA (1)
Plate ACP
Controller BA
29448
ACP + controller UA (1)
Plate ACP
29447
Controller UA
29446
ACP + controller UA150 (1) (communication option)
Plate ACP
Controller UA150
0 . OFF
P25M
GERIN
MERLIN
multi
0 . OFF
660V
AC3-IEC292-1
P25M
660V
AC3-IEC292-1
Test
Test
24 to 250 V DC
48/415 V AC 50/60 Hz
440 V 60 Hz
29356
29352
54655
220/240 V AC 50/60 Hz
380/415 V AC 50/60 Hz
440 V 60 Hz
29470
29363
29376
29472
29363
29378
29474
29363
29379
29471
29364
29377
29473
29364
29380
29475
29364
29381
Communication module
DB403922.eps
50823
N
DC150
com.
OK
error
BBus
com.
error
24V
JBus
9600
19200
N 1
N 2
3 5 7
N1
15 13
3 5 7
1
9 N2
15 13
(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type
of source-changeover system.
'
Catalogue numbers
and order forms
Source-changeover systems
for 2 or 3 devices
Masterpact NW circuit breakers
and switch-disconnectors
&RPSOHWHDVVHPEO\ZLWKDGDSWDWLRQ[WXUHVURGV
0DVWHUSDFW1:[HGGHYLFHV
2 Masterpact NW drawout devices
&DQEHXVHGZLWK1:[HG1:GUDZRXW
48612
48612
47926
47926
33209
For 2 devices
29356
:LULQJNLWIRUFRQQHFWLRQRI[HGGUDZRXWGHYLFHVWRWKH,9(XQLW
24 to 250 V DC
110/127 V AC 50/60 Hz
220/240 V AC 50/60 Hz
48/415 V AC 50/60 Hz
440 V 60 Hz
29352
54655
380/415 V AC 50/60 Hz
440 V 60 Hz
MERLIN
multi
P25M
GERIN
MERLIN
multi
0 . OFF
660V
AC3-IEC292-1
P25M
660V
AC3-IEC292-1
Test
Test
D-8
0 . OFF
Catalogue numbers
and order forms
Source-changeover systems
for 2 or 3 devices
Masterpact NW circuit breakers
and switch-disconnectors
Communication module
DB403922.eps
50823
N
DC150
com.
OK
error
BBus
com.
error
24V
JBus
9600
19200
N 1
N 2
3 5 7
N1
15 13
3 5 7
1
9 N2
15 13
48610
48609
48608
D-9
Catalogue numbers
and order forms
Source-changeover systems
for 2 devices
Compact INS40 to INS630
Switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.
INS320/400/500/630
INS100/125/160
INS250
INS320/400/500/630
Downstream coupling
accessory
INS250
INS320/400/500/630
INS250
INS320/400/500/630
D-10
INS250-100 A
INS250-160 A
INS250-200 A
INS250-250 A
INS320
INS400
INS500
INS630
Source-changeover systems
for 2 devices
Catalogue numbers
and order forms
For INS250
Rating
100 A
150 A
250 A
'HYLFHLGHQWLFDWLRQ
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
Switch-disconnector
400 A
For INS250
Rating
100 A
600 A
4P current-transformer
module
INS40/63/80
Compact type
For INS320/630
150 A
INS100/125/160
250 A
INS250
For INS320/630
Rating
400 A
For INS40/160
1OF/CAF/CAO
Standard
For INS250/630
1 OF/CAM
Standard
INS320/400/500/630
Rating
Number of poles
3 or 4
600 A
Auxiliary contact
Low level
Connections
Front connection Standard
Low level
Rotary handles
Rear connection
2 short
INS40/80
connectors
INS100/160
connectors
INS250
connectors
2 long
INS40 to INS160
Black
INS250
Black
Snap-on y 95v
INS320 to INS630
Black
INS250
INS320/630
Padlocking
Keylocking
Set of 10
Installation accessories
Front-panel escutcheon
For switch-disconnectors
For ammeter module, IP40
Distribution
blocks
Linergy DX
4P
125 A
160 A
1P
160 A
Linergy BS
(multi stage)
160 A
250 A
Linergy DP
250 A
250 A
630 A
INS630
Spreader
Cu cable lugs
supplied with
2 or 3 inter-phase
barriers
INS320/630
52.5 mm
PP
One-piece
INS250
INS630
INS100/160
INS250
INS320/630
INS250
Terminal shrouds
INS40/63/80
INS100/125/160
Terminal shields
INS40/63/80
INS100/125/160
INS250
Long
INS320/630
Long
INS100/160
Set of 6
INS250
Set of 6
INS320/630
Set of 6
D-11
Catalogue numbers
and order forms
Source-changeover systems
for 2 devices
Compact NSX100 to NSX630 / Circuit
breakers and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.
