Professional Documents
Culture Documents
PDVSA N
90616.1.029
TITLE
VENT SYSTEMS
OCT.02
Modified Figure 3
28
JUL.90
FOR APPROVAL
31
REV.
DATE
E PDVSA, 1983
DESCRIPTION
DATE
L.T.
PAG. REV.
Y.K.
R.R.
J.S.
APPD.
DATE
APPD.
OCT.02
ESPECIALISTAS
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 1
.Men Principal
Indice manual
Indice volumen
Indice norma
Index
1 SCOPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2
4.3
Atmospheric Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Toxic Vapors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
9
5 VENT SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
6 VENT STACKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
6.1
6.2
6.3
6.4
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Design Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vent Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Vents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
12
14
14
15
7.4
Design Consideration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
8 NOISE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
8.1
8.2
19
20
PDVSA
PDVSA 90616.1.029
VENT SYSTEMS
REVISION
FECHA
OCT.02
Pgina 2
.Men Principal
Indice manual
Indice volumen
Indice norma
SCOPE
This Engineering Guide contains criteria for the selection of vent equipment and
calculation methods for the basic sizing of emergency venting equipment.
REFERENCES
The following publications are referred to herein or are of general interest:
2.1
2.2
2.3
2.4
API R.P 520, Recommended Practice for the Design and Installation of Pressure
Relieving Systems in Refineries.
2.5
2.6
2.7
David Evans/Dwight Pfenning. Water sprays suppress gas well blowout fires Oil
and Gas Journal. April 29, 1985 pp 8086.
NOTES
This guide deals only with vent systems. This Engineering Guide does not
discuss, Flare Systems, nor Safety Relief Valves or Header Sizing. Please
refer to Guides 90616.1.021 and 90616.1.022 for information on those subjects.
For Petrochemical Industries, each specific case shall meet regulations of
MARNR.
GENERAL
4.1
The selection of a disposal method is subject to many factors that may be specific
to a particular location or an individual unit. The purpose of a disposal system is
to conduct the relieved fluid to a location where it may be safely discharged.
In general, gases and vapors should be discharged upward well overhead and
liquids downward to proper receivers or nearby trapped drains which lead to
waste collection facilities. Frequently, liquids will be discharged with vapors, and
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 3
.Men Principal
Indice manual
Indice volumen
Indice norma
this requires a proper separation pot or enlarged section of line. Liquids in flashing
condition require open vent pipes to release vapors overhead as well as
downpipes for safe disposal of liquids. All vent pipes must be drained to minimize
backpressures due to atmospheric condensate, rain, or process fluid condensate.
Vent outlets should be designed to discharge upward in order to prevent the
relieving system from being plugged and inoperative. All gas and vapor must be
projected above equipment, piping, structures, and operating levels or to large
open areas for rapid dissipation in the atmosphere. Considerations must be given
to any phase change either vaporization of liquid or condensation of vapor, that
occurs in the fluid when the pressure is reduced or as result of cooling.
Disposal systems generally consist of piping and vessels. All components must
be suitable in size, pressure rating, and material for the service conditions
intended.
A remote controlled snuffing system is recommended for each vent stack,
specially in locations where the incidence of lightning is high or where access to
the point of discharge would be difficult with conventional fire extinguishing
equipment. An automatic water sprinkling system is required for each vent stack,
specially in locations where the incidence of lightning is high, in order to cool the
tip of the vent stack and avoid reignition (see schematic drawing in Fig. 1).
Other spray geometries, as shown in Figure 2 have been studied to supress gas
fires.
4.2
Atmospheric Discharge
4.2.1
4.2.2
4.2.3
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 4
.Men Principal
Indice manual
Indice volumen
Indice norma
ignition of relief streams at the point of emission, excesive noise levels, and air
pollution.
4.2.4
a.
