1.0
INTRODUCTION
01
2.0
OBJECT
02
3.0
03
4.0
DESIGN BASIS
04
5.0
11
ISSUE
P0A
FORM NO. 120 R1
WRITEUP
SHEET 1 OF 15
OF 4
1.0
INTRODUCTION:
1.1
1.2
ISSUE
P0A
FORM NO. 120 R1
2.0
2.1
WRITEUP
SHEET 2 OF 15
OF 4
OBJECT:
The scope of this document is to describe the Lighting and Socket
systems proposed to be provided for different buildings and associated
auxiliaries/facilities for the extension area completely.
ISSUE
P0A
FORM NO. 120 R1
3.0
3.1
3.2
3.3
3.4
3.5
WRITEUP
SHEET 3 OF 15
OF 4
ISSUE
P0A
FORM NO. 120 R1
4.0
DESIGN BASIS:
4.1
Lighting system
WRITEUP
SHEET 4 OF 15
OF 4
4.1.1 The lighting system shall comprise the following two (2) categories:
a)
b)
DC Emergency Lighting :
DC Emergency lights would be fed from DC emergency lighting
panel, which in turn will be fed from 125V station DC distribution
board.(DCDB)
These DC emergency lights would be provided in all rooms with
a facility for manual switching in each room.
Emergency lighting main supply would be automatically
switched on in the event of normal AC lighting failure.
ii)
Exit Lighting :
Exit Light with self contained sealed lead acid rechargeable
standby batteries suitable for 90 minutes illumination and
charger circuit, connected to a dedicated 127Vac-branch circuit,
shall be provided near all the exit doors.
iii)
Emergency Lighting
This shall be provided by emergency lighting fixtures located
strategically in critical operating area and emergency exits.
These lights shall be ON all the time, normally from the normal
AC supply. In case of failure of normal AC system, these lights
shall be energised from the DC supply obtained from integrated
ISSUE
P0A
WRITEUP
SHEET 5 OF 15
OF 4
4.2.1 The Main Lighting Distribution board would be provided with two MCCB
controlled incomers and a MCCB controlled Bus coupler with Auto
Changeover scheme. Both the incomers would be fed through
480V/220V dry type lighting transformers, Dyn11 with off circuit taps
5% in steps of 2.5%. The lighting transformer shall be cast resin dry
type and shall be housed in the incomer panel.
The main lighting distribution board located in Main Switchgear building
fed from the 480V Sub Distribution board consist of 2 nos of MCCB
controlled incoming feeders and MCBs controlled 3 phase 4 wire
outgoing feeders feeding Sub Lighting Distribution Boards(SLDB) for
the following areas.
a)
b)
c)
d)
e)
f)
b)
WRITEUP
SHEET 6 OF 15
OF 4
The illumination levels required for various buildings in the plant viz.;
GTG building, Main switchgear room, Battery room, & outdoor
area/streets would be selected as per Cl.No: 6.20.15 of PTS-1022
page 251 of 336 as given below.
Area/Structure
Average
Illumination
Level in Lux
Type of Fixture
Type of
Luminaire
Transformer yard
20
General Purpose
Flood light
Medium beam
1 X 150W HPSV
Outdoor areas
20
Weather proof,
Dust proof
medium beam
150 W HPSV
lamp.150W
HPMV lamp
200
Highbay Lighting
fixtures
suspended from
structured ceiling
members
1x70 W/ 1x150
W HPMV lamp
Switchgear room
300
Industrial type
Energy Efficient
ISSUE
P0A
Sl.
No.
Area/Structure
Average
Illumination
Level in Lux
WRITEUP
SHEET 7 OF 15
OF 4
Type of Fixture
Type of
Luminaire
with vitreous
enamel reflector
FTL 2 x 40W
5.
Control Room
400
Mirror Optic
Recess mounted
2 x 40W ,
3 x 40W FTL
6.
Battery rooms
200
Acid Corrosionproof
Energy Efficient
FTL 2 x 40W
7.
100
Channel mounted
box type
Energy Efficient
FTL 2 x 40W
8.
Streets
50
9.
Fuel
Unloading
Pump Shed
200
Industrial type
with vitreous
enamel reflector
Energy Efficient
FTL 2 x 40 W
10
Fuel
Forwarding
Pump shed
150
Industrial type
with vitreous
enamel reflector
Energy Efficient
FTL 2 x 40W
11.
DC
Emergency
Lighting
10
Incandescent
lamps
60W, 125V DC
b)
If the mounting height is between 6 mtrs & 4 mtrs then the low
bay type fixtures are selected.
ISSUE
P0A
FORM NO. 120 R1
4.4
WRITEUP
SHEET 8 OF 15
OF 4
c)
d)
For all mounting height greater than 8 mtrs, high bay type
fixtures are selected.
e)
f)
4.4.2
i)
ii)
2.
3.
WRITEUP
SHEET 9 OF 15
OF 4
Incandescent lamps
General lighting service (GLS) lamps shall be tungsten filament
incandescent type. The filament shall be coiled coil type rated
for 127 volts, single phase AC.
b)
Fluorescent Lamps
Fluorescent lamp luminaires shall be with low wattage
consumption, high efficiency and longer burning life.
