PACiS System General

Presentation
PACiS Technical Training Level 1
CS&P Support Team

PCL

Content
What is a DCS?
PACiS Devices and Tools
PACiS Architectures
PACiS Station Bus
Cyber Security
PACiS System Key Concepts

Schneider Electric - CS&P - PACiS System Presentation G01

Content
What is a DCS?
PACiS Devices and Tools
PACiS Architectures
PACiS Station Bus
Cyber Security
PACiS System Key Concepts
PACiS 5 new features summary

Schneider Electric - CS&P - PACiS System Presentation G01

System Definition
System is :
a set of devices with specific functions that interact one to/with
other with common rules
HMI

BCU

To SCADA
GTW

Fast Ethernet
IEC61850

I/Os

IED

BCU

System is

BCU

Intelligent Electronic
Device (IED)

CONFIGURATION & COMMUNICATION

SBUS
TBUS

Station BUS (system federal network ...) (Ethernet / IP)


Tele control BUS (Remote Control Point or SCADA)

LBUS

Legacy BUS (Field BUS to IED)

Schneider Electric - CS&P - PACiS System Presentation G01

Main System Functions


Supervision

Control

from
Bay
Substation
SCADA

Maintenance

HMI
Flow Printing
Archives
Alarms
State/Event

Station/Bay
Sequence Of Event, Log in
with reports
Manage/audible/viewer/printing
viewer/printing

Control Mode (local/remote : Bay, Substation)


Operating Mode (run, stand-by, maintenance)
Uniqueness, InterLocK, automation running
Force - Suppress - Substitute of DP
Basic control sequence (DE, SBO)
Built-in Control (ATCC, Synchrocheck, AutoRecloser)
PSL, PLC
Time management
Databases management (download, switch, version)
Test mode, SBMC
Disturbance upload/viewing

Schneider Electric - CS&P - PACiS System Presentation G01

Content
What is a DCS?
PACiS Devices and Tools
PACiS Architectures
PACiS Station Bus
Cyber Security
PACiS System Key Concepts
PACiS 5 new features summary

Schneider Electric - CS&P - PACiS System Presentation G01

PACiS Devices Range


Visible to customer
PACiS Operator Interface / SUI
(Local / web access)
PACiS System Management Tool
(C264 / C264C)
MiCOM C264 Computer
MiCOM Ethernet Switches
(H3xx / H6xx / H1xx / SWx)
PACiS GTW (Gateway)

Hidden to customer
PACiS Agency (Station BUS)
(PACiS V4 = IEC61850)
PACiS System Configuration Editor

Schneider Electric - CS&P - PACiS System Presentation G01

PACiS Devices
HMI : SUI Substation User Interface

C264- MiCOM C264 BCU

MiCOM Ethernet Switches

GTW - PACiS Gateway


Schneider Electric - CS&P - PACiS System Presentation G01

PACiS Tools
SMT - PACiS System Management Tool
SCE - PACiS System Configuration
Editor
CAT - PACiS Computer Administration
Tool (for C264)
CGAT - PACiS Computer & GTW
Administration Tool (C264 + Gateway)
Schneider Electric - CS&P - PACiS System Presentation G01

Content
What is a DCS?
PACiS Devices and Tools
PACiS Architectures
PACiS Station Bus
Cyber Security
PACiS System Key Concepts
PACiS 5 new features summary

Schneider Electric - CS&P - PACiS System Presentation G01

10

Principle System Architecture


Up to 8 PACiS
OI/SUI Clients

PACiS OI or SUI Server +


Client

1 Remote
PACiS Gateway

TBUS

Redundant Server
SBUS IEC61850
MiCOM C264

11:32:28
17/02/06

GPS
Clock

LBUS
I/O Redundancy

SBUS IED

Set of MiCOM C264


Schneider Electric - CS&P - PACiS System Presentation G01

11

Distributed Architecture Example


Applications :
HV Substations
Distribution Stations
Industry
Railway
Oil & Gas

PACiS OI Twin Server or


Hot Redundancy (V4.6.x)
SOE printing
Data reports

MiCOM C264 Redundancy


Internal Synchrocheck
Auto Recloser
IED Management
Advanced automation

PACiS Gateway
Serial SCADA communication
Ethernet SCADA communication

Schneider Electric - CS&P - PACiS System Presentation G01

12

MiCOM Computer Stand-Alone Example


Up to 4 Serial Links (RS 485/232) for SCADA & IED interface
C264C
2 x DIU200
1

2 3

IEC-60870-5-101

3xModbus
RS485

11HKL

12HKL

Regional center

RS232

ION7330

ION7330

WAGO
Vesuvius

13HKL

14HKL

ION7330

21HKL

ION7330

22HKL

WAGO

23HKL

ION7330

ION7330

Etna
WAGO
Ketelhuis

Schneider Electric - CS&P - PACiS System Presentation G01

13

PACIS GTW Multiple use cases


PACiS HMI

DCS interface

PACiS HMI

SCADA
GATEWAYS

PACiS HMI

Ring A
IEC61850

GATEWAY
IEC/IEC

FLS
GTW

FLS ring
IEC61850

Ring B
IEC61850
GATEWAY
Data Concentr.