Vapor Emission
When hydrocarbon relief streams comprised entirely of vapors are discharged
into the atmosphere, mixtures in the flammable range will unavoidably occur
downstream of the outlet as the vapor mixes with air. Under most circumstances
where individual safety relief valves discharge vertically upward through their own
stacks, this flammable zone will be confined to a rather limited definable pattern
at elevations above the level of release. At exit velocities from the safety relief
valve stack, the jet momentum forces of release will usually be dominant. Under
these conditions the air entrainment rate is very high and the released gases will
then be diluted to below the lower flammable limit before the release passes out
of the jetdominated portion if:
Re u 1.54x10 4 f
a
Where:
Re = Reynolds number, calculated at vent outlet.
f
a
On the other hand, if the release is at too low a velocity (below 500 fps) and has
too low a Reynolds number, jet entraintment of air will be limited, and the released
material will be wind dominated. Principles of atmospheric dispersion will then
determine the dilution rate and how far flammable conditions can occur. Under
these conditions, it is possible that flammable mixtures can occur at grade or at
distant ignition sources. A complete evaluation requires consideration of the
following:
1.
2.
3.
PDVSA
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
VENT SYSTEMS
Pgina 5
.Men Principal
Indice manual
Indice volumen
Indice norma
4.
5.
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 6
.Men Principal
b.
Indice manual
Indice volumen
Indice norma
Mist Emission
Mists, as referred to in this guide, result from condensation following emissions.
Condensed mists are finely divided, the diameters of most drops is less than 10
micrometers, with few larger than 20 micrometers. Mechanical sprays do not
usually contain many drops below 100 micrometers in diameter.
Whether vapors will condense in appreciable quantities when released to the
atmosphere will depend on the stream composition, atmospheric temperature,
and exit velocity. Frequently, the assumption is made that if the lowest anticipated
atmospheric temperature is below the dew point of a released hydrocarbon,
significant condensation will occur.
In cases in which vapor discharges from safety relief valves condense,
consideration must be given to how the condensation influences the formation of
a flammable atmosphere. Combustible liquid mists in air are capable of
propagating flame when ignited, even though the liquid is so involatile that no
appreciable amount of vapor is formed at the ambient temperature. Thus, mists
of flammable liquids can present a hazard even at temperatures well below the
flash point.
In cases in which calculation indicates that vapor discharges from safety relief
valves may condense, it is possible for coalescence to produce droplets that
rapidly settle to grade rather than dispersing as a mist similar to vapors. The
hydrocarbon partial pressure at which the calculated cooling curve intersects the
dewpoint curve should be considered indicative of bounding the region in which
coalescence seems unlikely.
Although no conclusive data are now available, it is suggested that condensation
at hydrocarbon partial pressures of 34 kilopascals absolute (5 pounds per square
inch absolute) or lees should be treated as finely divided mists without
coalescence. In the absence of coalescence, the effect of gravity should be
negligible since the freefall velocity of 10 micrometer hydrocarbon particles in air
is approximately 3 millimeters per second (0.01 feet per second). Therefore, even
with very light wind, the discharge from an elevated location will travel a
considerable distance before reaching grade.
Based on the foregoing factors pertaining to the dispersion and combustion
characteristics of a mist, it can be concluded that as long as the condensate
remains in finely divided form and is airborne, the mixture can be treated for
flammability and dispersion characteristics as though it were completely
vaporized.
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 7
.Men Principal
c.
Indice manual
Indice volumen
Indice norma
Liquid Emission
Unlike discharges composed of vapor or mist, which rapidly disperse when vented
to the atmosphere at high velocity, liquid discharges settle to grade. If volatile
components are present a flammable atmosphere may result. The risk of fire or
explosion may be high if appreciable quantities of liquid hydrocarbon are released
to the atmosphere when the ambient temperature is at or above the flash point
of the liquid or when their presence concur whith an unexpected source of ignition.
