You are on page 1of 47

LG AIR CONDITIONERS

Heat Recovery Ventilator

0CZH9-02C
Replace 0CZH9-02B

General Description
Ventilation is a process by which one can exchange indoor air to outdoor air in order to improve the air quality
and to maintain environmental temperature conditions.
LGs heat recovery ventilation system,
, modulates the temperature and humidity of incoming fresh air to
match indoor conditions. A balance is thus achieved between indoor and outdoor ambients, enabling the cooling or heating load placed on the air conditioning system to be reduced significantly.
can be controlled
individually or integral with the air conditioning system.
provides efficiency, cost savings, superior performance, compact & light design, linear E.S.P control
ensuring vaious design of duct system and easy maintenance. Units are ideal for hotels, dormitories, restaurants, hospitals, retail establishments, theaters, schools, and office buildings.
A lot of information regarding the design & installation of this system is provided in this publication. The new
products series contains data on the same pattern. Please utilize all the information for conducting your business efficiently. Make sure the specification, dimension or others technical data are same as provided in engineering data book before you start the project.
We look forward to your continuing support.

LG Electronics Inc.
Air Conditioning Division

LG Airconditioners Product Data

Table of contents
Table of contents

Page

1. Models List ...........................................................................................4


2. Model Number Nomenclature ...............................................................5
3. Feature & Benefits.................................................................................6
4. Specifications ......................................................................................14
5. Characteristic Curve............................................................................20
6. Dimensional Drawings.........................................................................27
7. Wiring Diagrams ..................................................................................33
8. External Static Pressure Settings........................................................37
9. Installation ...........................................................................................38
10. LCD Wired Remote Control(AZLRAD) ..............................................45

1. Models List
1.1 Total Heat Recovery Ventilator
[50Hz]
Nominal Capacity

Model Name

CMH(CFM)

Power Supply
,V,Hz

100(59)

LZ-H0106BA0

150(88)

LZ-H0156BA0

250(147)

LZ-H0256BA0

350(206)

LZ-H0356BA0

350(206)

LZ-H0356BA1

500(294)

LZ-H0506BA0

500(294)

LZ-H0506BA1

800(471)

LZ-H0806BA0

1000(589)

LZ-H1006BA0

1500(883)

LZ-H1506BA0

2000(1177)

LZ-H2006BA0

1, 220-240V, 50Hz

[60Hz]
Nominal Capacity

Model Name

CMH(CFM)

Power Supply
,V,Hz

100(59)

LZ-H0102BA0

150(88)

LZ-H0152BA0

250(147)

LZ-H0252BA0

350(206)

LZ-H0352BA0

350(206)

LZ-H0352BA1

500(294)

LZ-H0502BA0

500(294)

LZ-H0502BA1

800(471)

LZ-H0802BA0

1000(589)

LZ-H1002BA0

1500(883)

LZ-H1502BA0

2000(1177)

LZ-H2002BA0

1, 220V, 60Hz

2. Model Number Nomenclature


L Z - H 0 8 0 2 B A 0
Development Sequence
Function
A : Basic

Model Type
B : Ceiling Concealed Type

Electric Standard (Volts / Freq. / Phase)


2 : 220V,60Hz,1

6 : 220-240V,50Hz,1

Capacity
Ex) 080 -> 800 CMH 100 -> 1000 CMH

Heat Exchange Type


H : Total Heat Recovery
T : Sensible Heat Recovery

Indicates that this is LGs

system

3. Features & Benefits


The LG heat recovery ventilation system,
improving your indoor air quality.

, is the solution for

Ventilation is a process by which one can exchange indoor air to outdoor air in order to improve the air quality
and to maintain environmental temperature conditions.
With todays concern for a healthy indoor environment,
is an integral component of HVAC system.
Using
in the HVAC system allows contaminants to be removed quickly and effectively from the airconditioned space. A balance is thus achieved between indoor and outdoor ambients, enabling the cooling or
heating load on the air conditioning system to be reduced significantly.
Low-noise Design

Energy Savings

is accoustically engineered and


tested for quiet operation. (ensuring
comfort to be felt, not heard.)

The indoor air is passed through the


heat exchanger to prewarm or precool
the incoming outside air, saving energy and money.

Air Purifying

Easy Maintenance

Removing common pollutants from


home which create an unhealthy
environment.

The briefcase-style latches allows


easy filter replacement and heat
exchanger cleaning.

Efficiency & Comfort


exhaust the polluted indoor air to
outdoor and supply the fresh outdoor air
to indoor in order to maintain the residents healthy and comfortable indoor
environment.

3. Features & Benefits


Healthy and Fresh Indoor Environmental Maintenance :
Case of the window ventilation

(Indoor)
30C
26C

(Outdoor)
EA

30 C

OA

In order to ventilate the indoor air is


to open the window in summer.
While opening the window, the
conditioned indoor air goes out.
Indoor air has to be cooling again.

Case of Enthalpy heat exchange ventilation

(Indoor)
SA EA
27C

(Outdoor)
o

30 C

25%
Saving Energy

26C

When using the enthalpy heat


exchanger,it maintains the
temperature and humidity of the
indoor and changes the polluted
indoor air to the fresh outdoor air.

Comparing to Enthalpy heat exchange ventilation with the window ventilation,Enthalpy heat exchange enables
to economize a electric bill.It also helps the environmental protection due to saving energy.

Enthalpy Heat and Sensible Heat Exchangers Comparisons :


Enthalpy Heat Exchanger
= Temperature heat (temperatures) +
Latentheat (humidity)

Sensible Heat Exchanger


= Temperature heat (temperatures)

The Enthalpy Heat Exchanger consists of Mechanism which is exchanged to the temperature heat
(temperatures)as well as the latent heat (moisture heat capacity).When it calculates at the electric heat
frequency quantity,it has an energy recovery effect above 3 times than the temperature heat.

3. Features & Benefits


Reclaimed Energy Comparisons in Psychrometric Chart :
Enthalpy heat exchanger

EA(Exhaust Air)
OA(Outdoor Air)
SA(Supply Air)
RA(Return Air)

Temperature heat
efficiency

Enthalpy heat
efficiency

Latent heat
efficiency

Temperature heat exchanger


EA(Exhaust Air)
OA(Outdoor Air)
SA(Supply Air)
RA(Return Air)

Enthalpy heat
efficiency

Temperature heat
efficiency

Latent heat
efficiency

Like appearing from the picture of the case only of the temperature heat exchange,the efficiency is high.
But when it calculates at enthalpy heat frequency quantity,it has a difference above 3 times.

Zero Standby Power Consumption :

5~6W

- Due to SMPS (Switching Modulation Power Supply)


technology, there is almost zero power consumption
in the standby mode.
It saves energy and cost.

0.5W
Others

LG

3. Features & Benefits


High Efficiency Heat Exchanger :
- Cross flow heat exchanger ensure no mixing of the
stale air with the fresh air. Efficiency and comfort is
ensured by the high-efficiency energy recovery central core which recovers energy from the indoor air
and transfers it to the fresh incoming air without mixing airstreams.The heat exchanger also helps to
remove unwanted humidity from air inside your
home during winter, and removes the humidity from
the outside air before it enters your home in the
summer.

Supply Air

Exhaust Air

Deodorization Filter

(Option)

High performance Filter


Outdoor Air

Air Filter

Indoor Air

Air Filter

:(External Static Pressure Control)


E.S.P Control
M

L
Air volume

- Individual air volume control (Supply&Exhaust).


Generally, when External Static Pressure increases
air volume decreases. But by controlling the phase
of motor E.S.P. is controlled linearly. E.S.P. control
provides required constant air volume irrespective of
E.S.P. change. Desired E.S.P. can also be set
through LCD wired remote. Setting of the desired
E.S.P. gives required combination of ESP and airflow.
So, air volume is kept constant for various duct
work system. All
units feature Phase control
of Motor.

H
M
L

Air volume
at 10 mmAq.

