You are on page 1of 47

6 Distance Protection / 7SA6

SIPROTEC 4 7SA6
Distance Protection Relay for all Voltage Levels
Function overview

Protection functions
• Non-switched distance protection with
6 measuring systems (21/21N)
• High resistance earth-fault protection
for single and three-phase tripping
(50N, 51N, 67N)
• Earth-fault detection in isolated and
resonant-earthed networks
• Tele (pilot) protection (85)
• Fault locator (FL)
• Power-swing detection/tripping (68/68T)
• Phase overcurrent protection (50/51)

LSP2318-afp.tif
• Switch-onto-fault protection (50HS)
• STUB bus overcurrent protection
(50STUB)
Fig. 6/1 • Overvoltage/undervoltage protection
SIPROTEC 4
(59/27)
7SA6 distance protection relay
• Over/underfrequency protection (81O/U)
6
• Auto-reclosure (79)
• Synchro-check (25)
Description • Breaker failure protection (50BF)
The SIPROTEC 4 7SA6 distance protection • Thermal overload protection (49)
relay is a universal device for protection, Control function
control and automation on the basis of the • Commands f. ctrl. of CBs and isolators
SIPROTEC 4 system. Its high level of flexi-
bility makes it suitable to be implemented at Monitoring functions
all voltage levels. With this relay you are ide- • Trip circuit supervision (74TC)
ally equipped for the future: it offers security • Self-supervision of the relay
of investment and also saves on operating • Measured-value supervision
costs.
• Event logging/fault logging
− High-speed tripping time • Oscillographic fault recording
− Low-impedance setpoints to protect also • Switching statistics
very short lines Front design
− Self-setting power swing detection for fre- • Easy operation w. numeric keys
quencies up to 7 Hz • Function keys
− Current transformer saturation detector • LEDs for local alarm
ensures fast tripping and highest distance • PC front port for convenient relay
measurement accuracy setting
− Phase-segregated teleprotection for im-
proved selectivity and availability Communication interfaces
• Front interface for connecting a PC
− Digital relay-to-relay communication by
means of an integrated serial protection • System interface for connecting to a
data interface control system via various protocols
− Adaptive auto-reclosure (ADT) – IEC 60870-5-103 protocol
– PROFIBUS-FMS/-DP
– DNP 3.0
– IEC 618501) Ethernet
• 1 serial protection data interface for
teleprotection
• Rear-side service/modem interface
• Time synchronization via
– IRIG-B or DCF 77 or
1) Available approx. as of mid 2004.
– system interface

Siemens SIP · 2004 6/3


6 Distance Protection / 7SA6

Cost-effective power system management


Application ANSI Protection functions
The SIPROTEC 4 units are numerical relays 21/21N Distance protection
The distance protection relay 7SA6 is which also provide control and monitoring
non-switched incorporating all the addi- functions and therefore support the user in FL Fault locator
tional functions for protection of overhead view of a cost-effective power system man- 50N/51N Directional earth-fault protection
lines and cables at all voltage levels from agement. The security and reliability of
67N
5 to 765 kV. power supply is increased as a result of min-
imizing the use of hardware. 50/51 Backup overcurrent protection
All methods of neutral point connection
(resonant earthing, isolated, solid or The local operation has been designed ac- 50 STUB STUB-bus overcurrent stage
low-resistance earthing) are reliably dealt cording to ergonomic criteria. Large, easy- 68/68T Power swing detection/tripping
with. The unit can issue single or three-pole to-read backlit displays are provided.
TRIP commands as well as CLOSE com- 85/21 Teleprotection for distance protection
mands. Consequently both single-pole, The SIPROTEC 4 units have a uniform de- 27WI Weak-infeed protection
three-pole and multiple auto-reclosure is sign and a degree of functionality which
represents a whole new level of performance 85/67N Teleprotection for earth-fault protection
possible.
in protection and control. If the require- 50HS Switch-onto-fault protection
Teleprotection functions as well as ments for protection, control or interlock-
earth-fault protection and sensitive 50BF Breaker-failure protection
ing change, it is possible in the majority of
earth-fault detection are included. Power cases to implement such changes by means 59/27 Overvoltage/undervoltage protection
swings are detected reliably and of parameterization using DIGSI 4 without 81O/U Over/underfrequency protection
non-selective tripping is prevented. The unit having to change the hardware.
operates reliably and selectively even under The use of powerful microcontrollers and 25 Synchro-check
6 the most difficult network conditions. the application of digital measured-value 79 Auto-reclosure
conditioning and processing largely sup-
74TC Trip circuit supervision
presses the influence of higher-frequency
transients, harmonics and DC components. 86 Lockout (CLOSE command inter-
locking)
49 Thermal overload protection
IEE Sensitive earth-fault detection

Fig. 6/2 Function diagram 1) Teleprotection schemes can use


conventional signaling or serial
data exchange

6/4 Siemens SIP · 2004


6 Distance Protection / 7SA6

Construction

Connection techniques and housing with


many advantages
1/3, 1/2, 2/3, and 1/1-rack sizes:
These are the available housing widths of
the 7SA6 relays, referred to a 19" module
frame system. This means that previous
models can always be replaced. The height is

LSP2174-afp.tif

LSP2166-afp.tif
a uniform 255 mm for flush-mounting
housings and 266 mm for surface-mounting
housings for all housing widths. All cables
can be connected with or without ring lugs.
Plug-in terminals are available as an option.
It is thus possible to employ prefabricated
cable harnesses. In the case of surface Fig. 6/3 Fig. 6/4
mounting on a panel, the connection termi- Flush-mounting housing Rear view of flush-mounting housing with
with screw-type terminals covered connection terminals and wirings
nals are located above and below in the
form of screw-type terminals. The commu-
nication interfaces are located in a sloped
case at the top and bottom of the housing.
The housing can also be supplied optionally
with a detached operator panel (refer to 6
Fig. 6/5), in order to allow optimum opera-
tion for all types of applications.

LSP2244-afp.eps

Fig. 6/5 Flush-mounting housing with plug-in terminals and detached operator panel
LSP2237-afp.tif
LSP2219-afp.eps

Fig. 6/7
Communication interfaces
in a sloped case in a surface-
mounting housing

Fig. 6/6
Surface-mounting housing with screw-type
terminals

Siemens SIP · 2004 6/5


6 Distance Protection / 7SA6

Protection functions

Distance protection (ANSI 21, 21N)


The main function of the 7SA6 is a non-
switched distance protection. By parallel
calculation and monitoring of all six imped-
ance loops, a high degree of sensitivity and
selectivity is achieved for all types of fault.
The shortest tripping time is less than one
cycle. All methods of neutral-point connec-
tion (resonant earthing, isolated, solid or
low-resistance earthing) are reliably dealt
with. Single-pole and three-pole tripping is
possible. Overhead lines can be equipped
with or without series capacitor compensa-
tion. Fig. 6/8
Four pickup methods Impedance fault detection Z<
with quadrilateral characteristic
The following pickup methods can be em-
ployed alternatively:
• Overcurrent pickup I>>
6 • Voltage-dependent overcurrent pickup
V/I
• Voltage-dependent and phase angle-
dependent overcurrent pickup V/I/ϕ
• Impedance pickup Z<
Load zone
The pickup mode with quadrilateral imped-
ance pickup (Z<) is fitted with a variable
load zone. In order to guarantee a reliable
discrimination between load operation and
short-circuit (especially on long high loaded
lines), the relay is equipped with a selectable
load encroachment characteristic. Imped-
ances within this load encroachment char-
acteristic prevent the distance zones from
unwanted tripping. Fig. 6/9 Fig. 6/10
Voltage and angle- dependent overcurrent Angle pickup for the V / I / ϕ fault detection
Absolute phase-selectivity fault detection V / I / ϕ
The 7SA6 distance protection incorporates a
well-proven, highly sophisticated phase se-
lection algorithm. The pickup of unfaulted
phases is reliably eliminated. This phase se-
lection algorithm achieves single-pole trip-
ping and correct distance measurement in a
wide application range. Interference to dis-
tance measurement caused by parallel lines
can be compensated by taking the earth cur-
rent of the parallel system into account.
This parallel line compensation can be taken
into account both for distance measure-
ment and for fault locating.

Fig. 6/11
Distance zones with circle
characteristic

6/6 Siemens SIP · 2004


6 Distance Protection / 7SA6

Protection functions

Six distance zones


Five independent distance zones and one
separate overreach zone are available. Each
distance zone has dedicated time stages,
partially separate for single-phase and
three-phase faults. Earth faults are detected
by monitoring the earth current 3I0 and the
zero-sequence voltage 3V0. The quadrilateral
tripping characteristic allows use of separate
settings for the X and the R directions. Differ-
ent R settings can be employed for earth and
phase faults. This characteristic offers advan-
tages in the case of faults with fault resistance.
For applications to medium-voltage cables

LSP2208-afp.tif
with low line angles, it may be advantageous
to select the distance zones with the optional
circle characteristic.
All the distance protection zones can be set to Fig. 6/12 Power swing current and voltage wave forms
forward, reverse or non-directional.
Optimum direction detection Power swing detection (ANSI 68, 68T) The carrier send and receive signals are
Use of voltages, which are not involved with available as binary inputs and outputs and 6
Dynamic transient reactions, for instance
the short-circuit loop, and of voltage mem- can be freely assigned to each physical relay
short-circuits, load fluctuations, auto-
ories for determination of the fault direction input or output. At least one channel is re-
reclosures or switching operations can cause
ensure that the results are always reliable. quired for each direction.
power swings in the transmission network.
During power swings, large currents along Common transmission channels are power-
Elimination of interference signals
with small voltages can cause unwanted line carrier microwave radio and fiber-
Digital filters render the unit immune to in-
tripping of distance protection relays. To optic links. A serial protection data interface
terference signals contained in the measured
avoid uncontrolled tripping of the distance for direct connection to a digital communi-
values. In particular, the influence of DC
protection and to achieve controlled trip- cation network or fiber-optic link is avail-
components, capacitive voltage transform-
ping in the event of loss of synchronism, the able.
ers and frequency changes is considerably
7SA6 relay is equipped with an efficient
reduced. A special measuring method is em- 7SA6 also permits the transfer of phase-
power swing detection function. Power
ployed in order to assure protection selec- selective signals. This feature is particularly
swings can be detected under symmetrical
tivity during saturation of the current advantageous as it ensures reliable single-
load conditions as well as during single-pole
transformers. pole tripping, if single-pole faults occur on
auto-reclosures.
different lines. The transmission methods
Measuring voltage monitoring
are suitable also for lines with three ends
Tripping of the distance protection is Tele (pilot) protection for distance protection
(three-terminal lines). Phase-selective trans-
blocked automatically in the event of failure (ANSI 85-21)
mission is also possible with multi-end ap-
of the measuring voltage, thus preventing
A teleprotection function is available for fast plication, if some user-specific linkages are
spurious tripping.
clearance of faults up to 100 % of the line implemented by way of the integrated CFC
The measuring voltage is monitored by the
length. The following operating modes may logic.
integrated fuse failure monitor. Distance
be selected:
protection is blocked if either the fuse fail- During disturbances in the signaling chan-
ure monitor or the auxiliary contact of the • POTT nel receiver or on the transmission circuit,
voltage transformer protection switch oper- the teleprotection function can be blocked
• Directional comparison pickup
ates and in this case the EMERGENCY defi- via a binary input signal without losing the
nite-time overcurrent protection can be • Unblocking zone selectivity.
activated. • PUTT acceleration with pickup
The control of the overreach zone Z1B
• PUTT acceleration with Z1B (zone extension) can be switched over to the
Fault locator
• Blocking auto-reclosure function.
The integrated fault locator calculates the • Pilot-wire comparison Transient blocking (current reversal guard)
fault impedance and the distance-to-fault.
• Reverse interlocking is provided for all the release and blocking
The results are displayed in ohms, kilome-
• DUTT, direct underreaching zone trans- methods in order to suppress interference
ters (miles) and in percent of the line length.
fer trip (together with Direct Transfer signals during tripping of parallel lines.
Parallel line compensation and load current
Trip function).
compensation for high-resistance faults is
also available.