Theoretically, liquide that have a flash point above the maximum anticipated
ambient temperature would not vaporize enough to create a flammable
atmosphere. However widespread spraying of oil droplets could create concern
in an emergency and could constitute a serious nuisance. Also, minor fires might
occur if liquid came in contact with very hot line or equipment.
Fluids that are discharged from relief devices as liquide should be handled in the
following manner.
Flammable liquide with atmospheric boiling points above 35C (95F) should be
directed downward within 1020 cm (48 inches) of grade and shielded to prevent
splashing of liquid and debris. The discharge should be in or near a trapped drain
or some other safe location.
Flammable liquide with atmospheric boiling points between 35C (95 F) and
50C (58 F) should be routed to a liquid knockout pot to separate vapor and
liquid. The vapors should be disposed of as in the section on Vapors Emission.
Flammable liquide with atmospheric boiling points below 50C (58 F) should
be directed upward and discharged at least 45 meters (150 feet) above grade or
above the tallest column in the unit. The discharge should be a minimum of 2.4
m (8 feet) above the shutoff valve underneath the relief device.
Nonflammable liquids that are not hazardous to personnel with atmospheric
boiling points above 35C (95F) should be directed downward within 1020 cm
(48 inches) above grade and shielded to prevent splashing of liquid and debris.
Nonflammable liquids that are not hazardous to personnel with atmospheric
boiling points below 35C (95F) should be discharged up in the air a minimum
of 2.4 m (8 feet) above the shutoff valve under the relief device.
Nonflammable liquide that are hazardous to personnel must be discharged in a
safe manner to prevent personnel injury. Each case will require individual
consideration because of the many types of hazards that can be encountered.
d.
Sources of Ignition
The possibility of accidental ignition of the outflow of hydrocarbon vapors from a
safety relief valve can best be analyzed in terms of four possible causes of ignition:
outside sources (including open flames, hot surfaces, or nonclassified electrical
equipment), lightning, static electricity, and autoignition.
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 8
.Men Principal
Indice manual
Indice volumen
Indice norma
1.
2.
3.
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 9
.Men Principal
Indice manual
Indice volumen
Indice norma
4.3
Toxic Vapors
4.3.1
4.3.2
However, certain refinery and production streams may contain vapors that are
dangerous at extremely low concentrations: for example, hydrogen sulfide vapors
can cause unconsciousness and death within seconds following exposure to a
concentration above 1000 parts per million. This is approximately onetenth the
concentration representing the lowest flammable limits of any hydrocarbon.
Therefore where hydrogen sulfide or similar toxic materials are present in a relief
stream, an investigation should be made to predict the maximum downwind
concentration at any location where personnel may be exposed. Special attention
should be given to adjacent elevated structures that may he within the path of the
plume and will thus be subject to relatively high concentrations. If the presence
of toxic vapors can not be avoided proper disposal system must be designed and
installed, and safety equipment must be available on site.
4.3.3
The ground level concentration of toxic vapors at any location downwind a stack
can be estimated as described in PDVSA Guide 90616.1.020.
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 10
.Men Principal
Indice manual
Indice volumen
Indice norma
VENT SYSTEMS
5.1
5.2
5.3
5.4
Collected liquids will be pumped to the common K.O drum at plant inlet or at any
other suitable location. The pump should be spared, start automatically at high
liquid level and cut out at low liquid level and shall be connected to the emergency
power generator. An on/of f light in the control room should indicate on/off of the
pump. The pumps shall be sized for specific gravity range from 0.6 to 1.0.
5.5
The complete system shall be continuously purged at a low and sufficient rate. A
restriction orifice should be installed to pass the required amount. Provide purge
connection at the farthest end of vent header to ensure that the entire system will
remain purged.
5.6
5.7
For atmospheric vents the discharge shall be vertical, with the vent pipe:
5.8
In addition, for production facilities and gas compression plants the discharge
shall be:
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 11
.Men Principal
Indice manual
Indice volumen
Indice norma
5.9
The possibility that the vented stream catches fire should be considered, in which
case the heat input on neighbouring working platforms shall not exceed 5400
kcal/m2hr (2000 BTU/sq.ft.hr.) nor be damaging to the nearest structures. A
flame arrestor should not be fitted.