Air volume
at 2 mmAq.
2

10

12

3. Features & Benefits


Auto Operation :
- Automatically switches the ventilation mode (Total Heat Exchange Mode/Bypass Mode) according to the operating status of the air conditioner.
Total Heat Exchange Mode
(Cooling operation in summer/
heating operation in winter)

Bypass Mode
(Intermediate season)

Damper
Exhaust
air

Return
air

Outdoor
air intake

Supply
air

Damper
Return
air

Exhaust
air

Supply
air

Outdoor
air intake

Flexibility of Installation :
- Possibility of opposite installation of up and lower part
Case of the installation of 2 units, generally it is necessary to two maintenance spaces. If it is installed opposite one unit of up and lower part, it is necessary to one maintencnce space.
(1500/2000 CMH models are not available.)
Maintenance
space

Installation of 2 units

Top

Low

Low

Top

Opposite installation of
up and lower part

Opposite Installation of up and


lower part of one unit

Auto Restart Operation :


- When theres Electricity failure to the unit. After resumption of the Power, It starts in the same mode as prior to
the power failure. This is as per the memorized condition. Any change will be memorized automatically to the
MICOM & it takes about 2 secs to keep it.

Interlocking with Air Conditioning System :


- It is able to install the ventilation system being interlocking with
the air conditioning /heating system. It can be also controlled individually or integral with the air conditioning /heating system.

10

3. Features & Benefits


Excellent Sound Arresting Blocking Effect :
- The enthalpy heat exchanger element is difficult to convey the vibration of air with structure and it has a
function of absorbing sounds.if it is installed a building in a serious noise place,it will be much more effective.

88.2dB(A)

42.9dB(A)

(45.3dB(A) Sound arresting blocking effect)

Collection Efficiency(%)

Air Filter :
100
80
60
40

Polyethylene

20
0

10

20

30

40

50

60

70

80

Dust Feed(g)

- Air filter has sufficient effects with collection efficiency above 80%, which is 0.3m sample particle smaller than
tobacco of smoke. It is even against floating particle from yellow sand.
- Few pressure loss in the static pressure plan.
- Excellent washing characteristic and durability.

External static pressure[pa]

High Efficiency Filter(Option) :


250
200
150
100
50
0
600

700

800

900

1000

1100

Air Volume[m /h]

Media : Poly propylene


Frame : Paper

- Collection efficiency over 99%of an adopted law standard


- Low-noise and reduction of power supplying cost
- More multi-wind quantity than validity area
- Not-melting processing with media pleated filter uniform

11

3. Features & Benefits


LCD Wired Remote Control : (Accessory)
EXTERNAL

VENTILATOR OPERATION

Linked Run
Dual Remote
Central Run Heat XCH

- It can control all the functions of the unit. You can

PLASMA

e-SAVER

fresh

Auto

Normal

SUB FUNCTION
Hi

SHi

Heater Preheat
Defrost Humidify

Fan Speed
Filter Time

Delay Time

Timer

check and change operation mode, set timer & also

Auto
Lo

Auto

Program set

Sun Mon Tue Wed Thu

ZONE
1234
Fri

Sat

On Off
Set no. Timer

diagnose the error of the unit. It also has the option


of weekly program.
Timer

Cancel

Program

Week

fresh

Auto

Holiday
Plasma
Set/Clr

Hour

Group Control :

TIME RESET

Min

........

16

- It operate maximum 16unit by only one wired


remote controller and each units start sequentially
to prevent overcurrent.
All the units will follow same setting mode & other
sub functions.

........
EXTERNAL

VENTILATOR OPERATION

Linked Run
Dual Remote
Central Run Heat XCH
PLASMA

e-SAVER

fresh

Auto
Lo

Auto
Auto

Normal

Delay Time

Timer

SUB FUNCTION
Hi

SHi

Heater Preheat
Defrost Humidify

Fan Speed

ZONE
1234

Filter Time

Program set

Sun Mon Tue Wed Thu

Fri

Sat

On Off
Set no. Timer

Timer

Cancel

Program

Week

fresh

Auto

Holiday
Plasma
Set/Clr

Hour

TIME RESET

Min

Central Control : (Accessory)


- It enables to control 16 x 8 = 128 units with the help
of 8 controllers. All units can be put on and off from

Main
PCB

one Central Room. For Setting Temperature, Fan


speed and other sub functions, access the LCD

M
1

M
2

M
16

M
17

M
18

M
128

Sub
1

Sub
2

Sub
16

Sub
17

Sub
18

Sub
128

wired remote controller of each unit.

Controller
#1

12

Controller
#2

Controller
#8

3. Features & Benefits


Ventilation System + Multi V :

Indoor / Outdoor Communication Line


Wired Remote Controller Line
Ventilation Connected Control Line
Central Control Line

Ethernet
Remote
Controller

LGAP Central
Control System

Remote
Controller

13

4. Specifications
4.1 50Hz
Item
Nominal Capacity
Power Supply
Step

eco-V Mode

Current

SH/H/L

LZ-H0106BA0

LZ-H0156BA0

LZ-H0256BA0

CMH(CFM)

100(59)

150(88)

250(147)

,V,Hz

1, 220~240, 50

1, 220~240, 50

1, 220~240, 50

S-HIGH / HIGH / LOW

S-HIGH / HIGH / LOW

S-HIGH / HIGH / LOW

Amps

0.32/0.3/0.28

0.36/0.36/0.35

0.55/0.5/0.34

68/60/50

83/80/78

130/115/80

Power Input

SH/H/L

Air Flow

SH/H/L

CMH(CFM)

100/100/90(59/59/53)

150/150/100(88/88/59)

250/250/180(147/147/106)

External Static Pressure

SH/H/L

Pa(in.wg)

40/35/30(0.16/0.14/0.12)

70/55/45(0.28/0.22/0.18)

65/50/40(0.26/0.20/0.16)

78/78/80

75/75/79

80/80/85

68/68/70

62/62/69

70/70/78

Temperature Exchange Efficiency SH/H/L


Enthalpy Exchange Efficiency Heating(SH/H/L)
Cooling(SH/H/L)
Noise Level(Sound Level, 1.5m) SH/H/L
Step
Current

Bypass Mode

Unit

SH/H/L

58/58/60

55/55/59

64/64/68

dBA

28/26/20

32/30/22

32/28/21

-/-/-

-/-/-

-/-/-

Amps

-/-/-

-/-/-

-/-/-

Power Input

SH/H/L

-/-/-

-/-/-

-/-/-

Air Flow

SH/H/L

CMH(CFM)

-/-/-

-/-/-

-/-/-

External Static Pressure

SH/H/L

Pa(in.wg)

-/-/-

-/-/-

-/-/-

Temperature Exchange Efficiency SH/H/L

-/-/-

-/-/-

-/-/-

Enthalpy Exchange Efficiency

Heating(SH/H/L)

-/-/-

-/-/-

-/-/-

Cooling(SH/H/L)

-/-/-

-/-/-

-/-/-

dBA

-/-/-

-/-/-

-/-/-

Crossflow

Crossflow

Crossflow

Noise Level(Sound Level, 1.5m) SH/H/L


Heat Exchanger

Type

Weight
Dimension

W*H*D

Duct work*

Qty
Size()

Supply Air Fan


Exhaust Air Fan
Filters

kg(lb)

23(50.70)

23(50.70)

24(52.91)

mm(inch)

590*204*590(23.23*8.03*23.23)

590*204*590(23.23*8.03*23.23)

596*320*640(23.46*12.60*25.20)

EA

mm(inch)

100(3.94)

100(3.94)

150(5.91)

Qty

EA

Type

Direct-Drive

Direct-Drive

Direct-Drive

Qty

EA

Type

Direct-Drive

Direct-Drive

Direct-Drive

Qty

EA

Type

Cleanable

Cleanable

Cleanable

Size(W*H*D)
Packing Dimension

W*H*D

Stuffing Quantity

Without S/Parts

mm(inch)

580*10*113(22.83*0.39*4.45)

580*10*113(22.83*0.39*4.45)

590*10*175(23.23*0.39*6.89)

mm(inch)

850*280*760(33.46*11.02*29.92)

850*280*760(33.46*11.02*29.92)

850*405*760((33.46*15.94*29.92)

20/40ft

160/336

160/336

100/210

Notes:
1. eco-V mode : Total Heat Recovery Ventilation mode
2. * : Refer to dimensional drawings.
3. Noise level : - The operating conditions are assumed to be standard.
- Sound measured at 1.5m below the center the body.
- Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound.

