1. Scope
1.1 This fire-test-response standard for the comparative
surface burning behavior of building materials is applicable to
exposed surfaces such as walls and ceilings. The test is
conducted with the specimen in the ceiling position vvith the
surface to be evaluated exposed face down to the ignition
source. The material, product, or assembly shall be capable of
being mounted in the test position during the test. Thus, the
specimen shall either be selfMsupporting by its own structural
quality, held in place by added supports along the test surface,
or secured from the back side.
1.2 The purpose of this test metllOd is to detennine the
relative burning behavior of the material by observing the
flame spread along the specimen. Flame spread and smoke
developed index are reported. However, there is not necessarily
a relationship between these two measurements.
1.3 The use of supporting materials on the underside of the
test specimen has the ability to lower the flame spread index
from those which might be obtained if the specimen could be
tested without such support. These test results do not necessarily relate to indices obtained by testing materials without
such support.
1.4 Testing of materials that melt, drip, or delaminate to
such a degree that the continuity of the flame front is destroyed,
results in low flame spread indices that do not relate directly to
indices obtained by testing materials that remain in place.
LS The values stated in inch-pound lmits are to be regarded
as the standard.
1.6 The text of this standard references notes and fooinotes
that provide explanatory infonnation. These notes and footnotes, excluding those in tables and figures, shall not be
considered as requirements of the standard.
1.7 This standard is used to measure and describe the
response of materials, products, or assemblies to heat and
flame under controlled conditions, but does not by itself
incorporate all factors required for fire-hazard or fire-risk
2. Referenced Documents
2.1 ASTM Stamards:
A 390 Specification for Zinc-Coated (Galvanized) Steel
Poultry Fence Fabric (Hexagonal and Straight Linef
C 36 Specification for Gypsum Wallboard3
D 4442 Test Methods for Direct Moisture Content Measurement of Wood and Wood-Base Materials'
D 4444 Test Methods for Use and Calibration of Hand-Held
Moisture Meters4
E 69 Test Method for Combustible Properties of Treated
Wood by the Fire-lUbe Apparatus'
E 160 Test Method for Combustible Properties of Treated
Wood by the Crib Test'
E 162 Test Method for Surface Flammability of Materials
Using a Radiant Heat Energy Source"
E 176 Tenninology of Fire Standards"
E 286 Test Method for Surface Flammability of Building
Materials Using an 8-ft (2.44-m) Tunnel Furnace"
3. Terminology
3.1 Definitions-For definitions of terms used in this test
method refer to Tenninology E 176. The term ftame spread
index from Tenninology E 176 is of perticular interest to this
standard and is defined in 3.1.1.
3.1.1 flame spread index, n-a number or classification
indicating a comparative measure derived from observations
made during the progress of the boundary of a zone of flame
under defined test conditions.
Annual Book ofASTM Blandmria, Vol 01.06.
Annual Book ofASTM Suuldards, Vol 04.01.
4 Annual Book ofAS1M SIGndmris, Vol 04.10.
S Discontinued; see 1993 Annual Book of ASrM Standards, Vol 04.09.
Ii Annllal Book ofASTM Standards. Vol 04.07.
1 Discontinued; see 1991 Annual Book ofASTM Standards, Vol 04.07.
2
This test method is under the jurisdiction of ASTM Committee E5 on. Fire
Standards and is the direct responsibility of Subcommittee EOS.22 on Sud'ace
Burning.
CUrrent edition approved July 10, 2001. Published July 2001. Originally
published as E 84 - 50 T. Last previous edition E 84 - OOa.
t
Copyrlght@ASTM InternatIonal, 100 Barr Harbor DrIve, PO Box C700, West Conshohocken, PA 19425-2959,
United Statas.
NOTIC~;:
This standard has either been superceded and ..eplaced by a new version or discontinued.
Contact ASTJ.\tI International ("\\"''W .astm.org) for the latest information.
E84-01
Vv1dth:
Depth:
*'
Length:
5.1.2 The sides aud base of the chamber shall be lined with
au insulating firebrick with the dimensions of 4 y, in. by 9 in.
by 2 y, in. thick as illustrated in Fig. 2. The insulating firebrick
shall have thc following properties:
5. Apparatns
1r
----15-
ASTME84
C.
5"
<;
---~--
J 1c:;:;J1
g Heat-resistant glass, high-silica, 100 % silica glass, nominal %-rn. thick has
been found suitable for theinteriOI pane. Borosilicate glass, nominal V4-in. thick has
__________ ~~~~~~~~~S~9~~R~:x~~gST
~
~
19ft.6in.