Siemens SIP · 2004 6/7


6 Distance Protection / 7SA6

The undervoltage measuring elements can


Protection functions
be blocked by means of a minimum current
criterion and by means of binary inputs.

Under certain conditions on the power sys- Frequency protection (ANSI 81O/U)
tem it is necessary to execute remote trip-
ping of the circuit-breaker. The 7SA6 relay Frequency protection can be used for
is equipped with phase-selective in- overfrequency and underfrequency protec-
tertripping signal inputs and outputs. tion. Unwanted frequency changes in the
network can be detected and the load can be
Weak-infeed protection: removed at a specified frequency setting.
echo and/or trip (ANSI 27 WI) Frequency protection can be used over a
wide frequency range (45 to 55, 55 to
To prevent delayed tripping of permissive 65 Hz). There are four elements (selectable
schemes during weak or zero infeed situa- as overfrequency or underfrequency) and
tions, an echo function is provided. each element can be delayed separately.
If no fault detector is picked up at the weak-
infeed end of the line, the signal received Directional earth-fault protection for
here is returned as echo to allow accelerated high-resistance faults (ANSI 50N, 51N, 67N)
tripping at the strong infeed end of the line.
It is also possible to initiate phase-selective In an earthed network it may happen that
tripping at the weak-infeed end. A phase- the distance protection´s sensitivity is not
sufficient to detect high-resistance earth 014
.
selective single-pole or three-pole trip is t= Tp
faults. The 7SA6 protection relay therefore
(I / I p )
0 .02
6 issued if a permissive trip signal (POTT or
offers protection functions for faults of this
−1
Unblocking) is received and if the phase-
earth voltage drops correspondingly. As an nature. Fig. 6/13 Normal inverse
option, the weak infeed logic can be The earth-fault protection can be used with
equipped according to a French specifica- three definite-time stages and one inverse-
tion. time stage (IDMT).

Overvoltage protection, undervoltage Inverse-time characteristics according to


protection (ANSI 59, 27) IEC 60255-3 and ANSI/IEEE are provided
(see “Technical data”). A 4th definite-time
A voltage rise can occur on long lines that stage can be applied instead of the 1st in-
are operating at no-load or that are only verse-time stage.
lightly loaded. The 7SA6 contains a number
of overvoltage measuring elements. Each An additional logarithmic inverse-time
measuring element is of two-stage design. characteristic is also available.
The following measuring elements are avail- The direction decision is determined by the
able: earth current and the zero-sequence voltage
or by the negative-sequence components V2
• Phase-to-earth overvoltage
and I2. In addition or as an alternative, the
• Phase-to-phase overvoltage
LSP2209-afp.tif

direction can be determined with the earth


• Zero-sequence overvoltage current of an earthed power transformer and
The zero-sequence voltage can be the zero-sequence voltage. Dual polarization
connected to the 4th voltage input or applications can therefore be fulfilled. Alter-
be derived from the phase voltages. natively, the direction can be determined by
• Positive-sequence overvoltage of the local evaluation of zero-sequence power. Each
end or calculated for the remote end of overcurrent stage can be set in forward or re-
the line (compounding) verse direction or in both directions
• Negative-sequence overvoltage (non-directional).
The function is equipped with special digital Fig. 6/14
Tripping by the overvoltage measuring Transient earth-fault relay 7SN60
elements can be effected either at the local filter algorithms, providing the elimination
circuit-breaker or at the remote station by of higher harmonics. This feature is particu-
means of a transmitted signal. larly important for small zero-sequence
fault currents which usually have a high
The 7SA6 is fitted, in addition, with three content of 3rd and 5th harmonic.
two-stage undervoltage measuring elements:
• Phase-to-earth undervoltage
• Phase-to-phase undervoltage
• Positive-sequence undervoltage

6/8 Siemens SIP · 2004


6 Distance Protection / 7SA6

With smaller fault currents, instantaneous STUB bus overcurrent protection


Protection functions
tripping after switch-onto-fault is also pos- (ANSI 50(N)-STUB)
Inrush stabilization and instantaneous sible with the overreach distance zone Z1B
The STUB bus overcurrent protection is a
switch-onto-fault tripping can be activated or with pickup.
separate definite-time overcurrent stage. It
separately for each stage as well. The switch-onto-fault initiation can be de- can be activated via a binary input signaling
Different operating modes can be selected. tected via the binary input “manual close” that the open line isolator (disconnector) is
The earth-fault protection is suitable for or automatically via measurement. open.
three-phase and, optionally, for single- Separate settings are available for phase and
phase tripping by means of a sophisticated Earth-fault detection in systems with a
earth faults.
phase selector. It may be blocked during the star-point that is not effectively earthed
dead time of single-pole auto-reclose In systems with an isolated or resonant Auto-recIosure (ANSI 79)
cycles or during pickup of the distance pro- earthed (grounded) star-point, single-phase
tection. The 7SA6 relay is equipped with an auto-
earth faults can be detected. The following
reclosure function (AR). The function in-
functions are integrated for this purpose:
Tele (pilot) protection for directional cludes several operating modes:
earth-fault protection (ANSI 85-67N) • Detection of an earth fault by monitoring
• 3-pole auto-reclosure for all types of
of the displacement voltage
The directional earth-fault protection can faults; different dead times are available
• Determination of the faulted phase by depending on the type of fault
be combined with the available signaling
measurement of the phase-to-earth volt-
methods: • 1-pole auto-reclosure for 1-phase faults,
age
no reclosing for multi-phase faults
• Directional comparison • Determination of the earth-fault direction
• 1-pole auto-reclosure for 1-phase faults
by highly accurate measurement of the ac-
• BLOCKING
tive and reactive power components in
and for 2-phase faults without earth, no 6
• UNBLOCKING reclosing for multi-phase faults
the residual earth fault current.
The transient blocking function (current re- • 1-pole auto-reclosure for 1-phase and
• Alarm or trip output can be selected in the
versal guard) is also provided in order to 3-pole auto-reclosure for multi-phase
event of an earth-fault in the forward di-
suppress interference signals during tripping faults
rection.
of parallel lines. • 1-pole auto-reclosure for 1-phase faults
• Operation measurement of the active and
reactive component in the residual earth and 2-phase faults without earth and
The pilot functions for distance protection
current during an earth-fault. 3-pole auto-reclosure for multi-phase
and for earth-fault protection can use the
faults
same signaling channel or two separate and
Earth-fault direction detection can also be • Multiple-shot auto-reclosure
redundant channels.
effected on the basis of the transient
earth-fault principle by interfacing with the • Interaction with an external device for
Backup overcurrent protection additional unit 7SN60 (see Fig. 6/14). Pro- auto-reclosure via binary inputs and
(ANSI 50, 50N, 51, 51N) cedures for logging, time stamping and outputs
The 7SA6 provides a backup overcurrent event recording for the network control • Control of the internal AR function by
protection. Two definite-time stages and system are standardized by the 7SA6. external protection
one inverse-time stage (IDMTL) are avail- • Interaction with the internal or an
able, separately for phase currents and for Breaker failure protection (ANSI 50BF) external synchro-check
the earth current. Two operating modes are • Monitoring of the circuit-breaker auxil-
The 7SA6 relay incorporates a two-stage
selectable. The function can run in parallel iary contacts
breaker failure protection to detect failures
to the distance protection or only during
of tripping command execution, for exam- In addition to the above-mentioned operat-
failure of the voltage in the VT secondary
ple, due to a defective circuit-breaker. The ing modes, several other operating princi-
circuit (emergency operation).
current detection logic is phase-selective ples can be employed by means of the
The secondary voltage failure can be de- and can therefore also be used in single-pole integrated programmable logic (CFC).
tected by the integrated fuse failure monitor tripping schemes. If the fault current is not
or via a binary input from a VT miniature interrupted after a settable time delay has
circuit-breaker (VT m.c.b. trip). expired, a retrip command or a busbar trip
command will be generated. The breaker
Inverse-time characteristics according to failure protection can be initiated by all in-
IEC 60255-3 and ANSI/IEEE are provided tegrated protection functions, as well as by
(see “Technical data”). external devices via binary input signals.
Instantaneous high-speed switch-onto-fault
overcurrent protection (ANSI 50HS)
Instantaneous tripping is required when en-
ergizing a faulty line. In the event of large
fault currents, the high-speed switch-onto-
fault overcurrent stage can initiate very fast
three-pole tripping.