14

4. Specifications
Item
Nominal Capacity
Power Supply

eco-V Mode

LZ-H0356BA0

LZ-H0356BA1

LZ-H0506BA0

LZ-H0506BA1

350(206)

350(206)

500(294)

500(294)

1, 220~240, 50

1, 220~240, 50

1, 220~240, 50

1, 220~240, 50

,V,Hz

Step

SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW

Current

SH/H/L

Amps

1.40/1.33/0.9

1.42/1.39/1.06

1.51/1.39/1.06

1.54/1.52/1.36

Power Input

SH/H/L

205/195/170

209/204/175

260/225/200

293/244/225

Air Flow

SH/H/L

External Static Pressure

SH/H/L

CMH(CFM) 350/350/210(206/206/124) 350/350/210(206/206/124) 500/500/320(294/294/124) 500/500/320(294/294/124)


Pa(in.wg)

170/88/40(0.68/0.35/0.16)

Temperature Exchange Efficiency SH/H/L

83/83/87

81/81/85

75/75/79

75/75/81

Enthalpy Exchange Efficiency Heating(SH/H/L)

80/80/85

68/68/76

75/75/80

63/63/68

78/78/83

64/64/72

70/70/75

56/56/64

dBA

33/28/23

33/28/23

34/32/25

35/33/26

Cooling(SH/H/L)
Noise Level(Sound Level, 1.5m) SH/H/L
Step
Current
Bypass Mode

Unit
CMH(CFM)

SH/H/L

Power Input

SH/H/L

Air Flow

SH/H/L

External Static Pressure

SH/H/L

170/88/40(0.68/0.35/0.16) 150/60/28(0.60/0.24/0.11) 120/100/40(0.48/0.40/0.16)

SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW

Amps

1.40/1.33/0.9

1.42/1.39/1.06

1.51/1.39/1.06

1.54/1.52/1.36

205/195/170

209/204/175

260/225/200

293/244/225

CMH(CFM) 350/350/210(206/206/124) 350/350/210(206/206/124) 500/500/320(294/294/124) 500/500/320(294/294/124)


Pa(in.wg)

170/88/40(0.68/0.35/0.16)

Temperature Exchange Efficiency SH/H/L

-/-/-

-/-/-

Enthalpy Exchange Efficiency

Heating(SH/H/L)

-/-/-

-/-/-

Cooling(SH/H/L)

-/-/-

-/-/-

dBA

33/28/23

33/28/23

34/32/25

35/33/26

Crossflow

Crossflow

Crossflow

Crossflow

38(83.8)

35(77.2)

45(99.2)

35(77.2)

Noise Level(Sound Level, 1.5m) SH/H/L


Heat Exchanger

Type

Weight
Dimension
Duct work*

kg(lb)
W*H*D
Qty
Size()

Supply Air Fan


Exhaust Air Fan
Filters

mm(inch)

170/88/40(0.68/0.35/0.16) 150/60/28(0.60/0.24/0.11) 120/100/40(0.48/0.40/0.16)

988*273*1014(38.9*10.75*39.92) 988*273*1014(38.9*10.75*39.92) 988*273*1014(38.9*10.75*39.92) 988*273*1014(38.9*10.75*39.92)

EA

mm(inch)

200(7.87)

200(7.87)

200(7.87)

200(7.87)

Qty

EA

Type

Direct-Drive

Direct-Drive

Direct-Drive

Direct-Drive

Qty

EA

Type

Direct-Drive

Direct-Drive

Direct-Drive

Direct-Drive

Qty

EA

Type

Cleanable

Cleanable

Cleanable

Cleanable

855*10*160(33.66*0.39*6.30)

855*10*166(33.66*0.39*6.54)

855*10*160(33.66*0.39*6.30)

Size(W*H*D)

mm(inch)

855*10*166(33.66*0.39*6.54)

Packing Dimension

W*H*D

mm(inch)

1160*360*1275(45.67*14.17*50.20) 1160*360*1275(45.67*14.17*50.20) 1160*360*1275(45.67*14.17*50.20) 1160*360*1275(45.67*14.17*50.20)

Stuffing Quantity

Without S/Parts

20/40ft

48/108

48/108

48 / 108

48 / 108

Notes:
1. eco-V mode : Total Heat Recovery Ventilation mode
2. * : Refer to dimensional drawings.
3. Noise level : - The operating conditions are assumed to be standard.
- Sound measured at 1.5m below the center the body.
- Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound.

15

4. Specifications
Item

Unit

Nominal Capacity
Power Supply
Step

eco-V Mode

Current

LZ-H1506BA0

LZ-H2006BA0

800(470)

1000(588)

1500(882)

2000(1177)

,V,Hz

1, 220~240, 50

1, 220~240, 50

1, 220~240, 50

1, 220~240, 50

Amps

SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW
2.8/2.7/2.6

3.0/2.9/2.6

5.6/5.4/5.2

6.0/5.8/5.2

Power Input

SH/H/L

405/360/320

560/540/470

950/925/795

1020/970/860

Air Flow

SH/H/L

CMH(CFM)

800/800/660(470/470/388)

1000/1000/800(588/588/470)

1500/1500/1200(882/882/706)

2000/2000/1600(1177/1177/941)

External Static Pressure

SH/H/L

Pa(in.wg)

200/110/60(0.80/0.44/0.24) 160/90/50(0.80/0.44/0.24) 200/110/60(0.80/0.44/0.24) 160/90/50(0.80/0.44/0.24)

79/79/82

75/75/78

79/79/82

75/75/78

Enthalpy Exchange Efficiency Heating(SH/H/L)

70/70/75

66/66/71

70/70/75

66/66/71

Cooling(SH/H/L)

65/65/70

61/61/66

65/65/70

61/61/66

dBA

36/34/30

37/35/31

39/37/33

39/37/33

SUPER-HIGH / HIGH / LOW

SUPER-HIGH / HIGH / LOW

SUPER-HIGH / HIGH / LOW

SUPER-HIGH / HIGH / LOW

Temperature Exchange Efficiency SH/H/L

Noise Level(Sound Level, 1.5m) SH/H/L


Step

Bypass Mode

LZ-H1006BA0

CMH(CFM)
SH/H/L

LZ-H0806BA0

Current

SH/H/L

Amps

2.8/2.7/2.6

2.8/2.7/2.4

5.6/5.4/5.2

5.6/5.4/4.8

Power Input

SH/H/L

405/360/320

560/540/470

950/925/795

1020/970/860

Air Flow

SH/H/L

CMH(CFM)

800/800/660(470/470/388)

1000/1000/800(588/588/470)

1500/1500/1200(882/882/706)

2000/2000/1600(1177/1177/941)

External Static Pressure

SH/H/L

Pa(in.wg)

200/110/60(0.80/0.44/0.24) 160/90/50(0.80/0.44/0.24) 200/110/60(0.80/0.44/0.24) 160/90/50(0.80/0.44/0.24)

Temperature Exchange Efficiency SH/H/L

-/-/-

-/-/-

-/-/-

-/-/-

Enthalpy Exchange Efficiency

Heating(SH/H/L)

-/-/-

-/-/-

-/-/-

-/-/-

Cooling(SH/H/L)

-/-/-

-/-/-

-/-/-

-/-/-

dBA

36/34/30

37/35/31

37/35/31

37/35/31

Crossflow

Crossflow

Crossflow

Crossflow

kg(lb)

63(139)

63(139)

138(305)

138(305)

Noise Level(Sound Level, 1.5m) SH/H/L


Heat Exchanger

Type

Weight
Dimension

W*H*D

Duct work*

Qty

mm(inch)

1062*365*1140(41.9*14.4*44.9) 1062*365*1140(41.9*14.4*44.9) 1313*737*1140(51.7*28.8*44.9) 1313*737*1140(51.7*28.8*44.9)

EA

4+2

4+2
250(9.54)+350(13.77)

mm(inch)

250(9.54)

250(9.54)

250(9.54)+350(13.77)

Qty

EA

Type

Direct-Drive

Direct-Drive

Direct-Drive

Direct-Drive

Qty

EA

Type

Direct-Drive

Direct-Drive

Direct-Drive

Direct-Drive

Qty

EA

Type

Cleanable

Cleanable

Cleanable

Cleanable

Size(W*H*D)

mm(inch)

1056*10*212.5(41.57*0.39*8.37)

Packing Dimension

W*H*D

mm(inch)

1320*450*1350(51.97*17.72*53.15) 1320*450*1350(51.97*17.72*53.15) 1630*900*1330(64.17*35.43*52.36) 1630*900*1330(64.17*35.43*52.36)

Stuffing Quantity

Without S/Parts

Size()
Supply Air Fan
Exhaust Air Fan
Filters

20/40ft

24 / 45

1056*10*212.5(41.57*0.39*8.37) 1056*10*212.5(41.57*0.39*8.37) 1056*10*212.5(41.57*0.39*8.37)


24 / 45

8 / 18

8 / 18

Notes:
1. eco-V mode : Total Heat Recovery Ventilation mode
2. * : Refer to dimensional drawings.
3. Noise level : - The operating conditions are assumed to be standard.
- Sound measured at 1.5m below the center the body.
- Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound.

