7UT6 Power System Data 2


Energy Automation

Setting Group A (B,C,D) / Power System Data 2


parameter 1111, 1112, 1113 Pole Open Current Threshold Side 1, 2, 3
Setting range: 0.041.00 I/InS
Example: CT primary current IP = 3000 A , InO = 1128 A IP/InO = 2.66
with this the value range becomes: 2.66(0.041.00) = 0.10642.66
The setting(s) must be within this range !!
If the setting is to low (default setting is 0.10 I/InS), the Protection will be
blocked and in online mode the message
30067 parameter too low will appear.