(24) AC-1-V1-GF-Livi/Dining Input Data

Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)


Prepared by: reyami

08/05/2015
09:02AM

1. General Details:
Air System Name ............................................... (24) AC-1-V1-GF-Livi/Dining
Equipment Type ............................................................................. Split AHU
Air System Type ................................................................. Single Zone CAV
Number of zones ........................................................................................... 1
2. System Components:
Ventilation Air Data:
Airflow Control .................................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Unocc. Damper Position ...................................................................... Closed
Damper Leak Rate ........................................................................................ 0 %
Outdoor Air CO2 Level .............................................................................. 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................ 52.0 F
Coil Bypass Factor ................................................................................. 0.100
Cooling Source ........................................................................ Air-Cooled DX
Schedule ............................................................................ JFMAMJJASOND
Capacity Control .................................. Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type .............................................................................. Forward Curved
Configuration .................................................................................. Draw-thru
Fan Performance ...................................................................................... 0.00 in wg
Overall Efficiency ......................................................................................... 54 %
Fan Control ............................................... 1-speed fan, cooling and heating
Duct System Data:
Supply Duct Data:
Duct Heat Gain .............................................................................................. 0 %
Duct Leakage ................................................................................................ 0 %
Return Duct or Plenum Data:
Return Air Via ................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 0 %
Roof Heat Gain to Plenum ........................................................................... 70 %
Lighting Heat Gain to Plenum ...................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
V1M-GF-Livi/Dining

x1

Thermostats and Zone Data:


Zone ........................................................................................................... All
Cooling T-stat: Occ. .................................................................................. 74.0
Cooling T-stat: Unocc. .............................................................................. 80.0
Heating T-stat: Occ. .................................................................................. 70.0
Heating T-stat: Unocc. .............................................................................. 65.0
T-stat Throttling Range ............................................................................. 1.50
Diversity Factor ......................................................................................... 100
Direct Exhaust Airflow ................................................................................. 0.0
Direct Exhaust Fan kW ............................................................................... 0.0

F
F
F
F
F
%
CFM
kW

Thermostat Schedule ................................................................................... th


Unoccupied Cooling is ..................................................................... Available
Supply Terminals Data:
Zone ........................................................................................................... All
Terminal Type ................................................................................... Diffuser
Minimum Airflow ....................................................................................... 0.00 CFM/person
Zone Heating Units:
Zone ........................................................................................................... All
Zone Heating Unit Type .......................................................................... None
Zone Unit Heat Source ................................................... Electric Resistance
Zone Heating Unit Schedule ............................................... JFMAMJJASOND

Hourly Analysis Program v4.61

Page 1 of 16

(24) AC-1-V1-GF-Livi/Dining Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature .................................................................... 52.0 F
Supply Fan Airflow .................................................................................. 850.5 CFM
Ventilation Airflow ....................................................................................... 0.0 CFM
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................... 10.0 F
Hot Water Delta-T ..................................................................................... 20.0 F
Safety Factors:
Cooling Sensible .......................................................................................... 10 %
Cooling Latent ............................................................................................... 5 %
Heating .......................................................................................................... 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................ Sum of space airflow rates
Space Airflow Sizing Method ............................ Individual peak space loads

Zone

Supply Airflow
(CFM)

850.5

Zone Htg Unit


(MBH)

Reheat Coil
(MBH)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ........................................................................ 22.9
Design OAT ............................................................................................ 115.0
Equipment Sizing .......................................................................... Auto-Sized
Capacity Oversizing Factor ............................................................................ 0
ARI Performance Rating ....................................................................... 11.000
DX System Configuration ............................. 1-stage compression, 1 circuit
Conventional Cutoff OAT .......................................................................... 55.0
Low Temperature Operation ................................................................... Used
Low Temperature Cutoff OAT ..................................................................... 0.0

Hourly Analysis Program v4.61

(CFM)

MBH
F
%
EER
F
F

Page 2 of 16

(25) AC-2-V1-GF-Kitchen Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

1. General Details:
Air System Name .................................................... (25) AC-2-V1-GF-Kitchen
Equipment Type ............................................................................. Split AHU
Air System Type ................................................................. Single Zone CAV
Number of zones ........................................................................................... 1
2. System Components:
Ventilation Air Data:
Airflow Control .................................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Unocc. Damper Position ...................................................................... Closed
Damper Leak Rate ........................................................................................ 0 %
Outdoor Air CO2 Level .............................................................................. 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................ 52.0 F
Coil Bypass Factor ................................................................................. 0.100
Cooling Source ........................................................................ Air-Cooled DX
Schedule ............................................................................ JFMAMJJASOND
Capacity Control .................................. Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type .............................................................................. Forward Curved
Configuration .................................................................................. Draw-thru
Fan Performance ...................................................................................... 0.00 in wg
Overall Efficiency ......................................................................................... 54 %
Fan Control ............................................... 1-speed fan, cooling and heating
Duct System Data:
Supply Duct Data:
Duct Heat Gain .............................................................................................. 0 %
Duct Leakage ................................................................................................ 0 %
Return Duct or Plenum Data:
Return Air Via ................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 0 %
Roof Heat Gain to Plenum ........................................................................... 70 %
Lighting Heat Gain to Plenum ...................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
V1M-GF-Kitchen

x1

Thermostats and Zone Data:


Zone ........................................................................................................... All
Cooling T-stat: Occ. .................................................................................. 75.0
Cooling T-stat: Unocc. .............................................................................. 80.0
Heating T-stat: Occ. .................................................................................. 70.0
Heating T-stat: Unocc. .............................................................................. 65.0
T-stat Throttling Range ............................................................................. 1.50
Diversity Factor ......................................................................................... 100
Direct Exhaust Airflow ................................................................................. 0.0
Direct Exhaust Fan kW ............................................................................... 0.0

F
F
F
F
F
%
CFM
kW

Thermostat Schedule ................................................................................... th


Unoccupied Cooling is ..................................................................... Available
Supply Terminals Data:
Zone ........................................................................................................... All
Terminal Type ................................................................................... Diffuser
Minimum Airflow ....................................................................................... 0.00 CFM/person
Zone Heating Units:
Zone ........................................................................................................... All
Zone Heating Unit Type .......................................................................... None
Zone Unit Heat Source ................................................... Electric Resistance
Zone Heating Unit Schedule ............................................... JFMAMJJASOND

Hourly Analysis Program v4.61

Page 3 of 16

(25) AC-2-V1-GF-Kitchen Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature .................................................................... 52.0 F
Supply Fan Airflow .................................................................................. 469.4 CFM
Ventilation Airflow ....................................................................................... 0.0 CFM
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................... 10.0 F
Hot Water Delta-T ..................................................................................... 20.0 F
Safety Factors:
Cooling Sensible .......................................................................................... 10 %
Cooling Latent ............................................................................................... 5 %
Heating .......................................................................................................... 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................ Sum of space airflow rates
Space Airflow Sizing Method ............................ Individual peak space loads

Zone

Supply Airflow
(CFM)

469.4

Zone Htg Unit


(MBH)

Reheat Coil
(MBH)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ........................................................................ 18.0
Design OAT ............................................................................................ 115.0
Equipment Sizing .......................................................................... Auto-Sized
Capacity Oversizing Factor ............................................................................ 0
ARI Performance Rating ....................................................................... 11.000
DX System Configuration ............................. 1-stage compression, 1 circuit
Conventional Cutoff OAT .......................................................................... 55.0
Low Temperature Operation ................................................................... Used
Low Temperature Cutoff OAT ..................................................................... 0.0

Hourly Analysis Program v4.61

(CFM)

MBH
F
%
EER
F
F

Page 4 of 16

(26) AC-3-V1-GF-Majlis+corr Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

1. General Details:
Air System Name .............................................. (26) AC-3-V1-GF-Majlis+corr
Equipment Type ............................................................................. Split AHU
Air System Type ................................................................. Single Zone CAV
Number of zones ........................................................................................... 1
2. System Components:
Ventilation Air Data:
Airflow Control .................................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Unocc. Damper Position ...................................................................... Closed
Damper Leak Rate ........................................................................................ 0 %
Outdoor Air CO2 Level .............................................................................. 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................ 55.0 F
Coil Bypass Factor ................................................................................. 0.100
Cooling Source ........................................................................ Air-Cooled DX
Schedule ............................................................................ JFMAMJJASOND
Capacity Control .................................. Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type .............................................................................. Forward Curved
Configuration .................................................................................. Draw-thru
Fan Performance ...................................................................................... 0.00 in wg
Overall Efficiency ......................................................................................... 54 %
Fan Control ............................................... 1-speed fan, cooling and heating
Duct System Data:
Supply Duct Data:
Duct Heat Gain .............................................................................................. 0 %
Duct Leakage ................................................................................................ 0 %
Return Duct or Plenum Data:
Return Air Via ................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 0 %
Roof Heat Gain to Plenum ........................................................................... 70 %
Lighting Heat Gain to Plenum ...................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
V1M-GF-Majlis+corr

x1

Thermostats and Zone Data:


Zone ........................................................................................................... All
Cooling T-stat: Occ. .................................................................................. 74.0
Cooling T-stat: Unocc. .............................................................................. 80.0
Heating T-stat: Occ. .................................................................................. 70.0
Heating T-stat: Unocc. .............................................................................. 65.0
T-stat Throttling Range ............................................................................. 1.50
Diversity Factor ......................................................................................... 100
Direct Exhaust Airflow ................................................................................. 0.0
Direct Exhaust Fan kW ............................................................................... 0.0

F
F
F
F
F
%
CFM
kW

Thermostat Schedule ................................................................................... th


Unoccupied Cooling is ..................................................................... Available
Supply Terminals Data:
Zone ........................................................................................................... All
Terminal Type ................................................................................... Diffuser
Minimum Airflow ....................................................................................... 0.00 CFM/person
Zone Heating Units:
Zone ........................................................................................................... All
Zone Heating Unit Type .......................................................................... None
Zone Unit Heat Source ................................................... Electric Resistance
Zone Heating Unit Schedule ............................................... JFMAMJJASOND

Hourly Analysis Program v4.61

Page 5 of 16

(26) AC-3-V1-GF-Majlis+corr Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature .................................................................... 55.0 F
Supply Fan Airflow .................................................................................. 601.1 CFM
Ventilation Airflow ....................................................................................... 0.0 CFM
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................... 10.0 F
Hot Water Delta-T ..................................................................................... 20.0 F
Safety Factors:
Cooling Sensible .......................................................................................... 10 %
Cooling Latent ............................................................................................... 5 %
Heating .......................................................................................................... 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................ Sum of space airflow rates
Space Airflow Sizing Method ............................ Individual peak space loads