5.10
The tail pipes shall be provided with a steam hose connection or other systems
for flame extinguishing.
5.11
The vent outlet velocity shall not be lees than 150 m/sec (500 ft/sec) and not
higher than 80% of the sonic velocity at the rated capacity. The tail pipe shall not
be smaller in diameter than the relief valve outlet.
5.12
The bottom of the vent shall be provided with a 1/2 dia (minimum) drain at the
lowest point, which should be opened frequently (i.e. once a week), to prevent the
liquid build up. The vent pipe shall be adequately supported against reaction
forces.
VENT STACKS
6.1
Sizing
6.1.1
The size of a vent stack is determined by the available pressure drop and by any
minimum velocity required to prevent hazardous conditions due to combustible
or toxic material at grade or working levels. Normally, a size is selected that will
result in a high discharge velocity for example, velocity of 150 meters per second
(500 feet per second) will provide excellent dispersion. The size should be
checked to ensure that sonic flow is not established or, if it is, that allowance has
been made for the pressure discontinuity at the discharge end in calculating
pressure drop. A sample calculation is presented afterwards.
6.1.2
Assume the following conditions: The maximum relief rate, W, is 113400 kg/h
(250000 pounds per hour). The molecular weight of the vapor, M, is 44. The
temperature of the vapor just inside the tip, T. is 361K (650R). The exit velocity,
V, is 150 meters per second (500 feet per second)).
6.1.3
The pressure of the vapor just inside the vent tip, P, is 101 kilopascals absolute
(14.7 pounds per square inch absolute). The gas constant, R, is 8.3 for metric
units (10.7). The density is then calculated as follows:
PDVSA
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
VENT SYSTEMS
Pgina 12
.Men Principal
Indice manual
Indice volumen
Indice norma
+ MP
RT
+
(44) (101)
+ 1.48 kilograms per cubic meter
(8.3) (361)
W
3600 V
250000
+ 1.39 square feet
(3600) (0.1) (500)
Thus the pipe diameter should be about 16 inches nominal pipe size.
6.2
Design Details
6.2.1
Once the vent stack has been sized in accordance with recommendations,
indicated in section 6.1, the design is primarily a structural problem.
6.2.2
If the vent stack is in a location remote from other facilities, a guyed stack will
usually be as satisfactory as, and more economical than, providing a structure to
support the stack. Vent stacks are frequently located in a process area that
contains equipment connected to the stack. It is often possible to support the stack
from a fractionating tower, chimney, or other tall structure in the unit. Such an
arrangement provides for economical discharge at a safe elevation.
PDVSA
PDVSA
REVISION
FECHA
Pgina 13
.Men Principal
Indice manual
Indice volumen
Indice norma
6.2.3
The height of the vent stack is selected so that the concentration of vapor at a point
of interest is well below the lower flammable limit of the vapor. Usually 0.10.5
times the lower flammable limit is an acceptable concentration. Toxicity requires
much lower concentrations on certain applications and is therefore the controlling
factor. The radiant heat intensity for vent stack should also be checked in the event
a relieving vapor should ignite; calculation should be made assuming a flow rate
equivalent to an outlet velocity of 150 m/seg (500 FPS), this is done by the same
means as for flare stacks, and the came limits apply for radiant heat intensity.
Radiant heat levels sometimes take precedence over dispersion in determining
stack height. Methods of flare calculations are presented in PDVSA Guide
90616.1.021.