4'-
euRIEDTHEHMOCOUP
,
_ _ _ _ _,'~3UH~.~ill~2~lnh.
_ _ _ _ _ _~1
i"-_
. -_
-- - - - -!l3!JHL.....1[f./2Clln[h-----;;-3-,-/4-H-.--"1/2In.
I--_____________
-<;l
.'3.11~/4.1Ht...tlllr2J!lnh._ _ _ _ _ _ _ _ _ _ _ _--I
23 ft. .:-:;t?in.
23ft.+il'>in.
24 if.
f.
~3in.
2 .3in.
SIUni\s
7B.2
76.2 1.6mm
i.Bmm
304,8mm
381 mm
54::1: 51n.
1.37m127mm
5451n.
4 ft, 61n.
Bin.
1.37 m
19 ft. 61n.
5.94m
13 ft. 1/2 in.
3.96 m 12.7 mm
23 1/4 ft. 112 in. 7.1 rn12.7mm
m12.7mm
23 ft 1/2
112 In.
7.0 m 12.7 mm
mm
24 ft.
7.32m
25ft.::I:31n.
25ft.31n.
7.62 m 76.2 mm
FIG. 1 Test Furnace, Showing Some Critical Dimensions (Not a Construction Drawing)
12 In.
151n.
II
BURIED TH61MOCOUPLEdj
EXPOSED THERMOCOUPLE
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM International (www.a.lm.org) for the latest information
E84-01
f-L-LL
----------,, 1
,
'r
,
,
,
,
.~
CASTABLE INSULATION
, __________ .J
-------
rp
UQUIDSEAL./
FURNACE LEDGES
'---EXPANDED METAL
CASTABLE INSULATION
7--TT----
-""
ID~I
.~
on
,..:
IE
4.0 + 0.5 in 1
.-7-
~i
17.625 ,0.375 in.
DOUBLE PANE
OBSERVATION
WINDOWS
on
ci
~-I"-
.;
oi
rtf
c,L,
OPTIONAL: CASTABlE
REFRACTORY OR FIRE
BRICKUNING
2600 F
7.SO.Sln.
12.0 0.5 in.
17.75 0.25 in.
.s.t..!.!ni
Inch-Pound UOil
Inch-Pound Uni!
101.6 13 mm
190.5 13 mm
447.7 9.5 mm
317.S 13 mm
liB in.
91n.
4.5 in.
2.5 in.
228.6mm
114.3 mm
63.5 mm
1427C
3.2mm
450.9 6.4 mm
114 in.
6.4mm
FIG. 2 Test Furnace Showing Critical Dimensions (Not a Construction Drawing)
0.102 Wlm'K)
NOTJ:CE: This standard has either been superceded and replaced by a new version or discontinued.
ES4-01
24 in.
3 in.
lill.h:!i!.
450.8 6.4 mm
203.2 mm
304.8 12.7 mm
609.6 mm
76.2 mm
17-3/4 + 1/4"
II~
15
UJ
Cl
in
~
<0
a:
a:
41~.o--___-,,::,,-:____.141"'
.1'3~ 1---'
141.
18"
24"
..
~I
"o
=8"
-- - - - --
AS REQUIRED
a:
UJ
-'"
tJ
~oCl
~
tl
tl
UJ
OJ
oCl
iii
@
a:
5
@
a:
~
.0-........
/0.
o
<0
'"
(190 13 rum) below the under surface of the test sample. Gas
to the burners shall be provided through a single inlet pipe,
turbulance baffling shall be provided by positiouing six reftaetory firebricks (as defined in 5.1.2) along the side walls of the
chamber. With the long dimension vertical, 4 "'in. (114-rum)
dimension along the Wall, place the bricks as follows from the
Fig. 2).
On the window side at 7, 12, and 20 :!: ~ ft (2.1, 3.7. and 6.1 :!: 0.2 m)
:!:
0.2 m)
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTlVllnternational (www.astm.org) for the latest information
TRANSITION
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
['"
E84-01
rum) in length, with a cross-sectional area of not less than 200
in. 2 (1290 em2 ) at any point (see Fig. 3).
5.1.8.2 The transition piece shall in tnrn be fitted to a 16 in.
(406 rum) diameter duct pipe. A typical duct system shown in
Fig. 4 contains two 90' elbows (see Fig. 5) with the exhaust
duct running beside the fire test chamber. In order to comply
with this typical design, the vertical centerline of the exhaust
duct system is identical to that of the fire test chamber.