Zone

Supply Airflow
(CFM)

601.1

Zone Htg Unit


(MBH)

Reheat Coil
(MBH)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ........................................................................ 16.8
Design OAT ............................................................................................ 115.0
Equipment Sizing .......................................................................... Auto-Sized
Capacity Oversizing Factor ............................................................................ 0
ARI Performance Rating ....................................................................... 11.000
DX System Configuration ............................. 1-stage compression, 1 circuit
Conventional Cutoff OAT .......................................................................... 55.0
Low Temperature Operation ................................................................... Used
Low Temperature Cutoff OAT ..................................................................... 0.0

Hourly Analysis Program v4.61

(CFM)

MBH
F
%
EER
F
F

Page 6 of 16

(27)AC-4-V1-GF-Maids rm+guest r Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

1. General Details:
Air System Name .................................... (27)AC-4-V1-GF-Maids rm+guest r
Equipment Type ............................................................................. Split AHU
Air System Type ................................................................. Single Zone CAV
Number of zones ........................................................................................... 1
2. System Components:
Ventilation Air Data:
Airflow Control .................................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Unocc. Damper Position ...................................................................... Closed
Damper Leak Rate ........................................................................................ 0 %
Outdoor Air CO2 Level .............................................................................. 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................ 55.0 F
Coil Bypass Factor ................................................................................. 0.100
Cooling Source ........................................................................ Air-Cooled DX
Schedule ............................................................................ JFMAMJJASOND
Capacity Control .................................. Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type .............................................................................. Forward Curved
Configuration .................................................................................. Draw-thru
Fan Performance ...................................................................................... 0.00 in wg
Overall Efficiency ......................................................................................... 54 %
Fan Control ............................................... 1-speed fan, cooling and heating
Duct System Data:
Supply Duct Data:
Duct Heat Gain .............................................................................................. 0 %
Duct Leakage ................................................................................................ 0 %
Return Duct or Plenum Data:
Return Air Via ................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 0 %
Roof Heat Gain to Plenum ........................................................................... 70 %
Lighting Heat Gain to Plenum ...................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
V1M-GF-Maids rm+guest rm

x1

Thermostats and Zone Data:


Zone ........................................................................................................... All
Cooling T-stat: Occ. .................................................................................. 74.0
Cooling T-stat: Unocc. .............................................................................. 80.0
Heating T-stat: Occ. .................................................................................. 70.0
Heating T-stat: Unocc. .............................................................................. 65.0
T-stat Throttling Range ............................................................................. 1.50
Diversity Factor ......................................................................................... 100
Direct Exhaust Airflow ................................................................................. 0.0
Direct Exhaust Fan kW ............................................................................... 0.0

F
F
F
F
F
%
CFM
kW

Thermostat Schedule ................................................................................... th


Unoccupied Cooling is ..................................................................... Available
Supply Terminals Data:
Zone ........................................................................................................... All
Terminal Type ................................................................................... Diffuser
Minimum Airflow ....................................................................................... 0.00 CFM/person
Zone Heating Units:
Zone ........................................................................................................... All
Zone Heating Unit Type .......................................................................... None
Zone Unit Heat Source ................................................... Electric Resistance
Zone Heating Unit Schedule ............................................... JFMAMJJASOND

Hourly Analysis Program v4.61

Page 7 of 16

(27)AC-4-V1-GF-Maids rm+guest r Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature .................................................................... 55.0 F
Supply Fan Airflow .................................................................................. 638.6 CFM
Ventilation Airflow ....................................................................................... 0.0 CFM
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................... 10.0 F
Hot Water Delta-T ..................................................................................... 20.0 F
Safety Factors:
Cooling Sensible .......................................................................................... 10 %
Cooling Latent ............................................................................................... 5 %
Heating .......................................................................................................... 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................ Sum of space airflow rates
Space Airflow Sizing Method ............................ Individual peak space loads

Zone

Supply Airflow
(CFM)

638.6

Zone Htg Unit


(MBH)

Reheat Coil
(MBH)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ........................................................................ 17.9
Design OAT ............................................................................................ 115.0
Equipment Sizing .......................................................................... Auto-Sized
Capacity Oversizing Factor ............................................................................ 0
ARI Performance Rating ....................................................................... 11.000
DX System Configuration ............................. 1-stage compression, 1 circuit
Conventional Cutoff OAT .......................................................................... 55.0
Low Temperature Operation ................................................................... Used
Low Temperature Cutoff OAT ..................................................................... 0.0

Hourly Analysis Program v4.61

(CFM)

MBH
F
%
EER
F
F

Page 8 of 16

(28) AC-5-V1-FF-Master bed rm Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

1. General Details:
Air System Name ......................................... (28) AC-5-V1-FF-Master bed rm
Equipment Type ............................................................................. Split AHU
Air System Type ................................................................. Single Zone CAV
Number of zones ........................................................................................... 1
2. System Components:
Ventilation Air Data:
Airflow Control .................................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Unocc. Damper Position ...................................................................... Closed
Damper Leak Rate ........................................................................................ 0 %
Outdoor Air CO2 Level .............................................................................. 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................ 55.0 F
Coil Bypass Factor ................................................................................. 0.100
Cooling Source ........................................................................ Air-Cooled DX
Schedule ............................................................................ JFMAMJJASOND
Capacity Control .................................. Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type .............................................................................. Forward Curved
Configuration .................................................................................. Draw-thru
Fan Performance ...................................................................................... 0.00 in wg
Overall Efficiency ......................................................................................... 54 %
Fan Control ............................................... 1-speed fan, cooling and heating
Duct System Data:
Supply Duct Data:
Duct Heat Gain .............................................................................................. 0 %
Duct Leakage ................................................................................................ 0 %
Return Duct or Plenum Data:
Return Air Via ................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 0 %
Roof Heat Gain to Plenum ........................................................................... 70 %
Lighting Heat Gain to Plenum ...................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
V1M-FF-Master bed rm

x1

Thermostats and Zone Data:


Zone ........................................................................................................... All
Cooling T-stat: Occ. .................................................................................. 74.0
Cooling T-stat: Unocc. .............................................................................. 80.0
Heating T-stat: Occ. .................................................................................. 70.0
Heating T-stat: Unocc. .............................................................................. 65.0
T-stat Throttling Range ............................................................................. 1.50
Diversity Factor ......................................................................................... 100
Direct Exhaust Airflow ................................................................................. 0.0
Direct Exhaust Fan kW ............................................................................... 0.0

F
F
F
F
F
%
CFM
kW

Thermostat Schedule ................................................................................... th


Unoccupied Cooling is ..................................................................... Available
Supply Terminals Data:
Zone ........................................................................................................... All
Terminal Type ................................................................................... Diffuser
Minimum Airflow ....................................................................................... 0.00 CFM/person
Zone Heating Units:
Zone ........................................................................................................... All
Zone Heating Unit Type .......................................................................... None
Zone Unit Heat Source ................................................... Electric Resistance
Zone Heating Unit Schedule ............................................... JFMAMJJASOND

Hourly Analysis Program v4.61

Page 9 of 16

(28) AC-5-V1-FF-Master bed rm Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature .................................................................... 55.0 F
Supply Fan Airflow .................................................................................. 586.3 CFM
Ventilation Airflow ....................................................................................... 0.0 CFM
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................... 10.0 F
Hot Water Delta-T ..................................................................................... 20.0 F
Safety Factors:
Cooling Sensible .......................................................................................... 10 %
Cooling Latent ............................................................................................... 5 %
Heating .......................................................................................................... 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................ Sum of space airflow rates
Space Airflow Sizing Method ............................ Individual peak space loads

Zone

Supply Airflow
(CFM)

586.3

Zone Htg Unit


(MBH)

Reheat Coil
(MBH)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ........................................................................ 15.9
Design OAT ............................................................................................ 115.0
Equipment Sizing .......................................................................... Auto-Sized
Capacity Oversizing Factor ............................................................................ 0
ARI Performance Rating ....................................................................... 11.000
DX System Configuration ............................. 1-stage compression, 1 circuit
Conventional Cutoff OAT .......................................................................... 55.0
Low Temperature Operation ................................................................... Used
Low Temperature Cutoff OAT ..................................................................... 0.0

Hourly Analysis Program v4.61

(CFM)

MBH
F
%
EER
F
F

Page 10 of 16

(29) AC-6-V1-FF-Bed rm 1 Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

1. General Details:
Air System Name .................................................. (29) AC-6-V1-FF-Bed rm 1
Equipment Type ............................................................................. Split AHU
Air System Type ................................................................. Single Zone CAV
Number of zones ........................................................................................... 1
2. System Components:
Ventilation Air Data:
Airflow Control .................................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Unocc. Damper Position ...................................................................... Closed
Damper Leak Rate ........................................................................................ 0 %
Outdoor Air CO2 Level .............................................................................. 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................ 53.0 F
Coil Bypass Factor ................................................................................. 0.100
Cooling Source ........................................................................ Air-Cooled DX
Schedule ............................................................................ JFMAMJJASOND
Capacity Control .................................. Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type .............................................................................. Forward Curved
Configuration .................................................................................. Draw-thru
Fan Performance ...................................................................................... 0.00 in wg
Overall Efficiency ......................................................................................... 54 %
Fan Control ............................................... 1-speed fan, cooling and heating
Duct System Data:
Supply Duct Data:
Duct Heat Gain .............................................................................................. 0 %
Duct Leakage ................................................................................................ 0 %
Return Duct or Plenum Data:
Return Air Via ................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 0 %
Roof Heat Gain to Plenum ........................................................................... 70 %
Lighting Heat Gain to Plenum ...................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
V1M-FF-Bed rm 1

x1

Thermostats and Zone Data:


Zone ........................................................................................................... All
Cooling T-stat: Occ. .................................................................................. 74.0
Cooling T-stat: Unocc. .............................................................................. 80.0
Heating T-stat: Occ. .................................................................................. 70.0
Heating T-stat: Unocc. .............................................................................. 65.0
T-stat Throttling Range ............................................................................. 1.50
Diversity Factor ......................................................................................... 100
Direct Exhaust Airflow ................................................................................. 0.0
Direct Exhaust Fan kW ............................................................................... 0.0

F
F
F
F
F
%
CFM
kW

Thermostat Schedule ................................................................................... th


Unoccupied Cooling is ..................................................................... Available
Supply Terminals Data:
Zone ........................................................................................................... All
Terminal Type ................................................................................... Diffuser
Minimum Airflow ....................................................................................... 0.00 CFM/person
Zone Heating Units:
Zone ........................................................................................................... All
Zone Heating Unit Type .......................................................................... None
Zone Unit Heat Source ................................................... Electric Resistance
Zone Heating Unit Schedule ............................................... JFMAMJJASOND