6.2.4
6.2.5
6.2.6
The possibility that vapors from the vent stack may be accidentally ignited by
lightning or other sources usually makes a remotecontrolled snuffing steam,
water (for cooling) or CO2 connection necessary on the vent stack. This is
specially true in locations where the incidence of lightning is high or where access
to the point of discharge would be difficult with conventional fireextinguishing
equipment. Each system consists of CO2 cylinders, connected by flexible
discharge loops to a manifold which is piped to two opposed discharge nozzles,
installed approximately 4.5 m (15 feet) below the top of the vent stack. The
operation of the valves is manual.
6.2.7
It is frequently impractical to size the steam supply line for a rate sufficient to
extinguish a fire under maximum venting conditions, however, steam would still
be essential, since in most cases, vent fires occur when the only flow to the system
consist of leakage or minor venting. With relatively small amounts of vented vapor
in small stacks, it is possible to dilute the vented vapor to the point where
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 14
.Men Principal
Indice manual
Indice volumen
Indice norma
combustion ceases. It requires on the order of one pound of steam per cubic foot
of vented vapor to dilute a flammable vapor to this point. As the vented vapor rate
and stack size increase, the steam rate for dilution to the extinguishing ratio
becomes excessive, and. it becomes necessary to depend on a blowout
phenomena for achieving extinguishment. Blowout results from the combined
effects of dilution with steam and outside air at high velocities and cooling resulting
from the dilution.
6.2.8
6.3
Furthermore, unless steam or cooling water and CO2 is supplied, if ignition occurs
when venting at or near the maximum design load, the fire will quite likely continue
to burn when the cause of overpressure is corrected with an accompanying
reduction in venting.
Vent Valves
Vent valves are frequently installed for relieving pressure in piping systems prior
to opening for maintenance. In some cases the pressure can be safely relieved
by cautiously opening a flange or loosening a threaded connection. For example,
it is not necessary to install vent valves under pressure gages in the typical plant
cooling water system. However, when fluids hazardous to personnel are handled
(phosgene, carcinogens, strong caustic, or acid solutions, etc.) vent valves should
be provided in portions of the piping where the fluid can be trapped under
pressure.
6.4
Local Vents
6.4.1
Often neglected from a safety point of view are local vents, such as those on fixed
roof tanks and lube oil/seal oil tanks.
6.4.2
The hazardous area around local vents shall be classified according to the
frequency of flammable vapor release. In addition, high ignition risk vents, such
as those on oil savers shall be positioned so as not to endanger nearby
equipment, especially electric cables, when ignited.
6.4.3
In complying with hazardous area requirements, special care should be taken not
to extend a tank vent to a height where overfilling the tank will overpressures it due
to the liquid column in the vent. In such cases, a separate pressure/vacuum valve
or permanent vent drains must be installed.
6.4.4
During drilling, flammable vapors released from low pressure or atmospheric mud
separators may be vented without being ignited through the vent line attached to
the derrick.
6.4.5
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 15
.Men Principal
Indice manual
Indice volumen
Indice norma
7.2
It is estimated that the loss of heat in a vent system is 24.4 to 48.8 kcal/ m2 C (5
to 10 British thermal units per square foot of surface per degree Fahrenheit)
temperature difference between the steel and the atmosphere. The range is due
partly to the effect of wind, while the rate of cooling would be greater in a rain
storm. The vapor space in the knockout drum must be sufficiently large to reduce
the vapor velocity below the dropout velocity of the fine entrained droplets. API
RP 521 present a method for sizing knockout drums to remove droplets of 150
microns and larger. Drums equipped with pumps on automatic control should
have sufficient capacity for the maximum liquid accumulation expected in 15
minutes. The pumps must be capable of handling the lowest molecular weight
liquids that are likely to accumulate.
7.3
If a very heavy flow of vapor should occur suddenly, previously condensed liquide
may be entrained and carried out the stack. Experiments carried out showed the
relative effectiveness of cyclones, mist eliminators, water seals, and knockout
drums. The use of mist eliminators is objected because they may become plugged
and increase the pressure drop of the systems. Experience has demostrated that
a combination of water seals with vane type mist eliminators is a good design to
prevent liquid carryover. Cyclones are effective at high velocities but poor at less
than design flows.
