You are on page 1of 8

DUPLEX 1500 to 8000

Multi-N Rooftop

DUPLEX 1500 8000 Multi-N is a new generation


of all-purpose ventilation units with counterflow heat recovery
exchangers.
The rooftop version of DUPLEX 1500 8000 Multi-N
compact units are used for comfort ventilation, hot-air
heating and cooling in small facilities, shop floors, stores,
schools, restaurants, shops, sports and industrial halls and
swimming pools.
They are suitable wherever efficient ventilation and possibly
hot-air circulation ventilation and cooling must be provided
atminimum running cost, i.e. the highest efficiency of heat
recovery, low power input of fans and as little noise as
possible.
DUPLEX Multi-N units are compact appliances containing
inasingle cabinet two independently controlled EC fans with
suspended motors, a heat recovery exchanger with large
heat-transfer surface and high efficiency, slide-out supply and
exhaust air class G4, M5 or F7 filters, drain pans and
possibly also an internal bypass with a servo drive and
acirculation damper with a servo drive.
The cabinet has a sandwich structure and consists ofsilver
painted metal sheet panels with 30 mm of PIR fill with an
outstanding heat transfer coefficient ( = 0,024 W/mK).
DUPLEX Multi-N ventilation units meet the
requirements of the most stringent European
standards:
Casing properties according to EN 1886
EC motors according to ErP 2015
3
SFP < 0,45 W/(m /h) according to PassivHaus*
Hygienic requests according to VDI6022

15 0 0 t o 8 0 0 0 M u l t i - N

All-purpose ventilation units


with counterflow heat exchangers

Advantages of DUPLEX Multi-N units:


New design of ventilation units with excellent parameters
Great thermal insulation of the casing (class T3)
Reduced thermal idging (class TB2)
Filter side changing
Elegant and efficient connections through the roof
Compact dimensions
Ease of installation
Variable configuration of discharge ports
Unified dimensions of ports
Optional versions with a bypass and circulation damper
3
High efficiency fans SFP < 0,45 W/(m /h)*
High heat recovery efficiency of the counterflow heat
exchanger up to 93 %
Recessed junction box
Integrated control system including temperature sensors
Integrated web server
Comprehensive design software
*in a limited area

AVAILABLE MODIFICATIONS

B
C
T

(CAN BE COMBINED)

PT
CHF
CHW

with built-in bypass damper


with built-in circulation damper
with built-in hot-water heater

with built-in preheater


with built-in direct chiller
with built-in water-based chiller

OPERATING MODES OF DUPLEX MULTI-N UNITS


i2

Unit ventilators, heat recovery issue 06/2014

T CH

i2

T CH

e2

e2

e2

Mi

Mi

e1

i1

Ventilation with heat recovery


with heating, cooling and preheating

... Fresh outdoor air suction


... Fresh filtered air outlet

Mi

e1

i1

PT

e1
e2

i2

T CH

PT

PT

Ventilation without heat recovery


(via bypass)

Circulation heating
or cooling

i1
i2

e1

i1

... Exhaust air suction


... Exhaust air outlet

T, PT ... Central heating connection


CH ... Cooling connection

SELECTION SOFTWARE

s a v e

y o u r

e n e r g y

For the detailed design of DUPLEX series


units, accessories and control systems
werecommend using our dedicated design
software. You can find it on our website
atwww.atrea.cz or request a CD at our office.

N I T

V E N T I L A T O R S

&

H E A T

ATREA s.r.o., s. armdy 32


466 05 Jablonec n. N.
Czech Republic

R E C O V E R Y

Phone: +420 483 368 111


Fax: +420 483 368 112
E - m a i l : atr ea@ a t r e a . c z
www.atrea.cz

PERFORMANCE GRAPHS
DUPLEX MULTI-N

DUPLEX
Supply air max. 1)
Extraction air max. 1)
Heat recovery efficiency 2)
Number of versions and positions
Weight 3)
Max. power input
Voltage
Frequency
Revolutions
Heating output T max. 4)
Cooling output CHW max. 4)
Cooling output CHF max. 4)
1)
2)