Siemens SIP · 2004 6/9


6 Distance Protection / 7SA6

•Protection functions This secondary voltage interruption can be Analog output 0 to 20 mA


detected by means of the integrated fuse
Some measured values can be output as an-
Auto-recIosure (cont’d) (ANSI 79) failure monitor. Immediate blocking of dis-
alog values (0 to 20 mA). On a plug-in
tance protection and switching to the
Integration of auto-reclosure in the feeder module (Fig. 6/21) two analog channels are
backup-emergency overcurrent protection
protection allows evaluation of the line-side made available. Up to two plug-in modules
is provided for all types of secondary voltage
voltages. A number of voltage-dependent can be installed in the 7SA6. As an option, 2,
failures.
supplementary functions are thus available: 4 or no analog channels are available (please
Additional measurement supervision refer to the selection and ordering data).
• DLC functions are The available measured values can be gath-
By means of dead-line check, reclosure is ered from the technical data.
effected only when the line is deenergized • Symmetry of voltages and currents
(prevention of asynchronous breaker clo- • Broken-conductor supervision Commissioning and fault event analyzing
sure). • Summation of currents and voltages
Special attention has been paid to commis-
• ADT • Phase-sequence supervision. sioning. All binary inputs and outputs can
The adaptive dead time is employed only
be displayed and activated directly. This can
if auto-reclosure at the remote station was Trip circuit supervision (ANSI 74TC) simplify the wiring check significantly for
successful (reduction of stress on equip-
the user. The operational and fault events
ment). One or two binary inputs for each circuit-
and the fault records are clearly arranged.
• RDT breaker pole can be used for monitoring the
For applications with serial protection data
Reduced dead time is employed in con- circuit-breaker trip coils including the con-
interface, all currents, voltages and phases
junction with auto-reclosure where no necting cables. An alarm signal is issued
are available via communication link at each
teleprotection method is employed: whenever the circuit is interrupted.
local unit, displayed at the front of the unit
6 When faults within the zone extension with DIGSI 4 or with WEB Monitor1).
but external to the protected line are Lockout (ANSI 86)
A common time tagging facilitates the com-
switched off for rapid auto-reclosure Under certain operating conditions it is ad- parison of events and fault records.
(RAR), the RDT function decides on the visable to block CLOSE commands after a
basis of measurement of the return volt- TRIP command of the relay has been issued. WEB Monitor1) - Internet technology simpli-
age from the remote station which has not Only a manual “RESET” command un- fies visualization
tripped whether or not to reduce the dead blocks the CLOSE command. The 7SA6 is
time. In addition to the universal DIGSI 4 operat-
equipped with such an interlocking logic.
ing program, the relay contains a WEB
Synchronism check (ANSI 25) server that can be accessed via a
Thermal overload protection (ANSI 49)
telecommunication link using a browser
Where two network sections are switched in For thermal protection of cables and trans- (e.g. Internet Explorer). The advantage of
by control command or following a 3-pole formers an overload protection with an this solution is to operate the unit with stan-
auto-reclosure, it must be ensured that both early-warning stage is provided. The ther- dard software tools and at the same time
network sections are mutually synchronous. mal replica can be generated with the maxi- make use of the Intranet/Internet infra-
For this purpose a synchro-check function mum or mean value of the respective structure. Apart from numeric values,
is provided. After verification of the net- overtemperatures in the three phases, or graphical displays in particular provide clear
work synchronism, the function releases the with the overtemperature corresponding to information and a high degree of operating
CLOSE command. Alternatively, reclosing the maximum phase current. reliability. Of course, it is also possible to
can be enabled for different criteria, e.g. call up detailed measured value displays and
checking that the busbar or line is not carry- The tripping time characteristics are expo-
annunciation buffers. By emulation of the
ing a voltage (dead line or dead bus). nential functions according to IEC 60255-8
integrated unit operation on the PC it is also
and they take account of heat loss due to the
possible to adjust selected settings for com-
Fuse failure monitoring and other supervi- load current and the accompanying drop in
missioning purposes.
sion functions temperature of the cooling medium. The
previous load is therefore taken into ac-
The 7SA6 relay provides comprehensive su- count in the tripping time with overload. A
pervision functions covering both hardware settable alarm stage can output a current or
and software. Furthermore, the measured temperature-dependent indication before
values are continuously checked for plausi- the tripping point is reached.
bility. Therefore the current and voltage
transformers are also included in this super- BCD-coded output of fault location
vision system.
The fault location calculated by the unit can
If any measured voltage is not present due be output for remote indication in BCD
to short-circuit or open circuit in the volt- code. The output of the fault location is
age transformer secondary circuit, the dis- made in percent of the set line length with
tance protection would respond with an 3 decimal digits.
unwanted trip due to this loss of voltage.

1) Available as of mid 2004.

6/10 Siemens SIP · 2004


6 Distance Protection / 7SA6

Time synchronization interface


Communication
The time synchronization interface is a stan-
With respect to communication, particular dard feature in all units. The supported for-
emphasis is placed on the customer require- mats are IRIG-B and DCF77.
ments in energy automation:
• Every data item is time-stamped at the Reliable bus architecture
source, i.e. where it originates. • RS485 bus
• Already during the process of communi- With this data transmission via copper
cation, information is assigned to the conductors, electromagnetic fault influ-
cause thereof (e.g. assignment of the indi- ences are largely eliminated by the use of
cation “circuit-breaker TRIP” to the cor- twisted-pair conductors. Upon failure of a
responding command). unit, the remaining system continues to
operate without any problem.
• The communication system automatically
handles the transfer of large data blocks • Fiber-optic double ring circuit
(e.g. fault recordings or parameter data The fiber-optic double ring circuit is im-
Fig. 6/15
files). The user has access to these features mune to electromagnetic interference.
IEC 60870-5-103 star-type RS232 copper
without any additional programming ef- Upon failure of a section between two conductor connection or fiber-optic connection
fort. units, the communication system contin-
ues to operate without disturbance. It is
• For the safe execution of a control com- usually impossible to communicate with
mand the corresponding data telegram is a unit that has failed. Should a unit fail,
initially acknowledged by the unit which there is no effect on the communication 6
will execute the command. After the re- with the rest of the system.
lease and execution of the command a
feedback signal is generated. At every stage Retrofitting: Modules for every type of
of the control command execution partic- communication
ular conditions are checked. If these are
not satisfied, command execution may be Communication modules for retrofitting
terminated in a controlled manner. are available for the entire SIPROTEC 4 unit
range. These ensure that, where different
The units offer a high degree of flexibility by communication protocols
supporting different standards for connec- (IEC 60870-5-103, PROFIBUS, DNP, etc.)
tion to industrial and power automation are required, such demands can be met. For
systems. By means of the communication fiber-optic communication, no external
modules, on which the protocols run, ex- converter is required for SIPROTEC 4.
change and retrofit is possible. Therefore,
the units will also in future allow for opti- IEC 60870-5-103 protocol
mal adaptation to changing communication
infrastructure such as the application of IEC 60870-5-103 is an internationally stan-
Ethernet networks (which will also be used dardized protocol for efficient communica- Fig. 6/16
increasingly in the power supply sector in tion with protection relays. Bus structure: Fiber-optic double ring circuit
the years to come). IEC 60870-5-103 is supported by a number
of protection device manufacturers and is
used world-wide. Supplements for the con- Master control unit
Local PC interface
trol function are defined in the manufac-
The serial RS232 PC interface accessible turer-specific part of this standard.
from the front of the unit permits quick ac-
cess to all parameters and fault event data. PROFlBUS-FMS
The use of the DIGSI 4 operating program
is particularly advantageous during commis- PROFIBUS-FMS is an internationally
sioning. standardized communication protocol
(EN 50170). PROFIBUS is supported inter-
Service/modem interface nationally by several hundred manufactur-
ers and has to date been used in more than
7SA6 units are always fitted with a rear-side 1,000,000 applications all over the world.
hardwired service interface, optionally as Connection to a SIMATIC programmable
RS232 or RS485. In addition to the controller is made on the basis of the data
front-side operator interface, a PC can be con- obtained (e.g. fault recording, fault data,
nected here either directly or via a modem. measured values and control functionality) Fig. 6/17
via the SICAM energy automation system. Bus structure: RS485 copper conductor
connection

Siemens SIP · 2004 6/11


6 Distance Protection / 7SA6

Communication

LSP2164-afpen.tif
LSP2162-afpen.tif
PROFIBUS-DP
PROFIBUS-DP is an industrial
communications standard and is
supported by a number of PLC and
protection device manufacturers.
DNP 3.0
DNP 3.0 (Distributed Network Pro-
tocol, Version 3) is an internation-
ally recognized protection and bay
Fig. 6/18 Fig. 6/20
unit communication protocol.
Fiber-optic communication module Fiber-optic double ring communication module
SIPROTEC 4 units are Level 1 and
Level 2 compatible.

LSP2163-afpen.tif

LSP2207-afp.tif
IEC 61850 protocol1)
The Ethernet-based IEC 61850 pro-
tocol will be the worldwide stan-
dard for protection and control
systems used by power utilities.
6 Siemens is one of the first manufac-
turers to support this standard. By
means of this protocol, information
can also be exchanged directly be-
tween IEDs. Access to the units via
the Ethernet bus will also be possi- Fig. 6/19 Fig. 6/21
ble with DIGSI. Electrical communication module Output module 0 to 20 mA, 2 channels

Analog outputs 0 to 20 mA
2 or 4 analog output interfaces for
transmission of measured or fault
location values are available for the
7SA6. Two analog output interfaces
are provided in an analog output
module. Up to two analog output
modules can be inserted per unit.

Fig. 6/22
Communication

1) Available approx. as of mid 2004.