Hourly Analysis Program v4.61

Page 11 of 16

(29) AC-6-V1-FF-Bed rm 1 Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature .................................................................... 53.0 F
Supply Fan Airflow .................................................................................. 370.1 CFM
Ventilation Airflow ....................................................................................... 0.0 CFM
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................... 10.0 F
Hot Water Delta-T ..................................................................................... 20.0 F
Safety Factors:
Cooling Sensible .......................................................................................... 10 %
Cooling Latent ............................................................................................... 5 %
Heating .......................................................................................................... 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................ Sum of space airflow rates
Space Airflow Sizing Method ............................ Individual peak space loads

Zone

Supply Airflow
(CFM)

370.1

Zone Htg Unit


(MBH)

Reheat Coil
(MBH)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ........................................................................ 11.7
Design OAT ............................................................................................ 115.0
Equipment Sizing .......................................................................... Auto-Sized
Capacity Oversizing Factor ............................................................................ 0
ARI Performance Rating ....................................................................... 11.000
DX System Configuration ............................. 1-stage compression, 1 circuit
Conventional Cutoff OAT .......................................................................... 55.0
Low Temperature Operation ................................................................... Used
Low Temperature Cutoff OAT ..................................................................... 0.0

Hourly Analysis Program v4.61

(CFM)

MBH
F
%
EER
F
F

Page 12 of 16

(30) AC-7-V1-FF-Bed rm 2 Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

1. General Details:
Air System Name .................................................. (30) AC-7-V1-FF-Bed rm 2
Equipment Type ............................................................................. Split AHU
Air System Type ................................................................. Single Zone CAV
Number of zones ........................................................................................... 1
2. System Components:
Ventilation Air Data:
Airflow Control .................................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Unocc. Damper Position ...................................................................... Closed
Damper Leak Rate ........................................................................................ 0 %
Outdoor Air CO2 Level .............................................................................. 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................ 55.0 F
Coil Bypass Factor ................................................................................. 0.100
Cooling Source ........................................................................ Air-Cooled DX
Schedule ............................................................................ JFMAMJJASOND
Capacity Control .................................. Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type .............................................................................. Forward Curved
Configuration .................................................................................. Draw-thru
Fan Performance ...................................................................................... 0.00 in wg
Overall Efficiency ......................................................................................... 54 %
Fan Control ............................................... 1-speed fan, cooling and heating
Duct System Data:
Supply Duct Data:
Duct Heat Gain .............................................................................................. 0 %
Duct Leakage ................................................................................................ 0 %
Return Duct or Plenum Data:
Return Air Via ................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 0 %
Roof Heat Gain to Plenum ........................................................................... 70 %
Lighting Heat Gain to Plenum ...................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
V1M-FF-Bed rm 2

x1

Thermostats and Zone Data:


Zone ........................................................................................................... All
Cooling T-stat: Occ. .................................................................................. 74.0
Cooling T-stat: Unocc. .............................................................................. 80.0
Heating T-stat: Occ. .................................................................................. 70.0
Heating T-stat: Unocc. .............................................................................. 65.0
T-stat Throttling Range ............................................................................. 1.50
Diversity Factor ......................................................................................... 100
Direct Exhaust Airflow ................................................................................. 0.0
Direct Exhaust Fan kW ............................................................................... 0.0

F
F
F
F
F
%
CFM
kW

Thermostat Schedule ................................................................................... th


Unoccupied Cooling is ..................................................................... Available
Supply Terminals Data:
Zone ........................................................................................................... All
Terminal Type ................................................................................... Diffuser
Minimum Airflow ....................................................................................... 0.00 CFM/person
Zone Heating Units:
Zone ........................................................................................................... All
Zone Heating Unit Type .......................................................................... None
Zone Unit Heat Source ................................................... Electric Resistance
Zone Heating Unit Schedule ............................................... JFMAMJJASOND

Hourly Analysis Program v4.61

Page 13 of 16

(30) AC-7-V1-FF-Bed rm 2 Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature .................................................................... 55.0 F
Supply Fan Airflow .................................................................................. 415.8 CFM
Ventilation Airflow ....................................................................................... 0.0 CFM
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................... 10.0 F
Hot Water Delta-T ..................................................................................... 20.0 F
Safety Factors:
Cooling Sensible .......................................................................................... 10 %
Cooling Latent ............................................................................................... 5 %
Heating .......................................................................................................... 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................ Sum of space airflow rates
Space Airflow Sizing Method ............................ Individual peak space loads

Zone

Supply Airflow
(CFM)

415.8

Zone Htg Unit


(MBH)

Reheat Coil
(MBH)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 9.1
Design OAT ............................................................................................ 115.0
Equipment Sizing .......................................................................... Auto-Sized
Capacity Oversizing Factor ............................................................................ 0
ARI Performance Rating ....................................................................... 11.000
DX System Configuration ............................. 1-stage compression, 1 circuit
Conventional Cutoff OAT .......................................................................... 55.0
Low Temperature Operation ................................................................... Used
Low Temperature Cutoff OAT ..................................................................... 0.0

Hourly Analysis Program v4.61

(CFM)

MBH
F
%
EER
F
F

Page 14 of 16

(31)AC-8-V1-FF-Bed rm 3+Fam liv Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

1. General Details:
Air System Name ..................................... (31)AC-8-V1-FF-Bed rm 3+Fam liv
Equipment Type ............................................................................. Split AHU
Air System Type ................................................................. Single Zone CAV
Number of zones ........................................................................................... 1
2. System Components:
Ventilation Air Data:
Airflow Control .................................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Unocc. Damper Position ...................................................................... Closed
Damper Leak Rate ........................................................................................ 0 %
Outdoor Air CO2 Level .............................................................................. 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................ 55.0 F
Coil Bypass Factor ................................................................................. 0.100
Cooling Source ........................................................................ Air-Cooled DX
Schedule ............................................................................ JFMAMJJASOND
Capacity Control .................................. Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type .............................................................................. Forward Curved
Configuration .................................................................................. Draw-thru
Fan Performance ...................................................................................... 0.00 in wg
Overall Efficiency ......................................................................................... 54 %
Fan Control ............................................... 1-speed fan, cooling and heating
Duct System Data:
Supply Duct Data:
Duct Heat Gain .............................................................................................. 0 %
Duct Leakage ................................................................................................ 0 %
Return Duct or Plenum Data:
Return Air Via ................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 0 %
Roof Heat Gain to Plenum ........................................................................... 70 %
Lighting Heat Gain to Plenum ...................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
V1M-FF-Bed rm 3+Liv+corr

x1

Thermostats and Zone Data:


Zone ........................................................................................................... All
Cooling T-stat: Occ. .................................................................................. 74.0
Cooling T-stat: Unocc. .............................................................................. 80.0
Heating T-stat: Occ. .................................................................................. 70.0
Heating T-stat: Unocc. .............................................................................. 65.0
T-stat Throttling Range ............................................................................. 1.50
Diversity Factor ......................................................................................... 100
Direct Exhaust Airflow ................................................................................. 0.0
Direct Exhaust Fan kW ............................................................................... 0.0

F
F
F
F
F
%
CFM
kW

Thermostat Schedule ................................................................................... th


Unoccupied Cooling is ..................................................................... Available
Supply Terminals Data:
Zone ........................................................................................................... All
Terminal Type ................................................................................... Diffuser
Minimum Airflow ....................................................................................... 0.00 CFM/person
Zone Heating Units:
Zone ........................................................................................................... All
Zone Heating Unit Type .......................................................................... None
Zone Unit Heat Source ................................................... Electric Resistance
Zone Heating Unit Schedule ............................................... JFMAMJJASOND

Hourly Analysis Program v4.61

Page 15 of 16

(31)AC-8-V1-FF-Bed rm 3+Fam liv Input Data


Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
Prepared by: reyami

08/05/2015
09:02AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature .................................................................... 55.0 F
Supply Fan Airflow ................................................................................ 1156.3 CFM
Ventilation Airflow ....................................................................................... 0.0 CFM
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................... 10.0 F
Hot Water Delta-T ..................................................................................... 20.0 F
Safety Factors:
Cooling Sensible .......................................................................................... 10 %
Cooling Latent ............................................................................................... 5 %
Heating .......................................................................................................... 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................ Sum of space airflow rates
Space Airflow Sizing Method ............................ Individual peak space loads

Zone

Supply Airflow
(CFM)

1156.3

Zone Htg Unit


(MBH)

Reheat Coil
(MBH)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ........................................................................ 28.4
Design OAT ............................................................................................ 115.0
Equipment Sizing .......................................................................... Auto-Sized
Capacity Oversizing Factor ............................................................................ 0
ARI Performance Rating ....................................................................... 11.000
DX System Configuration ............................. 1-stage compression, 1 circuit
Conventional Cutoff OAT .......................................................................... 55.0
Low Temperature Operation ................................................................... Used
Low Temperature Cutoff OAT ..................................................................... 0.0

Hourly Analysis Program v4.61

(CFM)

MBH
F
%
EER
F
F

Page 16 of 16

Space Input Data


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

08/05/2015
09:02AM

V1M-FF-Bed rm 1
1. General Details:
Floor Area .......................................................... 192.0
Avg. Ceiling Height ............................................... 10.2
Building Weight .................................................... 70.0
1.1. OA Ventilation Requirements:
Space Usage ......................................... User-Defined
OA Requirement 1 ................................................. 0.0
OA Requirement 2 ................................................ 0.00
Space Usage Defaults .......... ASHRAE Std 62.1-2007

ft
ft
lb/ft
CFM
CFM/ft

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Unvented)
Wattage ................................................................ 1.20 W/ft
Ballast Multiplier ................................................... 1.25
Schedule ............................................................. Villa

2.4. People:
Occupancy ............................................................. 3.0 People
Activity Level ........................................... Office Work
Sensible ............................................................. 245.0 BTU/hr/person
Latent ................................................................. 205.0 BTU/hr/person
Schedule .............................................................. Villa

2.2. Task Lighting:


Wattage ................................................................ 0.00 W/ft
Schedule ............................................................ None

2.5. Miscellaneous Loads:


Sensible .................................................................... 0 BTU/hr
Schedule ............................................................ None
Latent ........................................................................ 0 BTU/hr
Schedule ............................................................ None

2.3. Electrical Equipment:


Wattage .............................................................. 150.0 Watts
Schedule ............................................................. Villa
3. Walls, Windows, Doors:
Exp.

Wall Gross Area (ft)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

NW

150.0

47

3.1. Construction Types for Exposure NW


Wall Type ................................................................. U=0.15
1st Window Type ..................................................... U - 0.37
4. Roofs, Skylights:
Exp.