16

4. Specifications
4.2 60Hz
Item
Nominal Capacity
Power Supply
Step

eco-V Mode

Current

SH/H/L

LZ-H0102BA0

LZ-H0152BA0

LZ-H0252BA0

CMH(CFM)

100(59)

150(88)

250(147)

,V,Hz

1, 220, 60

1, 220, 60

1, 220, 60

S-HIGH / HIGH / LOW

S-HIGH / HIGH / LOW

S-HIGH / HIGH / LOW

Amps

0.45/0.41/0.39

0.5/0.48/0.42

0.65/0.60/0.36

76/64/60

100/95/77

140/130/80

Power Input

SH/H/L

Air Flow

SH/H/L

CMH(CFM)

100/100/70(59/59/41)

150/150/90(88/88/53)

250/250/150(147/147/88)

External Static Pressure

SH/H/L

Pa(in.wg)

70/50/25(0.281/0.200/0.100)

70/50/25(0.281/0.200/0.100)

100/50/20(0.401/0.200/0.080)

78/78/80

75/75/79

80/80/85

68/68/70

62/62/69

70/70/78

Temperature Exchange Efficiency SH/H/L


Enthalpy Exchange Efficiency Heating(SH/H/L)
Cooling(SH/H/L)
Noise Level(Sound Level, 1.5m) SH/H/L
Step
Current

Bypass Mode

Unit

SH/H/L

58/58/60

55/55/59

64/64/68

dBA

28/26/20

32/30/22

32/28/21

-/-/-

-/-/-

-/-/-

Amps

-/-/-

-/-/-

-/-/-

Power Input

SH/H/L

-/-/-

-/-/-

-/-/-

Air Flow

SH/H/L

CMH(CFM)

-/-/-

-/-/-

-/-/-

External Static Pressure

SH/H/L

Pa(in.wg)

-/-/-

-/-/-

-/-/-

Temperature Exchange Efficiency SH/H/L

-/-/-

-/-/-

-/-/-

Enthalpy Exchange Efficiency

Heating(SH/H/L)

-/-/-

-/-/-

-/-/-

Cooling(SH/H/L)

-/-/-

-/-/-

-/-/-

dBA

-/-/-

-/-/-

-/-/-

Crossflow

Crossflow

Crossflow

Noise Level(Sound Level, 1.5m) SH/H/L


Heat Exchanger

Type

Weight
Dimension

W*H*D

Duct work*

Qty
Size()

Supply Air Fan


Exhaust Air Fan
Filters

kg(lb)

23(50.70)

23(50.70)

24(52.91)

mm(inch)

590*204*590(23.23*8.03*23.23)

590*204*590(23.23*8.03*23.23)

596*320*640(23.46*12.60*25.20)

EA

mm(inch)

100(3.94)

100(3.94)

150(5.91)

Qty

EA

Type

Direct-Drive

Direct-Drive

Direct-Drive

Qty

EA

Type

Direct-Drive

Direct-Drive

Direct-Drive

Qty

EA

Type

Cleanable

Cleanable

Cleanable

580*10*113(22.83*0.39*4.45)

590*10*175(23.23*0.39*6.89)

Size(W*H*D)
Packing Dimension

W*H*D

Stuffing Quantity

Without S/Parts

mm(inch)

580*10*113(22.83*0.39*4.45)

mm(inch)

850*280*760(33.46*11.02*29.92)

20/40ft

160/336

850*280*760(33.46*11.02*29.92) 850*405*760(33.46*15.94*29.92)
160/336

100/210

Notes:
1. eco-V mode : Total Heat Recovery Ventilation mode
2. * : Refer to dimensional drawings.
3. Noise level : - The operating conditions are assumed to be standard.
- Sound measured at 1.5m below the center the body.
- Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound.

17

4. Specifications

Item
Nominal Capacity
Power Supply

eco-V Mode

SH/H/L
SH/H/L

Air Flow

SH/H/L

External Static Pressure

SH/H/L

Temperature Exchange Efficiency SH/H/L


Enthalpy Exchange Efficiency Heating(SH/H/L)
Cooling(SH/H/L)
Noise Level(Sound Level, 1.5m) SH/H/L
Step

Bypass Mode

LZ-H0352BA1

LZ-H0502BA0

LZ-H0502BA1

CMH(CFM)

350(206)

350(206)

500(294)

500(294)

1, 220, 60

1, 220, 60

1, 220, 60

1, 220, 60

Power Input

Current

LZ-H0352BA0

,V,Hz

Step
Current

Unit

Amps

1.15/1.08/1.01

1.63/1.1/0.98

1.25/1.07/0.9

1.35/1.28/1.25

240/220/207

269/230/210

258/235/195

289/281/277

CMH(CFM) 350/350/210(206/206/124) 350/350/210(206/206/124) 500/500/320(294/294/124) 500/500/320(294/294/124)


Pa(in.wg)

Power Input

SH/H/L

Air Flow

SH/H/L

External Static Pressure

SH/H/L

190/50/20(0.76/0.2/0.08) 190/50/20(0.76/0.2/0.08) 200/70/28(0.80/0.28/0.11) 200/70/28(0.80/0.28/0.11)

83/83/87

81/81/85

82/82/86

75/75/81

80/80/85

68/68/76

79/79/83

63/63/68

78/78/83

64/64/72

76/76/80

56/56/64

dBA

32/27/22

32/27/22

34/32/25

34/32/25

SH/H/L

SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW

SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW

Amps

1.15/1.08/1.01

1.63/1.1/0.98

1.25/1.07/0.9

1.35/1.28/1.25

240/220/207

269/230/210

258/235/195

289/281/277

CMH(CFM) 350/350/210(206/206/124) 350/350/210(206/206/124) 500/500/320(294/294/124) 500/500/320(294/294/124)


Pa(in.wg)

190/50/20(0.76/0.2/0.08) 190/50/20(0.76/0.2/0.08) 200/70/28(0.80/0.28/0.11) 200/70/28(0.80/0.28/0.11)

Temperature Exchange Efficiency SH/H/L

-/-/-

-/-/-

-/-/-

-/-/-

Enthalpy Exchange Efficiency

Heating(SH/H/L)

-/-/-

-/-/-

-/-/-

-/-/-

Cooling(SH/H/L)

-/-/-

-/-/-

-/-/-

-/-/-

dBA

32/27/22

32/27/22

34/32/25

34/32/25

Crossflow

Crossflow

Crossflow

Crossflow

38(83.8)

35(77.2)

45(99.2)

35(77.2)

Noise Level(Sound Level, 1.5m) SH/H/L


Heat Exchanger

Type

Weight

kg(lb)

Dimension

W*H*D

Duct work*

Qty
Size()

Supply Air Fan


Exhaust Air Fan
Filters

mm(inch)

988*273*1014(38.9*10.75*39.92) 988*273*1014(38.9*10.75*39.92) 988*273*1014(38.9*10.75*39.92) 988*273*1014(38.9*10.75*39.92)

EA

mm(inch)

200(7.87)

200(7.87)

200(7.87)

200(7.87)

Qty

EA

Type

Direct-Drive

Direct-Drive

Direct-Drive

Direct-Drive

Qty

EA

Type

Direct-Drive

Direct-Drive

Direct-Drive

Direct-Drive

Qty

EA

Type

Cleanable

Cleanable

Cleanable

Cleanable

mm(inch)

855*10*166(33.66*0.39*6.54)

855*10*160(33.66*0.39*6.30)

855*10*166(33.66*0.39*6.54)

855*10*160(33.66*0.39*6.30)

mm(inch)

1160*360*1275(45.67*14.17*50.20) 1160*360*1275(45.67*14.17*50.20) 1160*360*1275(45.67*14.17*50.20) 1160*360*1275(45.67*14.17*50.20)

Size(W*H*D)
Packing Dimension

W*H*D

Stuffing Quantity

Without S/Parts

20/40ft

48/108

48/108

48 / 108

48 / 108

Notes:
1. eco-V mode : Total Heat Recovery Ventilation mode
2. * : Refer to dimensional drawings.
3. Noise level : - The operating conditions are assumed to be standard.
- Sound measured at 1.5m below the center the body.
- Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound.