1500
2 500
2 300

m3h-1
m3h-1
%

kg
kW
V
Hz
min-1
kW
kW
kW

2500
3 600
3 650

3500
4 700
4 600

5000
5 500
5 550

6500
7 200
7 100

8000
8 800
8 900

to 93 %
see table Mounting positions, page 4
350 480
405 480
460 560
520 630
2,5
4,4
4,1
6,7
400
400
400
400
50
3 000
2 980
2 420
2 820
27
36
46
67
12
22
30
39
13
25
37
41

290 350
1,5
230
2 920
18
9
10

3)

Maximum flow rate through units at zero external pressure


According to air volume

630 750
8,9
400
2 570
75
46
50

Depending on equipment
Depending on register type, liquid and flow rates

4)

Pressure reserve pst (Pa)

PERFORMANCE SUMMARY

1 000
Supply section (G4)
Supply section with T.3+CHW.5+G4
Supply section with T.3+CHW.5+F7
Exhaust section (G4)

900
800
700
600

DU
EX

PL

500

i-N

ult

0M
50
X 6M112
-N

i-N

ult

ulti

0M
00
X 5M111

ulti5 000

M
00
80113

PLE

PLE

3 000

DU

DU

0M
351010

4 000

2 000

ulti-

1 000

LEX

M1

0
0

-N

ulti

100

0M
25009

0M
50
X 1M108

200

DUP

300

LEX

PLE

DU

DUP

400

6 000

7 000

8 000
9 000
Air volume (m3/h)

Heat recovery efficiency (%)

HEAT RECOVERY EFFICIENCY

100
95
90
85
80
75
70

for te1 = -15 C, ti1 = +20 C, rhi1 = 55 %, Mi = Me


for te1 = +5 C, ti1 = +25 C, rhi1 = 40 %, according to EN 308

2500 Multi-N

1500 Multi-N
0

1 000

2 000

5000 Multi-N

3500 Mu

6500 Multi-N

lti-N

4 000

3 000

8000 Multi-N

5 000

6 000

7 000

8 000
9 000
Air volume (m3/h)

Heating / cooling capacity QT/CH (kW)

HEATING AND COOLING PERFORMANCES

100
Max. heating capacity data T are valid for
70/50 C water temperature dropand +10 C,
r.h. 10 % supply air (after recovery)
Max. cooling capacity data CHW are valid for
30 % water/ethylene-glycol mixture, 6/12 C
temperature drop, +30 C, r.h. 50 % supply air

80
60

lti-N

6500 Mu

ulti-N

40

i-N

lt
1500 Mu

20
0

1 000

2 000

i-N
2500 Mult

5000 M

maximum heating capacity for T.3


maximum cooling capacity for CHF.4 and CHW.5

i-N
3500 Mult
3 000

4 000

ulti-N

8000 M

5 000

6 000

7 000

8 000
9 000
Air volume (m3/h)

DIMENSIONS
BASIC DIMENSIONS

ROOFTOP

BASE FRAME (optional accessorie)

400

B
Y

duct extension
1 000

configuration 4/16

(X+100) x (Y+100)
D

400

22

22

i1
XxY
95

X
D
E

e2
XxY

i1
XxY

75

For position 3 / x

105 X x Y

105

22

105

XxY

XxY

e2
XxY

75

22

XxY

Mi

Me

For position 4 / x

XxY

XxY

B
75

DUPLEX Multi-N
Dimension H
Dimension B
Length L
Dimension N
Dimension U
Dimension P
Dimension J
Dimension M
Condensate drain line
Connecting ports
Dimension X x Y
Base frame
Dimension D
Dimension F
Dimension E
Dimension G (between anchoring holes)
Dimension S
Dimension Q
Dimension T

mm
mm
mm
mm
mm
mm
mm
mm
mm

1500
1 605
555
2 560
130
270
135
100
155

2500
1 605
685
2 560
105
105
105
100
185

3500
1 605
770
2 560
105
105
105
165
205

300 x 300

400 x 400

400 x 400

500 x 500

500 x 500

700 x 500

mm
mm
mm
mm
mm
mm
mm

2 500
1 545
1 228
1 505
795
400
470

2 500
1 545
1 228
1 505
595
300
370

2 500
1 545
1 228
1 505
595
300
370

2 500
1 545
1 228
1 505
395
200
270

2 500
1 545
1 228
1 505
395
200
270

2 590
1 640
1 273
1 600
490
278
287

Outlet port e2

Outlet port i2

Inlet port i1

Inlet port e1

8000
1 700
1 390
2 650
105
105
105
340
350

mm

TYPES AND DIMENSIONS OF CONNECTING PORTS

Y+20

6500
1 605
1 170
2 560
105
105
105
315
355

32

Note: For detailed design and technical data we recommend using our dedicated design software.

