DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

SHEET OF
i i
OF 4

SAUDI ELECTRICITY COMPANY


EASTERN OPERATING AREA
Dammam, Saudi Arabia
GENERATION EXPANSION OF RAFHA POWER PLANT
(CONTRACT NO :30421008/00)
DESIGN BASIS REPORT
FOR
LIGHTING AND SOCKET SYSTEMS
DOCUMENT NO. : 30421008-3CL-00019-P0A
OCTOBER 2004

ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST. MARKS ROAD
BANGALORE 560 001
INDIA

CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O. BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL. 00966-1-4633660 : FAX. 009661-4631150

P0A
29-10-2004

MP

SR

REV NO . DATE

PREPARED BY

CHECKED BY

CLEARED BY

APPROVED BY
TCE FORM 032 R1

TCE CONSULTING ENGINEERS LIMITED


30421007-3CL-00019-

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

CONTENTS
SHEET OF
i i
OF 4

CONTENTS

CLAUSE No.

DESCRIPTION

PAGE NO

1.0

INTRODUCTION

01

2.0

OBJECT

02

3.0

REFERENCE DOCUMENTS & STANDARDS

03

4.0

DESIGN BASIS

04

5.0

DESIGN CALCULATIONS FOR LIGHTING


SYSTEM

11

ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

WRITEUP
SHEET 1 OF 15
OF 4

1.0

INTRODUCTION:

1.1

Al-Toukhi company for Industry & Trading has been awarded


turnkey contract for Open Cycle Gas Turbine based CPS expansion
project at Rafha of Saudi Electric Company-Eastern Operation Area
(SEC-EOA), Saudi Arabia.
The project consists of design, engineering, procurement,
installation, testing and commissioning of two (2) Nos. 29.92MW @
50C, Gas Turbine Generator unit of GE make along with associated
Generator

1.2

ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

2.0
2.1

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

WRITEUP
SHEET 2 OF 15
OF 4

OBJECT:
The scope of this document is to describe the Lighting and Socket
systems proposed to be provided for different buildings and associated
auxiliaries/facilities for the extension area completely.

ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

3.0

REFERENCE DOCUMENTS & STANDARDS

3.1

IES Lighting Handbook

3.2

National Electrical Code (NEC): NFPA 70

3.3

National Electrical Safety Code: ANSI/IEEE C.2

3.4

SEC-ERB Engineering standard SES-P-119.25

3.5

Scope of work and Technical Specification PTS-1024

WRITEUP
SHEET 3 OF 15
OF 4

ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

4.0

DESIGN BASIS:

4.1

Lighting system

WRITEUP
SHEET 4 OF 15
OF 4

4.1.1 The lighting system shall comprise the following two (2) categories:
a)
b)

Normal 127V AC Lighting System


Emergency DC Lighting System

4.1.2 Normal 127V AC Lighting System


In this system, the lighting circuits shall be fed by normal AC supply
through 3 phase, 4 wire lighting distribution boards. All the lighting
fixtures connected to this system shall be available as long as supply is
available from normal source through 480V/220V lighting transformer.
4.1.3 DC & Emergency Lighting System
i)

DC Emergency Lighting :
DC Emergency lights would be fed from DC emergency lighting
panel, which in turn will be fed from 125V station DC distribution
board.(DCDB)
These DC emergency lights would be provided in all rooms with
a facility for manual switching in each room.
Emergency lighting main supply would be automatically
switched on in the event of normal AC lighting failure.

ii)

Exit Lighting :
Exit Light with self contained sealed lead acid rechargeable
standby batteries suitable for 90 minutes illumination and
charger circuit, connected to a dedicated 127Vac-branch circuit,
shall be provided near all the exit doors.

iii)

Emergency Lighting
This shall be provided by emergency lighting fixtures located
strategically in critical operating area and emergency exits.
These lights shall be ON all the time, normally from the normal
AC supply. In case of failure of normal AC system, these lights
shall be energised from the DC supply obtained from integrated