18

4. Specifications

Item
Nominal Capacity
Power Supply

eco-V Mode

LZ-H1002BA0

LZ-H1502BA0

LZ-H2002BA0

CMH(CFM)

800(470)

1000(588)

1500(882)

2000(1177)

1, 220, 60

1, 220, 60

1, 220, 60

1, 220, 60

SH/H/L

3.1/3.0/2.5

3.5/3.4/2.9

6.2/6.0/5.0

7.0/6.8/5.8

585/555/470

660/500/400

1190/1151/960

1344/1306/1122

800/800/660(470/470/388)

1000/1000/800(588/588/470)

SH/H/L

Air Flow

SH/H/L

CMH(CFM)

External Static Pressure

SH/H/L

Pa(in.wg)

Temperature Exchange Efficiency SH/H/L


Cooling(SH/H/L)
Noise Level(Sound Level, 1.5m) SH/H/L
Step

SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW

Amps

Power Input

Enthalpy Exchange Efficiency Heating(SH/H/L)

Bypass Mode

LZ-H0802BA0

,V,Hz

Step
Current

Unit

1500/1500/1200(882/882/706) 2000/2000/1600(1177/1177/941)

200/110/60(0.80/0.44/0.24) 200/110/60(0.80/0.44/0.24) 200/110/70(0.80/0.44/0.28) 200/110/70(0.80/0.44/0.28)

79/79/82

75/75/78

75/75/78

75/75/78

70/70/75

66/66/71

66/66/71

66/66/71

65/65/70

61/61/66

61/61/66

61/61/66

dBA

36/34/30

37/35/31

39/37/33

42/38/33

3.1/3.0/2.5

3.5/3.4/2.9

6.2/6.0/5.0

7.0/6.8/5.8

Current

SH/H/L

Power Input

SH/H/L

585/555/470

660/500/400

1190/1151/960

1344/1306/1122

Air Flow

SH/H/L

CMH(CFM)

800/800/660(470/470/388)

1000/1000/800(588/588/470)

1500/1500/1200(882/882/706)

2000/2000/1600(1177/1177/941)

External Static Pressure

SH/H/L

Pa(in.wg)

200/110/60(0.80/0.44/0.24)

200/110/60(0.80/0.44/0.24)

200/110/70(0.80/0.44/0.28)

200/110/70(0.80/0.44/0.28)

Temperature Exchange Efficiency SH/H/L

-/-/-

-/-/-

-/-/-

-/-/-

Enthalpy Exchange Efficiency

Heating(SH/H/L)

-/-/-

-/-/-

-/-/-

-/-/-

Cooling(SH/H/L)

-/-/-

-/-/-

-/-/-

-/-/-

dBA

36/34/30

37/35/31

39/37/33

42/38/33

Crossflow

Crossflow

Crossflow

Crossflow

63(139)

63(139)

138(305)

138(305)

Noise Level(Sound Level, 1.5m) SH/H/L


Heat Exchanger

Type

Weight

kg(lb)

Dimension

W*H*D

Duct work*

Qty
Size()

Supply Air Fan


Exhaust Air Fan
Filters

Amps

SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW SUPER-HIGH / HIGH / LOW

mm(inch)

1062*365*1140(41.9*14.4*44.9) 1062*365*1140(41.9*14.4*44.9) 1313*737*1140(51.7*28.8*44.9) 1313*737*1140(51.7*28.8*44.9)

EA

mm(inch)

250(9.54)

250(9.54)

4+2

4+2

250(9.54)+350(13.77) 250(9.54)+350(13.77)

Qty

EA

Type

Direct-Drive

Direct-Drive

Direct-Drive

Direct-Drive

Qty

EA

Direct-Drive

Direct-Drive

Direct-Drive

Direct-Drive

Type

Qty

EA

Type

Cleanable

Cleanable

Cleanable

Cleanable

Size(W*H*D)
Packing Dimension

W*H*D

Stuffing Quantity

Without S/Parts

mm(inch)

1056*10*212.5(41.57*0.39*8.37) 1056*10*212.5(41.57*0.39*8.37) 1056*10*212.5(41.57*0.39*8.37) 1056*10*212.5(41.57*0.39*8.37)

mm(inch)

1320*450*1350(51.97*17.72*53.15) 1320*450*1350(51.97*17.72*53.15) 1630*900*1330(64.17*35.43*52.36) 1630*900*1330(64.17*35.43*52.36)

20/40ft

24 / 45

24 / 45

8 / 18

8 / 18

Notes:
1. eco-V mode : Total Heat Recovery Ventilation mode
2. * : Refer to dimensional drawings.
3. Noise level : - The operating conditions are assumed to be standard.
- Sound measured at 1.5m below the center the body.
- Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound.

19

5. Characteristic Curve
Model No. : LZ-H0102BA0
[Ventilation]

[Efficiency]
90
Exchange efficiency[%]

External static pressure[Pa]

150

100
Super-High
50

High

80

Temperature exchanger efficiency


)
(Sensible Efficiency)

70

Enthalpy exchanger efficiency


(Sensible
(
Efficiency Heating)

60

Low
0

Enthalpy exchanger efficiency


(Total Efficiency Cooling)
50

50

100

150

20

40

60

Air Volume[m3/h]

80
100 120
Air Volume[m3/h]

140

160

180

200

Model No. : LZ-H0106BA0


[Ventilation]

[Efficiency]
90
Exchange efficiency[%]

External static pressure[Pa]

150

100

High

Super-High

50

Temperature exchanger efficiency


(Sensible Efficiency)

80

Enthalpy exchanger efficiency


(Sensible Efficiency Heating)

70

60

Low

Enthalpy exchanger efficiency


(Total Efficiency Cooling)
0

50

100
Air

50

150

20

40

60

Volume[m3/h]

80

100

120

140

160

180

200

Air Volume[m3/h]

Model No. : LZ-H0152BA0


[Ventilation]

[Efficiency]
90
Exchange efficiency[%]

External static pressure[Pa]

200

150
Super-High
100
High

Enthalpy exchanger efficiency


(Sensible Efficiency Heating)

70

60

Low

50

Temperature exchanger efficiency


(Sensible Efficiency)

80

Enthalpy exchanger efficiency


(Total Efficiency Cooling)
50

0
0

50

100
Air Volume[m3/h]

20

150

200

20

40

60

80
100 120
Air Volume[m3/h]

140

160

180

200

5. Characteristic Curve
Model No. : LZ-H0156BA0
[Ventilation]

[Efficiency]
90

150

Exchange efficiency[%]

External static pressure[Pa]

200

Super-High
High

100

Enthalpy exchanger efficiency


(Sensible Efficiency Heating)

70

60

Low

50

Temperature exchanger efficiency


(Sensible Efficiency)

80

Enthalpy exchanger efficiency


(Total Efficiency Cooling)
50

0
0

50

100

150

200

20

40

60

80

100

120

140

160

180

200

Air Volume[m3/h]

Air Volume[m3/h]

Model No. : LZ-H0252BA0


[Ventilation]

[Efficiency]
100
Exchange efficiency[%]

External static pressure[Pa]

300
250
200
Super-High

150
High
100

Temperature exchanger efficiency


(Sensible Efficiency)

90

80

Enthalpy exchanger efficiency


(Sensible Efficiency Heating)

70
Enthalpy exchanger efficiency
(Total Efficiency Cooling)

60

50

Low
50

0
0

50

100

150

200

250

300

350

400

50

100

150

200

250

300

350

400

Air Volume[m3/h]