5.1.8.3 The exhaust duct is to be insulated with at least 2 in.
(51 mm) of bigh temperature mineral composition material
from the exhaust end of the fire chamber to the photometer
location.
5.1.8.4 An exhaust fan shall be installed at the end of the
exhaust duct. The air flow shall be controlled as specified in
5.1.11.
5.1.8.5 An alternative exhaust duct layout design shall
demonstrate equivalency by meeting the requirements speci~
fied in Section 7.
5.1.9 Photometer System:
5.1.9.1 A photometer system consisting of a lamplO aod
photocell" shall be mowrted on a horizontal section of the
16-in. (406-rum) diameter vent pipe at a point where it will be
preceded by a straight run of pipe (at least 12 diameters or 16
it (4.88 m) and not more than 30 diameters or 40 it (12.19 m)
from the vent end of the chamber, and with the light beam
directed upward along the vertical axis of the vent pipe. The
vent pipe shall be insulated with at least 2 in. (51 rum) of
high~temperature mineral composition material, from the vent
end of the chamber to the photometer location. The photoelectric cell of which the output is directly proportional to the
amollOt of light received shall be mollOted over the light source
and connected to a recording device having a minimum
operating chart width of 5 in. (127 rum) with an accuracy
within 1 % of full scale, for indicating changes in the
attenuation of incident light by the passing smoke, particulate,
and other eflluent. The distance between the light source lens
and the photoceillens shall be 36 4 in. (914 102 rum). The
cylindrical light beam shall pass through 3-in. (76-mm) diameter openings at the top and bottom of the 16-in. diameter duct,
with the resultant light beam centered on the photocell.
5.1.9.2 Lineatity of the photometer system shall be verified
periodically by interrupting the light beam with callbrated
neutral density filters. The filters shall cover the full range of
the recording instrument. Transmittance values measured by
the photometer, using neutral density filters, shall be within
3 % of the calibrated value for each filter.
5.1.10 Draft Regulating Device:
5.1.10.1 An automatically controlled damper to regulate the
draft pressure shall be installed in the vent pipe down-stream of
I
I
DAMPER
rt
Ie
I
I
I
PHOTOCEL -I-
I
I
I
I
I
I
I
I
I
J
"I
6'-0"
F=
"'
R=1\1
111;:rJ
I\'
III
6'-Od
2"
INCH-POUND UNITS
16 in.
2 in.
5 ft.
6 ft.
16-40ft.
SIUNITS
406.4 mm
50.8mm
1.52 m
1.83 m
4.88 -12.2 m
FIG. 4 Plan View-Typical Duct System (Not a Construction
lO The sole source of supply of the apparatus ]rnO\vn to the committee at this time
is 12N sealed beam., clear lens, auto spot lamp, No. 4405, from General Electric,
Nela Park, OR. If you are aware of alternative suppliers, please provide this
Drawing)
infonnation to ASTM Headquarters. Your comments will receive careful consideration at a meeting of the responsible technical committee, I which you may attend.
II The sole source of supply of the apparatus known to the committee at this time
is No. 856BB from Weston Instruments, Wauconda, IL. If you are a'WllIe of
alternative ffilPpliers, please provide this infonnatiOll to ASTM Headquarters. Your
comments will receive careful consideration at a meeting of the responsible
technical committee,! which you may attend.
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
the latest infonnation
Contact ASTM International (www.astm.org) for thelotest
E84-01
o
<Xl
"'I
R=8
6>"0 "'I
~~
~ ~~L-~--~--~I~
I------L-----J'
1l
__
SI Units
406.4
203.2
482.6
mm
mm
mm
the smoke-indicating attachment. The damper shall be provided with a manual override.
5.1.10.2 Other manual or automatic draft regulation devices, or both, are allowed to be incorporated to help maintain
fan characterization and air-flow control throughout the test.
5.1.11 Thermocouples:
5.1.11.1 ANo. IS Awg (1.02-mm) thermocouple, with 'Is :':
y, in. (9.5 :': 3.2 mm) of the jnnction exposed in the air, shall
be inserted through the floor of the test chamber so that the tip
is 1 :': Y"in. (25.4 :': O.S mm) below the top surface of the
gasketing tape and 23 ft :': Y, in. (7.0 m :': 13 mm) from the
centerline of the burner ports at the center of its width.
5.1.11.2 Two No. IS Awg (1.02 mm) thermocouples are
embedded below the floor surface of the test chamber. These
thermocouples shall be mounted at distances of 13 ft :!: Jh in.