6/12 Siemens SIP · 2004


6 Distance Protection / 7SA6

• Signaling for directional earth-fault pro- • FO181): For direct connection


Communication
tection – directional comparison for high up to 60 km3) 1300 nm, for mono-mode
System solutions for protection and station resistance faults in solidly earthed systems fiber 9/125 µm, LC-Duplex connector
control • Echo-function • FO191): For direct connection
Together with the SICAM power automa- • Two and three-terminal line applications up to 100 km3) 1550 nm, for mono-mode
tion system, SIPROTEC 4 can be used with can be implemented without additional fiber 9/125 µm, LC-Duplex connector
PROFIBUS-FMS. Over the low-cost electri- logic
The link to a multiplexed communication
cal RS485 bus, or interference-free via the • Interclose command transfer with the network is made by separate communica-
optical double ring, the units exchange in- auto-reclosure “Adaptive dead time” tion converters (7XV5662). These have a fi-
formation with the control system. Units (ADT) mode ber-optic interface with 820 nm and ST
equipped with IEC 60870-5-103 interfaces • Redundant communication path switch connectors to the protection relay. The link
can be connected to SICAM in parallel via over is possible with the 7SA6 when 2 se- to the communication network is optionally
the RS485 bus or connected in star by fi- rial protection data interfaces are installed an electrical X21 or a G703.1 interface.
ber-optic link. Through this interface, the
• 28 remote signals for fast transfer of For operation via copper wire communica-
system is open for the connection of units of
binary signals tion (pilot wires), a modern communica-
other manufacturers (see Fig. 6/22).
• Flexible utilisation of the communication tion converter for copper cables is available.
Because of the standardized interfaces, channels by means of the programmable This operates with both the two-wire and
SIPROTEC units can also be integrated into CFC logic three-wire copper connections which were
systems of other manufacturers or in • Display of the operational measured val- used by conventional differential protection
SIMATIC. Electrical RS485 or optical inter- ues of the opposite terminal(s) with systems before. The communication con-
faces are available. The optimum physical phase-angle information relative to a verter for copper cables is designed for 5 kV
data transfer medium can be chosen thanks common reference vector insulation voltage. An additional 20 kV iso- 6
to opto-electrical converters. Thus, the lation transformer can extend the field of
RS485 bus allows low-cost wiring in the cu- • Clock synchronization: the clock in only applications of this technique into ranges
bicles and an interference-free optical con- one of the relays must be synchronized with higher insulation voltage requirements.
nection to the master can be established. from an external so called “Absolute Mas- With SIPROTEC 4 and the communication
ter” when using the serial protection data converter for copper cables a digital fol-
For IEC 61850, an interoperable system so- interface. This relay will then synchronize
lution is offered with SICAM PAS. Via the low-up technique is available for two-wire
the clock of the other (or the two other protection systems (typical 15 km) and all
100 Mbits/s Ethernet bus, the units are relays in 3 terminal applications) via the
linked with PAS electrically or optically to three-wire protection systems using existing
protection data interface. copper communication links. Furthermore,
the station PC. The interface is standard-
ized, thus also enabling direct connection of • 7SA522 and 7SA6 can be combined via a communication converter is available,
units of other manufacturers to the Ethernet the protection data interface. which enables the link to an ISDN connec-
bus. With IEC 61850, however, the units tion via the S0-bus.
The communication possibilities are identi-
can also be used in other manufacturers’ cal to those for the line differential protec- Communication data:
systems. Units with an IEC 60870-5-103 in- tion relays 7SD5 and 7SD610. The following
terface are connected with PAS via the • Supported network interfaces G703.1 with
options are available: 64 kBit/s; X21/RS422 with 64 or 128 or
Ethernet station bus by means of se-
rial/Ethernet converters. DIGSI and the • FO51), OMA12) module: Optical 820 nm, 512 kBit/s
Web monitor can also be used via the same 2 ST connectors, FO cable length up to • Max. channel delay time 0.1 ms to 30 ms
station bus. 1.5 km for link to communication (in steps of 0.1 ms)
networks via communication converters • Protocol HDLC
Serial protection data interface or for direct FO cable connection
• 32-bit CRC-check according to CCITT
The tele (pilot) protection schemes can be • FO61), OMA22) module: Optical 820 nm, and ITU
implemented using digital serial communi- 2 ST connectors, FO cable length up to
• Each protection relay possesses a unique
cation. The 7SA6 is capable of remote relay 3.5 km, for direct connection via
relay address
communication via direct links or multi- multi-mode FO cable
• Continuous communication link supervi-
plexed digital communication networks. • FO71), OMA32) module: Optical 1300 nm, sion: Individual faulty data telegrams do
The serial protection data interface has the 2 ST connectors, FO cable length up to not constitute an immediate danger, if
following features: 10 km, for direct connection via they occur only sporadically. The statisti-
mono-mode FO cable cal availability, per minute and hour, of
• Fast phase-selective teleprotection signal-
• FO81), OMA42) module: Optical 1300 nm, the serial protection data interface can be
ing for distance protection, optionally
2 FC connectors, FO cable length up to displayed.
with POTT or PUTT schemes
35 km, for direct connection via
mono-mode FO cable Figure 6/23 shows four applications for the
serial protection data interface on a two-
1) For flush-mounting housing.
New fiber-optic interfaces, series FO1x4) terminal line.
2) For surface-mounting housing.
3) For surface-mounting housing the internal • FO171): For direct connection
fiber-optic module OMA1 will be delivered up to 25 km3), 1300 nm, for mono-mode
together with an external repeater. fiber 9/125 µm, LC-Duplex connector
4) Available approx. 10/2004.

Siemens SIP · 2004 6/13


6 Distance Protection / 7SA6

Communication

Fig. 6/23
Communication topologies for the serial protection data interface on a two-terminal line

1) Available approx. 10/2004.

6/14 Siemens SIP · 2004


6 Distance Protection / 7SA6

Communication

Three-terminal lines can also be protected


with a tele (pilot) protection scheme by us-
ing SIPROTEC 4 distance protection relays.
The communication topology may then be
a ring or a chain topology, see Fig. 6/24. In a
ring topology a loss of one data connection
is tolerated by the system. The topology is
re-routed in a chain with less than 100 ms.
To reduce communication links and to save
money for communications, a chain topol-
ogy may be generally applied.

Ring topology

Chain topology

Fig. 6/24
Ring or chain communication topology

Siemens SIP · 2004 6/15


6 Distance Protection / 7SA6

Typical connection

Connection for current and voltage trans-


formers
3 phase current transformers with neutral
point in the line direction, I4 connected as
summation current transformer (=3I0):
Holmgreen circuit
3 voltage transformers, without connection
of the broken (open) delta winding on the
line side; the 3V0 voltage is derived inter-
nally.

Fig. 6/25 Example of connection for current and voltage transformers

Alternative current measurement


6 The 3 phase current transformers are con-
nected in the usual manner. The neutral
point is in line direction. I4 is connected to a
separate neutral core-balance CT, thus per-
mitting a high sensitive 3I0 measurement.
Note: Terminal Q7 of the I4 transformer
must be connected to the terminal of the
core balance CT pointing in the same direc-
tion as the neutral point of the phase cur-
rent transformers (in this case in line
direction). The voltage connection is
effected in accordance with Fig. 6/25, 6/29
or 6/30.

Fig. 6/26 Alternative connection of current transformers for sensitive


earth-current measuring with core-balance current transformers

6/16 Siemens SIP · 2004


6 Distance Protection / 7SA6

Typical connection

Alternative current connection


3 phase current transformers with neutral
point in the line direction, I4 connected to a
current transformer in the neutral point of
an earthed transformer for directional
earth-fault protection. The voltage connec-
tion is effected in accordance with Fig. 6/25,
6/29 or 6/30.

Fig. 6/27 Alternative connection of current transformers for measuring


neutral current of an earthed power transformer

Alternative current connection


6
3 phase current transformers with neutral
point in the line direction, I4 connected to
summation current of the parallel line for
parallel line compensation on overhead
lines. The voltage connection is effected in
accordance with Fig. 6/25, 6/29 or 6/30.

Fig. 6/28 Alternative connection of current transformers for measuring


the earth current of a parallel line

Siemens SIP · 2004 6/17


6 Distance Protection / 7SA6

Typical connection

Alternative voltage connection


3 phase voltage transformers, V4 connected
to broken (open) delta winding (Ven) for
additional summation voltage monitoring
and earth-fault directional protection.
The current connection is effected in
accordance with Fig. 6/25, 6/26, 6/27
and 6/28.

Fig. 6/29 Alternative connection of voltage transformers for measuring the


displacement voltage (e-n voltage)

Alternative voltage connection


6
3 phase voltage transformers, V4 connected
to busbar voltage transformer for synchro-
check.
Note: Any phase-to-phase or phase-to-earth
voltage may be employed as the busbar volt-
age. Parameterization is carried out on the
unit. The current connection is effected in
accordance with Fig. 6/25, 6/26, 6/27
and 6/28.

Fig. 6/30 Alternative connection of voltage transformers for measuring the


busbar voltage

6/18 Siemens SIP · 2004


6 Distance Protection / 7SA6

Technical data

General unit data Output contacts


Analog inputs “Unit ready” contact 1 NC/NO contact1)
Rated frequency 50 or 60 Hz (selectable) (live status contact)

Rated current Inom 1 or 5 A (selectable) Command/indication relay


Quantity
Rated voltage Vnom 80 to 125 V (selectable)
7SA610*-*A/E/J 7 NO contacts, 1 NC/NO contact1)
Power consumption 7SA610*-*B/F/K 5 NO contacts,
With Inom = 1 A Approx. 0.05 VA 7SA6*1*-*A/E/J 14 NO contacts, 2 NC/NO contacts1)
With Inom = 5 A Approx. 0.30 VA 7SA6*1*-*B/F/K 8 NO contacts, 4 power relays2)
For IE, sensitive with 1 A Approx. 0.05 VA 7SA6*2*-*A/E/J 21 NO contacts, 3 NC/NO contacts1)
Voltage inputs ≤ 0.10 VA 7SA6*2*-*B/F/K 28 NO contacts, 4 NC/NO contacts1)
Overload capacity of current circuit 7SA6*2*-*C/G/L 11 NO contacts, 8 power relays2)
(r.m.s.) NO/NC contact
Thermal 500 A for 1 s
Switching capacity
150 A for 10 s
Make 1000 W / VA
Dynamic (peak value) 20 A continuous
Break, high-speed trip outputs 1000 W / VA
1250 A (half cycle)
Break, contacts 30 VA
Earth current Break, contacts (for resistive load) 40 W
Sensitive 300 A for 1 s Break, contacts
100 A for 10 s (for τ = L/R ≤ 50 ms) 25 VA
15 A continuous
Switching voltage 250 V
Dynamic (peak value) 750 A (half cycle)
Thermal overload capacity of volt- 230 V continuous
Permissible total current 30 A for 0.5 seconds 6
5 A continuous
age circuit
Operating time, approx.
Auxiliary voltage
NO contact 8 ms
Rated voltages 24 to 48 V DC NO/NC contact (selectable) 8 ms
60 to 125 V DC Fast NO contact 5 ms
110 to 250 V DC High-speed NO trip outputs < 1 ms
and 115 V AC (50/60 Hz)
Power relay
Permissible tolerance -20 % to +20 % for direct control of disconnector
Superimposed AC voltage ≤ 15 % actuator motors
(peak-to-peak) Switching capacity
Power consumption Make for 48 to 250 V 1000 W/ VA
Quiescent Approx. 5 W Break for 48 to 250 V 1000 W/ VA
Energized Approx. 12 W to 18 W, depending on Make for 24 V 500 W/ VA
design Break for 24 V 500 W/ VA
Bridging time during failure of the Switching voltage 250 V
auxiliary voltage Permissible total current 30 A for 0.5 seconds
For Vaux = 48 V and Vaux ≥ 110 V ≥ 50 ms 5 A continuous
For Vaux = 24 V and Vaux = 60 V ≥ 20 ms
Max. operating time 30 s
Binary inputs
Permissible relative operating time 1%
Quantity
LEDs
7SA610*-*A/E/J 5
7SA610*-*B/F/K 7 Quantity
7SA6*1*-*A/E/J 13 RUN (green) 1
7SA6*1*-*B/F/K 20 ERROR (red) 1
7SA6*2*-*A/E/J 21 LED (red),
7SA6*2*-*B/F/K 29 function can be assigned
7SA6*2*-*C/G/L 33 7SA610 7
Rated voltage range 24 to 250 V, bipolar 7SA6*1/2/3 14
Pickup threshold 17 or 73 or 154 V DC, bipolar
Functions are freely assignable
Minimum pickup voltage 17 or 73 or 154 V DC, bipolar
Ranges are settable by means of (3 operating ranges)
jumpers for each binary input
Maximum permissible voltage 300 V DC
Current consumption, energized Approx. 1.8 mA
Input impulse suppression 220 nF coupling capacitance at 220 V
with a recovery time >60 ms

1) Can be set via jumpers.