QR
QR
QR
Identical voltages:
48 to 415 V AC 50/60 Hz
24 to 250 V DC
440/480 V AC 60 Hz
Normal NSX100/250
Replacement NSX100/250
Normal NSX400/630
Replacement NSX400/630
Normal NSX400/630
Replacement NSX100/250
2 OF + 2 SDE (mandatory)
Options
Quantity
Plug-in base
3P
NSX100/250
4P
NSX400/630
Quantity
Automatic-control option
Power supply 220/240 V - 50/60 Hz:
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
D-12
Source-changeover systems
for 2 devices
Catalogue numbers
and order forms
Plug-in
ME, MH, MB
NSX400/630
Front connections
Withdrawable
Voltage
4P option on 3P NSX
Extended
3P
3P
3P
3P
3P
4P
SDE
SDE
SDV
SDV
Standard
Low level
AC
AC
AC
AC
AC
DC
DC
DC
DC
DC
4P
4P
4P
V
V
V
V
V
Indication auxiliary
1 early-break switch
2 early-make switches
Locking
Toggle (1 to 3 padlocks) Removable
Fixed
Rotary handle
Keylock adapter (keylock not included)
Keylocks Ronis 1351B.500
Profalux KS5 B24 D4Z
Motor mechanism
Keylock adapter + keylock Ronis (special)
NSX100/250
Keylock adapter (keylock not included)
NSX400/630
Keylocks Ronis 1351B.500
Profalux KS5 B24 D4Z
Interlocking
Mechanical
Toggle operated
Rotary Handle
By key (2 keylocks,
Locking kit without locks
1 key) for rotary handle Keylocks Ronis 1351B.500
Profalux KS5 B24 D4Z
Installation accessories
IP30 escutcheon for all types (toggle/rotary handle/motor mechanism)
IP30 escutcheon (with access to toggle + trip unit)
IP30 escutcheon for Vigi module
IP40 escutcheon for all types (toggle/rotary handle/motor mechanism)
IP40 escutcheon for Vigi module
IP40 escutcheon for Vigi or ammeter module
Toggle cover
Sealing accessories
DIN rail adapter
3P 60 mm busbar adapter
3OXJLQZLWKGUDZDEOHFRQJXUDWLRQDFFHVVRULHV
Auxiliary connections
DXWRPDWLFFRQQHFWRU[HGSDUWZLWKZLUHVIRUEDVH
1 automatic connector moving part with 9 wires (for circuit breaker)
1 sup. for 3 auto. conn. moving parts
1 sup. for 2 auto. conn.
ZLUHPDQXDODX[LOLDU\FRQQHFWRU[HGPRYLQJ
Plug-in base
Long insulated terminals
Set of 2
accessories
2 IP4 shutters for base
Chassis accessories
Escutcheon collar
Toggle
Vigi
Locking kit (keylock not included)
2 carriage switches (conn./disconnected position indication)
Parts or plug-in
Plug-in base FC/RC
2P
3P
4P
Withdrawable kits
Set of two power connections
Standard
Vigi
Safety trip for advanced opening
For 3P/4P chassis
Moving part
Fixed part
Adaptater for plug-in base (for terminal shield or interphase barriers)
Communication
NSX Cord L = 0.35 m
NSX Cord L = 1.3 m
NSX Cord U > 480 V AC L = 0.35 m
NSX Cord L = 3 m
BSCM (NSX400/630)
Communicating motor mechanism 220-240 V
Switchboard front display module FDM121
FDM mounting accessory
Modbus interface
Stacking accessory
ULP line termination
RJ45 connectors
Wire length RJ45 L = 0.3 m
Wire length RJ45 L = 0.6 m
female/female
Wire length RJ45 L = 1 m
Wire length RJ45 L = 2 m
Wire length RJ45 L = 3 m
Wire length RJ45 L = 5 m
D-13
Catalogue numbers
and order forms
Source-changeover systems
for 2 devices
Compact NS630b to NS1600 / Circuit
breakers and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.