7.4
Design Consideration
Blowdown drums for normal hydrocarbon service are designed in accordance
with the following (see Figures 4 and 4A for typical refineries and gas compression
plants respectively):
7.4.1
7.4.2
A single blowdown drum may be used for more than one process unit, if
economically attractive. However, when this is done, all units served by it must be
shut down in order to take the drum out of service, unless cross connections are
made to another system of adequate capacity.
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 16
.Men Principal
Indice manual
Indice volumen
Indice norma
7.4.3
Normally all closed safety valve discharges are combined into one header
entering the drum, although separate headers and inlet nozzles are acceptable
if economically advantageous
7.4.4
Sizing of the blowdown drum and location of the level instruments are based on
the following (see Figure 4 and 4A):
a.
Liquid holdup below the LH (CO) A (AB in Figure 4 and 4A) is the light ends
stream diversion requirement or the closed drainage requirement for residual
process liquide at a normal shutdown, whichever is greater. This closed dram
requirement is taken as 10% of the total liquid hydrocarbon inventory of all vessels
in one process unit which are provided with closed dram header connections. This
assumes that 90% of the liquid inventory of these vessels can be removed by
pressuring or pumping out through normal process disposal routes. The process
unit to be used for sizing purpose is the one which has the largest closed dram
requirement and which can shutdown independently for turnaround. Inventory of
vessels is calculated at the top of the working level range, excluding tray holdup
and the contents of piping. In the case of vessels containing large liquid
inventories, e.g., surge drums, the individual closed dram header requirement
may be reduced below 10%, where appropriate, by taking credit for alternative
means of disposal of the liquid contents, e.g. water displacement to storage.
b.
The space in the drum above the LH (CO) A (Above the upper LH (CO) A when
two are installed) is made up of a holdup capacity (BD in Figure 4 and 4A) for 30
minutes accumulation of liquid safety valve releases, plus a vapor space (DF)
for the associated vapor release. The drum sizing is determined by the single
contingency which requires the maximum combined space BD plus DF.
c.
d.
1.
2.
The single contingency which results in the largest vapor load regardless of
any associated liquid load, is used to determine the maximum required
vapor space CF, and a high level alarm is placed at point C.
Vapor load considerations must include all safety valve, emergency vapor
blowdown and vapor stream diversion sources which release as a result of
a single contingency.
PDVSA
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
VENT SYSTEMS
Pgina 17
.Men Principal
Indice manual
Indice volumen
Indice norma
2.
Liquid loads are considered from all safety valves that discharge as a result
of a single contingency, plus in each case an allowance for knockout drum
liquids (fuel gas K.O. drums, absorber overhead K.O. drums) equal to the
inventory of all drums which discharge to the blowdown drum, at their LHA
point. In a typical gas compression plant, this allowance is not necessary
since those liquids are not directed to the vent knock out drum, they are
connected either to the suction plant knock out drum or with another suitable
facility.
3.
L * v
v
Where:
VC
The depth of the vapor space should under no contingency be less than 20%
of the drum diameter, or less than 30 cm (12 inch).
A LL (CO) A with local manual reset is provided to trip the pumpout pump when
the liquid has been pump down to a low level.
7.4.5
The blowdown drum design pressure is 3.4 bar g. (50 psig) or less.
7.4.6
a.
The maximum allowable back pressure on safety valves which discharge to the
blowdown drum, according to set pressure and type of safety valve, or
b.
The pressure at which vapor diversion from any gas compressor suction to the
blowdown drum is required to be released. These facilities are normally provided
on cat cracker and steam cracker process gas compressors.
c.
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 18
.Men Principal
Indice manual
Indice volumen
Indice norma
7.4.7
7.4.8
Blowdown drum materials must be adequate for any corrosive substance that
may be released into it, and for the temperature limits defined by paragraph 7.1.7
above. The corrosion allowance shall be 3 mm.