(3.96 m :': 13 mm) and 23 14 ft :': Y,in. (7.09 m :': 13 mm)
measW"ed from the centerline of the burner ports. The thermocouples shall be inserted from below the fire test chamber
tln'ough the firebrick until the tip of the thermocouple is 1/8
O.S mm) below the floor surface. The tip of the
'h,in. (3.2 :':
thermocouples shall be covered with refractory or portland
cement, carefully <hied to avoid cracking.
a 0.15-in. (3.S-mm) water-colnnm reading on the draft manometer, with the fire-end shutter open 3 V16 in. (76 1.5 rum),
by manually setting the damper as a characterization of fan
performance. Then close and seal the fire-end shutter, without
changing the damper position. The manometer reading shall
increase to at least 0.375 in. (9.53 mm), indicating that no
excessive all' leakage exists.
7.2.1 In addition, conduct a supplemental leakage test periperi~
odically with the tmmel sealed from the inlet end to beyond the
photometer system, by placing a smoke bomb in the chamber.
Ignite the bomb and pressurize the chamber to 0.375 :': 0.125
in. (9.53 :': 3.1S mm) water co1nnm. Seal all points ofleakage
observed in the fOlm of escaping smoke particles.
6. Test Specimens
6.1 The test specimen shall be at least 2 in. (51 mm) wider
(nominally 2014 :': % in. (514 :': 19 mm) than the interior
width of the tmmel. The length of the specimen shall be a total
of24 ft:': Y, in. (7.32 m :': 13 mm) and shall be butted against
the vent end of the fire test chamber. The specimen consists of
a continuous, lIDbroken len~ or of sections joined end-toend. Specimens shall be truly representative of the materials
for which test results are desired. Properties adequate for
6
NOTICE: TWs standard has either been superceded and replaced by a new version or discontinued.
E84-01
readings to the preheat temperature shown in the timetemperature curve in Fig. 3. This preheating is for the porpose
of establishiog the conditions that will exist following successive tests and for indicating the control of the heat input into
ment of velocity, remove the turbulence bricks (see 4.3) and the
exposed 23-ft thennocouple and place 24-in. (670-mm) long
straightening vanes between 16 and 18 ft (4.88 and 5049 m)
from the bumer. The straightening vanes shall divide the
furnace cross section into nine unifonn sections. Detennine the
test.
paper. Figs. 4-6 are representative curves for red oak flame
spread distance, time-temperature development, and smoke
density, respectively. Flame spread distance shall be determined as the observed distance minus 4V, ft (1.37 m).
7.10 Following the calibration tests for red oak, conduct a
similar test or tests on samples of V4-in. (6.3-mm) inorganic
reinforced cement board These results shall be considered as
NOTICE: This standard bas either been superceded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information.
OE84-01
600
600
i~
L-J........!---.!.-.--I-
-l-..i.~,..j.-t_.j..j.._~
-I-~
550
2"
-!!
500
260
450
232
,;
t
~
<;
3031111111111111111111111111111111111111111..
301111111111111111111111111111111111111111t4.
o
1I
Time. minutes
Time,
FIG. 7 Representative Time-Temperature Curve for Fuel Contribution of Inorganic Reinforced Cement Board
8. Procedure
8.1 With the furnace draft operating, place the test specimen
on the test chamber ledges that have been completely covered
with nominal I/S-in. (3.2-nnn) thick by 1 Y2-in. (38-nnn) wide
tape. Place the specimen as quickly as is
woven gasketing tape,
practical. Place the removable top in position over the specimen.
8.2 Keep the completely mounted specimen in position in
the chamber with the thrnace draft operating for 120 :': 15 s
prior to the application of the test flame.
8.3 Ignite the bmner gas. Observe and record the distance
and time of maximum flame front travel with the room
lO-min period. Termination of
darkened Continue the test for a 10-min
the test prior to 10 min is permitted if the specimen is
completely consumed in the fire area and no further progressive burning is evident and the photoelectric cell reading has
retmned to the baseline.
inunediately prior
804 Record the photoelectric cell output immediately
duriog the test.
to the test and at least every 15 s during
8.5 Record the gas pressure, the pressure differential across
the orifice plate. and the volume of gas used in each test. If a
temperature- and pressure-compensating mass flowmeter device is used to monitor the gas flow, record only the volume of
gas.