ISSUE
P0A

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

WRITEUP
SHEET 5 OF 15
OF 4

rechargeable batteries through automatic switching. The change


over in the reverse direction will also be automatic. The duration
of emergency lighting shall be 3 hours.
4.2

Main Lighting Distribution Board(MLDB) and Sub Lighting Distribution


Boards(SLDB)

4.2.1 The Main Lighting Distribution board would be provided with two MCCB
controlled incomers and a MCCB controlled Bus coupler with Auto
Changeover scheme. Both the incomers would be fed through
480V/220V dry type lighting transformers, Dyn11 with off circuit taps
5% in steps of 2.5%. The lighting transformer shall be cast resin dry
type and shall be housed in the incomer panel.
The main lighting distribution board located in Main Switchgear building
fed from the 480V Sub Distribution board consist of 2 nos of MCCB
controlled incoming feeders and MCBs controlled 3 phase 4 wire
outgoing feeders feeding Sub Lighting Distribution Boards(SLDB) for
the following areas.
a)
b)
c)
d)
e)
f)

SLDB for Switchgear Room


SLDB for Control Room
SLDB for GTG hall
SLDB for Fuel tank area
SLDB for Outdoor area
SLDB for Street Lights

4.2.2 The Sub Lighting Distribution Boards (SLDB) shall have :


a)

1 No. 3 phase 4 wire incoming feeder controlled by earth


leakage circuit breaker and number of single-phase outgoing
circuits controlled by MCBs. This feeder arrangement is used to
feed all the indoor lighting system.

b)

SLDBs feeding street lighting and outdoor area lighting will be


provided with three phase outgoing feeder circuits controlled by
MCBs.
SLDBs feeding the street lighting & outdoor area shall
ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

WRITEUP
SHEET 6 OF 15
OF 4

be provided with contactors for control from a remote point.


Automatic switching ON/OFF of these circuits shall be done
through timers/photo cell.
4.2.3 Lighting fixtures in indoor areas shall be controlled from the respective
SLDBs.
4.2.3 Individual control in office rooms shall be through single pole flush type
switches / MCBs.
4.2.5. The distribution of lighting fixtures/receptacles shall be such that the
loading on each phase of the SLDB is approximately equal.
4.2.6 125V DC emergency lighting fixture would be fed through separate DC
emergency lighting panels which in turn are fed from 125V DC
Distribution Boards.
4.3.

The illumination levels required for various buildings in the plant viz.;
GTG building, Main switchgear room, Battery room, & outdoor
area/streets would be selected as per Cl.No: 6.20.15 of PTS-1022
page 251 of 336 as given below.

4.3.1 Illumination Levels:


Sl.
No.

Area/Structure

Average
Illumination
Level in Lux

Type of Fixture

Type of
Luminaire

Transformer yard

20

General Purpose
Flood light
Medium beam

1 X 150W HPSV

Outdoor areas

20

Weather proof,
Dust proof
medium beam

150 W HPSV
lamp.150W
HPMV lamp

GTG Power House

200

Highbay Lighting
fixtures
suspended from
structured ceiling
members

1x70 W/ 1x150
W HPMV lamp

Switchgear room

300

Industrial type

Energy Efficient

ISSUE
P0A

FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

Sl.
No.

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

Area/Structure

Average
Illumination
Level in Lux

WRITEUP
SHEET 7 OF 15
OF 4

Type of Fixture

Type of
Luminaire

with vitreous
enamel reflector

FTL 2 x 40W

5.

Control Room

400

Mirror Optic
Recess mounted

2 x 40W ,
3 x 40W FTL

6.

Battery rooms

200

Acid Corrosionproof

Energy Efficient
FTL 2 x 40W

7.

Toilets, stairs, etc,.

100

Channel mounted
box type

Energy Efficient
FTL 2 x 40W

8.

Streets

50

Street light with 1 x 250W HPSV


clear acrylic cover
cut-off type with
integral mounted
control gear

9.

Fuel
Unloading
Pump Shed

200

Industrial type
with vitreous
enamel reflector

Energy Efficient
FTL 2 x 40 W

10

Fuel
Forwarding
Pump shed

150

Industrial type
with vitreous
enamel reflector

Energy Efficient
FTL 2 x 40W

11.