7.4.9
Depending on the weather or operating conditions at the plant site a heating coil
could be provided in the blowdown drum for deicing, winterizing and weathering
purposes. Sizing of the coil is based upon weathering off the light ends from the
flashed liquids at the maximum level accumulated as a result of any of the design
contingencies described in paragraph 7.1.4 above. This material must be
weathered in two hours to temperature and vapor pressure conditions which will
permit safe pumpout to associated shops or other receiving facilities. In some
cases weathering must be followed by cooling of the pumpout stream (see
paragraph 7.1.13 below). For most applications when steam is available, a steam
coil consisting of a nominal 60 m (200 ft) of 2 inch pipe is adequated. The coil
should be sloped to insure condensate drainage.
7.4.10
a.
A 5 cm (2 inch) steam trap by pass direct to sewer. This is required in all cases
where temperatures below 0C (32F) may occur in the blowdown drum.
b.
Connections for methanol injection into the steam coil inlet and outlet piping for
deicing.
c.
d.
Use of a hot oil heating medium to the coil, or a cascade heating system (e.g.,
steam, methanol).
7.4.11
In some cases the drum is provided with a drawoff boot of nominal 60 cm (2 ft)
diameter by 90 cm (3 feet) in height, with a separate steam coil fabricated from
1 inch pipe. Normally it is not necessary to withdraw hydrocarbon and water
separately, and the pumpout pump takes suction from the bottom of the boot. The
LL (CO) A is located as close as possible to the top of the boot to ensure that the
pump is shutdown before losing suction.
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 19
.Men Principal
Indice manual
Indice volumen
Indice norma
7.4.12
7.4.13
Disposal of pumpout material from the blowdown drum at the refineries is normally
to pressure shops storage, light atmospheric slops storage, or other atmospheric
tankage. At the gas compression plants these liquids are directed either to the
suction plant knock out drum or another suitable location. Design features must
be incorporated to avoid the hazards of excessive vapor evolution or boilover
which can result from routing light or hot materials to atmospheric tankage.
Requirements for weathering off light ends from liquid accumulated in the
blowdown drum are defined in paragraph 7.1.9 above.
In addition, a cooler should be provided in the discharge line from the pumpout
pump if either of the following applies:
a.
The blowdown drum can receive hot liquids above 93C (200F), or
b.
NOISE
8.1
8.1.1
Noise created from the venting of hydrocarbons may cause problems due to either
the potential hearing loss of exposed personnel or the nuisance created in
surrounding areas.
8.1.2
The noise generated by a pressure relief valve discharging to the atmosphere can
be relatively loud. Emergency relief is ordinarily of short duration and occurs
infrequently, so a high noise level is usually acceptable.
8.1.3
The allowable noise intensity and duration should be evaluated at areas where
operating personnel would normally work or at property limits. Where two or more
pressure relief valves can discharge to the atmosphere simultaneously, the
combined effects will need to be evaluated.
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 20
.Men Principal
8.2
Indice manual
Indice volumen
Indice norma
Noise Calculation
The noise level at 30 meters (100 feet) from the point of discharge to the
atmosphere can be approximated by equation:
L100 = L(from figure 5) + L log 1012 MC 2
Figure 5 ilustrates the noise intensity measured as the sound pressure level at 30
meters (100 feet) from the stack tip versus the pressure ratio across the safety
valve.
The following symbols are used in the procedure for calculating the noise level:
M = Mass flow through the valve, in kilograms per second (slugs per second).
C = Speed of sound in the gas at the valve, in meters per second (feet per
second).
Notes:
In feet per second:
C + 223
MolecularkT Weight
MolecularkT Weight
Where,
k
PR = ratio of the upstream to the downstream pressure across the safety valve
(absolute)
An example of calculating in English units, the noise level at 100 feet from the point
of discharge to the atmosphere is presented below:
a.