(no. 51201183)
(no. 51201184)
(no. 51201185)
[HG16GHYLFHV
2 withdrawable NS devices
[HG16GHYLFHV
2 withdrawable NS devices
[HG16GHYLFHZLWKGUDZDEOH16GHYLFH
Automatic-control option
Power supply 110 V - 50/60 Hz:
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
D-14
Source-changeover systems
for 2 devices
Catalogue numbers
and order forms
6 A-240 V AC
Low level
6 A-240 V AC
Low level
qty
Device iGHQWLFDWLRQ
CD - disconnected position
6 A-240 V AC
qty
Q 1 - NORMAL SOURCE
CT - test position
6 A-240 V AC
qty
Q 2 - REPLACEMENT SOURCE
qty
Low level
qty
Remote operation
NS630b to NS1600
Rating
A
N, H, L
Switch-disconnector
NA
Number of poles
3 or 4
Device
Fixed
MN delay unit
Electrical operation
Voltage releases
Standard
Communicating
V
Power supply
AC
DC
MX
AC
DC
MN
AC
DC
Adjustable
Non-adjustable
5RWDU\KDQGOHVIRU[HGDQGZLWKGUDZDEOHGHYLFH
Direct
Black
Extended
Black
Basic protection
2.0
5.0
6.0
A - ammeter
2.0
5.0
6.0
E - energy meter
2.0
5.0
6.0
5.0
6.0
P - power meter
AD - external power-supply module
Indication auxiliary
6 A-240 V AC
2 early-break switches
Locking
7.0
V
Toggle (1 to 3 padlocks)
Removable system
OFF position
Ronis 1351B.500
Standard 0.4 to 1 Ir
VCPO - by padlocks
VSPO - by keylocks
LT OFF
Communication
Device
Fixed system
280 x 115 mm
2 early-make switches
7.0
qty
Low level
Jumpers (set of 10)
Circuit breaker
Rectangular sensor
qty
Low level
Chassis
Mounting accessory
Profalux
Ronis
Profalux
Ronis
Profalux
Ronis
Profalux
Ronis
L = 0.35 m
Kirk
Castell
1 keylock
Profalux
Ronis
L = 1.3 m
L=3m
Connections
Profalux
Ronis
Top
Bottom
Profalux
Ronis
Top
Bottom
Front connections
Top
Bottom
16)&[HG
+ shields
Long connection shields
16)&[HG
Vertical-connection adapters
16)&[HGZLWKGU
Cable-lug adapters
16)&[HGZLWKGU
16)&[HG
CDP - escutcheon
Interphase barriers
16)&[HGZLWKGU
Spreaders
16)&[HGZLWKGU
0RXQWLQJEUDFNHWVIRU[HG16
Test kits
D-15
Catalogue numbers
and order forms
Source-changeover systems
for 2 devices
Masterpact NT or NW / Circuit breakers
and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.
(no. 51201142)
(no. 51201143)
(no. 51201144)
(no. 51156904)
(no. 51156905)
(no. 51156903)
Interlocking using connecting rods (NT/NW devices one above the other)
6HOHFWDFRPSOHWHVHWLQFOXGLQJWZRDGDSWDWLRQ[WXUHVDQGWKHFRQQHFWLQJURGV
Complete set for:
2 drawout NT devices
[HG17GHYLFHV
2 drawout NW devices
[HG1:GHYLFHV
[HG17GHYLFH[HG1:GHYLFH
1 drawout NT device + 1 drawout NW device
Interlocking using cables (NT/NW devices one above the other or side-by-side)
6HOHFWWZRDGDSWDWLRQ[WXUHVRQHIRUHDFKGHYLFHDQGDVHWRIWZRFDEOHV
$GDSWDWLRQ[WXUHIRU
[HG17GHYLFH
171:[HGDQGGUDZRXW 1 drawout NT device
devices may be mixed)
[HG1:GHYLFH
qty
qty
qty
1 drawout NW device
qty
Automatic-control option
Power supply 220/240 V - 50/60 Hz:
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
D-16
Source-changeover systems
for 2 devices
Catalogue numbers
and order forms
Name of customer:
Address for delivery:
Standard
Additional
1 block of 4 OF for NW
max. 2
qty
1 EF 6 A-240 V AC for NW
max. 8
qty
1 EF low-level for NW
max. 8
qty
Standard
1 SDE 6 A-240 V AC
Device iGHQWLFDWLRQ
Additional
1 SDE 6 A-240 V AC
Q 1 - NORMAL SOURCE
Programmable contacts
2 M2C contacts
Q 2 - REPLACEMENT SOURCE
Carriage switches
6 A-240 V AC
CE - connected position
max. 3 for NW / NT
qty
CD - disconnected position
qty
Masterpact type
NW
Rating
CT - test position
Sensor rating
Circuit breaker
Switch-disconnector
Number of poles
3 or 4
qty
qty
Remote operation
Remote ON/OFF
Device
Fixed
Low level
6 A-240 V AC
2.0
5.0
6.0
E - energy meter
2.0
5.0
6.0
P - power meter
5.0
6.0
7.0
H - harmonic meter
5.0
6.0
7.0
MN - undervoltage release
R - delay unit (non-adjustable)
7.0
Locking
VBP - ON/OFF pushbutton locking (by transparent cover + padlocks)
VCPO - by padlocks
earth-leakage protection
1:[PP
VSPO - by keylocks
Profalux
Castell
1 keylock
Profalux
Ronis
Profalux
Ronis
LT OFF
Profalux
Ronis
Profalux
Ronis
VSPD - by keylocks
Device
Chassis
Mounting accessory
Kirk
Castell
1 keylock
Profalux
Ronis
Profalux
Ronis
Profalux
Ronis
L = 0.35 m
VPEC - door interlock
L = 1.3 m
L=3m
VPOC - racking interlock
Connections
Horizontal
Top
Bottom
Vertical
Top
Bottom
Front
Top
Bottom
Vertical-connection adapters
17)&[HGGUDZ
Cable-lug adapters
17)&[HGGUDZ
17)&[HG
Interphase barriers
171:[HGGUDZ
Spreaders
17[HGGUDZRXW
CDP - escutcheon
Disconnectable front
1:[HG
connection adapter
Lugs for 240v or 300v cables
%UDFNHWVIRUPRXQWLQJ1:[HG
1:[HGGUDZRXW
Ronis
Kirk
Test kits
On backplates
Mini test kit
NW
'
Catalogue numbers
and order forms
Source-changeover systems
for 3 devices
Masterpact NW / Circuit breakers
and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.