2) Each pair of power relays is mechanically
interlocked to prevent simultaneous closing.

Siemens SIP · 2004 6/19


6 Distance Protection / 7SA6

Technical data

Unit design PROFIBUS fiber-optic


Housing 7XP20 Only for flush-mounting housing ST connector
For surface-mounting housing Optical interface with OLM5)
Dimensions Refer to part 16 f. dimension drawings Baud rate Max. 1.5 Mbaud
Degree of protection acc. to Optical wavelength λ = 820 nm
EN 60529 Permissible attenuation Max. 8 dB for 62.5/125 µm fiber
Surface-mounting housing IP 51 Distance 500 kbit/s 1.6 km 1500 kbit/s 530 m
Flush-mounting housing Protection data interface
Front IP 51
Rear IP 50 Quantity 1
For the terminals IP 20 with terminal cover put on FO51), OMA12): Fiber-optic interface For multi-mode fiber 62.5/125 µm,
Weight with clock recovery for direct con- ST connectors
Flush-mounting 1/3 x 19" 4 kg nection up to 1.5 km or for connec- Permissible fiber attenuation 8 dB
housing 1/2 x 19" 6 kg tion to a communication converter,
2/3 x 19" 8 kg 820 nm
1/1 x 19" 10 kg FO61), OMA22): Fiber-optic interface For multi-mode fiber 62.5/125 µm,
Surface-mounting 1/3 x 19" 6 kg for direct connection up to 3.5 km, ST connectors
housing 1/2 x 19" 11 kg 820 nm Permissible fiber attenuation 16 dB
1/1 x 19" 19 kg FO71), OMA32): Fiber-optic interface For mono-mode fiber 9/125 µm,
for direct connection up to 10 km, ST connectors
Serial interfaces 1300 nm Permissible fiber attenuation 7 dB

Operating interface for DIGSI 4 (front of unit) FO81), OMA42): Fiber-optic interface For mono-mode fiber 9/125 µm,
6 Connection Non-isolated, RS232,
for direct connection up to 35 km, FC connectors
1300 nm Permissible fiber attenuation 18 dB
9-pin subminiature connector
(SUB-D) New fiber-optic interfaces, series FO1x4)

Baud rate 4800 to 115200 baud FO171): for direct connection up to For mono-mode fiber 9/125 µm,
setting as supplied: 38400 baud; 25 km3), 1300 nm LC-Duplex connector
parity 8E1 Permissible fiber attenuation 13 dB

Time synchronization FO181): for direct connection up to For mono-mode fiber 9/125 µm,
60 km3), 1300 nm LC-Duplex connector
DCF77/ IRIG-B signal (format IRIG-B000) Permissible fiber attenuation 29 dB
Connection 9-pin subminiature connector FO191): for direct connection up to For mono-mode fiber 9/125 µm,
(SUB-D) 100 km3), 1550 nm LC-Duplex connector
(terminal with surface-mounting Permissible fiber attenuation 29 dB
housing)
Relay communication equipment
Voltage levels 5 V, 12 V or 24 V (optional)
External communication converter 7XV5662-0AA00 with X21/RS422 or
Service/modem interface for DIGSI 4 / modem / service G703.1 interface
Isolated RS232/RS485 9-pin subminiature connector External communication converter Electrical X21/RS422 or G703.1 inter-
(SUB-D) for linking the optical 820 nm inter- face settable by jumper
Dielectric test 500 V / 50 Hz face of the unit (FO5/OMA1 option Baud rate settable by jumper
Distance for RS232 Max. 15 m with clock recovery) to the
Distance for RS485 Max. 1000 m X21/RS422/G703.1 interface of the
System interface communication network
IEC 60870-5-103 protocol FO interface with 820 nm with clock Max. 1.5 km with 62.5/125 µm multi-
PROFIBUS-FMS recovery mode fiber to protection relay
PROFIBUS-DP Electrical X21/RS422 interface 64/128/512 kbit (settable by jumper)
DNP 3.0 max. 800 m, 15-pin connector to the
IEC 61850 Ethernet communication network
Isolated RS232/RS485 9-pin subminiature connector Electrical G703.1 interface 64 kbit/s max. 800 m, screw-type ter-
(SUB-D) minal to the communication network
Baud rate 4800 to 38400 baud
Dielectric test 500 V / 50 Hz
Distance for RS232 Max. 15 m
Distance for RS485 Max. 1000 m
PROFIBUS RS485
Dielectric test 500 V / 50 Hz
Baud rate Max. 12 Mbaud
Distance 1 km at 93.75 kBd; 100 m at 12 MBd

1) For flush-mounting housing. 5) Conversion with external OLM


2) For surface mounting housing. For fiber-optic interface please complete order number at 11th position
3) For surface mounting housing the internal fiber-optic module with 4 (FMS RS485) or 9 and Order Code L0A (DP RS485) and addition-
OMA1 will be delivered together with an external repeater. ally order:
For single ring: SIEMENS OLM 6GK1502-3AB10
4) Available approx. 10/2004. For double ring: SIEMENS OLM 6GK1502-4AB10

6/20 Siemens SIP · 2004


6 Distance Protection / 7SA6

Technical data

External communication converter 7XV5662-0AC00 for pilot wires Irradiation with RF field, 10 V/m; 900 MHz; repetition frequency
External communication converter Typical distance: 15 km max. pulse-modulated 200 Hz; duty cycle 50 %
for linking the optical 820 nm inter- IEC 61000-4-3/ ENV 50204, class III
face of the unit (FO5/OMA1 option Fast transient disturbance/bursts 4 kV; 5/50 ns; 5 kHz;
with clock recovery) to pilot wires. IEC 60255-22-4 and burst length = 15 ms;
FO interface for 820 nm with clock IEC 61000-4-4, class IV repetition rate 300 ms; both polarities;
recovery Max. 1.5 km with 62.5/125 µm multi- Ri = 50 Ω; test duration 1 min
mode fiber to protection relay, 128 kbit High-energy surge voltages Impulse: 1.2/50 µs
Electrical interface to pilot wires 5 kV-isolated (SURGE),
IEC 61000-4-5 installation class III
External communication converter 7XV5662-0AB00 for ISDN connections Auxiliary supply Common (longitudinal) mode: 2 kV;
External communication converter 12 Ω; 9 µF
to interface between relays optical Differential (transversal) mode:1 kV;
820 nm interf. and ISDN telep. line 2 Ω; 18 µF
Input: fiber-optic 820 nm Max. 1.5 km with 62.5/125 µm Measurement inputs, binary inputs, Common (longitudinal) mode:
with clock recovery multi-mode FO cable to device side binary output relays 2 kV; 42 Ω; 0.5 µF
Output: ISDN electrical interface 64/128 kbit (selectable by jumper) Differential (transversal) mode:
max. 800 m, 15-pin connector 1 kV; 42 Ω; 0.5 µF
Permissible time delay (duration of data transmission) Line-conducted HF, amplitude- 10 V; 150 kHz to 80 MHz; 80 % AM;
Delay of telegrams due to transmis- Max. 30 ms per transmission path modulated, IEC 61000-4-6, class III 1 kHz
sion for one unit to the other. Permissible max. value can be selected Magnetic field with power fre- 30 A/m continuous; 300 A/m for 3 s;
Delay constantly measured/adjusted quency IEC 61000-4-8, class IV; 50 Hz
IEC 60255-6 0.5 mT; 50 Hz 6
Oscillatory surge withstand capabil- 2.5 to 3 kV (peak); 1 to 1.5 MHz
Electrical tests
ity, ANSI/IEEE C37.90.1 damped wave; 50 surges per second,
Specifications duration 2 s, Ri = 150 to 200 Ω
Standards IEC 60255 (product standards) Fast transient surge withstand capa- 4 to 5 kV; 10/150 ns; 50 surges per
ANSI/IEEE C37.90.0/.1/.2; UL 508 bility, ANSI/IEEE C37.90.1 second; both polarities; duration 2 s;
DIN 57435 Part 303 Ri = 80 Ω
Further standards see “Individual tests”
Radiated electromagnetic interfer- 35 V/m; 25 to 1000 MHz,
Insulation tests ence ANSI/IEEE C37.90.2 amplitude and pulse-modulated
Standards IEC 60255–5 and 60870-2-1 Damped oscillation 2.5 kV (peak value); polarity alternating
Voltage test (100 % test) IEC 60694, IEC 61000-4-12 100 kHz; 1 MHz; 10 and 50 MHz; Ri =
200 Ω
All circuits except for auxiliary 2.5 kV (r.m.s.), 50 Hz
supply, binary inputs, EMC tests for interference emission; type test
communication and time Standard EN 50081-* (generic standard)
synchronization interfaces Conducted interference voltage on 150 kHz to 30 MHz
Auxiliary voltage and binary 3.5 kV DC lines, only auxiliary voltage Limit class B
inputs (100 % test) IEC-CISPR 22
RS485/RS232 rear side communi- 500 V (r.m.s.), 50 Hz Radio interference field strength 30 to 1000 MHz
cation interfaces and time syn- IEC-CISPR 22 Limit class B
chronization interface Mechanical stress test
(100 % test)
Vibration, shock stress and seismic vibration
Impulse voltage test (type test)
During operation
All circuits except for communi- 5 kV (peak); 1.2/50 µs; 0.5 J,
cation interfaces and time 3 positive and 3 negative impulses in Standards IEC 60255–21 and IEC 60068–2
synchronization interface, class III intervals of 5 s Vibration Sinusoidal
EMC tests for noise immunity; type tests IEC 60255–21–1, class 2 10 to 60 Hz: ± 0.075 mm amplitude;
IEC 60068–2–6 60 to 150 Hz: 1 g acceleration
Standards IEC 60255-6/-22 (product standard) frequency sweep 1 octave/min
EN 50082-2 (generic standard), 20 cycles in 3 orthogonal axes
DIN 57435 Part 303
Shock Half-sinusoidal
High-frequency test 2.5 kV (peak); 1 MHz; τ = 15 ms; IEC 60255–21–2, class 1 Acceleration 5 g, duration 11 ms,
IEC 60255-22-1 class III and 400 surges per s; test duration 2 s IEC 60068–2–27 3 shocks on each of the 3 axes in both
DIN 57435 Part 303, class III directions
Electrostatic discharge 8 kV contact discharge; 15 kV air Seismic vibration Sinusoidal
IEC 60255-22-2 class IV discharge; both polarities; 150 pF; IEC 60255–21–2, class 1 1 to 8 Hz: ± 3.5 mm amplitude
and EN 61000-4-2, class IV Ri = 330 Ω IEC 60068–3–3 (horizontal axis)
Irradiation with RF field, 10 V/m; 27 to 500 MHz 1 to 8 Hz: ± 1.5 mm amplitude
non-modulated (vertical axis)
IEC 60255-22-3 (report) class III 8 to 35 Hz: 1 g acceleration
(horizontal axis)
Irradiation with RF field, 10 V/m; 80 to 1000 MHz; 80 % AM; 8 to 35 Hz: 0.5 g acceleration
amplitude-modulated 1 kHz (vertical axis)
IEC 61000-4-3, class III Frequency sweep 1 octave/min
1 cycle in 3 orthogonal axes