FLS HMI

C264
C264s - Feeders

LV

Schneider Electric - CS&P - PACiS System Presentation G01

14

Content
What is a DCS?
PACiS Devices and Tools
PACiS Architectures
PACiS Station Bus
Cyber Security
PACiS System Key Concepts
PACiS 5 new features summary

Schneider Electric - CS&P - PACiS System Presentation G01

15

Station BUS : Definition


SBUS
Station BUS
(integrate all system devices)
Except PACiS SCE for configuration

Use a Communication Agency


Common Application Program. Interface
to all system device

Schneider Electric - CS&P - PACiS System Presentation G01

16

Station BUS : Overview


Network: Ethernet
Standard 10/100 Mbps, Copper Tx, Optic Fx
EMC Electric Plant
Public : RuggedCom, Belden-Hirshmann
AREVA Specific : Immunity, Power Supply
Star/Tree
=> MiCOM H34x, SWU20x
Redundancy
=> MiCOM H35x, SWR20x, SWR21x
Dual Homing
=> MiCOM H36x, SWD20x, SWD21x
Dual Ring + Dual Star
=> MiCOM H356 & H362, SWD21x
RSTP - Compatible
=> MiCOM H17x, SWS21x
PRP - Compatible
=> MiCOM H18, REU board for C264
Protocol: IEC61850 Client/Server
Standard/Open
N Clients & M Servers
Optimized traffic
Fast Communication

Schneider Electric - CS&P - PACiS System Presentation G01

17

Station BUS : Client/Server Mechanism


(1)
Protocol: IEC61850
SERVERS

Client/Server
These are all
my data

HMI OI or SUI
Server

MiCOM C264

SBUS IED

CLIENTS

I subscribe to
these data

I report the change of


state of these data
you subscribed

PACiS
Gateway
MiCOM C264
(TBUS)

OPTIMIZED TRAFFIC
Schneider Electric - CS&P - PACiS System Presentation G01

18

Station BUS : Client/Server Mechanism


(2)
Protocol: IEC61850

Client/Server

SERVER
Send Reports (RP)
Receive Controls
Send Control Acknowledgements

CLIENT
Receive Reports (RP)
Send Controls
Receive Control Acknowledgements

Send GOOSE (fast message for


shared automation)

Schneider Electric - CS&P - PACiS System Presentation G01

19

Station BUS : Network devices (1)


Ethernet Switch: Actual Range
Reference

Description

SWU 200
SWU 202/ 204
SWR 212/ 214
SWD 212/ 214
SWS 212/ 214
MICOM H 140
MICOM H 152/ 154/ 156/ 158
MICOM H 162/ 164/ 166/ 168
MICOM H 172/ 174/ 176/ 178
MICOM H 340
MICOM H341/ 343
MICOM H 342/ 344
MICOM H 352/ 354
MICOM H 356/ 358

Switch simple copper


Switch simple (multi/ mono)
Switch Redundant (multi/ mono)
Switch Dual Homing (multi/ mono)
Switch RSTP compatible (multi/ mono)
Switch simple Copper
Switch Redundant (multi/ mono/ LC)
Switch Dual Homing (multi/ mono/ LC)
Switch RSTP compatible (multi/ mono/ LC)
Switch simple Copper
Switch simple (multi/ mono)
Switch simple (multi/ mono)
Switch Redundant (multi/ mono ST)
Switch dual Ring / dual Star (multi/ mono
LC )
Switch Dual Homing (multi/ mono ST)
Optical Star with
1 to 4 of following board
V2 double switch (multi/ mono)
V3 (multi/ mono)

MICOM H 362/ 364


MICOM H 60x
MICOM H 621/ 623
MICOM H 631/ 633

Ethernet
Tx
Fx
4
0
4
2
4
2
4
2
4
2
6
0
4
2
4
2
4
2
6
0
6
1
6
2
6
2
2
2+
4
6
2

2*4
2

Device
Cx6x board
Cx6x board
Cx6x board
Cx6x board
Cx6x board
PCI board
PCI board
PCI board
PCI board
DIN Rack
DIN Rack
DIN Rack
DIN Rack
DIN Rack
DIN Rack
19 Rack

2*1
6

New in 2013 : compatible PRP


C264 board = REU (ex SWP)
PCi board = MICOM H18
Schneider Electric - CS&P - PACiS System Presentation G01

20

Station BUS : Network devices (2)