X + 20

95

5000
1 605
990
2 560
105
105
105
225
265

INSTALLATION AND VERSIONS OF DUPLEX MULTI-N


INSTALLATION VERSIONS AND CONNECTING PORTS

Detailed drawings are shown in the summary table Mounting


positions.
DUPLEX units are characterised by a wide range
of accessories the ports may be optionally fitted with flexible
flanges, duct extensions or special hoods if required.

DUPLEX 1500 to 8000 Multi-N units are available in a range


ofversions to facilitate their installation on the roof (outside).
Rooftop units enable to go through the roof which is an excellent
solution that saves material and labour costs in ducting and also
significantly saves the energy lost
MOUNTING POSITIONS
Position 3; 4 top view

R O O F T O P U N I T S F L AT

i2

e2

i2

e2
e2

e2

4
3

e1

i1

i1

i1

i1

e1

i1
i1

PORT CONFIGURATION
i2

i2

i2

e2

e2

e2

3/8*

3/10
i1

e1

3/12*
i1

e1

e1
i1

i2

i2

e2

i2

e2

e2
3/14

3/17

3/16

e1

e1

i1

e1

i1

i1
i2

i2

i2

e2

e2

e2

3/19

3/18
e1

e1

3/20*
e1

i1

i1

i1
i2

i2

i2

e2

e2

e2
4/8*

4/12*

4/10
e1

i1

i1

e1

e1
i1

i2

e2

i2

i2

e2

e2
4/14

4/17

4/16
e1

e1

i1

i1

e1

i1
i2

i2

e2

i2

e2
4/18

e2
4/19

e1
i1

* DUPLEX 540010100 Basic-N with max. one coil

i1

4/20*
e1

i1

e1

HANDLING SPACE
MOUNTING POSITIONS CONNECTIONS THROUGH THE ROOF

HANDLING SPACE

condensate drain line. This line must run through a U-bend at least
150 mm high into a sewer. Handling space in front of the unit must
be maintained for replacing filters.
min. 700

DUPLEX units must be installed with the prescribed handling


space around the unit in mind.
Below the unit at least 150 mm must be left to install the DN 32

Handling space

min. 700*

min. T

min.
700*

Mi

Me

min. 700

* only for units with built-in coil

Typ
DUPLEX 1500 Multi-N
DUPLEX 2500 Multi-N
DUPLEX 3500 Multi-N
DUPLEX 5000 Multi-N
DUPLEX 6500 Multi-N
DUPLEX 8000 Multi-N

T (mm)
600
700
800
1 000
1 200
1 400

ACOUSTIC POWER LW AND ACOUSTIC PRESSURE LD1

Type
DUPLEX 1500 Multi-N
DUPLEX 2500 Multi-N
DUPLEX 3500 Multi-N
DUPLEX 5000 Multi-N
DUPLEX 6500 Multi-N
DUPLEX 8000 Multi-N

Working point
1 500 m3/h (200 Pa)
2 500 m3/h (200 Pa)
3 500 m3/h (200 Pa)
5 000 m3/h (200 Pa)
6 500 m3/h (200 Pa)
8 000 m3/h (200 Pa)

inlet e1
57
58
59
69
73
67

Acoustic power Lw [dB(A)]


inlet i1
outlet e2 outlet i2
57
87
88
58
82
82
59
87
88
69
89
89
73
95
95
67
80
80

unit
61
61
59
63
66
71

Acoustic pressure LD1 [dB(A)]


at distance of 1 m
50
50
48
52
55
60

MODIFICATIONS
DUPLEX MULTI-N BASIC UNIT

DUPLEX xxxx Multi-N


Basic configuration
The compact unit consists of supply and exhaust centrifugal fans with electric motors in anti-vibration mounting,
removable counterflow air-to-air heat recovery core assembled from thin plastic plates, removable G4, M5 or F7
supply andexhaust air filters, and a condensate pan with DN 32 flexible hose. Top doors enable easy access to all
built-in components. Front doors for easy filters changing.