8.6 When the test is ended, shut off the gas supply, observe
withio the test duct, aod
smoldering aod other conditions within
remove the specimen for fmther examination.
temperature, aod change
8.7 Plot the flame spread distaoce, teroperature,
in photoelectric cell readings separately on the same type of
coordinate paper as used in 7.9 for use in detennining the
flame~spread and smoke-developed indexes as outlined in
Section 9. Flame front advancement shall be recorded at the
time of occurrence or at least every 30 s if no advancement is
noted. Flame spread distance shall be determined as the
observed distaoce minus 4Y, ft (1.37 m).
9. Interpretation of Results
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest information
EB4-01
20
18
16
1~
~12
w
w
'710
~
t;
;:;
6
4
2
0
10
5
TIME - MJ NUTE~
FIG. 8 Example of Time-Distance Relationship with Flame Front Recession
(Total Area, AT = A1 + A 2 )
1
11. Report
11.1 Report the following information:
11.1.1 Description of the material being tested, including its
composition or generic identification, thickness, and any relevant additional details,
11.1.2 Test results as calculated in Section 9,
11.1.3 Details of the method used in placing the specimeu in
the chamber, to include the following:
11.1.3.1 A statement whether a continuous or sectioned
specimen is used,
11.1.3.2 A description of the number of sections and their
sizes, when the specimen consists of sections joined end-toend,
11.1.3.3 The mounting method employed,
11.1.3.4 The method of placement of the cement board
protecting the furnace lid assembly.
11.1.4 Observations of the burning characteristics of the
specimen dlning test exposme, such as delamination, sagging,
shrinkage, fallout, etc., and
11.1.5 Graphical plots of flame spread and smoke developed
data.
TABLE 1
12
Materlal
Mean Value
Douglas Ar Plyv.IOod
Fire Retardant Treated
Douglas FIr Plywood
Type X Gypsum Board
RigId Polystyrene Foam
Rigid Polyurethane Foam
Composite Panel
Supporting data have been. filed at ASTM Headquarters and may be obtained
Repeatability
Standard
DevIation, Sr
Relative
Standard
Devlatlon.%
91
15
16
17
17
2.
17
1
3
2
,.
18
13
12
NOTICE: This standard has either been superceded and reillaced by a new version or discontinued.
Contact ASTM International (\\'ww.astm.org) for the latest information.
OE84-01
TABLE 2
Betvw'een~Laboratory
Material
Mean value
Douglas Fir Plywood
Fire Retardant Treated
Douglas Fir Plywood
Type X Gypsum Board
Rigid Polystyrene Foam
Rigid Polyurethane Foam
Composite Panel
91
17
Reproducibility
Standard
Deviation, SR
Relative
Standard
Deviatlon,%
23
6
25
33
36
60
23
21
9
7
2'
17
ANNEXES
(Mandatory Information)
AI.I Introduction
10
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM Internationnl (\\'ww.astm.org) for the latest information.
<0 E84-01
IFTHERE IS AN OlITSIDE JOIN')
,
,
.
,
,
,
,
,
,
I'I .1
1----1I' .11--- - 1 .
,
,
, ,
,
r'J
I' .1
"-f
1 1
I minimum
61n.
I
I1
1
1
, ,
,
24 In.
12 in.
t==:12
12 In.
In.
24 In.
24 in.
1
------------ 9
- -6
9I6
.r l-1
- ----nI.n
----------------1
1 in.
2in.
6 in.
12 in.
24 in.
96 in.
25.4mm
50.Smm
152.4 mm
304.8mrn
304.Smrn
609.6mm
2.44m
A2.1 Introduction
1l
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the
tbe latest information.
E84-01
APPENDIXES
(Nonmandatory Information)
Xl. GUIDE TO MOUNTING METHODS
Xl.! Introduction
X1.1.1 Discussion:
X1.1.l.l This guide has been compiled as an aid in selecting
a method for mounting various building materials in the fire
test chamber. These mountings are suggested for test method
uniformity and convenience; they are not meant to imply
restriction in the specific details of field installation.
X1.1.1.2 For some building materials none of the methods
described may be applicable. In such cases, other means of
support may have to be devised.
X1.1.1.3 These suggested mounting methods are grouped
according to building materials to be tested whicb are broadly
described either by usage or by form of the material.
X1.1.2 Support Pieces:
X1.1.2.1 Whenever inorganic reinforced cement board is
specified as a backing in this appendix, the material shall be
nominal ';." (6.3 mm) thick, higb density (110 5 Ib/ft') and
uncoated.
X1.1.2.2 Whenever metal rods or bars are specified in this
appendix as supports they should be:
(a) The rods or bars should span the width of the tunnel.
Rods should be placed approximately 2 in. (51 mm) from eacb
end of each panel and at approxinlately 2-ft (0.6-m) intervals
starting with the fire end of each panel.