Roof Gross Area (ft)

Roof Slope (deg.)

Skylight Qty.

192.0

4.1. Construction Types for Exposure H


Roof Type .......................................................... Roof ( TYP)
5. Infiltration:
Design Cooling ................................................... 52.00 CFM
Design Heating ..................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type ......................................... Slab Floor On Grade
Floor Area .......................................................... 192.0
Total Floor U-Value ............................................ 0.100
Exposed Perimeter ................................................ 0.0
Edge Insulation R-Value ....................................... 0.00
7. Partitions:
7.1. 1st Partition Details:
Partition Type ....................................... Wall Partition
Area ................................................................... 129.0
U-Value .............................................................. 0.400
Uncondit. Space Max Temp .................................. 95.0
Ambient at Space Max Temp .............................. 115.0
Uncondit. Space Min Temp ................................... 75.0
Ambient at Space Min Temp ................................. 55.0

Hourly Analysis Program v4.61

ft
BTU/(hr-ft-F)
ft
(hr-ft-F)/BTU
7.2. 2nd Partition Details:
(No partition data).
ft
BTU/(hr-ft-F)
F
F
F
F

Page 1 of 12

Space Input Data


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

08/05/2015
09:02AM

V1M-FF-Bed rm 2
1. General Details:
Floor Area .......................................................... 188.0
Avg. Ceiling Height ............................................... 10.2
Building Weight .................................................... 70.0
1.1. OA Ventilation Requirements:
Space Usage ......................................... User-Defined
OA Requirement 1 ................................................. 0.0
OA Requirement 2 ................................................ 0.00
Space Usage Defaults .......... ASHRAE Std 62.1-2007

ft
ft
lb/ft
CFM
CFM/ft

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Unvented)
Wattage ................................................................ 1.20 W/ft
Ballast Multiplier ................................................... 1.10
Schedule ............................................................. Villa

2.4. People:
Occupancy ............................................................. 2.0 People
Activity Level ........................................... Office Work
Sensible ............................................................. 245.0 BTU/hr/person
Latent ................................................................. 205.0 BTU/hr/person
Schedule .............................................................. Villa

2.2. Task Lighting:


Wattage ................................................................ 0.00 W/ft
Schedule ............................................................ None

2.5. Miscellaneous Loads:


Sensible .................................................................... 0 BTU/hr
Schedule ............................................................ None
Latent ........................................................................ 0 BTU/hr
Schedule ............................................................ None

2.3. Electrical Equipment:


Wattage .............................................................. 150.0 Watts
Schedule ............................................................. Villa
3. Walls, Windows, Doors:
Exp.

Wall Gross Area (ft)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

SE

106.0

75

SE

60.0

3.1. Construction Types for Exposure SE


Wall Type ................................................................. U=0.22
1st Window Type ..................................................... U - 0.37
3.2. Construction Types for Exposure SE
Wall Type ............................................................... U=0.096
4. Roofs, Skylights:
Exp.

Roof Gross Area (ft)

Roof Slope (deg.)

Skylight Qty.

188.0

4.1. Construction Types for Exposure H


Roof Type .......................................................... Roof ( TYP)
5. Infiltration:
Design Cooling ..................................................... 0.00 CFM
Design Heating ..................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type ...................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details:
Partition Type ....................................... Wall Partition
Area ................................................................... 106.0
U-Value .............................................................. 0.400
Uncondit. Space Max Temp .................................. 95.0
Ambient at Space Max Temp .............................. 115.0
Uncondit. Space Min Temp ................................... 75.0
Ambient at Space Min Temp ................................. 55.0

Hourly Analysis Program v4.61

ft
BTU/(hr-ft-F)
F
F
F
F

7.2. 2nd Partition Details:


Partition Type ....................................... Wall Partition
Area ................................................................... 327.0
U-Value .............................................................. 0.400
Uncondit. Space Max Temp ................................. 95.0
Ambient at Space Max Temp ............................. 115.0
Uncondit. Space Min Temp .................................. 75.0
Ambient at Space Min Temp ................................ 55.0

ft
BTU/(hr-ft-F)
F
F
F
F

Page 2 of 12

Space Input Data


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

08/05/2015
09:02AM

V1M-FF-Bed rm 3+Liv+corr
1. General Details:
Floor Area .......................................................... 555.0
Avg. Ceiling Height ............................................... 10.2
Building Weight .................................................... 70.0
1.1. OA Ventilation Requirements:
Space Usage ......................................... User-Defined
OA Requirement 1 ................................................. 0.0
OA Requirement 2 ................................................ 0.00
Space Usage Defaults .......... ASHRAE Std 62.1-2007

ft
ft
lb/ft
CFM
CFM/ft

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Unvented)
Wattage ................................................................ 1.20 W/ft
Ballast Multiplier ................................................... 1.25
Schedule ............................................................. Villa

2.4. People:
Occupancy ............................................................. 6.0 People
Activity Level ........................................... Office Work
Sensible ............................................................. 245.0 BTU/hr/person
Latent ................................................................. 205.0 BTU/hr/person
Schedule .............................................................. Villa

2.2. Task Lighting:


Wattage ................................................................ 0.00 W/ft
Schedule ............................................................ None

2.5. Miscellaneous Loads:


Sensible .................................................................... 0 BTU/hr
Schedule ............................................................ None
Latent ........................................................................ 0 BTU/hr
Schedule ............................................................ None

2.3. Electrical Equipment:


Wattage .............................................................. 300.0 Watts
Schedule ............................................................. Villa
3. Walls, Windows, Doors:
Exp.

Wall Gross Area (ft)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

NW

170.0

SE

163.0

SW

166.0

152

SW

130.0

SW

40.0

SW

50.0

3.1. Construction Types for Exposure NW


Wall Type ............................................................... U=0.093
3.2. Construction Types for Exposure SE
Wall Type ............................................................... U=0.093
3.3. Construction Types for Exposure SW
Wall Type ................................................................. U=0.15
1st Window Type ..................................................... U - 0.37
3.4. Construction Types for Exposure SW
Wall Type ............................................................... U=0.112
3.5. Construction Types for Exposure SW
Wall Type ............................................................... U=0.104
3.6. Construction Types for Exposure SW
Wall Type ................................................................. U=0.12
4. Roofs, Skylights:
Exp.

Roof Gross Area (ft)

Roof Slope (deg.)

Skylight Qty.

555.0

4.1. Construction Types for Exposure H


Roof Type .......................................................... Roof ( TYP)
5. Infiltration:
Design Cooling ................................................... 52.00 CFM
Hourly Analysis Program v4.61

Page 3 of 12

Space Input Data


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

08/05/2015
09:02AM

Design Heating ..................................................... 0.00 CFM


Energy Analysis .................................................... 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type ...................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details:
Partition Type ....................................... Wall Partition
Area ................................................................... 846.0
U-Value .............................................................. 0.400
Uncondit. Space Max Temp .................................. 95.0
Ambient at Space Max Temp .............................. 115.0
Uncondit. Space Min Temp ................................... 75.0
Ambient at Space Min Temp ................................. 55.0

Hourly Analysis Program v4.61

7.2. 2nd Partition Details:


(No partition data).
ft
BTU/(hr-ft-F)
F
F
F
F

Page 4 of 12

Space Input Data


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

08/05/2015
09:02AM

V1M-FF-Master bed rm
1. General Details:
Floor Area .......................................................... 352.0
Avg. Ceiling Height ............................................... 10.2
Building Weight .................................................... 70.0
1.1. OA Ventilation Requirements:
Space Usage ......................................... User-Defined
OA Requirement 1 ................................................. 0.0
OA Requirement 2 ................................................ 0.00
Space Usage Defaults .......... ASHRAE Std 62.1-2007

ft
ft
lb/ft
CFM
CFM/ft

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Unvented)
Wattage ................................................................ 1.20 W/ft
Ballast Multiplier ................................................... 1.25
Schedule ............................................................. Villa

2.4. People:
Occupancy ............................................................. 3.0 People
Activity Level ........................................... Office Work
Sensible ............................................................. 245.0 BTU/hr/person
Latent ................................................................. 205.0 BTU/hr/person
Schedule .............................................................. Villa

2.2. Task Lighting:


Wattage ................................................................ 0.00 W/ft
Schedule ............................................................ None

2.5. Miscellaneous Loads:


Sensible .................................................................... 0 BTU/hr
Schedule ............................................................ None
Latent ........................................................................ 0 BTU/hr
Schedule ............................................................ None

2.3. Electrical Equipment:


Wattage .............................................................. 150.0 Watts
Schedule ............................................................. Villa
3. Walls, Windows, Doors:
Exp.

Wall Gross Area (ft)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

NE

117.0

70

SE

167.0

NE

127.0

3.1. Construction Types for Exposure NE


Wall Type ................................................................. U=0.58
1st Window Type ..................................................... U - 0.37
3.2. Construction Types for Exposure SE
Wall Type ............................................................... U=0.093
3.3. Construction Types for Exposure NE
Wall Type ............................................................... U=0.096
4. Roofs, Skylights:
Exp.

Roof Gross Area (ft)

Roof Slope (deg.)

Skylight Qty.

352.0

4.1. Construction Types for Exposure H


Roof Type .......................................................... Roof ( TYP)
5. Infiltration:
Design Cooling ................................................... 52.00 CFM
Design Heating ..................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type ...................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details:
Partition Type ....................................... Wall Partition
Area ................................................................... 200.0 ft
U-Value .............................................................. 0.400 BTU/(hr-ft-F)
Hourly Analysis Program v4.61

Uncondit. Space Max Temp ................................. 95.0


Ambient at Space Max Temp ............................. 115.0
Uncondit. Space Min Temp .................................. 75.0
Ambient at Space Min Temp ................................ 55.0

F
F
F
F
Page 5 of 12

Space Input Data


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

7.2. 2nd Partition Details:


Partition Type ....................................... Wall Partition
Area ................................................................... 120.0 ft
U-Value .............................................................. 0.400 BTU/(hr-ft-F)

Hourly Analysis Program v4.61

08/05/2015
09:02AM

Uncondit. Space Max Temp ................................. 95.0


Ambient at Space Max Temp ............................. 115.0
Uncondit. Space Min Temp .................................. 75.0
Ambient at Space Min Temp ................................ 55.0

F
F
F
F

Page 6 of 12

Space Input Data


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

08/05/2015
09:02AM

V1M-GF-Kitchen
1. General Details:
Floor Area .......................................................... 182.0
Avg. Ceiling Height ............................................... 10.2
Building Weight .................................................... 70.0
1.1. OA Ventilation Requirements:
Space Usage ......................................... User-Defined
OA Requirement 1 ................................................. 0.0
OA Requirement 2 ................................................ 0.00
Space Usage Defaults .......... ASHRAE Std 62.1-2007

ft
ft
lb/ft
CFM
CFM/ft

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Unvented)
Wattage ................................................................ 1.50 W/ft
Ballast Multiplier ................................................... 1.25
Schedule ............................................................. Villa

2.4. People:
Occupancy ............................................................. 2.0 People
Activity Level ........................................ Medium Work
Sensible ............................................................. 295.0 BTU/hr/person
Latent ................................................................. 455.0 BTU/hr/person
Schedule .............................................................. Villa

2.2. Task Lighting:


Wattage ................................................................ 0.00 W/ft
Schedule ............................................................ None

2.5. Miscellaneous Loads:


Sensible .................................................................... 0 BTU/hr
Schedule ............................................................ None
Latent ........................................................................ 0 BTU/hr
Schedule ............................................................ None

2.3. Electrical Equipment:


Wattage .............................................................. 300.0 Watts
Schedule ............................................................. Villa
3. Walls, Windows, Doors:
Exp.