DC
Emergency
Lighting

10

Incandescent
lamps

60W, 125V DC

Note: The stack aviation lighting is not part of the DBR


4.3.2 The types of luminaires selected are based on the mounting height.
a)

If the mounting height is equal to or less than 4 mtrs, then


fluorescent type luminaires are selected.

b)

If the mounting height is between 6 mtrs & 4 mtrs then the low
bay type fixtures are selected.

ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

4.4

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

WRITEUP
SHEET 8 OF 15
OF 4

c)

If the mounting height is between 8 mtrs & 6 mtrs, then medium


bay type fixtures are selected.

d)

For all mounting height greater than 8 mtrs, high bay type
fixtures are selected.

e)

For street lighting, pole mounted streetlight type luminaires are


used.

f)

The street lighting pole height is maintained as 8 mtrs, and for


area lighting, a pole height of 10mtrs is adopted.

Lamps & Luminaires:

4.4.1 Outdoor lighting

4.4.2

i)

High Pressure sodium vapour & High pressure mercury vapour


lamp shall be generally outdoor weather proof and dust proof
type with degree of protection IP 55 suitable for conduit
mounting.

ii)

The luminaire may be provided with integral mounted control


accessories

Street Lighting Luminaires


250 watts High pressure sodium vapour lamps shall be provided with
integral controlgear.

4.4.3 Fluorescent Luminaires


1.

These luminaires shall be generally industrial type provided with


cold rolled cold annealed (CRCA) sheet steel channel / rail cum
reflector housing complete with all electrical control accessories
mounted on it. The finish shall be stove enamelled.

2.

Luminaires shall be suitable for the number of lamps of specified


wattage (generally 1 or 2 lamps of 40W), direct mounting on
ceiling / wall/ column pendant mounting.
ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

3.

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

WRITEUP
SHEET 9 OF 15
OF 4

Low loss electronic ballasts shall be provided for all


fluorescent lamp luminaires.

4.4.4 Bulk head luminaire:


The luminaire shall be robust construction, cast aluminium / vitreous
enamelled housing, heat and shock resistant prismatic or clear glass
cover fixed with neoprene gaskets for sealing. For mechanical
protection to the glass cover, round steel wire guard with vitreous
enamelled finish shall be provided. The luminaire shall be suitable for
incandescent lamp upto 150 watts, for direct mounting to ceiling / wall /
column and is used for general-purpose indoor lighting.
4.4.5 Lamps
Lamps shall be capable of withstanding small vibrations and the
connections at lead in wires and filaments / electrodes shall not break
under such circumstances.
a)

Incandescent lamps
General lighting service (GLS) lamps shall be tungsten filament
incandescent type. The filament shall be coiled coil type rated
for 127 volts, single phase AC.

b)

Gas Discharge Lamps


(I)

Fluorescent Lamps
Fluorescent lamp luminaires shall be with low wattage
consumption, high efficiency and longer burning life.
Lamps shall be of warm white or cool day light type with
triband phosphor coated type, suitable for operation on
127V, single phase AC, in standard lengths of 1200mm.

(II)

High Intensity Discharge Lamps


These lamps include the high pressure sodium vapour
lamp operating at 127V
High pressure sodium vapour lamps shall be with
polycrystalline translucent, coated discharge tube, coated
ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

WRITEUP
SHEET 10 OF 15
OF 4

shell, quick restrike time (of within 5 minutes) in standard


ratings upto 400 watts would be used.
4.5

Sockets (Power Receptacles)