Air Volume[m3/h]

Model No. : LZ-H0256BA0


[Ventilation]

[Efficiency]
100

250

Exchange efficiency[%]

External static pressure[Pa]

300

200
150
100
Super-High
50

Low

Temperature exchanger efficiency


(Sensible Efficiency)

90

80

Enthalpy exchanger efficiency


(Sensible Efficiency Heating)

70
Enthalpy exchanger efficiency
(Total Efficiency Cooling)

60

High
50

0
0

50

100

150

200

250

Air Volume[m3/h]

300

350

400

50

100

150

200

250

300

350

400

Air Volume[m3/h]

21

5. Characteristic Curve
Model No. : LZ-H0352BA0
[Ventilation]

[Efficiency]
90

350

Exchange efficiency[%]

External static pressure[Pa]

400

300
Super High

250
200

High

150
Low

100

80

Tem
p
efficie erature
exch
ncy
a

nge

Enth

alpy

Enth

alpy

70

exch

ange

exch

ange

efficie

ncy(H

eatin

efficie

g)

ncy(C

oolin

g)

60

50
0

50

100

200

300

400

500

600

100

200

300

400

500

600

700

Air Volume[m3/h]

Air Volume[m3/h]

Model No. : LZ-H0352BA1


[Ventilation]

[Efficiency]

450

90
Exchange efficiency[%]

External static pressure[Pa]

400
350
300
Super High

250
200

High

150
100

80

Tem
p
efficie erature
exch
ncy
a

nge

Enth

alpy

Enth

alpy

70

exch

ange

exch

ange

efficie

ncy(H

eatin

efficie

g)

ncy(C

oolin

g)

60

Low

50
0
0

100

200
Air

300

400

50

500

100

200

300

Volume[m3/h]

400

500

600

700

Air Volume[m3/h]

Model No. : LZ-H0356BA0


[Ventilation]

[Efficiency]

400

90
Tem
p
efficie erature
exch
ncy
a

Exchange efficiency[%]

External static pressure[Pa]

350
300
250

Super High

200
150

High
100

80

Enth

alpy

Enth

alpy

70

nge

exch

ange

exch

ange

efficie

ncy(H

efficie

eatin

ncy(C

g)

oolin

g)

60

Low
50
0
0

100

200

300

400

Air Volume[m3/h]

22

500

600

50
0

100

200

300

400

Air Volume[m3/h]

500

600

700

5. Characteristic Curve
Model No. : LZ-H0356BA1
[Ventilation]

[Efficiency]

400

90
Exchange efficiency[%]

External static pressure[Pa]

350
300
Super High

250
High
200
Low

150
100

80

Tem
p
efficie erature
exch
ncy
a

nge

Enth

alpy

Enth

alpy

70

exch

ange

exch

ange

efficie

ncy(H

eatin

efficie

g)

ncy(C

oolin

g)

60

50
0
0

100

200

300

400

500

50

600

100

200

300

400

500

600

700

Air Volume[m3/h]

Air Volume[m3/h]

Model No. : LZ-H0502BA0


[Ventilation]

[Efficiency]

400

90

300

Exchange efficiency[%]

External static pressure[Pa]

350
Super High

250

High

200
Low

150
100

80

Tem
p
efficie erature
exch
ncy
a

nge

Enth

alpy

Enth

alpy

70

exch

ange

exch

ange

efficie

ncy(H

eatin

efficie

g)

ncy(C

oolin

g)

60

50
0
0

100

200

300
Air

400

500

600

50

700

100

200

300

400

500

600

700

Air Volume[m3/h]

Volume[m3/h]

Model No. : LZ-H0502BA1


[Ventilation]

[Efficiency]
90

600

Exchange efficiency[%]

External static pressure[Pa]

700

500
High

400

Super High

Low

300
200

80

Tem
p
efficie erature
exch
ncy
a

nge

Enth

alpy

Enth

alpy

70

exch

exch

ange

ange

efficie

ncy(H

efficie

eatin

ncy(C

g)

oolin

g)

60

100
0
0

100

200

300
400
Air Volume[m3/h]

500

600

700

50
0

100

200

300
400
Air Volume[m3/h]

500

600

700

23

5. Characteristic Curve
Model No. : LZ-H0506BA0
[Ventilation]

[Efficiency]

400

90
Exchange efficiency[%]

External static pressure[Pa]

350
300
250
Super High
200
150

High

Low

100

Tem
effic perature
ienc
exch
y

80

ange

Enth

alpy

Enth

alpy

70

exch

ange

exch

ange

efficie

ncy(H

eatin

effic

ienc

g)

y(Co

oling

60

50
0

50
0

100

200

300

400

500

600

700

100

200

300

400

500

600

700

Air Volume[m3/h]

Air Volume[m /h]

Model No. : LZ-H0506BA1


[ Ventilation]

[Efficiency]
90

500

Tem
p
efficie erature
exch
ncy
a

Exchange efficiency[%]

External static pressure[Pa]

450
400
350
300
Super High

250
200

High

150
Low

100

80

nge

Enth

alpy

Enth

alpy

70

exch

ange

exch

ange

efficie

ncy(H

eatin

efficie

g)

ncy(C

oolin

g)

60

50
0

50
0

100

200

300 400
500
Air Volume[m3/h]

600

700

100

200

300
400
Air Volume[m3/h]

500

600

700

Model No. : LZ-H0802(6)BA0


[Ventilation]

[Efficiency]
90

400

Super High

300

High

Low
200

En

Tem
p
effic erature
ienc
exch
y
an

tha

lpy

80

ge

exc

han

ge

En

effi

cie

tha

70

lpy

200

400
Air

600

800

Volume[m3/h]

1000

1200

ncy

(He

exc

ha

atin

ng

g)

ee

ffic

ien

cy(

60

100

24

Exchange efficiency[%]

External static pressure[Pa]

500

Co

olin

g)

50
0

200

400

600

Air Volume[m3/h]

800

1000

1200

5. Characteristic Curve
Model No. : LZ-H1002BA0
[Ventilation]

[Efficiency]
90
Exchange efficiency[%]

External static pressure[Pa]

500

400
Super High
300

High
Low

200

En

Tem
effic peratur
ienc
e ex
y
cha

nge

tha

80

lpy

exc

han
ge

effi

cie

En

70

tha

lpy

ncy

(He

atin

g)

exc

han

ge

effi

cie

60

ncy

(Co

100

olin

g)

50

0
0

200

400

600
Air

800

1000

1200

1400

200

400

600

800

1000

1200

1400

Air Volume[m3/h]

Volume[m3/h]

Model No. : LZ-H1006BA0


[Ventilation]

[Efficiency]
90
Exchange efficiency[%]

External static pressure[Pa]

500

400
Super High
300

High
Low

200

En

Tem
effic peratu
re e
ienc
xcha
y

nge

tha

80

lpy

exc

han

ge

cie

70

tha
lpy

0
0

200

400

600
Air

800

1000

1200

ncy

(He

atin

g)

exc

han

ge

effi

cie

60

100

effi

En

ncy
(Co

olin

g)

50

1400

200

400

600

Volume[m3/h]

800

1000

1200

1400

Air Volume[m3/h]

Model No. : LZ-H1502(6)BA0


[Ventilation]

[Efficiency]
90
Exchange efficiency[%]

External static pressure[Pa]

500

400

300
Super High

??

200

High
?