Wall Gross Area (ft)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

NW

128.0

46

3.1. Construction Types for Exposure NW


Wall Type ............................................................... U=0.104
1st Window Type ..................................................... U - 0.37
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 127.00 CFM
Design Heating ..................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type ......................................... Slab Floor On Grade
Floor Area .......................................................... 182.0
Total Floor U-Value ............................................ 0.100
Exposed Perimeter ................................................ 0.0
Edge Insulation R-Value ....................................... 0.00
7. Partitions:
7.1. 1st Partition Details:
Partition Type ....................................... Wall Partition
Area ................................................................... 126.0
U-Value .............................................................. 0.400
Uncondit. Space Max Temp .................................. 95.0
Ambient at Space Max Temp .............................. 115.0
Uncondit. Space Min Temp ................................... 75.0
Ambient at Space Min Temp ................................. 55.0

Hourly Analysis Program v4.61

ft
BTU/(hr-ft-F)
ft
(hr-ft-F)/BTU
7.2. 2nd Partition Details:
(No partition data).
ft
BTU/(hr-ft-F)
F
F
F
F

Page 7 of 12

Space Input Data


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

08/05/2015
09:02AM

V1M-GF-Livi/Dining
1. General Details:
Floor Area .......................................................... 430.0
Avg. Ceiling Height ............................................... 10.2
Building Weight .................................................... 70.0
1.1. OA Ventilation Requirements:
Space Usage ......................................... User-Defined
OA Requirement 1 ................................................. 0.0
OA Requirement 2 ................................................ 0.00
Space Usage Defaults .......... ASHRAE Std 62.1-2007

ft
ft
lb/ft
CFM
CFM/ft

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Unvented)
Wattage ................................................................ 2.00 W/ft
Ballast Multiplier ................................................... 1.25
Schedule ............................................................. Villa

2.4. People:
Occupancy ............................................................. 8.0 People
Activity Level .................................... Sedentary Work
Sensible ............................................................. 280.0 BTU/hr/person
Latent ................................................................. 270.0 BTU/hr/person
Schedule .............................................................. Villa

2.2. Task Lighting:


Wattage ................................................................ 0.00 W/ft
Schedule ............................................................ None

2.5. Miscellaneous Loads:


Sensible .................................................................... 0 BTU/hr
Schedule ............................................................ None
Latent ........................................................................ 0 BTU/hr
Schedule ............................................................ None

2.3. Electrical Equipment:


Wattage .............................................................. 200.0 Watts
Schedule ............................................................. Villa
3. Walls, Windows, Doors:
Exp.

Wall Gross Area (ft)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

NW

137.0

NE

320.0

140

SE

137.0

NE

110.0

3.1. Construction Types for Exposure NW


Wall Type ............................ External Wall Secton ( TYP)-1
3.2. Construction Types for Exposure NE
Wall Type ............................................................... U=0.106
1st Window Type ..................................................... U - 0.37
3.3. Construction Types for Exposure SE
Wall Type ............................................................... U=0.093
3.4. Construction Types for Exposure NE
Wall Type ............................................................... U=0.322
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ..................................................... 0.00 CFM
Design Heating ..................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type ......................................... Slab Floor On Grade
Floor Area .......................................................... 430.0
Total Floor U-Value ............................................ 0.100
Exposed Perimeter ................................................ 0.0
Edge Insulation R-Value ....................................... 0.00

ft
BTU/(hr-ft-F)
ft
(hr-ft-F)/BTU

7. Partitions:
7.1. 1st Partition Details:
Partition Type ....................................... Wall Partition
Area ................................................................... 333.0 ft
Hourly Analysis Program v4.61

U-Value .............................................................. 0.400 BTU/(hr-ft-F)


Uncondit. Space Max Temp ................................. 95.0 F
Ambient at Space Max Temp ............................. 115.0 F
Page 8 of 12

Space Input Data


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

Uncondit. Space Min Temp ................................... 75.0 F


Ambient at Space Min Temp ................................. 55.0 F

Hourly Analysis Program v4.61

08/05/2015
09:02AM

7.2. 2nd Partition Details:


Partition Type ....................................... Wall Partition
Area ................................................................... 430.0
U-Value .............................................................. 0.400
Uncondit. Space Max Temp ................................. 95.0
Ambient at Space Max Temp ............................. 115.0
Uncondit. Space Min Temp .................................. 75.0
Ambient at Space Min Temp ................................ 55.0

ft
BTU/(hr-ft-F)
F
F
F
F

Page 9 of 12

Space Input Data


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

08/05/2015
09:02AM

V1M-GF-Maids rm+guest rm
1. General Details:
Floor Area .......................................................... 191.0
Avg. Ceiling Height ............................................... 10.2
Building Weight .................................................... 70.0
1.1. OA Ventilation Requirements:
Space Usage ......................................... User-Defined
OA Requirement 1 ................................................. 0.0
OA Requirement 2 ................................................ 0.00
Space Usage Defaults .......... ASHRAE Std 62.1-2007

ft
ft
lb/ft
CFM
CFM/ft

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Unvented)
Wattage ................................................................ 1.20 W/ft
Ballast Multiplier ................................................... 1.25
Schedule ............................................................. Villa

2.4. People:
Occupancy ............................................................. 3.0 People
Activity Level ........................................... Office Work
Sensible ............................................................. 245.0 BTU/hr/person
Latent ................................................................. 205.0 BTU/hr/person
Schedule .............................................................. Villa

2.2. Task Lighting:


Wattage ................................................................ 0.00 W/ft
Schedule ............................................................ None

2.5. Miscellaneous Loads:


Sensible .................................................................... 0 BTU/hr
Schedule ............................................................ None
Latent ........................................................................ 0 BTU/hr
Schedule ............................................................ None

2.3. Electrical Equipment:


Wattage .............................................................. 250.0 Watts
Schedule ............................................................. Villa
3. Walls, Windows, Doors:
Exp.

Wall Gross Area (ft)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

SW

48.0

23

SE

121.0

47

SW

76.0

SW

130.0

3.1. Construction Types for Exposure SW


Wall Type ............................ External Wall Secton ( TYP)-1
1st Window Type ..................................................... U - 0.37
3.2. Construction Types for Exposure SE
Wall Type ............................................................... U=0.100
1st Window Type ..................................................... U - 0.37
3.3. Construction Types for Exposure SW
Wall Type ............................................................... U=0.112
3.4. Construction Types for Exposure SW
Wall Type ............................................................... U=0.104
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 104.00 CFM
Design Heating ..................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type ......................................... Slab Floor On Grade
Floor Area .......................................................... 191.0
Total Floor U-Value ............................................ 0.100
Exposed Perimeter ................................................ 0.0
Edge Insulation R-Value ....................................... 0.00
7. Partitions:
7.1. 1st Partition Details:
Partition Type ....................................... Wall Partition
Hourly Analysis Program v4.61

ft
BTU/(hr-ft-F)
ft
(hr-ft-F)/BTU
Area ................................................................... 156.0 ft
U-Value .............................................................. 0.400 BTU/(hr-ft-F)
Page 10 of 12

Space Input Data


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

Uncondit. Space Max Temp .................................. 95.0


Ambient at Space Max Temp .............................. 115.0
Uncondit. Space Min Temp ................................... 75.0
Ambient at Space Min Temp ................................. 55.0

Hourly Analysis Program v4.61

08/05/2015
09:02AM

F
F
F
F

7.2. 2nd Partition Details:


Partition Type ....................................... Wall Partition
Area ..................................................................... 80.0
U-Value .............................................................. 0.400
Uncondit. Space Max Temp ................................. 95.0
Ambient at Space Max Temp ............................. 115.0
Uncondit. Space Min Temp .................................. 75.0
Ambient at Space Min Temp ................................ 55.0

ft
BTU/(hr-ft-F)
F
F
F
F

Page 11 of 12

Space Input Data


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

08/05/2015
09:02AM

V1M-GF-Majlis+corr
1. General Details:
Floor Area .......................................................... 400.0
Avg. Ceiling Height ............................................... 10.2
Building Weight .................................................... 70.0
1.1. OA Ventilation Requirements:
Space Usage ......................................... User-Defined
OA Requirement 1 ................................................. 0.0
OA Requirement 2 ................................................ 0.00
Space Usage Defaults .......... ASHRAE Std 62.1-2007

ft
ft
lb/ft
CFM
CFM/ft

2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Unvented)
Wattage ................................................................ 1.20 W/ft
Ballast Multiplier ................................................... 1.25
Schedule ............................................................. Villa

2.4. People:
Occupancy ........................................................... 10.0 People
Activity Level ........................................... Office Work
Sensible ............................................................. 245.0 BTU/hr/person
Latent ................................................................. 205.0 BTU/hr/person
Schedule .............................................................. Villa

2.2. Task Lighting:


Wattage ................................................................ 0.00 W/ft
Schedule ............................................................ None

2.5. Miscellaneous Loads:


Sensible .................................................................... 0 BTU/hr
Schedule ............................................................ None
Latent ........................................................................ 0 BTU/hr
Schedule ............................................................ None

2.3. Electrical Equipment:


Wattage .............................................................. 250.0 Watts
Schedule ............................................................. Villa
3. Walls, Windows, Doors:
Exp.

Wall Gross Area (ft)

Window 1 Qty.

Window 2 Qty.

Door 1 Qty.