Lamps shall be of warm white or cool day light type with
triband phosphor coated type, suitable for operation on
127V, single phase AC, in standard lengths of 1200mm.
(II)
WRITEUP
SHEET 10 OF 15
OF 4
4.5.1 One (1) number 3 phase, 480 V AC, 200A, outdoor power receptacle
complete with male/female connector assembly with a fuse disconnect
switch/MCCB housed in weather proof IP54 enclosure, shall be
provided at the Main generator transformer bays for power supply to oil
treatment/filtration equipment. This would be fed from 480V Station
switchgear.
4.5.2 One (1) number 127V AC, 20A, galvanised finish IP54 weather proof
steel clad receptacle/outlets with spring flap cover shall be provided on
each lighting pole and transformer area for supplying power to
inspection lamps. All these receptacles shall be fed from AC lighting
panels.
4.5.3 Sufficient 480 V AC, 60A, 3 phase weather proof, IP54 welding
receptacles shall be provided at approved strategic locations and within
30 meters from power transformers and shall be mounted on structure
or equipment supporting columns. These shall be fed from the main LV
AC distribution boards.
4.5.4 127V, 60 Hz, 3 pin Power Receptacles shall be provided in all
building/areas of the plant. Inside a building, receptacles shall be
provided at interval of 10-15m or part there of for hand tools, water
coolers, exhaust fans etc. Inside each plant area, minimum two
receptacles shall be provided and the same shall be indoor/outdoor as
per the location. These receptacles would be fed from lighting panels.
4.5.5 Receptacle units shall consist of socket outlet with associated switch
and plug. The socket outlet and switch or MCB shall be flush mounted
within a stove enamelled/ galvanised 1.2-mm thick CRCA sheet steel
enclosure. The box may be recessed into or mounted on a wall/column
made of RCC, brick, or steel as per the location in a standard
arrangement.
4.5.6 The outdoor type receptacles shall be housed in a 2 mm thick CRCA
sheet steel epoxy painted enclosure with gaskets, hinged door having
locking arrangement. The enclosure shall be with rain canopy and
removable gland plate entry from bottom. Composite receptacle with
switch modules housed in a box shall be with degree of protection IP
54
ISSUE
P0A
FORM NO. 120 R1
5.0
5.1
WRITEUP
SHEET 11 OF 15
OF 4
0.8
0.7
0.6
:
:
:
:
0.7
0.5
0.3
0.1
The reflectance of the floor, wall, & ceiling would be taken based on the
type of floor, roof, & ceiling finishes present in the respective buildings
The working plane would be considered at 0.85 m from the floor level.
The suspension height for suspended fixtures would not exceed 1
meter.
The emergency lighting system shall provide average maintained
illumination level of 10 lux measured at the floor.
ISSUE
P0A
FORM NO. 120 R1
5.2
WRITEUP
SHEET 12 OF 15
OF 4
Outdoor Lighting
The recommended illumination levels for outdoor areas are 50 Lux for
roads, 20 for transformer area.
Mounting height, spacing of area/street lights shall be based on lamp
wattage, uniformity of illumination and vertical angles.
Maintenance factor shall be generally 0.6 under average conditions.
For outdoor lighting i.e. around the buildings provision to be made with
150W outdoor type flood light type lamps mounted on wall.
Automatic switching ON/OFF shall be through timers/photo cells.
5.3
Where,
N
E
LL
CU
LLF
LLD
LLD
=
=
=
=
=
=
=
WRITEUP
SHEET 13 OF 15
OF 4
5.5.1 Conductor size for power receptacles and lighting circuits shall be
selected taking into consideration the voltage drop (as indicated
above), but in no case it shall be less than 4 mm 2 stranded copper.
5.5.2 Wires used for conduit point wiring of lighting fixtures/exhaust fans and
receptacles shall be 1100 V grade, PVC insulated, single core,
stranded copper conductor wires. In general, concealed wiring would
be adopted for Main switchgear building, etc. where RCC structure
exists. For GTG building etc. where steel structures are present,
exposed conduits would be used. Pull boxes would be provided near
light fittings & where conduit drops down to switch box.
5.5.3 All conduit wiring, concealed or exposed wiring shall have provision for
easy inspection. Exposed wiring when run along wall would be as near
the ceiling as possible. Due consideration would be given for neatness
and appearance.
5.5.4 Wires of different phases would be run in separate conduits. However,
wires of same phase but having different circuit nos. can be run in
same conduit. Wires of lighting and 3 phase power receptacles shall
be carried out in separate conduits and on separate circuits.
5.5.5 Wherever lighting system has three phase distribution, separate
conduits would be used for different phases. For easy identification of
phases and neutral wires the following colour wires shall be used.
i)
ii)
iii)
iv)
R - Phase
Y - Phase
B - Phase
Neutral
Red
Yellow
Blue
Black
WRITEUP
SHEET 14 OF 15
OF 4
Earthing
All exposed metal parts of the plug, when the plug is in complete
engagement with the socket outlet, shall be in effective electrical
connection with the earthing pin.
5.7
Mounting
Socket outlets & welding receptacles shall be mounted at 750mm from
FFL.
5.8
WRITEUP
SHEET 15 OF 15
OF 4
ISSUE
P0A
FORM NO. 120 R1