4.5.1 One (1) number 3 phase, 480 V AC, 200A, outdoor power receptacle
complete with male/female connector assembly with a fuse disconnect
switch/MCCB housed in weather proof IP54 enclosure, shall be
provided at the Main generator transformer bays for power supply to oil
treatment/filtration equipment. This would be fed from 480V Station
switchgear.
4.5.2 One (1) number 127V AC, 20A, galvanised finish IP54 weather proof
steel clad receptacle/outlets with spring flap cover shall be provided on
each lighting pole and transformer area for supplying power to
inspection lamps. All these receptacles shall be fed from AC lighting
panels.
4.5.3 Sufficient 480 V AC, 60A, 3 phase weather proof, IP54 welding
receptacles shall be provided at approved strategic locations and within
30 meters from power transformers and shall be mounted on structure
or equipment supporting columns. These shall be fed from the main LV
AC distribution boards.
4.5.4 127V, 60 Hz, 3 pin Power Receptacles shall be provided in all
building/areas of the plant. Inside a building, receptacles shall be
provided at interval of 10-15m or part there of for hand tools, water
coolers, exhaust fans etc. Inside each plant area, minimum two
receptacles shall be provided and the same shall be indoor/outdoor as
per the location. These receptacles would be fed from lighting panels.
4.5.5 Receptacle units shall consist of socket outlet with associated switch
and plug. The socket outlet and switch or MCB shall be flush mounted
within a stove enamelled/ galvanised 1.2-mm thick CRCA sheet steel
enclosure. The box may be recessed into or mounted on a wall/column
made of RCC, brick, or steel as per the location in a standard
arrangement.
4.5.6 The outdoor type receptacles shall be housed in a 2 mm thick CRCA
sheet steel epoxy painted enclosure with gaskets, hinged door having
locking arrangement. The enclosure shall be with rain canopy and
removable gland plate entry from bottom. Composite receptacle with
switch modules housed in a box shall be with degree of protection IP
54
ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

5.0
5.1

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

WRITEUP
SHEET 11 OF 15
OF 4

DESIGN CALCULATIONS FOR LIGHTING SYSTEM:


Indoor Lighting
The recommended values of illumination level for various areas in the
plant as indicated would be followed for estimating the number of
lighting fixtures. Following factors would be considered while arriving
at the utilisation factor to determine the number of fixtures for each
area/buildings in the plant.
Maintenance Factor:
(a)
(b)
(c)

Air conditioned clean interiors like


office rooms,

0.8

Industrial areas with normal interiors such


GTG hall

0.7

Industrial areas with dusty interiors


:
such as fuel oil forwarding & Unloading sheds

0.6

Reflection factor for wall/ceiling


(a)
(b)
(c)
(d)

White and very light colours


Light colours
Middle tints
Dark colours

:
:
:
:

0.7
0.5
0.3
0.1

The reflectance of the floor, wall, & ceiling would be taken based on the
type of floor, roof, & ceiling finishes present in the respective buildings
The working plane would be considered at 0.85 m from the floor level.
The suspension height for suspended fixtures would not exceed 1
meter.
The emergency lighting system shall provide average maintained
illumination level of 10 lux measured at the floor.

ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

5.2

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

WRITEUP
SHEET 12 OF 15
OF 4

Outdoor Lighting
The recommended illumination levels for outdoor areas are 50 Lux for
roads, 20 for transformer area.
Mounting height, spacing of area/street lights shall be based on lamp
wattage, uniformity of illumination and vertical angles.
Maintenance factor shall be generally 0.6 under average conditions.
For outdoor lighting i.e. around the buildings provision to be made with
150W outdoor type flood light type lamps mounted on wall.
Automatic switching ON/OFF shall be through timers/photo cells.

5.3

Calculation for Number of fitting


The following formula per lumen method shall be used for general
lighting to estimate the quantity of fixture (N) needed to illuminate the
indoor areas:
N=

Emaintained x Workplane area


Lamps per luminaire x LL x CU x LLF

Where,
N
E
LL
CU
LLF
LLD
LLD

=
=
=
=
=
=
=

Number of luminaries or, fixture


illumination
initial rated lamp lumens
coefficient of utilisation
Light-loss factor (i.e. LLD x LLD x Ballast factor)
Lamp Lumen Depreciation
Lamp Dirt Depreciation

Alternatively, Sub vendors software would be used for calculating the


number of fixtures and the outputs of the software would be furnished
along with the layouts.
5.4