SE

80.0

SE

111.0

85

3.1. Construction Types for Exposure SE


Wall Type ............................................................... U=0.100
3.2. Construction Types for Exposure SE
Wall Type ............................................................... U=0.112
1st Window Type ..................................................... U - 0.37
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................... 50.00 CFM
Design Heating ..................................................... 0.00 CFM
Energy Analysis .................................................... 0.00 CFM
Infiltration occurs at all hours.
6. Floors:
Type ......................................... Slab Floor On Grade
Floor Area .......................................................... 400.0
Total Floor U-Value ............................................ 0.100
Exposed Perimeter ................................................ 0.0
Edge Insulation R-Value ....................................... 0.00
7. Partitions:
7.1. 1st Partition Details:
Partition Type ....................................... Wall Partition
Area ................................................................... 183.0
U-Value .............................................................. 0.400
Uncondit. Space Max Temp .................................. 95.0
Ambient at Space Max Temp .............................. 115.0
Uncondit. Space Min Temp ................................... 75.0
Ambient at Space Min Temp ................................. 55.0

Hourly Analysis Program v4.61

ft
BTU/(hr-ft-F)
ft
(hr-ft-F)/BTU
7.2. 2nd Partition Details:
(No partition data).
ft
BTU/(hr-ft-F)
F
F
F
F

Page 12 of 12

Air System Sizing Summary for (24) AC-1-V1-GF-Livi/Dining


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

Air System Information


Air System Name .......... (24) AC-1-V1-GF-Livi/Dining
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 430.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 1.9
Total coil load ....................................................... 22.9
Sensible coil load .................................................. 20.7
Coil CFM at Jul 1400 ............................................ 850
Max block CFM .................................................... 850
Sum of peak zone CFM ........................................ 850
Sensible heat ratio .............................................. 0.901
ft/Ton ................................................................. 225.1
BTU/(hr-ft) ........................................................... 53.3
Water flow @ 10.0 F rise ..................................... N/A

Tons
MBH
MBH
CFM
CFM
CFM

Load occurs at .................................................. Jul 1400


OA DB / WB ................................................. 114.3 / 84.9
Entering DB / WB ........................................... 76.5 / 62.3
Leaving DB / WB ............................................ 54.0 / 52.7
Coil ADP .................................................................. 51.5
Bypass Factor ........................................................ 0.100
Resulting RH ............................................................... 47
Design supply temp. ................................................. 52.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM ................................................... 850 CFM
Standard CFM ...................................................... 850 CFM
Actual max CFM/ft ............................................... 1.98 CFM/ft

Fan motor BHP ........................................................ 0.00 BHP


Fan motor kW .......................................................... 0.00 kW
Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 0.00 CFM/person

Page 1 of 32

Zone Sizing Summary for (24) AC-1-V1-GF-Livi/Dining


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

Air System Information


Air System Name .......... (24) AC-1-V1-GF-Livi/Dining
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 430.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
20.2

Design
Air
Flow
(CFM)
850

Minimum
Air
Flow
(CFM)
850

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(MBH)
2.1

Zone
Floor
Area
(ft)
430.0

Zone
CFM/ft
1.98

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
V1M-GF-Livi/Dining

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

20.2

Jul 1500

850

2.1

430.0

1.98

Page 2 of 32

Ventilation Sizing Summary for (24) AC-1-V1-GF-Livi/Dining


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
V1M-GF-Livi/Dining
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

430.0

8.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
850.5
850.5

0.00

Required
Outdoor Air
(CFM/ft)
0.00

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0

0.0

Uncorrected
Outdoor Air
(CFM)
0.0
0.0

Page 3 of 32

Air System Design Load Summary for (24) AC-1-V1-GF-Livi/Dining


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.61

08/05/2015
09:00AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1400
HEATING DATA AT DES HTG
COOLING OA DB / WB 114.3 F / 84.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
140 ft
2031
140 ft
564 ft
3013
564 ft
1292
0 ft
0
0 ft
0
140 ft
1850
140 ft
829
0 ft
0
0 ft
0
0 ft
0
0 ft
0
430 ft
0
430 ft
0
763 ft
5871
763 ft
0
0 ft
0
0 ft
0
1075 W
2567
0
0
0W
0
0
0
200 W
682
0
0
8
2240
2160
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
1825
108
0%
0
0
20080
2268
2121
0
19550
2268
5
0
0%
0
0
0
70%
0
0
0
30%
1100
0
0
850 CFM
0
850 CFM
0
0 CFM
0
0
0 CFM
0
0
850 CFM
0
850 CFM
0
0
0
0%
0
0%
0
20650
2268
5
0
20650
2268
0
0
20650
2268
0
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 4 of 32

Air System Sizing Summary for (25) AC-2-V1-GF-Kitchen


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
10:12AM

Air System Information


Air System Name ............... (25) AC-2-V1-GF-Kitchen
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 182.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 1.4
Total coil load ....................................................... 16.8
Sensible coil load .................................................. 11.1
Coil CFM at Aug 1600 .......................................... 449
Max block CFM .................................................... 449
Sum of peak zone CFM ........................................ 449
Sensible heat ratio .............................................. 0.660
ft/Ton ................................................................. 129.9
BTU/(hr-ft) ........................................................... 92.4
Water flow @ 10.0 F rise ..................................... N/A

Tons
MBH
MBH
CFM
CFM
CFM

Load occurs at ................................................ Aug 1600


OA DB / WB ................................................. 114.3 / 84.9
Entering DB / WB ........................................... 76.5 / 65.5
Leaving DB / WB ............................................ 53.6 / 52.7
Coil ADP .................................................................. 51.1
Bypass Factor ........................................................ 0.100
Resulting RH ............................................................... 57
Design supply temp. ................................................. 52.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM ................................................... 449 CFM
Standard CFM ...................................................... 449 CFM
Actual max CFM/ft ............................................... 2.47 CFM/ft

Fan motor BHP ........................................................ 0.00 BHP


Fan motor kW .......................................................... 0.00 kW
Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 0.00 CFM/person

Page 5 of 32

Zone Sizing Summary for (25) AC-2-V1-GF-Kitchen


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
10:12AM

Air System Information


Air System Name ............... (25) AC-2-V1-GF-Kitchen
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 182.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
11.1

Design
Air
Flow
(CFM)
449

Minimum
Air
Flow
(CFM)
449

Time
of
Peak
Load
Jul 1600

Maximum
Heating
Load
(MBH)
0.4

Zone
Floor
Area
(ft)
182.0

Zone
CFM/ft
2.47

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
V1M-GF-Kitchen

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

11.1

Jul 1600

449

0.4

182.0

2.47

Page 6 of 32

Ventilation Sizing Summary for (25) AC-2-V1-GF-Kitchen


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
10:12AM

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
V1M-GF-Kitchen
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

182.0

1.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
449.1
449.1

0.00

Required
Outdoor Air
(CFM/ft)
0.00

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0

0.0

Uncorrected
Outdoor Air
(CFM)
0.0
0.0

Page 7 of 32

Air System Design Load Summary for (25) AC-2-V1-GF-Kitchen


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.61

08/05/2015
09:00AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1600
HEATING DATA AT DES HTG
COOLING OA DB / WB 114.3 F / 84.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
46 ft
835
46 ft
82 ft
270
82 ft
136
0 ft
0
0 ft
0
46 ft
601
46 ft
272
0 ft
0
0 ft
0
0 ft
0
0 ft
0
182 ft
0
182 ft
0
126 ft
929
126 ft
0
0 ft
0
0 ft
0
273 W
652
0
0
0W
0
0
0
300 W
1024
0
0
1
295
455
0
0
0
5380
4979
0
0
0
0
0
0
10% / 5%
999
272
0%
0
0
10985
5706
409
0
10824
5706
1
0
0%
0
0
0
70%
0
0
0
30%
279
0
0
449 CFM
0
449 CFM
0
0 CFM
0
0
0 CFM
0
0
449 CFM
0
449 CFM
0
0
0
0%
0
0%
0
11104
5706
1
0
11104
5708
0
0
11104
5708
0
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 8 of 32

Air System Sizing Summary for (26) AC-3-V1-GF-Majlis+corr


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

Air System Information


Air System Name .......... (26) AC-3-V1-GF-Majlis+corr
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 400.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 1.4
Total coil load ....................................................... 16.8
Sensible coil load .................................................. 12.5
Coil CFM at Aug 1500 .......................................... 601
Max block CFM .................................................... 601
Sum of peak zone CFM ........................................ 601
Sensible heat ratio .............................................. 0.748
ft/Ton ................................................................. 286.3
BTU/(hr-ft) ........................................................... 41.9
Water flow @ 10.0 F rise ..................................... N/A

Tons
MBH
MBH
CFM
CFM
CFM

Load occurs at ................................................ Aug 1500


OA DB / WB ................................................. 115.0 / 85.0
Entering DB / WB ........................................... 76.4 / 65.4
Leaving DB / WB ............................................ 57.1 / 56.1
Coil ADP .................................................................. 55.0
Bypass Factor ........................................................ 0.100
Resulting RH ............................................................... 58
Design supply temp. ................................................. 55.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM ................................................... 601 CFM
Standard CFM ...................................................... 601 CFM
Actual max CFM/ft ............................................... 1.50 CFM/ft

Fan motor BHP ........................................................ 0.00 BHP


Fan motor kW .......................................................... 0.00 kW
Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 0.00 CFM/person

Page 9 of 32

Zone Sizing Summary for (26) AC-3-V1-GF-Majlis+corr


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

Air System Information


Air System Name .......... (26) AC-3-V1-GF-Majlis+corr
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 400.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
12.3

Design
Air
Flow
(CFM)
601

Minimum
Air
Flow
(CFM)
601

Time
of
Peak
Load
Aug 1500

Maximum
Heating
Load
(MBH)
0.7

Zone
Floor
Area
(ft)
400.0

Zone
CFM/ft
1.50

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
V1M-GF-Majlis+corr

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

12.3

Aug 1500

601

0.7

400.0

1.50

Page 10 of 32

Ventilation Sizing Summary for (26) AC-3-V1-GF-Majlis+corr


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
V1M-GF-Majlis+corr
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

400.0

10.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
601.1
601.1

0.00

Required
Outdoor Air
(CFM/ft)
0.00

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0

0.0

Uncorrected
Outdoor Air
(CFM)
0.0
0.0

Page 11 of 32

Air System Design Load Summary for (26) AC-3-V1-GF-Majlis+corr


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.61

08/05/2015
09:00AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 115.0 F / 85.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
85 ft
1233
85 ft
106 ft
449
106 ft
175
0 ft
0
0 ft
0
85 ft
1149
85 ft
503
0 ft
0
0 ft
0
0 ft
0
0 ft
0
400 ft
0
400 ft
0
183 ft
1428
183 ft
0
0 ft
0
0 ft
0
600 W
1433
0
0
0W
0
0
0
250 W
853
0
0
10
2450
2050
0
0
0
2213
1980
0
0
0
0
0
0
10% / 5%
1121
202
0%
0
0
12328
4232
678
0
11918
4232
9
0
0%
0
0
0
70%
0
0
0
30%
614
0
0
601 CFM
0
601 CFM
0
0 CFM
0
0
0 CFM
0
0
601 CFM
0
601 CFM
0
0
0
0%
0
0%
0
12532
4232
9
0
12532
4233
0
0
12532
4233
0
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 12 of 32