(b) Bars are used instead of rods ouly when they are required
to support the sample. The bars should be placed approximately 2 in. (51 rum) from eacb end of eacb panel and at
approxinlately 2-ft (0.6-m) intervals starting with the fire end
of each panel.
X1.1.2.3 Whenever netting is specified as a support in this
appendix, the material shall be 20-gage, 2-in. (51-mm) hexagonal galvanized steel netting conforming to Specification
A 390.
Xl.1.3
X1.1.3 Joints:
Xl.1.3.1 Products that are normally installed adjoining
X1.1.3.1
themselves longitudinally are evaluated under this paragraph.
(a) Mounting methods should be considered for building
products that normally incorporate joint details either in design
Nom ina r T'. 2"{2.0._ 4.1 em)
Woo d turring
fUrring s.trrps~
S.triPS:~
-,12"
<1m
.....L-
X1.3 Adhesives
X1.3.l To determine the surface bmuing cbaracteristics of
X1.3.1
adhesives, they shall be mixed as specified in the manufacturer's instructions and shall be applied to inorganic reinforced
cement board in the thickness or at the coverage rate recommended by the manufacturer. The adhesive application shall be
cured prior to testing.
Xl.4 Batt or Blanket-Type Insulating Materials
XI.4.! Batt or blaoket
blanket materials that do not have sufficient
rigidity or strength to support themselves shall be supported by
metal rods inserted through the material and positioned such
~corrl.lgated
,;,;.
1t--4'2"~1.21m
!t--4'2"~1.21m ~
12"i-'t2."~- 3.U m
12'-'-'12."--
O.5m
1.-1
-,.21mj
",.
1_ ",,,-,.21mj
Required
2 Requ'ired
FIG. X1.1 Wood Frame for Acoustical Materials and Other Similar Panel Products Less Than 20 in. (508 mm)
12
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact AS'I'lVI International (www.astm.org) for the latest information.
ES4-01
Xl. 7 Plastics
Xl. 7.1 The term plastics includes foams, reinforced panels,
laminates, grids, and transparent or translucent sheets.
The use of galvanized steel screening nonnally lowers the flame spread index
values obtained for some materials that are tested in this manner and, therefore, the
Iesults do not necessarily relate directly to values obtahted for other materials
mounted without galvanized steel screening.
13
I"
1"
J" SI
I"
191;."
Bars5
YI&
117;!lI.
7;! It 19'2l1.
2 It ,...
1& SteelI B
3.8 ~ ~9.5 It
lI. 0.5 em
20"
D.5m
"
l . _.
_.
"
Screening
S,,""og
I'"
1+--(:'l~{-1.2'm~I<--'I'I'"
/2"
8:'3 1'2"
~--.I~,.
1.2Im
:1
2.51 m
3 ReqUired
13
(I.6om)
!i.1om)
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
<4It E 84 -01
inorganic reinforcedcement board aod rolled using a 100lb
(45.4.kg) roller (nominal 5in. (127nrm) diameter, three 5in.
long sections placed end to end for a total length of 15 in. (381
nrm). The prepared samples can be dead stacked overnight but
Xl.1 Introduction
550
FSI=-I-~KA
where:
K
AT
If AT
550
55
K X 97.5. and
550
K ~
550
K
10
X 97.5
0.564
10 x
97.5 ~ 0.564
(X2.J)
GbYI9.5byOR) + GbY19.5bY(IO-AlJ)
195 - 9.75Al
't:J
W
w 19.5
Ci
A"
0
<t
W
0::
a..
rn
w
A'
:a
<t
-'
I.L
-'
<t
:::l
t-
(X2.4)
X2.3.1 In the idealized straightline flame spread distancetime curve of Fig. X2.2, lines OJ, 01', and 01' produce a
family of trapezoidal areas ORBI ranging from 97.5 to 195
ftmin (VZ by 10 min by 19.5 ft to 10 min by 19.5 ft). This
o0
<t
(X2.3)
550
FSJ ~ 100
(Xl.2)
TIME,t,MINUTES
FIG. X2.1 Idealized Straight-Line Flame Spread Distance-Time Curve for Total Areas Less than or Equal to 97.5 mlnft
14
(X2.5)
(X2.6)
NOTICE: This standard has either been superceded and repL'lced by a new vel'sian or discontinued.
Contne! ASTM International (www.astm.org) for the latest information
-w
E84-01
-'
"
19.5
W
u
z
~
m
i5
0
a:
0-
m
w
::;:
....J
u..