Me.xxx; Mi.xxx
Fans
All units are equipped with high-efficiency fans (ebm-papst and Ziehl Abegg) with free-running impellers and backward
curved blades. Whole range of DUPLEX Multi units meets the requirements of the European directive ErP 2015.

S7.C
Heat recovery core
The only heat recovery core type made of plastic in counterflow arrangement with high efficiency up to 93 %.

DUPLEX MULTI-N MODIFICATION DESCRIPTION

B.x
By-pass (B)
By-pass of the plate heat recovery core on supply air side. By-pass consists of an opposed-blade damper
andanactuator.
It is fitted next to the recovery core inside the unit; it does not increase size of the unit.
The standard actuator is BELIMO 24 V; other types are available upon request.

C.x
Mixing damper (C)
The mixing damper is used to mix exhaust and supply air. Circulation valve consists of an opposed-blade damper and
actuator. It is fitted next to the recovery core inside the unit, it does not increase the size of the unit.
The standard actuator is BELIMO 24 V; other types are available upon request.

T.x
H o t w a t e r h e a t i n g c o i l ( T )
Built-in water-to-air three-row (possibly five-row) heating coil; made of copper pipes and aluminum fins. Designed
forsystems up to 110 C and 1,0 MPa. The coil is standardly equipped with flexible connection and a steam-gas
capillary thermostat for freeze protection. Units in modification T (with heating coil) must be equipped with e1 supply
air shutoff damper; an actuator with spring-return function is reccommended. A coil hydraulic kitforheating capacity
control of RE-TPO4 or RE-TPO3 type can be supplied with the coil upon request.
Due to roof installation we strictly recommend to use non-freezing liquid.
CHF.x
Direct expansion (DX) coil (CHF)
A built-in coil made of copper pipes and aluminum fins, including a condensate pan with individual condensate drainage
and a pressure switch for freeze alarm. Three- or four-row coils with various evaporate temperature are chosen
depending on capacity required, refrigerant type and air parameters. Optionally it is possible to deliver double-circuit
evaporator in division 1:1 or 1:2, or completely atypical with needed capacity.

Chilled water cooling coil (CHW)

CHW.x

A built-in coil made of copper pipes and aluminum fins, including a condensate pan with individual condensate drainage.
Three- orfive-row coils are chosen depending on capacity required, cooling medium type and air parameters.
The cooling coil can be equipped with the R-CHW2 or R-CHW3 hydraulic kit on request.

Integrated pre-heater (PT)

PT.x

Built-in water-to-air three-row heating coil; made of copper pipes and aluminum fins. Designed forsystems up to 110 C

and 1,0 MPa. Non-freezing liquid must be used.

Individual modifications can be freely combined


Example:
DUPLEX-TC (unit with a hot-water heating coil and a mixing damper)
DUPLEX-T-CHF (unit with a hot-water heating coil and a DX coil)

ACCESSORIES
OTHER OPTIONAL ACCESSORIES (BASIC OVERVIEW)

Ke.xxx; Ki.xxx
Shutoff damper e1; i1
Shutoff dampers standardly fitted with BELIMO
actuators are located in the air inlet port.
The following damper types are available:
-- fresh air damper e1 mandatory for C
modification (with mixing damper) and T,
PTmodification (with heating coil)
-- exhaust air damper i1

Fe.xxx; Fi.xxx
Air filtration
All DUPLEX Multi-N units can be equipped with
supply or exhaust air filtration of M5 or F7 class
instead of standard G4 class. Pressure drop of
the filter is then 50 to100 Pa (clean filter)
depending on air flow rate, unit type and dirt
accumulated.