Siemens SIP · 2004 6/21


6 Distance Protection / 7SA6

Technical data

During transport Zone setting X 0.05 to 600 Ω (1A) / 0.01 to 120 Ω (5A)
Standards IEC 60255–21 and IEC 60068–2 (for distance zones and Z< starting) (step 0.01 Ω)
Vibration Sinusoidal Resistance setting
IEC 60255–21–1, class 2 5 to 8 Hz: ± 7.5 mm amplitude; (for distance zones and Z< starting)
IEC 60068–2–6 8 to 150 Hz: 2 g acceleration Phase-to-phase faults and 0.05 to 600 Ω (1A) / 0.01 to 120 Ω (5A)
Frequency sweep 1 octave/min phase-to-earth faults (step 0.01 Ω)
20 cycles in 3 orthogonal axes Line angle 30 ° to 89 °
Shock Half-sinusoidal R reach of distance zones runs parallel
IEC 60255–21–2, class 1 Acceleration 15 g, duration 11 ms, to the line angle setting
IEC 60068–2–27 3 shocks on each of the 3 axes in both Inclination angle for 30° to 90° (step 1°)
directions quadrilateral characteristic
Continuous shock Half-sinusoidal Overcurrent pickup I>> 0.25 to 10 A (1A) / 1.25 to 50 A (5A)
IEC 60255–21–2, class 1 Acceleration 10 g, duration 16 ms, (for I>>, V</I>, V</I>/ϕ>) (step 0.01 A)
IEC 60068–2–29 1000 shocks on each of the 3 axes in
both directions Minimum current pickup I> 0.05 to 4 A (1A) / 0.25 to 20 A (5A)
(for V</I>, V</I>/ϕ> and Z<) (step 0.01 A)
Minimum current pickup Iϕ> 0.1 to 8 A (1A) / 0.5 to 40 A (5A)
Climatic stress tests
(for V</I>, V</I>/ϕ>) (step 0.01 A)
Temperatures
Undervoltage pickup (for V</I>
Type-tested acc. to IEC 60068-2-1 -25 °C to +85 °C / -13 °F to +185 °F and V</I>/ϕ>)
and -2, test Bd, for 16 h VPH-e< 20 to 70 V (step 1 V)
6 Temporarily permissible operating -20 °C to +70 °C / -4 °F to +158 °F VPH-PH< 40 to 130 V (step 1 V)
temperature, tested for 96 h Load angle pickup (for V</I>/ϕ>)
(Legibility of display may be im- Load angle ϕ 30 ° to 80 °
paired above +55 °C / +131 °F) Load angle ϕ 90 ° to 120 °
Recommended permanent operat- -5 °C to +55 °C / +25 °F to +131 °F Load zone (for Z<) Impedances within the load zone do
ing temperature acc. to IEC 60255-6 not cause pickup in pickup mode Z<;
– Limiting temperature during -25 °C to +55 °C / -13 °F to 131 °F Load zones for phase-to-phase and
permanent storage phase-to-earth faults can be set sepa-
– Limiting temperature during -25 °C to +70 °C / -13 °F to +158 °F rately
transport Load angle 20 ° to 60 °
Humidity Resistance 0.1 to 600 Ω (1A) / 0.02 to 120 Ω (5A)
Permissible humidity stress: Annual average on ≤ 75 % relative Earth-fault detection
It is recommended to arrange the humidity; on 56 days in the year up to Earth current 3I0> 0.05 to 4 A (1A) / 0.25 A to 20 A (5A)
units in such a way that they are not 93 % relative humidity; condensation (step 0.01 A)
exposed to direct sunlight or pro- is not permitted. Zero-sequence voltage 3V0>
nounced temperature changes that for earthed networks 1 to 100 V (step 1 V) or deactivated
could cause condensation. for resonant-earthed networks 10 to 200 V (step 1 V)
Earth impedance matching
Functions Parameter formats RE/RL and XE/XL or k0 and ϕ (k0)
Separately settable for Distance protection zone Z1 and
Distance protection (ANSI 21, 21N) higher distance zones (Z1B, Z2 to Z5)
Types of pickup Overcurrent pickup (I>); RE/RL and XE/XL -0.33 to +7.00 (step 0.01)
Voltage-dependent overcurrent k0 and ϕ (k0) 0 to 4 (step 0.01) and - 135 ° to 135 °
pickup (V< / I>); (step 0.01 °)
Voltage-dependent and phase an- Parallel line matching For parallel compensation
gle-dependent overcurrent pickup RM/RL and XM/XL 0 to 8 (step 0.01)
(V< / I> / ϕ>);
Impedance pickup (Z<) Phase preference on double Phase preference or no preference
earth-faults in resonant-earthed / (selectable)
Types of tripping Three-pole for all types of faults;
non-earthed networks
Single-pole for single-phase faults /
otherwise three-pole; Direction decision for all types of With fault-free voltages and/or volt-
Single-pole for single-phase faults and faults age memory
two-pole phase-to-phase faults / Direction sensitivity Dynamically unlimited
otherwise three-pole Times
Characteristic Quadrilateral or circle Shortest trip time Approx. 17 ms for fN = 50 Hz
(measured at the fast relay; Approx. 15 ms for fN = 60 Hz
Distance protection zones 6, 1 of which as controlled zone refer to the terminal
All zones can be set to forward, re- connection diagram)
verse, non-directional or inactive Shortest trip time (measured at Approx. 12 ms at 50 Hz
Timer stages for tripping delay 6 for multi-phase faults the high-speed trip outputs) Approx. 10 ms at 60 Hz
3 for single-phase faults Reset time Approx. 30 ms
Setting range 0 to 30 s or deactivated (steps 0.01 s)

6/22 Siemens SIP · 2004


6 Distance Protection / 7SA6

Technical data

Tolerances For sinusoidal measured variables Direct transfer trip (DTT)


Response values (in conformity Direct phase-selective tripping via Alternatively with or without
with DIN 57435, Part 303) binary input auto-reclosure
V and I ≤ 5 % of setting value Trip time delay 0 to 30 s (step 0.01 s)
Angle (ϕ) ≤3°
Timer tolerance 1 % of setting value or 10 ms
∆X Power swing detection (ANSI 68, 68T)
Impedances ≤ 5 % for 30 ° ≤ ϕSC ≤ 90 °
(in conformity with DIN 57435, X
Power swing detection principle Measurement of the rate of change of
Part 303) ∆R the impedance vector and monitoring
≤ 5 % for 0 ° ≤ ϕSC ≤ 60 °
R of the vector path
Max. detectable power swing fre- Approx. 7 Hz
Time stages 1 % of setting value or 10 ms
quency
Fault locator
Operating modes Power swing blocking and/or
Output of the distance to fault X, R (secondary) in Ω power swing tripping for out-of-step
X, R (primary) in Ω conditions
Distance in kilometers or in % of line
Power swing blocking programs All zones blocked; Z1/Z1B blocked;
length
Z2 to Z5 blocked; Z1, Z1B, Z2
Start of calculation With trip, with reset of pickup, with blocked
binary input
Detection of faults during power Reset of power swing blocking for all
Reactance per unit length 0.005 to 6.5 Ω/km(1A) / 0.001 to swing blocking types of faults
1.3 Ω/km(5A)
Backup overcurrent protection (ANSI 50 (N), 51 (N))
(step 0.0001 Ω/km) 6
Operating modes Active only with loss of VT secondary
Tolerance For sinusoidal quantities
circuit or always active
≤ 2.5 % line length for
30 ° ≤ ϕSC ≤ 90 ° and VSC/Vnom > 0.1 Characteristic 2 definite-time stages / 1 inverse-time
stage
BCD-coded output of fault location
Instantaneous trip after Selectable for every stage
Indicated value Fault location in % of the line length
switch-onto-fault
Output signals Max. 10:
Definite-time stage (ANSI 50, 50N)
d[1 %], d[2 %], d[4 %], d[8 %],
d[10 %], d[20 %], d[40 %], d[80 %], Phase current pickup IPH>> 0.1 to 25 A (1A) / 0.5 to 125 A (5A)
d[100 %], d[release] (step 0.01 A)
Indication range 0 % to 195 % Earth current pickup 3I0>> 0.05 to 25 A (1A) / 0.25 to 125 A (5A)
(step 0.01 A)
Tele (pilot) protection for distance protection (ANSI 85-21)
Phase current pickup IPH> 0.1 to 25 A (1A) / 0.5 to 125 A (5A)
Modes of operation PUTT (Z1B acceleration); DUTT
(step 0.01 A)
PUTT (acceleration with pickup);
POTT; Directional comparison; Earth current pickup 3I0> 0.05 to 25 A (1A) / 0.25 to 125 A (5A)
Reverse interlocking (step 0.01 A)
Pilot-wire comparison; Unblocking; Time delay 0 to 30 s (step 0.01 s) or deactivated
Blocking
Tolerances
Additional functions Echo function Current pickup ≤ 3 % of setting value or 1 % IN
(refer to weak-infeed function) Delay times 1 % of setting value or 10 ms
Transient blocking for schemes with
measuring range extension Operating time Approx. 25 ms
Transmission and reception signals Phase-selective signals available for
maximum selectivity with single-pole
tripping; signals for 2- and 3-end-
lines
Weak-infeed protection (ANSI 27-WI)
Operating modes with carrier (sig- Echo
nal) reception and no fault detection Echo and trip with undervoltage
Undervoltage phase-earth 2 to 70 V (step 1 V)
Time delay 0 to 30 s (step 0.01 s)
Echo impulse 0 to 30 s (step 0.01 s)
Tolerances
Voltage threshold ≤ 5 % of setting value or 0.5 V
Timer 1 % of setting value or 10 ms