....J
;:)
TIME, t, MINUTES
<l
FIG. X2.2ldealized Straight-Line Flame Spread Distance-Time Curve for Total Areas Greater than 97.5 rnlnft
X2.3.2 The triangular area OIA divided into a proportionality constant K will determine a relationship between flame
K,
FSI ~ 195 _ A/A> K,)
K
195
AT
where:
(X2.7)
-,- =
K
195 - AT
(X2.8)
where:
AT
t
K,
Thus:
K
FSI
= 53 = 195 141.38'
141.38> or
FSI=TI
550
K ~
550 X (53.63)
5.5
(X2.10)
4900
(X2.11)
K,
4900/(97.5 X 97.5)
0.515
(X2.12)
5363
FSI = 0.515 AT
(X2.13)
as follows:
4900
15
(X2.14)
NOTICE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM International (www.astm.org) for the latest Information
E84-01
Xl. COMMENTARY
It was during this time that red oak flooring was selected as a
X3.1 Introduction
X3.1.1 This commentary has been prepared to provide the
user of Test Method E 84 with background information,
including literahrre references, on the development and use of
this test method. It also provides the reader and user with the
basis for the methods that have been used for deriving
nwnerical flame spread indexes; an appreciation of the variability of the test; and comments on its application and
limitations for testing selected types of materials.
X3.1.2 On Nov. 28, 1942, 490 people died In a fire in the
Boston Coconut Grove Nightclub. On June 5, 1946, 61 persons
died in the La Salle Street Hotel fire. On Dec. 7, 1946, a fire in
the Winecoff Hotel in Atlanta, Ga., c1ahned the lives of 119
persons. These fires had one thing in common. In all three fues,
rapid flame spread along the surfaces of interior finish was
judged to be a major factor in the spread of fire. 1\vo had burlap
wall coverings, and the other an early type of plywood which
seriously delaminated. The fire protection authorities investigated several test methods with the objective of providing one
that could be used to regulate interior finish materials and
minimize repetition of such fires. These tests included: The
Forest Products Laboratory Fire Tube Test (now Test Method
E 69); Federal SpeciJication SS A1l8b (acoustical tilelbunseo
bl101er test) (replaced by SS-A-1l8a-7/63-referencing Test
Method E 84); New York City Timber Test and Shavings Test
(now obsolete); Crib Test-SpeciJication C 160 - 41 T (now
Test Method E 160); and The Swedish Schlyter Test. (1)14 All
of these were relatively small laboratory tests. Test Method
E 84 was developed on the prentise that a large test would
provide a more realistic and comprehensive test, and it has
since been widely adopted for use by the building code
authorities to regulate the use of interior finish materials.
Subsequently during this same period, two other test methods
were developed for use in research and development of new
materials, the NBS Radiant Panel (Test MethodE 162) and the
FPL 8-ft tunnel (Test Method E 286). These test methods have
been widely used for research and development purposes.
16
NOTICE: This standard has either been superceded and replaced by a new vel'sion or discontinued.
E84-01
tunnel in 5.5 :!: 0.25 min, for a specimen of red oak flooring.
Tests are run with an inorganic reinforced cement board (ACB)
specimen to establish the distance of the exposing flame at 4.5
ft. It sbould be noted that the calibration specifies ouly the time
at which the flame passes over the end of the specimen. The
FSI depends on the area under the flame spread versns the time
cw:ve. Therefore, theFSI of red oak is no longer exactly 100 as
originally specified.
X3.4.3 Recogoition of the importance oftnrbulence, including the role of fire bricks and of window recesses, resulted in
a revision in the method in 1976 (see 3.1 and section 3.3 ).
it is based, does not provide a valid measure of fuel distribution. Therefore, although the data are recorded during the test,
this information is no longer normally reported.
composed of tunnel operators is now working on comprehensive design and on operational and procedural revisions to
volatile generation characteristic of the materials under evaluation resulting in a moving, wind-aided flame front.
X3.6.1.2 It involves a large specimen, nominally 36 ft' (3.25
m2 ) of exposed area, allowing for realistic fire involvement of
material surfaces and the development of physical and structnral failures (collapse, buckling, large roptnres or cracks, etc.)
that may influence flannnability performance during the test
period.
X3.6.1.3 It may be applied to a wide range of materials,
X3.6.1.5 It does characterize most ldgh-flame spread materials identified as haviog been involved in rapidly developing
field fires (for example, ldghly combustile coatiogs on wood
products, certain cellulosic acoustical materials, insulation
as a calibratiog material.