100

En

tha

80

lpy

nge

exc

ha

En

70

ng

ee

ffic

500

1000
Air

1500

Volume[m3/h]

2000

2500

cy(

lpy
e

He

atin

g)

xch

ang

ee

ffic

ien

ien

tha

60

Low

Tem
effic peratu
ienc re e
xch
y
a

cy(

Co

olin
g)

50
0

500

1000

1500

2000

2500

Air Volume[m3/h]

25

5. Characteristic Curve
Model No. : LZ-H2006BA0
[Ventilation]

[Efficiency]
90

400

Exchange efficiency[%]

External static pressure[Pa]

500

Super High
300
High
200

Low

100

80

Ent

Tem
p
effic erature
ienc
exch
y
ang

halp

y ex

cha

70

nge

effic

ienc

En

y(H

tha

lpy

exc
han
g

ee

60

ffic

ien

cy(

eat

ing)

Co

olin

g)

50
0

500

1000
Air

1500

2000

2500

500

1000

1500

2000

2500

Air Volume[m3/h]

Volume[m3/h]

Model No. : LZ-H2002BA0


[Ventilation]

[Efficiency]
90
Exchange efficiency[%]

External static pressure[Pa]

500

400
Super High
300
High
200
Low

80

Tem
effic peratur
e ex
ienc
chan
y

ge

Ent

halp

70

En

ye

xch

ang

ee

fficie

ncy

tha

lpy

(He

atin

exc

han
ge

effi

g)

cie

60
100

ncy

(Co

olin
g

500

1000

1500

Air Volume[m3/h]

26

2000

2500

50
0

500

1000

1500

Air Volume[m3/h]

2000

2500

6. Dimensional Drawings
Model No. : LZ-H010(015)2BA0, LZ-H010(015)6BA0

Suspension Fixture
Blower for
supplying air
L

Control Box

EA

SA
Total Heat Exchanger
K
B
E

Air Filter
Blower for Exhausting Air

RA

OA

Unit: mm
Model

LZ-H0102BA0
LZ-H0106BA0
LZ-H0152BA0
LZ-H0156BA0

Pitch of Suspension
Fixture

Figure
A

590

590

204

504

624.2

64

Nominal
Diameter

100

Duct Connection Flange

Duct Pitch

Weight

(kg)

97.5

160

90

402

93

23

27

6. Dimensional Drawingss
Model No. : LZ-H0252BA0, LZ-H0256BA0

Air Filter

Total Heat Exchanger

Maintenance Cover

Control Box

Suspension Fixture

Blower for supplying air

Blower for Exhausting Air

RA

EA

SA

OA

Unit: mm
Model

LZ-H0252BA0
LZ-H0256BA0

28

Pitch of Suspension
Fixture

Figure
A

640

596

320

568

636.2

55

Nominal
Diameter
150

Duct Connection Flange

Duct Pitch

Weight

(kg)

140

160

70

430

84

24

6. Dimensional Drawings
Model No. : LZ-H035(050)6BA0, LZ-H035(050)2BA0

Blower for Exhausting Air

Suspension Fixture

RA

OA

SA
50

EA

600

150~250

Blower for
supplying air
Control Box

Total Heat Exchanger


Air Filter
High Efficiency Filter
Blower
Maintenance space

Maintenance Cover

Maintenance space

Total Heat Exchanger

Suspension Fixture

Air Filter

Unit: mm
Model

Pitch of Suspension
Fixture

Figure
A

LZ-H0356BA0
1013.6 988.2
LZ-H0352BA0
LZ-H0506BA0
1013.6 988.2
LZ-H0502BA0

Nominal
Diameter

Duct Connection Flange

Duct Pitch

Weight

(kg)

271.6

938.8 1024.8

5.8

200

194

252

95.8

590

198

38

271.6

938.8 1024.8

5.8

200

194

252

95.8

590

198

45

29

6. Dimensional Drawings
Model No. : LZ-H035(050)6BA1, LZ-H035(050)2BA1

Blower for Exhausting Air

Suspension Fixture

RA

OA

SA
50

EA

600

150~250

Blower for
supplying air
Control Box

Total Heat Exchanger


Air Filter
High Efficiency Filter
Blower
Maintenance space

Maintenance Cover

Maintenance space

Total Heat Exchanger

Suspension Fixture

Air Filter

Unit: mm
Model
A

LZ-H0356BA1
LZ-H0352BA1
1013.6 988.2
LZ-H0506BA1
LZ-H0502BA1

30

Pitch of Suspension
Fixture

Figure
C

271.6

938.8 1024.8

5.8

Nominal
Diameter

200

Duct Connection Flange

Duct Pitch

Weight

(kg)

194

252

95.8

590

198

35

6. Dimensional Drawings
Model No. : LZ-H080(100)*BA0

Blower for Exhausting Air

Suspension Fixture

RA

EA
SA
Blower for
supplying air

Total Heat Exchanger


Air Filter
High Efficiency Filter
Blower
Maintenance space

Longer than 600

OA

Control Box
Maintenance Cover

Maintenance
space

Total Heat Exchanger

Suspension Fixture

Air Filter
Unit: mm
Model
A
LZ-H080*BA0
LZ-H100*BA0 1062

Pitch of Suspension
Fixture

Figure
B

1140

365

987

1176

52

Nominal
Diameter
250

Duct Connection Flange

Duct Pitch

Weight

(kg)

242

253

98

513

481

63

31

6. Dimensional Drawings
Model No. : LZ-H150(200)*BA0

RA

EA
N

SA

OA

Control Box
Maintenance Cover

Total Heat Exchanger


Air Filter
High Efficiency Filter
Blower
Maintenance space

Maintenance
space

L
K

H2

Unit: mm
Model
LZ-H150*BA0
LZ-H200*BA0

32

Pitch of Suspension
Fixture

Figure

Duct Connection Flange

Weight

(kg)

1312

1140

730

987

1176

52

242

253

98

340

350

138

7. Wiring Diagrams
Model No. : LZ-H010(015/025)2BA0, LZ-H010(015/025)6BA0

33

7. Wiring Diagrams
Model No. : LZ-H035(050)*BA0(1)

34

7. Wiring Diagrams
Model No. : LZ-H080(100)*BA0

35

7. Wiring Diagrams
Model No. : LZ-H150(200)*BA0

36

8. External Static Pressure Settings


Setting up Air Volume
By setting a phase value of motor, you can control the air volume.

Setting up the air volume of SA


EXTERNAL

VENTILATOR OPERATION

Linked Run
Dual Remote
Central Run Heat XCH
PLASMA

e-SAVER

fresh

Auto
Lo

Auto
Auto

Normal

Hi

SHi

Heater Preheat
Defrost Humidify

Fan Speed
Filter Time

Delay Time

Timer

SUB FUNCTION

Program set

Sun Mon Tue Wed Thu

ZONE
1234
Fri

Sat

On Off
Set no. Timer

1. If you simultaneously press [timer,


] button for more than
3 seconds, the current phase value is displayed at the display window as right Figure shows.
2. Select the Air volume mode which you want by pressing
[ ] button.

Timer

Cancel

fresh
Program

Week

Auto

Holiday
Plasma
Set/Clr

Hour

Min

3. Set up the phase value by pressing [


comes to the target value.

] button until it

4. If you simultaneously press [timer,


] button for more than
3 seconds again, setting up completes.

TIME RESET

EXTERNAL

VENTILATOR OPERATION

Linked Run
Dual Remote
Central Run Heat XCH

Cover open status

PLASMA

fresh

e-SAVER

Auto
Lo

Auto
Auto

SHi

Heater Preheat
Defrost Humidify

Fan Speed

Normal

ZONE

Filter Time

Delay Time

Timer

SUB FUNCTION
Hi

Program set

Sun Mon Tue Wed Thu

Fri

Sat

On Off
Set no. Timer

Phase value

Cipher
Supply air

Setting up the air volume of EA


1. If you simultaneously press [timer,
] button for more than 3
seconds, the current phase mvalue is displayed at the display
window as right Figure shows.

EXTERNAL

PLASMA

2. Select the Air volume mode which you want by pressing [


button.
3. Set up the phase value by pressing [
comes to the target value.

VENTILATOR OPERATION

Linked Run
Dual Remote
Central Run Heat XCH
Timer

e-SAVER

fresh

Auto
Lo

Auto
Auto

SHi

Heater Preheat
Defrost Humidify

Fan Speed

Normal

Delay Time

SUB FUNCTION
Hi

ZONE

Filter Time

Program set

Sun Mon Tue Wed Thu

Fri

Sat

On Off
Set no. Timer

] button until it

Phase value

Cipher
Exhaust air

4. If you simultaneously press [timer,


] button for more than 3
seconds again, setting up completes.

You can set up the air volume at all air volume mode according to installation circumstances.
The phase value can range from 00 to 254. As the value is low, the air volume increases.
As making a shipment from the factory, the initial setting up value is 00.
In case of model 'LZ-H1006BA0', it is recommended to set up the value from 0 to 100.
* For more information of setting up the phase value, refer to the external static pressure value table.