Calculate 1/2 MC2: in watts. Divide the weight flow (pounds per second) by 32 to
obtain M. Multiply 1/2 MC2 (foot pounds per second) by 1.36 to obtain 1/2 MC2 in
watts.
b.
c.
PDVSA
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
VENT SYSTEMS
Pgina 21
.Men Principal
d.
Indice manual
Indice volumen
Indice norma
Add items a and c to obtain the average sound pressure level at 100 feet, L100 in
decibels. Assume the followings:
M = 1 slug per second
= 32 pounds per second
k = 1.4
Molecular weight = 29
T = 560 degrees Rankine
PR = 48/16 = 3
C + 223
(1.4)29(560)
b.
c.
d.
2.
3.
4.
Add item 2 and 3 to obtain the average sound pressure level at 30 meters,
L100 in decibels. Assume the following:
M = 14.6 kilograms per second
k = 1.4
Molecular weight = 29
T = 311 degrees Kelvin
PR = 48/16 = 3
C + (91.2)
(1.4)29(311)
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 22
.Men Principal
Indice manual
Indice volumen
a.
b.
c.
d.
Indice norma
Note: The calculations are based on spherical spreading of the sound. If distances
much larger than the height of the vent above ground are of concem, add 3
decibels to the calculated result to correct for hemispherical diffusion.
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 23
.Men Principal
Indice manual
Indice volumen
Indice norma
12
SPRINKLING NOZZLES (3/4)
1 1/2
CO2 CONNECTION
2
1 1/2
GATE VALVE 2
LINE 2
DRAIN LINE
STACK PLATFORM
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 24
.Men Principal
Indice manual
Indice volumen
Mw/Mg = 6.4
30
Mw/Mg = 4.2
Mw/Mg =9.5
Mw/Mg =5.3
Indice norma
PDVSA
VENT SYSTEMS
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
Pgina 25
.Men Principal
Indice manual
Indice volumen
Indice norma
Vent Stack
Weld
Stack diameter D,
inches
Less than 8
1/2
8 to 12
3/4
12 to 20
20 to 24
Over 24
PDVSA
PDVSA 90616.1.029
VENT SYSTEMS
REVISION
FECHA
OCT.02
Pgina 26
.Men Principal
Indice manual
Indice volumen
Indice norma
TO FLARE
F
*
VAPOR SPACE FOR 100% OF CRITICAL VALOCITY
30 MINUTES LIQUID FROM SAFETY VALVES
PLUS
ALLOWANCE FOR LIQUID FROM KNOCKOUT DRUM
E
D
C
LHA
LH(CO) A
TI
LL(CO) A
CLOSED DRAIN
HEADER
(1)
STEAM
PUMPOUT FROM
MAXIMUM
LIQUID LEVEL IN
2 HOURS
PDVSA
PDVSA 90616.1.029
REVISION
FECHA
OCT.02
VENT SYSTEMS
Pgina 27
.Men Principal
Indice manual
Indice volumen
Indice norma
TO VENT
F
MAX. LIQUID LEVEL FOR PUMPOUT
PUMP SIZING
MAX. LIQUID LEVEL FOR DRUM SIZING
VAPOR SPACE FOR 100% OF CRITICAL VALOCITY * E
D
30 MINUTES LIQUID FROM SAFETY VALVES
TI
B
A
LL(CO) A
PUMPOUT FROM
MAXIMUM
LIQUID LEVEL
IN 2 HOURS
PDVSA
PDVSA 90616.1.029
VENT SYSTEMS
REVISION
FECHA
OCT.02
Pgina 28
.Men Principal
Indice manual
Indice volumen
Indice norma
Fig 5. NOISE INTENSITY AT 100 FEET (30 METERS) FROM THE STACK TIP
10
9
8
7
1.5
20
30
40
50
60
(DECIBELS)
SOUND PRESSURE LEVEL AT 100 FEET
(30 METERS) FROM STACK TIP
70