X3.4.2 The operatiog conditions of the tunnel are adjusted if
necessary to ensure that the flame spreads to the end of the
17
NOTI.CE: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASTM International (w\\w.astm.org) for the latest information.
E84-01
X3. 7.7 Some materials, such as cellular plastics, and thermoplastic and tbermosetting materials, may be difficult to
evaluate. Thermoplastic and thermosetting materials not mecbanica1iy fastened will often fali to tbe fioor of tbe tunnel and
also usually receive relatively low FSr (10). If supported 00
wire screen, rods or other supports, these materials may be
completely engulfed io fiarue, and a questionable comparison
is beiog made between tbe surface fiarue-spread of nomioal
I-in. (0.039-mm) thick red oak witb tbe burniog rate oftbese
materials. Where the entire specimen is consumed, as compared to the surface burning of red oak, much more oxygen is
used and higher smoke developed iodexes are usua1iy obtaioed
for these materials.
X3.7.8 The materials described above, tbat is, tbose !bat
drip, melt, delaminate, draw away from the fire, or require
artificial support present unique problems and require careful
interpretation of the test results. Some of these materials that
are assigned a low FSI based on this method may exhibit an
increasing propensity for generating flame-over conditions
during room fire test with increasing area of exposure of the
material and increasing intensity of the fire exposwe. The
result, therefore, may not be indicative of their performance if
evaluated under large-scale test procedures. Alternative means
of testing may be necessary to fully evaluate some of these
materials.
X3.7.9 In order to provide needed technical data, fiammability evaluations of cellular plastics for building construction
nsiog tbe Steiner twmel began with tbe testing and classification of a flame-retardant fonnulation of polystyrene foam
board in 1960, witb subsequent evaluation of po1yuretbanetype boards incmporating fiame-retardant resin systems (first
geoeration) beginoing io 1964, polymericaliy and chemicaliy
modified fiame retardant polyuretbane type formulations (second genenation) in 1965, polyisocyanurate-type foams initiated
io 1968 and, most recently, urea-formaldehyde type, cavity-fiJi
foams. Spray-applied and poured-io-place celiular foam systems were first subjected to tbe test io 1968 and 1972,
respectively.
X3.7.10 From 1960 through 1973, io excess of 2000 tunnel
tests have been conducted on flame retardant and generalpurpose polystyrene, polyurethane, polyisocyanurate and ureafOlmaidehyde cellular plastics, io board-stock, spray-applied or
pour-io-place forms, yielding fiarue spread values rangiog from
less !ban 5 to over 2000. See Ref (11) for full report on one test
series.
X3. 7.11 The fiarue spread index of some materials may vary
depending upon environmental conditions. The prescribed
limits on the temperature and relative humidity for specimen
conditioning aod tunnel air supply (both 73.4 5'F, 50 5 %
relative hwnidity) were selected to minimize these effects.
NOllC!!:: This standard has either been superceded and replaced by a new version or discontinued.
Contact ASThl !nt.mution,,1 (www,astm.org) for the latest information.
<0 E84...,01
Methods E 84, E 162, E 286, the "2-ft tunnel test," the "comer
test" (12) and other tests.
REFERENCES
and Evaluation, Vol 3, No.1, ASTM, 1975.
(S) Williamson, R B. and Baron, F. M., "A Comer Test to Simulate
Residential Fires," Journal of Fire and Flammability, Vol 4, April
1973, pp. 99-105.
(9) Waterman, T. E., "Relation of the Building Occupancy and Design to
Use of Combustible Materials on Construction," llTRI Report, Society
of Plastics Industry, Inc., llT Research Institute, Chicago, IL, October
1968.
(10) D'Souza, M. V. and McGuire, G. H., "ASTME84 and the Flammability of Thermosetting Plastics," Fire Technology, Vol 13, No.2,
May 1977, pp. 83-94.
(11) Underwriters Laboratories, Inc., Flammability Studies of Cellular
ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned
in this standard. Users of this standard are expressly advised that delenninatlon 0( the validity of any such patent rights, and the risk
of infringement of such rights, are entirely their o~ responsibilily.
This standard is subject to revision at any time by the responsIble technical committee and must be reviewed eve/)' five years and
if not revised, either reapproved or wfthdralMl. Your comments are Invited either for revision 0( this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments wifl receive careful consideration at a meeting of the
responsible technical committee, whlch you may attend. If you feel that your comments have not received a faIr hearing you should
make your viel.-1r'S knOIMl to the ASTM Committee on standards, at the address shO\M1 below.