Lighting circuit design


In an area, the lighting fixtures would be arranged in different phases
such that even in case one lighting phase is faulty, complete lighting
is not affected.
ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

WRITEUP
SHEET 13 OF 15
OF 4

The circuit loading on each circuit shall be restricted to 80% of the


MCB rating.
The voltage drop from SLDB and any fixture shall not exceed 3%.
5.5

Wires, cables, conduits and junction boxes

5.5.1 Conductor size for power receptacles and lighting circuits shall be
selected taking into consideration the voltage drop (as indicated
above), but in no case it shall be less than 4 mm 2 stranded copper.
5.5.2 Wires used for conduit point wiring of lighting fixtures/exhaust fans and
receptacles shall be 1100 V grade, PVC insulated, single core,
stranded copper conductor wires. In general, concealed wiring would
be adopted for Main switchgear building, etc. where RCC structure
exists. For GTG building etc. where steel structures are present,
exposed conduits would be used. Pull boxes would be provided near
light fittings & where conduit drops down to switch box.
5.5.3 All conduit wiring, concealed or exposed wiring shall have provision for
easy inspection. Exposed wiring when run along wall would be as near
the ceiling as possible. Due consideration would be given for neatness
and appearance.
5.5.4 Wires of different phases would be run in separate conduits. However,
wires of same phase but having different circuit nos. can be run in
same conduit. Wires of lighting and 3 phase power receptacles shall
be carried out in separate conduits and on separate circuits.
5.5.5 Wherever lighting system has three phase distribution, separate
conduits would be used for different phases. For easy identification of
phases and neutral wires the following colour wires shall be used.
i)
ii)
iii)
iv)

R - Phase
Y - Phase
B - Phase
Neutral

Red
Yellow
Blue
Black

5.5.6 All receptacles and switches to be installed in offices buildings would


be flush mounted within the wall and those in other areas would be wall
or column mounted.
5.5.7 Rigid PVC/galvanised sheet steel junction boxes with adequate
number of outlets/ways, suitable of the conduit entry would be provided
ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

WRITEUP
SHEET 14 OF 15
OF 4

in the circuits wherever required. Grounding screw shall be provided in


each junction box.
5.5.8 In Main switchgear room the wires would be routed through Rigid PVC
conduits of minimum 25mm size concealed in wall.
5.5.9 GTG building and in other steel structured area the wires shall be
routed through Rigid galvanised steel conduits of minimum 25mm size
installed on wall surface/structures/ceiling surface.
5.5.10 The cables shall be routed through duct banks/ cable trenches inside
buildings as best suited. Outside, the cables shall be directly buried at
900mm below FGL, At the road crossing, these cables shall be routed
through 110mm dia. PVC conduits (directly buried at a depth of
750mm). Warning tile & tape shall be provided at 300mm above the
cable.
5.6

Earthing
All exposed metal parts of the plug, when the plug is in complete
engagement with the socket outlet, shall be in effective electrical
connection with the earthing pin.

5.7

Mounting
Socket outlets & welding receptacles shall be mounted at 750mm from
FFL.

5.8

Light Control Switches


Light control switches of ratings and types, i.e. decorative/industrial,
shall be used. The switches shall be suitable for use on 220/127 V, 1
phase, 60 Hz supply.
Switches shall be of flush type for mounting behind an insulated plate
or incorporated with a switch or switch box/suitable enclosure. The
switch box/ enclosure may be recessed into or mounted on wall as per
the requirements of project layouts.
Lighting switches and receptacles shall be modular type.
Light control switches where applicable, would be mounted at 1500mm
from FFL.
ISSUE
P0A
FORM NO. 120 R1

TCE CONSULTING ENGINEERS LIMITED


30421008-3CL-00019-

DESIGN BASIS REPORT FOR LIGHTING AND


SOCKET SYSTEMS

WRITEUP
SHEET 15 OF 15
OF 4

Normally, lighting fixtures would be controlled from SLDBs except in


office room, where light control switches would be provided to control
the light fitting in that room..

ISSUE