RE-TPO.x
Heating coil
hydraulic kit
Its function is to control heating capacity
ofaheating coil. It consists of a three-speed
pump, two globe shutoff valves and connection
pipes. Further equipment depends on the type:
RE-TPO4 four-way mixing valve with
anactuator for digital control system
RE-TPO3 three-way mixing valve with
anactuator for digital control system

R-CHW.x
Cooling coil
hydraulic kit
Its function is to control cooling capacity of
achilled-water cooling coil. It always consists
oftwo globe shutoff valves and connection pipes.
Further equipment depends on the type:
R-CHW3 three-way mixing valve with
anactuator
R-CHW2 throttling valve with an actuator for
digital control system

Hot water heating coil (TPO)


Separately supplied coil for installation into
round duct.
It is suitable for cramped locations, where
itisimpossible to put the coil inside the unit,
aswell as for rooftop units.
The coil is standardly equipment with the steamgas capillary thermostat.

Electric heating coil (EPO-V)


Separately supplied heating coil to be fitted
into round or rectangular duct. Capacities and
diameters canbefound in respective
catalogue sheets.

FK.x
Spare cartride
filters
Replacement filter cartridges in different sizes
based on the unit type. Available in F5 and F7
filtration class.

H.P
Flexible
connections
Ports can be equipped with flexible connections
upon request.

CF.XXX
Constant air flow
and pressure
Manometers reading fan pressure together
with controls, enables intelligent fan control of
preselected airflow. This accessory assumes
the unit is equipped with digital controls of DC or
RD4 type. Using a second manometer (optional
accessory) in the supply air duct enables the
user to control constant pressure in the supply
duct.

Duct extension
Rectangular duct extension for connection
through the roof. Standard lenght is 1 m.

MFF
Tu b e m a n o m e t e r s
Accessory for filters for simple view of current
pressure drop. The tube manometers are
obligatory for hygienic unit design in accordance
with the VDI 6022.

Base frame
Dismountable base frame with integrated PIR
(30 mm) insulation and service doors. Standard
heigh 400 mm, others on request.

Feets
The Multi-N units can be equipped with an
adjustable feets (alternative to base frame).

Special hoods
Special weatherproof hoods for inlet (e1) and
outlet (i2) ports. The hood for e1 port in combine
with integrated droplet eliminator.

CONTROLS
DUPLEX Multi-N units are delivered with basic control
components or with complete control systems.
There are three types ofcontrol systems available (basic,
RD4 or DC) according tocustomer needs and an application.
The systems also include variety of sensors (temperature,
humidity, air quality, CO2) for effective operation control.

Features of the control systems


selection of the most suitable and efficient control
system atthe lowest cost, depending on the particular
application
control system is integrated with the unit, most
components arealready wired and checked in factory,
thus reducing the risk of incorect wiring
no control system project documentation is necessary
forstandard cases, standardized solutions can be used
simple wiring, system simplicity, error indication
qualified technical support and consulting

SUMMARY OF DUPLEX MULTI CONTROL SYSTEMS

Type

Use

basic

all electrical components are wired to a junction box


terminal strip inside or outside the unit
standard components are fans, damper actuators,
capillary freeze protection thermostat of hot water
heating coil
more components is included upon customer's
request (exact actuator type, sensors, thermostats,
pressure switches etc.)
suitable for applications with separate delivery of
control system; e.g. large buildings with central control
system etc.

RD4 controls

Standard functions of the RD4 controls


EC fan speed control (based on selected mode)
automatic by-pass damper position (heat and cool
recovery)
evaluates and prevents emergency limits based on
measured temperature
ventilation and temperature weekly program setting
A web server and an Ethernet interface built in as
standard connection for remote internet
communication
inputs for switching using 230 V
(4 inputs 3delayed, 1instantenious) switch e.g.
from bathrooms etc.
optional connection of CO2 or RH sensor
max. 2 sensors with a switch or 010 V output
outputs for electric preheater and heater control
(pulse 10 V) or hot-water control (010 V)
Additional RD4-IO modules
optional manometer connection to ensure constant
airflow control (see Constant airflow and pressure
control on previous page)
constant pressure control
cooling control outputs (DX- or chilled-water cooling)

Controller

basic version
(fans, actuators, thermostats,
pressure switches
and others on request)

Supervisory control system

CP 18 RD
installation in the standard
recessed dual box on the wall

CP 19 RD
installation on wall

Web server
(Standard)

Application for
Smartphones

You might also like