(no. 51156906)
QR
(no. 51156908)
(no. 51156909)
(no. 51156910)
(no. 51156911)
(no. 51156912)
(no. 51156913)
(no. 51156914)
Interlocking using cables (NW devices one above the other or side-by-side)
6HOHFWDFRPSOHWHVHWLQFOXGLQJWKUHHDGDSWDWLRQ[WXUHVDQGWKHFDEOHV
1 complete set for:
VRXUFHVGHYLFH21[HGRUGUDZRXW
VRXUFHVFRXSOLQJ[HGRUGUDZRXW
VRXUFHVUHSODFHPHQWVRXUFH[HGRUGUDZRXW
D-18
Source-changeover systems
for 3 devices
Catalogue numbers
and order forms
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
qty
qty
Remote operation
Remote ON/OFF
7.0
max. 8
max. 8
V
V
V
6 A-240 V AC
7.0
7.0
Remote tripping
Rectangular sensor
470 x 160 mm
for earth-leakage protection
TCW - external sensor for SGR protection
LR - long-time rating plug Standard 0.4 to 1 Ir
Low setting 0.4 to 0.8 Ir
High setting 0.8 to 1 Ir
LT OFF
PTE - external voltage measurement input (required for
reverse supply)
BAT - battery module
Locking
VBP - ON/OFF pushbutton locking (by transparent cover + padlocks)
OFF position locking:
VCPO - by padlocks
VSPO - by keylocks
Keylock kit (w/o keylock)
Profalux
Kirk
1 keylock
Profalux
2 identical keylocks, 1 key
Profalux
2 keylocks, different keys (NW) Profalux
Communication
Eco COM module Modbus
Device
Chassis
Front Display Module (FDM121)
Mounting accessory
Breaker ULP cord
L = 0.35 m
L = 1.3 m
L=3m
Interphase barriers
Disconnectable front
connection adapter
VO - safety shutters on chassis
VIVC - shutter position indication and locking
1 EF 6 A-240 V AC
1 EF low-level
1 SDE 6 A-240 V AC
1 SDE 6 A-240 V AC
Programmable contacts 2 M2C contacts
Carriage switches
6 A-240 V AC
CE - connected position Max. 3
CD - disconnected position Max. 3
CT - test position
Max. 3
Fixed
Drawout with chassis
Drawout without chassis
(moving part only)
Chassis alone without connections
Top
Top
Top
Fixed, drawout
Fixed
qty
Standard
Additional
Device
Connections
Horizontal
Vertical
Front
NW
2SWLRQQHXWUDORQULJKWVLGH
Standard
Additional
'HYLFHLGHQWLFDWLRQ
Masterpact type
Rating
Sensor rating
Circuit breaker
Switch-disconnector
Number of poles
Indication contacts
OF - ON/OFF indication contacts
Bottom
Bottom
Bottom
V
V
V
Ronis
Castell
Ronis
Ronis
Ronis
Profalux
Ronis
Kirk
Castell
1 keylock
Profalux
Ronis
2 identical keylocks, 1 key
Profalux
Ronis
2 keylocks, different keys
Profalux
Ronis
Optional connected/disconnected/test position locking
On right-hand side of chassis
On left-hand side of chassis
On backplates
Portable test kit
D-19
D-20
$VVWDQGDUGVVSHFLFDWLRQVDQGGHVLJQVFKDQJHIURP
WLPHWRWLPHSOHDVHDVNIRUFRQUPDWLRQRIWKH
LQIRUPDWLRQJLYHQLQWKLVSXEOLFDWLRQ
10-31-1247
04-2013