Siemens SIP · 2004 6/23


6 Distance Protection / 7SA6

Technical data

Inverse-time stage (ANSI 51, 51N) Time delay for definite-time stages 0 to 30 s (step 0.01 s) or deactivated
Phase current pickup IP 0.1 to 4 A (1A) / 0.5 to 20 A (5A) Tolerances
(step 0.01 A) Current pickup ≤ 3 % of setting value or 1 % Inom
Earth current pickup 3I0P 0.05 to 4 A (1A) / 0.25 to 20 A (5A) Delay times 1 % of setting value or 10 ms
(step 0.01 A) Command / pickup times 3I0>>> Approx. 30 ms
Tripping time characteristics acc. to Normal inverse; very inverse; and 3I0>>
IEC 60255-3 extremely inverse; long time inverse Command / pickup times 3I0> and Approx. 40 ms
Tripping time characteristics acc. to Inverse; short inverse; long inverse; 3I0, 4th stage
ANSI/IEEE moderately inverse; very inverse; Inverse-time stage (ANSI 51N)
(not for DE region, see selection and extremely inverse; definite inverse Earth-current pickup 3I0P 0.05 to 4 A (1A) / 0.25 to 20 A (5A)
ordering data 10th position) (step 0.01 A)
Time multiplier for IEC charac. T Tp = 0.05 to 3 s (step 0.01 s) Neutral (residual) current trans-
Time multiplier for ANSI charac. D DIP = 0.5 to 15 s (step 0.01 s) former with normal sensitivity
(refer to ordering data, position 7)
Pickup threshold Approx. 1.1 I/Ip (ANSI: I/Ip = M ) 0.003 to 4 A (1A) / 0.015 to 20 A (5A)
Reset threshold Approx. 1.05 x I/Ip (ANSI: I/Ip = M ) (step 0.001 A)
Neutral (residual) current trans-
Tolerances
former with high sensitivity (refer to
Operating time for 2 ≤ I/Ip ≤ 20 ≤ 5 % of setpoint ± 15 ms
ordering data, position 7)
Directional earth-fault overcurrent protection
for high-resistance faults in systems with earthed star point Tripping characteristics acc. to Normal inverse; very inverse;
(ANSI 50N, 51N, 67N) IEC 60255-3 extremely inverse; long time
6 ANSI/IEEE tripping characteristic Inverse; short inverse; long inverse;
Characteristic 3 definite-time stages / 1 inverse-time
stage or 4 definite-time stages or (not for region DE, see selection and moderately inverse; very inverse;
3 definite-time stages / 1 V0invers. stage ordering data, position 10) extremely inverse; definite inverse
Phase selector Permits 1-pole tripping for single- Inverse logarithmic tripping charac- 3I 0
phase faults or 3-pole tripping for teristics (not for regions DE and US, t = T3 I 0 Pmax − T3 I 0 P ln
see selection and ordering data, 3 I 0p
multi-phase faults
position 10)
Inrush restraint Selectable for every stage
Pickup threshold 1.1 to 4.0 x I/Ip (step 0.1 s)
Instantaneous trip after Selectable for every stage
switch-onto-fault Time multiplier for IEC charac. T Tp = 0.05 to 3 s (step 0.01 s)
Influence of harmonics Time multiplier for ANSI charac. D DI0P = 0.5 to 15 s (step 0.01 s)
Stages 1 and 2 (I>>> and I>>) 3rd and higher harmonics are com- Pickup threshold Approx. 1.1 I/Ip (ANSI: I/Ip = M)
pletely suppressed by digital filtering
Inverse logarithmic pickup threshold 1.1 to 4.0 x I/I0P (step 0.1)
Stages 3 and 4 2nd and higher harmonics are com-
(I> and inverse 4th stage) pletely suppressed by digital filtering Reset threshold Approx. 1.05 I/I0P (ANSI: I/Ip = M)
Definite-time stage (ANSI 50N) Tolerance
Operating time for 2 ≤ I/Ip ≤ 20 ≤ 5 % of setpoint ± 15 ms
Pickup value 3I0>>> 0.5 to 25 A (1A) / 2.5 to 125 A (5A)
(step 0.01 A) Zero-sequence voltage protection V0inverse
Pickup value 3I0>> 0.2 to 25 A (1A) / 1 to 125 A (5A) 2s
(step 0.01 A) Tripping characteristic t=
V0
Pickup value 3I0> 0.05 to 25 A (1A) / 0.25 to 125 A (5A) − V 0inv min
4
(step 0.01 A)
Neutral (residual) current trans-
Direction decision (ANSI 67N)
former with normal sensitivity
(refer to ordering data, position 7); Measured signals for direction deci- 3I0 and 3V0 or
0.003 to 25 A (1A) / 0.015 to 125 A (5A) sion 3I0 and 3V0 and IY (star point current
(step 0.001 A) of an earthed power transformer) or
Neutral (residual) current trans- 3I2 and 3V2 (negative-sequence
former with high sensitivity (refer to system) or zero-sequence power Sr or
ordering data, position 7) automatic selection of zero-sequence
or negative-sequence quantities de-
Pickup value 3I0, 4th stage 0.05 to 25 A (1A) / 0.25 to 125 A (5A)
pendent on the magnitude of the
(step 0.01 A)
component voltages
Neutral (residual) current trans-
former with normal sensitivity (refer Min. zero-sequence voltage 3V0 0.5 to 10 V (step 0.1 V)
to ordering data, position 7); Min. current IY (of earthed trans- 0.05 to 1 A (1A) / 0.25 to 5 A (5A)
0.003 to 25 A (1A) / 0.015 to 125 A (5A) formers) (step 0.01 A)
(step 0.001 A)
Neutral (residual) current trans- Min. negative-sequence voltage 3V2 0.5 to 10 V (step 0.1 V)
former with high sensitivity (refer to Min. negative-sequence current 3I2 0.05 to 1 A (1A) / 0.25 to 5 A (5A)
ordering data, position 7) (step 0.01 A)

6/24 Siemens SIP · 2004


6 Distance Protection / 7SA6

Technical data

Inrush current blocking, capable of being activated for each stage Time delays
Component of the 2nd harmonic 10 to 45 % of the fundamental Time delay for all stages 0 to 100 s (step 0.01 s) or deactivated
(step 1 %)
Command / pickup time Approx. 30 ms
Max. current, which cancels inrush 0.5 to 25 A (1A) / 2.5 to 125 A (5A)
Tolerances
current blocking (step 0.01 A)
Voltage limit values ≤ 3 % of setting value or 1 V
Tele (pilot) protection Time stages 1 % of setting value or 10 ms
For directional earth-fault protection (ANSI 85-67N) Frequency protection (ANSI 81)
Operating modes Directional comparison, blocking, Number of frequency elements 4
unblocking
Setting range 45.5 to 54.5 Hz
Additional functions Echo (see function “weak infeed”); (in steps of 0.01) at fnom = 50 Hz
transient blocking for schemes with 55.5 to 64.5 Hz
parallel lines (in steps of 0.01) at fnom = 60 Hz
Send and receive signals Suitable for 2 and 3 end-lines Delay times 0 to 600 s or ∞ (in steps of 0.01 s)
Instantaneous high-speed switch-onto-fault overcurrent protection Operating voltage range 6 to 230 V (phase-to-earth)
(ANSI 50HS) Pickup times Approx. 80 ms
Operating mode Active only after CB closing; Dropout times Approx. 80 ms
instantaneous trip after pickup Hysteresis Approx. 20 mHz
Pickup current I>>> 1 to 25 A (1A) / 5 to 125 A (5A) Dropout condition Voltage = 0 V and current = 0 A
(step 0.01 A) Tolerances
Reset ratio Approx. 0.90 Frequency 12 mHz for 29 to 230 V 6
Delay times 1 % of the setting value or 10 ms
Tolerances
Current starting ≤ 3 % of setting value or 1 % IN Thermal overload protection (ANSI 49)
Shortest tripping time Factor k acc. to IEC 60255-8 0.1 to 4 (steps 0.01)
With reference to fast relays Approx. 12 ms Time constant τ 1 to 999.9 min (steps 0.1 min)
With high-speed trip to outputs Approx. 8 ms
Thermal alarm stage ΘAlarm/ΘTrip 50 to 100 % referred to tripping
Voltage protection (ANSI 59, 27) temperature (steps 1 %)
Operating modes Local tripping and/or carrier trip for Current-based alarm stage IAlarm 0.1 to 4 A (1A) / 0.5 to 20 A (5A)
remote end (steps 0.01 A)
Overvoltage protection Calculating mode for Θmax, Θmean, Θ with Imax
overtemperature
Pickup values VPH-E>>, VPH-E> 1 to 170 V (step 0.1 V)
(phase-earth overvoltage) I 2 − I pre
2

Pickup time characteristic t = τ ln


I 2 − (k I nom)
2
Pickup values VPH-PH>>, VPH-PH> 2 to 220 V (step 0.1 V)
(phase-phase overvoltage)
Reset ratio
Pickup values 3V0>>, 3V0> 1 to 220 V (step 0.1 V) Θ/ΘAlarm Approx. 0.99
(3V0 can be measured via V4 trans- Θ/ΘTrip Approx. 0.99
formers or calculated by the relay) I/ IAlarm Approx. 0.97
(zero-sequence overvoltage)
Overload measured values Θ/ΘTrip L1; Θ/ΘTrip L2; Θ/ΘTrip L3;
Pickup values V1>>, V1> 2 to 220 V (step 0.1 V) Θ/ΘTrip
(positive-sequence overvoltage)
Measured voltage Local positive-sequence voltage or Tolerances Class 10 % acc. to IEC 60255-8
calculated remote positive- Breaker failure protection (ANSI 50BF)
sequence voltage (compounding)
Number of stages 2
Pickup values V2>>, V2> 2 to 220 V (step 0.1 V)
Pickup of current element 0.05 to 20 A (1A) / 0.25 to 100 A (5A)
(negative-sequence overvoltage)
(step 0.01 A)
Reset ratio (settable) 0.5 to 0.98 (step 0.01) Time delays T11phase, T13phase, T2 0 to 30 s (steps 0.01 s) or deactivated
Undervoltage protection Additional functions End-fault protection
Pickup values VPH-E<<, VPH-E< 1 to 100 V (step 0.1 V) CB pole discrepancy monitoring
(phase-earth undervoltage) Drop-off (overshoot) time, internal ≤ 15 ms, typical; 25 ms, max.
Pickup values VPH-PH<<, VPH-PH< 1 to 170 V (step 0.1 V) Tolerances
(phase-phase undervoltage) Current limit value ≤ 5 % of setting value or 1 % Inom
Pickup values V1<<, V1< 1 to 100 V (step 0.1 V) Time stages 1 % of setting value or 10 ms
(positive-sequence undervoltage)
Blocking of undervoltage prot. stages Minimum current; binary input
Reset ratio 1.05

Siemens SIP · 2004 6/25


6 Distance Protection / 7SA6

Technical data

Auto-reclosure (ANSI 79) Delay times 0 to 320 s (step 0.01 s)