Example : MiCOM H352

Schneider Electric - CS&P - PACiS System Presentation G01

21

Station BUS : Topology


Star / Tree
SWU20x / H34x

Redundant Ring
SWR20x or
SWR21x / H35x

Dual Homing
SWD20x or SWD21x /
H36x + H63x

Schneider Electric - CS&P - PACiS System Presentation G01

Dual Ring + Dual Star


SWD202 / H362
+ H356

22

Station BUS : PRP Integration


PRP on C264
PRP on PCi board
SAN
SAN

SAN
DAN
VDAN
RedBox

: Single Attached Node


: Dual Attached Node
: Virtual Dual Attached Node
: Redundancy Box

C264
with
REU
Schneider Electric - CS&P - PACiS System Presentation G01

PC SUI
with
H18

C264
with
REU
23

Content
What is a DCS?
PACiS Devices and Tools
PACiS Architectures
PACiS Station Bus
Cyber Security
PACiS System Key Concepts
PACiS 5 new features summary

Schneider Electric - CS&P - PACiS System Presentation G01

24

Cyber Security
4 levels of password
Hardening (disabling unused logical/physical ports)
Account management (log off, nb of tentatives)
Security logs
Antivirus (AVIRA Antivir v10)
White-Listing (Savant Protection)
Banner/Disclaimer

Schneider Electric - CS&P - PACiS System Presentation G01

25

Content
What is a DCS?
PACiS Devices and Tools
PACiS Architectures
PACiS Station Bus
Cyber Security
PACiS System Key Concepts
PACiS 5 new features summary

Schneider Electric - CS&P - PACiS System Presentation G01

26

Key Concepts
System is

Communication
Configuration

PACiS Devices & Softwares


SUI, SMT, CAT
MiCOM C264, MiCOM Switches, PACiS Gateway
SBUS Agency, PACiS SCE
PACiS Architectures
Distributed
Computer Stand alone RTU
Ethernet Architectures
Star - Tree
Ring
Dual Homing
Dual Ring + Dual Star
Networks

SBUS
TBUS
LBUS

Station BUS
TeleControl BUS
Legacy BUS

Schneider Electric - CS&P - PACiS System Presentation G01

Copper
Optical

Client/Server protocol (61850)


T101, T104, DNP3, ModBus,
ModBus, T103, T101, DNP3
27

Content
What is a DCS?
PACiS Devices and Tools
PACiS Architectures
PACiS Station Bus
Cyber Security
PACiS System Key Concepts
PACiS 5 new features summary

Schneider Electric - CS&P - PACiS System Presentation G01

28

PACiS 5 New features (1)


SUI = New SCADA / HMI, for demanding Utilities, Large
industrial sites

Cyber security : NERC compliance , Anti-Virus


Zooming, cluttering / decluttering
New Graphical objects : XY curves, Advanced reports
Multi Clustering architecture: to split the CPU load
Alarms : External klaxon management
Archiver : available on a separate PC

Windows 7, Windows server 2008


Localization with multiple languages
Compatible with extended FLS (Fast Load Shedding)

Schneider Electric - CS&P - PACiS System Presentation G01

29

PACiS 5 New features (2)


NEW GATEWAY = with extended capabilities
GTW IEC/IEC : Coupling IEC61850 networks -> Flexible
architectures
GTW IEC/IEC : Goose transfer, with filtering
GTW Data concentrator (HV, MV and LV devices):
IEDs Protocols (ModBus TCP and serial), IEC101, DNP3/IP
up to 16 serial links (up to 200 IEDs)
GTW to Remote Control Center : up to 6 Scada links
Hot redundancy -> availability
IEDs in daisy chain connection with network Split -> availability
Simulator of Legacy IEDs : HELPS
IED

RCP networks

IED

IED

IEC61850 Station bus

GTW
Field bus networks

IED

IED

IED

IED

IED

IED

IED

IED

IED

IED

IED

IED

IED

IED

IED

IED

IED

IED

New rugged Hw Plate-form : MiCOM G9xx


IEC61850-3 (environment and EMC) certified
19 rackable, no rotating parts
O.S. update : Windows 7 and Real Time OS= RTX on MiCOM G
WES2009 on A300
Cyber-security : White Listing

Schneider Electric - CS&P - PACiS System Presentation G01

30

PACiS 5 New features (3)


Companion facilities
Redundant ETHERNET Architectures
IEC62439 PRP Redundant Protocol : embedded in PCs (H18x), in
MiCOMC264, MiCOM Px40
Third party Ethernet switches with IEC62439- PRP
RSTP compatibility (Rapid Spanning Tree Protocol) industry

INTEGRATED IEDs
Meters : ION7650 over IEC61850
SEPAM 40,60,80 series

PSE Power Scada Expert companion HMI for PACIS basic


solutions
Fast Load Shedding for large Installations
Extended FLS for up to 3000 loads, 60ms
Load Restore

C264 New hardware


New BIU261 Dual Source Power Supply
New 60TE racks with 9 Slots (to extend current range 40T & 80T )

TVDA RTU based : HV-MV, MV/MV simple solution based on


C264 RTU