Air System Sizing Summary for (27)AC-4-V1-GF-Maids rm+guest r


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
10:13AM

System Information
Air System Name (27)AC-4-V1-GF-Maids rm+guest r
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 191.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 1.5
Total coil load ....................................................... 17.7
Sensible coil load .................................................. 12.4
Coil CFM at Aug 1600 .......................................... 523
Max block CFM .................................................... 523
Sum of peak zone CFM ........................................ 523
Sensible heat ratio .............................................. 0.703
ft/Ton ................................................................. 129.8
BTU/(hr-ft) ........................................................... 92.5
Water flow @ 10.0 F rise ..................................... N/A

Tons
MBH
MBH
CFM
CFM
CFM

Load occurs at ................................................ Aug 1600


OA DB / WB ................................................. 114.3 / 84.9
Entering DB / WB ........................................... 75.7 / 64.4
Leaving DB / WB ............................................ 53.6 / 52.7
Coil ADP .................................................................. 51.2
Bypass Factor ........................................................ 0.100
Resulting RH ............................................................... 56
Design supply temp. ................................................. 52.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM ................................................... 523 CFM
Standard CFM ...................................................... 522 CFM
Actual max CFM/ft ............................................... 2.74 CFM/ft

Fan motor BHP ........................................................ 0.00 BHP


Fan motor kW .......................................................... 0.00 kW
Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 0.00 CFM/person

Page 13 of 32

Zone Sizing Summary for (27)AC-4-V1-GF-Maids rm+guest r


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
10:13AM

Air System Information


Air System Name (27)AC-4-V1-GF-Maids rm+guest r
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 191.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
12.4

Design
Air
Flow
(CFM)
523

Minimum
Air
Flow
(CFM)
523

Time
of
Peak
Load
Aug 1500

Maximum
Heating
Load
(MBH)
0.9

Zone
Floor
Area
(ft)
191.0

Zone
CFM/ft
2.74

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
V1M-GF-Maids rm+guest rm

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

12.4

Aug 1500

523

0.9

191.0

2.74

Page 14 of 32

Ventilation Sizing Summary for (27)AC-4-V1-GF-Maids rm+guest r


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
10:13AM

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
V1M-GF-Maids rm+guest rm
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

191.0

3.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
522.6
522.6

0.00

Required
Outdoor Air
(CFM/ft)
0.00

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0

0.0

Uncorrected
Outdoor Air
(CFM)
0.0
0.0

Page 15 of 32

Air System Design Load Summary for (27)AC-4-V1-GF-Maids rm+guest r


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.61

08/05/2015
09:00AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1600
HEATING DATA AT DES HTG
COOLING OA DB / WB 114.3 F / 84.9 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
70 ft
1146
70 ft
305 ft
1159
305 ft
509
0 ft
0
0 ft
0
70 ft
940
70 ft
414
0 ft
0
0 ft
0
0 ft
0
0 ft
0
191 ft
0
191 ft
0
156 ft
1213
156 ft
0
0 ft
0
0 ft
0
287 W
684
0
0
0W
0
0
0
250 W
853
0
0
3
735
615
0
0
0
4518
4373
0
0
0
0
0
0
10% / 5%
1125
249
0%
0
0
12374
5238
924
0
12133
5238
2
0
0%
0
0
0
70%
0
0
0
30%
293
0
0
523 CFM
0
523 CFM
0
0 CFM
0
0
0 CFM
0
0
523 CFM
0
523 CFM
0
0
0
0%
0
0%
0
12426
5238
2
0
12426
5238
0
0
12426
5238
0
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 16 of 32

Air System Sizing Summary for (28) AC-5-V1-FF-Master bed rm


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

Air System Information


Air System Name ..... (28) AC-5-V1-FF-Master bed rm
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 352.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 1.3
Total coil load ....................................................... 15.9
Sensible coil load .................................................. 12.9
Coil CFM at Jul 1500 ............................................ 586
Max block CFM .................................................... 586
Sum of peak zone CFM ........................................ 586
Sensible heat ratio .............................................. 0.813
ft/Ton ................................................................. 265.7
BTU/(hr-ft) ........................................................... 45.2
Water flow @ 10.0 F rise ..................................... N/A

Tons
MBH
MBH
CFM
CFM
CFM

Load occurs at .................................................. Jul 1500


OA DB / WB ................................................. 115.0 / 85.0
Entering DB / WB ........................................... 77.2 / 64.8
Leaving DB / WB ............................................ 56.8 / 55.7
Coil ADP .................................................................. 54.5
Bypass Factor ........................................................ 0.100
Resulting RH ............................................................... 55
Design supply temp. ................................................. 55.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM ................................................... 586 CFM
Standard CFM ...................................................... 586 CFM
Actual max CFM/ft ............................................... 1.67 CFM/ft

Fan motor BHP ........................................................ 0.00 BHP


Fan motor kW .......................................................... 0.00 kW
Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 0.00 CFM/person

Page 17 of 32

Zone Sizing Summary for (28) AC-5-V1-FF-Master bed rm


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

Air System Information


Air System Name ..... (28) AC-5-V1-FF-Master bed rm
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 352.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
12.0

Design
Air
Flow
(CFM)
586

Minimum
Air
Flow
(CFM)
586

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(MBH)
1.4

Zone
Floor
Area
(ft)
352.0

Zone
CFM/ft
1.67

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
V1M-FF-Master bed rm

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

12.0

Jul 1500

586

1.4

352.0

1.67

Page 18 of 32

Ventilation Sizing Summary for (28) AC-5-V1-FF-Master bed rm


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
V1M-FF-Master bed rm
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

352.0

3.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
586.3
586.3

0.00

Required
Outdoor Air
(CFM/ft)
0.00

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0

0.0

Uncorrected
Outdoor Air
(CFM)
0.0
0.0

Page 19 of 32

Air System Design Load Summary for (28) AC-5-V1-FF-Master bed rm


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.61

08/05/2015
09:00AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 115.0 F / 85.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
70 ft
979
70 ft
341 ft
1394
341 ft
559
352 ft
306
352 ft
441
70 ft
946
70 ft
414
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
320 ft
2497
320 ft
0
0 ft
0
0 ft
0
528 W
1261
0
0
0W
0
0
0
150 W
512
0
0
3
735
615
0
0
0
2301
2212
0
0
0
0
0
0
10% / 5%
1093
141
0%
0
0
12023
2968
1414
0
11677
2968
6
0
0%
0
0
0
70%
714
0
0
30%
540
0
0
586 CFM
0
586 CFM
0
0 CFM
0
0
0 CFM
0
0
586 CFM
0
586 CFM
0
0
0
0%
0
0%
0
12932
2968
6
0
12932
2969
0
0
12932
2969
0
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 20 of 32

Air System Sizing Summary for (29) AC-6-V1-FF-Bed rm 1


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

Air System Information


Air System Name .............. (29) AC-6-V1-FF-Bed rm 1
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 192.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 1.0
Total coil load ....................................................... 11.7
Sensible coil load ................................................... 8.8
Coil CFM at Jul 1700 ............................................ 370
Max block CFM .................................................... 370
Sum of peak zone CFM ........................................ 370
Sensible heat ratio .............................................. 0.750
ft/Ton ................................................................. 197.2
BTU/(hr-ft) ........................................................... 60.9
Water flow @ 10.0 F rise ..................................... N/A

Tons
MBH
MBH
CFM
CFM
CFM

Load occurs at .................................................. Jul 1700


OA DB / WB ................................................. 112.5 / 84.5
Entering DB / WB ........................................... 77.4 / 65.1
Leaving DB / WB ............................................ 55.5 / 54.4
Coil ADP .................................................................. 53.1
Bypass Factor ........................................................ 0.100
Resulting RH ............................................................... 55
Design supply temp. ................................................. 53.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 0.1

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM ................................................... 370 CFM
Standard CFM ...................................................... 370 CFM
Actual max CFM/ft ............................................... 1.93 CFM/ft

Fan motor BHP ........................................................ 0.00 BHP


Fan motor kW .......................................................... 0.00 kW
Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 0.00 CFM/person

Page 21 of 32

Zone Sizing Summary for (29) AC-6-V1-FF-Bed rm 1


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

Air System Information


Air System Name .............. (29) AC-6-V1-FF-Bed rm 1
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 192.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
8.4

Design
Air
Flow
(CFM)
370

Minimum
Air
Flow
(CFM)
370

Time
of
Peak
Load
Jul 1700

Maximum
Heating
Load
(MBH)
0.8

Zone
Floor
Area
(ft)
192.0

Zone
CFM/ft
1.93

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
V1M-FF-Bed rm 1

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

8.4

Jul 1700

370

0.8

192.0

1.93

Page 22 of 32

Ventilation Sizing Summary for (29) AC-6-V1-FF-Bed rm 1


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
V1M-FF-Bed rm 1
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

192.0

3.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
370.1
370.1

0.00

Required
Outdoor Air
(CFM/ft)
0.00

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0

0.0

Uncorrected
Outdoor Air
(CFM)
0.0
0.0

Page 23 of 32

Air System Design Load Summary for (29) AC-6-V1-FF-Bed rm 1


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.61

08/05/2015
09:00AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1700
HEATING DATA AT DES HTG
COOLING OA DB / WB 112.5 F / 84.5 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
47 ft
1058
47 ft
103 ft
682
103 ft
253
192 ft
190
192 ft
240
47 ft
615
47 ft
278
0 ft
0
0 ft
0
0 ft
0
0 ft
0
192 ft
0
192 ft
0
129 ft
987
129 ft
0
0 ft
0
0 ft
0
288 W
688
0
0
0W
0
0
0
150 W
512
0
0
3
735
615
0
0
0
2161
2166
0
0
0
0
0
0
10% / 5%
763
139
0%
0
0
8390
2920
771
0
8026
2920
3
0
0%
0
0
0
70%
442
0
0
30%
295
0
0
370 CFM
0
370 CFM
0
0 CFM
0
0
0 CFM
0
0
370 CFM
0
370 CFM
0
0
0
0%
0
0%
0
8763
2920
3
0
8763
2920
0
0
8763
2920
0
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 24 of 32

