12796 Federal Register / Vol. 73, No.

47 / Monday, March 10, 2008 / Notices

Federal Transit Administration appear to be related to either the stress 5. Remind the public to contact the
published a notice regarding the of snow and ice or malfunction of gas company or designated emergency
National Rural Transportation pressure control equipment due to ice response officials if there is an odor of
Assistance Program Request for blockage of pressure control equipment gas present or if gas appliances are not
Proposals (RFP). The DATES and vents. Exposed piping at metering and functioning properly. Also remind the
Instruction sections of this notice pressure regulating stations, at service public that, if there is a gas or propane
should be corrected to read as follows: regulators, and at propane tanks, are at odor, occupants should leave the
DATES: Proposals must be submitted greatest risk. Damage may result from residence immediately and contact their
electronically by April 11, 2008. the stresses imposed by the additional gas company, propane operator or
loading of the snow or ice. Damage to designated emergency response
VII. Instructions facilities may also result from the officials.
2. Proposals must be received no later impact of snow or ice falling from roofs, Authority: 49 U.S.C. chapter 601; 49 CFR
than 5:30 p.m., EST, April 11, 2008. or ice forming in or on regulators 1.53.
Effective Date: This correction takes preventing their proper operation, or
Issued in Washington, DC on March 5,
effect on February 26, 2008. shoveling snow from roofs to protect 2008.
FOR FURTHER INFORMATION CONTACT: dwellings from abnormal snow
Jeffrey D. Wiese,
Pamela Brown at 202–493–2503, Fax: accumulation.
Associate Administrator for Pipeline Safety.
202–366–7951, or via e-mail: II. Advisory Bulletin (ADB–08–03) [FR Doc. 08–999 Filed 3–6–08; 2:18 pm]
Pamela.Brown@dot.gov, or Lorna
Wilson at 202–366–2053; or via e-mail To: Owners and Operators of BILLING CODE 4910–60–P

lorna.wilson@dot.gov. Petroleum Gas and Natural Gas


Facilities in Areas Subject to Heavy
Issued in Washington, DC this 4th day of Snowfall or Abnormally Icy Weather. DEPARTMENT OF TRANSPORTATION
March, 2008. Subject: Dangers of Abnormal Snow
James S. Simpson, and Ice Build-up on Gas Distribution Surface Transportation Board
Administrator. Systems. [STB Docket No. AB–398 (Sub-No. 7X)]
[FR Doc. E8–4721 Filed 3–7–08; 8:45 am] Purpose: To inform owners and
BILLING CODE 4910–57–P operators of the need (1) to monitor the San Joaquin Valley Railroad
potential impact of excessive snow and Company—Abandonment Exemption—
ice on these facilities; and (2) to inform in Tulare County, CA
DEPARTMENT OF TRANSPORTATION the public about possible hazards from
snow and ice accumulation on On February 19, 2008, San Joaquin
Pipeline and Hazardous Materials regulators and other pipeline facilities. Valley Railroad Company (SJVR) filed
Safety Administration Advisory: PHMSA is advising with the Board a petition under 49
operators of gas pipeline facilities, U.S.C. 10502 for exemption from the
[Docket No. PHMSA–RSPA–2004–19856]
regardless of whether those facilities are provisions of 49 U.S.C. 10903 to
Pipeline Safety: Dangers of Abnormal regulated by PHMSA or state agencies, abandon a 30.57-mile portion of the
Snow and Ice Build-Up on Gas to consider the following steps to South Exeter Branch between milepost
Distribution Systems address the safety risks from 268.60 at Strathmore, CA, and milepost
accumulated snow and ice on pipeline 299.17 at Jovista, CA, in Tulare County,
AGENCY: Pipeline and Hazardous facilities: CA. The line traverses United States
Materials Safety Administration 1. Notify customers and other entities Postal Service Zip Codes 93218, 93221,
(PHMSA), DOT. of the need for caution associated with 93247, 93257, 93258, 93261, 93267, and
ACTION: Notice; Issuance of Advisory excessive accumulation and removal of 93270, and includes the stations of
Bulletin. snow and ice. Notice should include the Strathmore (milepost 268.60),
need to clear snow and ice from exhaust Porterville (milepost 274.80), Elmco
SUMMARY: Recent events on natural gas (milepost 280.10), Ultra (milepost
and combustion air vents for gas
distribution system facilities appear to appliances to prevent accumulation of 282.00), Terra Bella (milepost 282.60),
be related to either the stress of snow carbon monoxide in buildings or Ducor (milepost 287.10), Richgrove
and ice or malfunction of pressure operational problems for the (milepost 294.90), and Jovista (milepost
control equipment due to ice blockage combustion equipment. 299.17).
of pressure control equipment vents by 2. Pay attention to snow and ice The line does not contain federally
ice. This advisory bulletin advises related situations that may cause granted rights-of-way. Any
owners and operators of gas pipelines of operational problems for pressure documentation in SJVR’s possession
the need to take steps to prevent damage control and other equipment. will be made available promptly to
to pipeline facilities from accumulated 3. Monitor the accumulation of those requesting it.
snow or ice. moisture in equipment and snow or ice The interest of railroad employees
FOR FURTHER INFORMATION CONTACT: blocking regulator or relief valve vents will be protected by the conditions set
Alan Mayberry at (202) 366–5124, or by which could prevent regulators and forth in Oregon Short Line R. Co.—
e-mail at alan.mayberry@dot.gov. relief valves from functioning properly. Abandonment—Goshen, 360 I.C.C. 91
SUPPLEMENTARY INFORMATION: 4. The piping on service regulator sets (1979).
is susceptible to damage that could SJVR states that the proposed
I. Background result in failure if caution is not abandonment may generate comments
The accumulation of snow and ice exercised in cleaning snow from around or replies, and it requests that the Board
pwalker on PROD1PC71 with NOTICES

increases the potential for damage to the equipment. Where possible, use a adopt a procedural schedule in this
meters and regulators and other pipeline broom, instead of a shovel to clear snow proceeding to permit SJVR to file
facilities. Several accidents occurring off regulators, meters, associated piping, rebuttal to any comments or replies
during the winter of 2007/2008 on propane tanks, tubing, gauges or other received. Rather than address the
natural gas distribution system facilities propane system appurtenances. request at this time, however, the Board

VerDate Aug<31>2005 16:39 Mar 07, 2008 Jkt 214001 PO 00000 Frm 00095 Fmt 4703 Sfmt 4703 E:\FR\FM\10MRN1.SGM 10MRN1