37

9. Installation
9.1 Typical Installation Map
Model No.: LZ-H010(015)2BA0, LZ-H010(015)6BA0

Air return grille


Air return system
A

OA
B

(Fresh air outlet)

Air supply grille

EA
(Exaust air outlet)

Control Box

Duct slope: More than 1/30(toward the wall)


Obtaining of right distance
(preventing penetration of rain water)

Duct

Inspection part

Ceiling Fixing Bolt


(user-supplied)

New hood
(preventing penetration
of rain water)

Air return
system

EA
(Exaust air outlet)

OA
(Fresh air outlet)

Inspection
part

SA

RA

(Supply air)

(Return air)
Air return grille

Air supply grille

[Unit : mm]

LZ-H0102BA0
LZ-H0152BA0
LZ-H0106BA0
LZ-H0156BA0

38

504

624.2

100

9. Installation
Model No.: LZ-H0252BA0, LZ-H0256BA0

Air supply grille


Air return system
A

OA
Air return
system

(Fresh air outlet)

EA

Air return grille

(Exaust air outlet)

Inspection part

Duct slope: More than 1/30(toward the wall)


Obtaining of right distance
(preventing penetration of rain water)

Duct

Ceiling Fixing Bolt


(user-supplied)

New hood
(preventing penetration
of rain water)

Air return
system

EA
(Exaust air outlet)

OA
(Fresh air outlet)

Inspection
part

SA

RA

(Supply air)

(Return air)
Air return grille

Air supply grille

[Unit : mm]

LZ-H0252BA0
LZ-H0256BA0

568

636.2

150

39

9. Installation
Model No.: LZ-H035(050)*BA0(1)

Ceiling suspension
bolts position

EA
(Exaust air outlet)
Air return grille
(user-supplied)

OA

Min.600

150~250

(Fresh air outlet)

Inspection
part
450
( 600)

Air supply grille


(user-supplied)

Maintenance space
Total heat Exchanger
Air Filter

Ceiling Fixing Bolt


(user-supplied)

Duct normal diameter


C(user-supplied)

EA
(Exaust air outlet)

OA

Inspection part
450( 600)

(Fresh air outlet)

Duct slope: More than 1/30(toward the wall)


Obtaining of right distance
(preventing penetration of rain water)

RA SA
(Return air)

Air supply grille


Air return grille

(Supply air)

[Unit : mm]

LZ-H050*BA0

40

938.8

1024.8

200

9. Installation
Model No.: LZ-H080(100)*BA0

Air supply grille


(user-supplied)

Ceiling suspension
bolts position
Air return grille
(user-supplied)

EA
(Exaust air outlet)

OA
(Fresh air outlet)

Min.600
150~250

Y duct connecting
(user-supplied)
Inspection
part
450
( 600)

Maintenance space
Exchanger
( Total heat
)
Air Filter

Ceiling Fixing Bolt


(user-supplied)

Duct normal diameter


C(user-supplied)

EA
(Exaust air outlet)

OA

Inspection part
450( 600)

(Fresh air outlet)

Air supply grille

Air return grille

RA
(Return air)
Duct slope: More than 1/30(toward the wall)
Obtaining of right distance
(preventing penetration of rain water)

SA

SA

(Supply air)

(Supply air)

[Unit : mm]

LZ-H080*BA0

987

1176

250

LZ-H100*BA0

987

1176

250

41

9. Installation
Model No.: LZ-H150(200)*BA0

Air return grille


(user-supplied)
Air supply grille
(user-supplied)

Ceiling suspension
bolts position
A

Air return grille


(user-supplied)
D

Air supply grille


(user-supplied)

EA
(Exaust air outlet)

OA
(Fresh air outlet)
Min.60
150~2

Y duct connecting
(user-supplied)
Inspection
port
450
( 600)

Air supply grille


(user-supplied)
Air supply grille
(user-supplied)
Maintenance space
Total Heat Exchanger
Air Filter

Duct normal diameter


C (user-supplied)

Ceiling Fixing Bolt


(user-supplied)

New Type Hood


(Preventing Penetration
of Rain Water)

EA

(Exaust air outlet)

OA

(Fresh air outlet)


Inspection port
450 ( 600)

Air return grille

Duct slope : More than 1/30(toward the wall)


Obtaining of right distance
(preventing penetration of rain water)

RA
(Return air)

SA
RA
(Supply air) (Return air)

Air supply
grille
SA
(Supply air)

SA
SA
(Supply air) (Supply air)

[Unit : mm]

42

LZ-H150*BA0

987

1176

350

250

LZ-H200*BA0

987

1176

350

250

9. Installation
9.2 Installation
Installation of Main Body
Assembly of Washer, Nut
Ceiling Fixing Bolt
(M10~12)

Tighten the commercial washer nut (more than 21mm for the outside
diameter of M10, to the commercial ceiling fixing bolt (M10) as shown
in the left figure.

Nut
Washer, Spring Lock

For the ceiling fixing bolt, perform work less than 50mm under the
ceil fixing bracket.

Washer, Plain
Nut

Connection of Duct
1. After securely connect the duct with the duct connection
flange, wrap it with a commercial aluminium tape so that air
cannot be leaked.

Duct

2. Adjust the duct from the ceiling so that no force is applied to


the main body of the ventilation system.
3. Always use two ducts at the outdoor with the heat insulating
material for prevention of dewing.

Taping
Duct

CAUTION:
Check that there are no foreign materials (paper, vinyl, etc)
or cutoff powders in the duct before connecting the duct.
Take care so that shock may not be applied to the damper
plate within the main body when performing the duct connection work.

Taping

It is recommended to perform adiabatic treatment even to


the duct pipe at the indoor side where ambient temperature
is expected when the main body of the ventilation system
for cooling in summer.
Take care so that work may not be performed as in the left
figure. Otherwise, it may cause reduction of air volume or
abnormal noise.

Heat Insulating Material


Aluminium

Main Body
Duct to OA
Duct Connection Flange

Rapid Bending

Excessive Bending

Too Close Bending


to Outlet

Rapid Reduction of
Duct Diameter

43

9. Installation
9.3 Wiring Connection
Method to Connect Power Cord
1. Release two screws and then open the cover of the control box.
With reference to the above wiring diagram, accurately
connect the main power cords into the terminal block.
Cover of Control Box
Cover of Control Box

Screw

Screw

2. After inserting the power cord into the bushing, fully insert it into the terminal
block for connection.
Fix the power cords with the clamp.
Make sure that the power cords may not be removed by pulling them.

Bushing

Bushing
GN/YL
GND

GN/YL
GND

Cord Clamp

BL
BR
Power

Cord Clamp

44

BL
BR
Power

10. LCD Wired Remote Control(AZLRAD)


LCD Remote Control (Ventilation System Remote Control AZLRAD)

EXTERNAL

VENTILATOR OPERATION

Linked Run
Dual Remote
Central Run Heat XCH
PLASMA

e-SAVER

fresh

Auto
Lo

Auto
Auto

Normal

Delay Time

Timer

SUB FUNCTION
Hi

SHi

Heater Preheat
Defrost Humidify

Fan Speed
Filter Time

Program set

Sun Mon Tue Wed Thu

ZONE
1234
Fri

Sat

On Off
Set no. Timer

10
Timer

Cancel

Program

Week

fresh

Auto

Holiday

Plasma
Set/Clr
Hour

Min

3
4
5
6
7
11

TIME RESET

8
12

9
Cover open status

1. Display Window

6. Ventilation Mode Button

2. Execute/Cancel of Time Reservation,Weekly


Reservation/Weed Day Select/Holiday Select
Button

7. Air volume Select Button

3. Operation/Stop Button
4. Delay Time Button
5. Rapid Ventilation Button

8. Power Saving/Filter Cleaning Button


9. Time Reset Button
10. Heater Button
11. Humidification Button
12. Plasma Button

45

20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355


Seoul 150-721, Korea
Phone: 3777-7969 Fax: 3777-5137/8
http://www.lge.com
http://biz.lgservice.com

Approvals:
EN ISO 9001
BS EN ISO 9001
ANSI/ASQC Q9001

P/No.: 3828A20428T

KS A 9001

For continual product development, LG reserves the right to change specifications without notice
LG Electronics INC. Printed in Korea. May/2006