Air System Sizing Summary for (30) AC-7-V1-FF-Bed rm 2


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

Air System Information


Air System Name .............. (30) AC-7-V1-FF-Bed rm 2
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 188.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 0.8
Total coil load ........................................................ 9.1
Sensible coil load ................................................... 8.7
Coil CFM at Aug 1500 .......................................... 416
Max block CFM .................................................... 416
Sum of peak zone CFM ........................................ 416
Sensible heat ratio .............................................. 0.953
ft/Ton ................................................................. 247.8
BTU/(hr-ft) ........................................................... 48.4
Water flow @ 10.0 F rise ..................................... N/A

Tons
MBH
MBH
CFM
CFM
CFM

Load occurs at ................................................ Aug 1500


OA DB / WB ................................................. 115.0 / 85.0
Entering DB / WB ........................................... 76.9 / 63.8
Leaving DB / WB ............................................ 57.6 / 56.4
Coil ADP .................................................................. 55.5
Bypass Factor ........................................................ 0.100
Resulting RH ............................................................... 51
Design supply temp. ................................................. 55.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 0.1

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM ................................................... 416 CFM
Standard CFM ...................................................... 416 CFM
Actual max CFM/ft ............................................... 2.21 CFM/ft

Fan motor BHP ........................................................ 0.00 BHP


Fan motor kW .......................................................... 0.00 kW
Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 0.00 CFM/person

Page 25 of 32

Zone Sizing Summary for (30) AC-7-V1-FF-Bed rm 2


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

Air System Information


Air System Name .............. (30) AC-7-V1-FF-Bed rm 2
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 188.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
8.5

Design
Air
Flow
(CFM)
416

Minimum
Air
Flow
(CFM)
416

Time
of
Peak
Load
Sep 1500

Maximum
Heating
Load
(MBH)
0.9

Zone
Floor
Area
(ft)
188.0

Zone
CFM/ft
2.21

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
V1M-FF-Bed rm 2

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

8.5

Sep 1500

416

0.9

188.0

2.21

Page 26 of 32

Ventilation Sizing Summary for (30) AC-7-V1-FF-Bed rm 2


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
V1M-FF-Bed rm 2
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

188.0

2.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
415.8
415.8

0.00

Required
Outdoor Air
(CFM/ft)
0.00

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0

0.0

Uncorrected
Outdoor Air
(CFM)
0.0
0.0

Page 27 of 32

Air System Design Load Summary for (30) AC-7-V1-FF-Bed rm 2


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.61

08/05/2015
09:00AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 115.0 F / 85.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
75 ft
1088
75 ft
91 ft
512
91 ft
203
188 ft
160
188 ft
235
75 ft
1013
75 ft
444
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
433 ft
3379
433 ft
0
0 ft
0
0 ft
0
248 W
593
0
0
0W
0
0
0
150 W
512
0
0
2
490
410
0
0
0
0
0
0
0
0
0
0
0
10% / 5%
775
21
0%
0
0
8521
431
882
0
8046
431
1
0
0%
0
0
0
70%
373
0
0
30%
254
0
0
416 CFM
0
416 CFM
0
0 CFM
0
0
0 CFM
0
0
416 CFM
0
416 CFM
0
0
0
0%
0
0%
0
8673
431
1
0
8673
432
0
0
8673
432
0
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 28 of 32

Air System Sizing Summary for (31) AC-8-V1-FF-Bed rm 3+Fam liv


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

Air System Information


Air System Name . (31)AC-8-V1-FF-Bed rm 3+Fam liv
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 555.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 2.4
Total coil load ....................................................... 28.4
Sensible coil load .................................................. 24.8
Coil CFM at Sep 1500 ......................................... 1156
Max block CFM ................................................... 1156
Sum of peak zone CFM ....................................... 1156
Sensible heat ratio .............................................. 0.874
ft/Ton ................................................................. 234.3
BTU/(hr-ft) ........................................................... 51.2
Water flow @ 10.0 F rise ..................................... N/A

Tons
MBH
MBH
CFM
CFM
CFM

Load occurs at ................................................. Sep 1500


OA DB / WB ................................................. 113.0 / 84.0
Entering DB / WB ........................................... 76.6 / 63.8
Leaving DB / WB ............................................ 56.6 / 55.5
Coil ADP .................................................................. 54.4
Bypass Factor ........................................................ 0.100
Resulting RH ............................................................... 53
Design supply temp. ................................................. 55.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM .................................................. 1156 CFM
Standard CFM ..................................................... 1156 CFM
Actual max CFM/ft ............................................... 2.08 CFM/ft

Fan motor BHP ........................................................ 0.00 BHP


Fan motor kW .......................................................... 0.00 kW
Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .................................................. 0 CFM
CFM/ft ................................................................. 0.00 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 0.00 CFM/person

Page 29 of 32

Zone Sizing Summary for (31)AC-8-V1-FF-Bed rm 3+Fam liv


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

Air System Information


Air System Name . (31)AC-8-V1-FF-Bed rm 3+Fam liv
Equipment Class ....................................... SPLT AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 555.0 ft
Location .......................... Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
23.7

Design
Air
Flow
(CFM)
1156

Minimum
Air
Flow
(CFM)
1156

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(MBH)
2.5

Zone
Floor
Area
(ft)
555.0

Zone
CFM/ft
2.08

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
V1M-FF-Bed rm 3+Liv+corr

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

23.7

Sep 1600

1156

2.5

555.0

2.08

Page 30 of 32

Ventilation Sizing Summary for (31)AC-8-V1-FF-Bed rm 3+Fam liv


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

08/05/2015
09:00AM

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
V1M-FF-Bed rm 3+Liv+corr
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

555.0

6.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
1156.3
1156.3

0.00

Required
Outdoor Air
(CFM/ft)
0.00

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0

0.0

Uncorrected
Outdoor Air
(CFM)
0.0
0.0

Page 31 of 32

Air System Design Load Summary for (31)AC-8-V1-FF-Bed rm 3+Fam liv


Project Name: AL ZAHIA VILLA-EDITED U VALUE - (05-08-15)

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.61

08/05/2015
09:00AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Sep 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 113.0 F / 84.0 F
HEATING OA DB / WB 54.0 F / 45.3 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
152 ft
3975
152 ft
567 ft
1950
567 ft
924
555 ft
427
555 ft
695
152 ft
1941
152 ft
900
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
846 ft
6376
846 ft
0
0 ft
0
0 ft
0
833 W
1988
0
0
0W
0
0
0
300 W
1024
0
0
6
1470
1230
0
0
0
2189
2181
0
0
0
0
0
0
10% / 5%
2134
171
0%
0
0
23475
3581
2518
0
22997
3581
7
0
0%
0
0
0
70%
997
0
0
30%
852
0
0
1156 CFM
0
1156 CFM
0
0 CFM
0
0
0 CFM
0
0
1156 CFM
0
1156 CFM
0
0
0
0%
0
0%
0
24846
3581
7
0
24846
3583
0
0
24846
3583
0
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 32 of 32

Design Weather Parameters & MSHGs


AL ZAHIA VILLA-EDITED U VALUE -(05-08-15)
reyami

08/05/2015
09:02AM

Design Parameters:
City Name .............................................................................................................. Dubai
Location ...................................................................................... United Arab Emirates
Latitude ..................................................................................................................... 25.3
Longitude ................................................................................................................. -55.3
Elevation ................................................................................................................... 16.0
Summer Design Dry-Bulb ....................................................................................... 115.0
Summer Coincident Wet-Bulb .................................................................................. 85.0
Summer Daily Range ............................................................................................... 25.0
Winter Design Dry-Bulb ............................................................................................ 54.0
Winter Design Wet-Bulb ........................................................................................... 45.3
Atmospheric Clearness Number ............................................................................... 1.00
Average Ground Reflectance ................................................................................... 0.20
Soil Conductivity ..................................................................................................... 0.800
Local Time Zone (GMT +/- N hours) .......................................................................... -4.0
Consider Daylight Savings Time ................................................................................ No
Simulation Weather Data .................................................................................. noneN/A
Current Data is ........................................................................................ User Modified
Design Cooling Months .............................................................. January to December

Deg.
Deg.
ft
F
F
F
F
F
BTU/(hr-ft-F)
hours

Design Day Maximum Solar Heat Gains


(The MSHG values are expressed in BTU/(hr-ft) )
Month
January
February
March
April
May
June
July
August
September
October
November
December
Month
January
February
March
April
May
June
July
August
September
October
November
December

N
26.5
29.8
33.3
36.6
42.1
54.2
44.0
38.2
34.3
30.4
26.7
24.9
SSW
242.9
216.9
172.6
113.5
72.7
58.9
70.1
109.1
167.6
208.5
238.0
246.9

NNE
26.5
29.8
43.6
88.1
118.5
128.5
116.9
87.1
41.5
30.4
26.7
24.9
SW
252.7
244.4
216.5
172.9
138.0
121.7
133.0
166.3
207.8
233.2
248.8
250.9

NE
39.4
78.4
119.7
156.5
176.9
180.9
173.1
151.0
116.5
78.7
38.4
24.9
WSW
238.7
243.2
236.2
210.4
188.9
179.2
185.8
202.6
229.1
239.6
234.0
231.8

ENE
124.8
162.7
192.1
204.6
209.5
210.8
208.7
200.2
179.6
151.9
121.6
109.4
W
187.6
218.8
232.7
227.0
218.2
212.4
214.0
219.0
215.8
210.8
191.5
180.8

E
187.6
217.0
233.3
226.7
216.6
211.2
213.6
219.6
221.5
211.7
191.4
176.9
WNW
124.8
162.6
193.1
208.9
214.7
214.0
210.3
202.1
181.4
149.4
117.5
101.8

ESE
238.7
245.1
238.3
214.5
191.7
180.6
186.8
206.0
229.8
238.9
230.3
230.3
NW
39.4
76.1
122.4
159.2
178.9
183.8
175.5
155.2
119.8
79.8
41.5
28.8

SE
252.7
244.3
216.0
170.0
137.5
121.8
131.8
164.4
206.3
234.4
250.0
252.9
NNW
26.5
29.8
42.9
83.3
115.0
125.5
114.2
82.8
38.0
30.4
26.7
24.9

SSE
242.9
216.9
172.2
111.9
71.8
57.9
69.4
107.8
166.1
209.0
239.1
249.2
HOR
208.6
244.1
272.0
281.1
281.0
278.7
277.2
275.0
262.1
237.2
205.4
192.2

S
230.9
196.9
143.7
80.5
49.3
43.9
48.9
78.2
140.2
190.3
226.6
239.8
Mult
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

Mult. = User-defined solar multiplier factor.

Hourly Analysis Program v4.61

Page 1 of 1