Number of auto-reclosures Up to 8 Pickup time Approx. 50 ms
Operating mode Only 1-pole; only 3-pole, 1 or 3-pole Earth-fault measured values Active and reactive component
Operating modes with line voltage DLC – dead-line check of earth-fault current IEEac, IEEreac
check ADT – adaptive dead time Tolerances
RDT – reduced dead time Voltage limit values ≤ 5 % of setting value or 1 V
Dead times T1-PH, T3-PH, TSeq 0 to 1800 s (step 0.01 s) or deactivated Current limit values ≤ 10 % of setting value
Time stages 1 % of setting value or 10 ms
Action times 0.01 to 300 s (step 0.01 s) or deactivated
Trip circuit supervision (ANSI 74TC)
Reclaim times 0.5 to 300 s (step 0.01 s)
Number of supervisable trip circuits Up to 3
Start-signal monitoring time 0.01 to 300 s (step 0.01 s)
Number of required binary inputs 1 or 2
Additional functions Synchro-check request per trip circuit
3-phase intertripping
InterCLOSE command to the remote Indication relay 1 to 30 s (step 1 s)
end
Check of CB ready state Additional functions
Blocking with manual CLOSE
Operational measured values
Voltage limit values for DLC, ADT,
RDT Representation Primary, secondary and percentage
Healthy line voltage PH-E 30 to 90 V (step 1 V) referred to rated value
Dead line voltage PH-E 2 to 70 V (step 1 V) Currents 3 x IPhase ; 3I0; IE sensitve; I1; I2; IY;
6 Tolerances 3I0PAR
Time stages 1 % of setting value or 10 ms Tolerances ≤ 0.5 % of indicated measured value
Voltage limit values ≤ 3 % of setting value or 1 V or 0.5 % Inom
Synchro-check (ANSI 25) Voltages 3 x VPhase-Earth; 3 x VPhase-Phase; 3V0,
Initiate options Auto-reclosure; V1, V2, VSYNC, Ven
Manual CLOSE control Tolerances ≤ 0.5 % of indicated measured value
Control commands or 0.5 % Vnom
Operating modes Power with direction indication P, Q, S
With auto-reclosure Synchro-check
Tolerances
Line dead/busbar live
P: for cos ϕ = 0.7 to 1 and Typical ≤ 1%
Line live/busbar dead
V/Vnom, I/Inom = 50 to 120 %
Line and busbar dead
Q: for sin ϕ = 0.7 to 1 and Typical ≤ 1%
Bypassing
V/Vnom , I/Inom = 50 to 120 %
For manual closure
S: for V/Vnom, I/Inom = 50 to Typical ≤ 1%
and control commands As for auto-reclosure
120 %
Permissible voltage difference 1 to 60 V (step 0.1 V)
Frequency f
Permissible frequency difference 0.03 to 2 Hz (step 0.01 Hz) Tolerance ≤ 10 mHz
Permissible angle difference 2 to 80 ° (step 1°) Power factor p.f. (cos ϕ)
Max. duration of synchronization 0.01 to 600 s (step 0.01 s) or deactivated Tolerance for cos ϕ = 0.7 to 1 Typical ≤ 0.02
Release delay with synchronous 0 to 30 s (step 0.01 s) Load impedances with directional 3 x RPhase-Earth, XPhase-Earth
networks indication 3 x RPhase-Phase, XPhase-Phase
Minimum measuring time Approx. 80 ms Earth-fault measured values Active and reactive component
Tolerances of earth-fault current IEEac, IEEreac
Time stages 1 % of setting value or 10 ms Overload measured values Θ/ΘTrip L1; Θ/ΘTrip L2; Θ/ΘTrip L3;
Voltage limit values ≤ 2 % of setting value or 1 V Θ/ΘTrip
Earth-fault detection for compensated / isolated networks Long-term mean values
Zero-sequence voltage 3V0 1 to 150 V (step 1 V) Interval for derivation of mean value 15 min / 1 min; 15 min / 3 min;
Phase selection with phase voltages 10 to 100 V (step 1 V) 15 min / 15 min
V< and V> Synchronization instant Every ¼ hour; every ½ hour; every
Directional determination Active / reactive power measurements hour
Minimum current for directional 3 to 1000 mA (steps 1 mA) Values 3 x IPhase; I1; P; P+; P-; Q; Q+; Q-; S
determination
Angle correction for core-balance 0 to 5 ° at 2 operating points
CT (step 0.1 °)
Operating modes Only indication; indication and trip

6/26 Siemens SIP · 2004


6 Distance Protection / 7SA6

Technical data

Minimum/maximum memory Further additional functions


Indication Measured values with date and time Measured value supervision Current sum
Resetting Cyclically Current symmetry
Via binary input Voltage sum
Via the keyboard Voltage symmetry
Via serial interface Phase sequence
Fuse failure monitor
Values
Min./max. of measured values 3 x IPhase; I1; 3 x VPhase-Earth; Indications
3 x VPhase-to-phase; 3V0; V1; Operational indications Buffer size 200
P+; P-; Q+; Q-; S; f; power factor (+); System disturbance indication Storage of indications of the last 8
power factor (–) faults, buffer size 600
Min./max. of mean values 3 x IPhase; I1; P; Q; S Earth-fault indication Storage of indications of the last 8
Energy meters faults, buffer size 200
Four-quadrant meters WP+; WP-; WQ+; WQ- Switching statistics Number of breaking operations per
CB pole
Tolerance
Sum of breaking current per phase
for cos ϕ > 0.7 and V > 50 % 5 %
Breaking current of last trip operation
Vnom and I > 50 % Inom
Max. breaking current per phase
Analog measured value output 0 to 20 mA Circuit-breaker test TRIP/CLOSE cycle, 3 phases
Number of analog channels 2 per plug-in module TRIP/CLOSE per phase
Alternatively 1 or 2 or no plug-in Dead time for CB TRIP / CLOSE 0 to 30 s (steps 0.01 s)
module (Refer to ordering data, posi-
tion 11 and Order code for position
cycle 6
12) Commissioning support Operational measured values, c.-b.
test, status display of binary inputs,
Indication range 0 to 22 mA setting of output relays, generation
Selectable measured values Fault location [%]; of indications for testing serial inter-
fault location [km]; VL23 [%]; IL2 faces
[%]; |P| [%]; |Q| [%]; Phase rotation adjustment Clockwise or anti-clockwise
breaking current Imax-primary
Max. burden 350 Ω
CE conformity
Oscillographic fault recording
This product is in conformity with the Directives of the European Commu-
Analog channels 3 x IPhase, 3I0, 3I0 PAR nities on the harmonization of the laws of the Member States relating to
3 x VPhase, 3V0, VSYNC, Ven electromagnetic compatibility (EMC Council Directive 89/336/EEC) and
Max. number of available recordings 8, backed-up by battery if auxiliary electrical equipment designed for use within certain voltage limits (Council
voltage supply fails Directive 73/23/EEC).
Sampling intervals 20 samplings per cycle This unit conforms to the international standard IEC 60255, and the Ger-
Total storage time > 15 s man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
Further applicable standards: ANSI/IEEE C37.90.0 and C37.90.1.
Binary channels Pickup and trip information; number
and contents can be freely configured This conformity is the result of a test that was performed by Siemens AG in
by the user accordance with Article 10 of the Council Directive complying with the
generic standards EN 50081-2 and EN 50082-2 for the EMC Directive and
Max. number of displayed binary 40 standard EN 60255-6 for the “low-voltage Directive”.
channels
Control
Number of switching units Depends on the number of binary /
indication inputs and indication /
command outputs
Control commands Single command / double command
1, 1 plus 1 common or 2 pole
Feed back CLOSE, TRIP, intermediate position
Interlocking Freely configurable
Local control Control via menu, function keys,
control keys (if available)
Remote control Control protection, DIGSI,
pilot wires

Siemens SIP · 2004 6/27


6 Distance Protection / 7SA6

Selection and ordering data Description Order No.


7SA61 distance protection relay for all voltage levels
Housing, number of LEDs
7SA61¨¨-¨¨¨¨¨-¨oo¨
123
Housing width 1/3 19", 7 LEDs 0 see pages 6/31
to 6/34
Housing width 1/2 19", 14 LEDs 1
Housing width 1/1 19", 14 LEDs 2
Housing width 2/3 19", 14 LEDs 3

Measuring input (4 x V, 4 x I)
Operator panel with: IPH = 1 A1), Ie = 1 A (min. = 0.05 A) 1
- 4-line backlit display, IPH = 1 A1), Ie = sensitive (min. = 0.003 A) 2
- function keys, IPH = 5 A1), Ie = 5 A (min. = 0.25 A) 5
- numerical keys, IPH = 5 A1), Ie = sensitive (min. = 0.003 A) 6
- PC interface
Rated auxiliary voltage (power supply, binary inputs)
24 to 48 V DC, binary input threshold 17 V3) 2
60 to 125 V DC2), binary input threshold 17 V3) 4
110 to 250 V DC2), 115 V AC, binary input threshold 73 V3) 5

Binary/ Indication/ Fast High-speed Power Flush- Flush- Surface-


indica- command relay4) trip output relay5) mounting mounting mounting
tion outputs incl. housing/ housing/ housing/
inputs live status screw-type plug-in screw-type
6 contact terminals terminals terminals
For 7SA610
5 9 n A
5 9 n E
5 9 n J
7 6 n B
7 6 n F
7 6 n K

For 7SA611
13 10 7 n A
13 10 7 n E
13 10 7 n J
13 9 3 5 n M
13 9 3 5 n N
13 9 3 5 n P
20 9 4 n B
20 9 4 n F
20 9 4 n K

For 7SA612
21 18 7 n A
21 18 7 n E
21 18 7 n J
21 17 3 5 n M
1) Rated current can be selected by
means of jumpers. 21 17 3 5 n P
21 17 3 5 n R
2) Transition between the two auxiliary
voltage ranges can be selected by 29 26 7 n B
means of jumpers. 29 26 7 n F
29 26 7 n K
3) The binary input thresholds are
selectable in three stages by means of 29 25 3 5 n N
jumpers, exception: versions with 29 25 3 5 n Q
power relays have some binary inputs 29 25 3 5 n S
with only two binary input thresh- 33 12 8 n C
olds. 33 12 8 n G
4) Fast relays are identified in the 33 12 8 n L
terminal connection diagram.
5) Power relay for direct control of For 7SA613
disconnector actuator motors. 21 18 7 n A
Each pair of contacts is mechanically 21 17 3 5 n M
interlocked to prevent simultaneous
closure.

6/28 Siemens SIP · 2004


6 Distance Protection / 7SA6

Selection and ordering data Description Order No.


7SA63 distance protection relay for all voltage levels
Housing, number of LEDs
7SA63¨¨-¨¨¨¨¨-¨oo¨
123
Housing width 1/2 19", 14 LEDs 1 see pages 6/31
LSA2539-agpen.eps

to 6/34
Housing width 1/1 19", 14 LEDs 2

Measuring input (4 x V, 4 x I)
IPH = 1 A1), Ie = 1 A (min. = 0.05 A) 1
Operator panel with: IPH = 1 A1), Ie = sensitive (min. = 0.003 A) 2
- backlit graphic display for IPH = 5 A1), Ie = 5 A (min. = 0.25 A) 5
single-line diagram IPH = 5 A1), Ie = sensitive (min. = 0.003 A) 6
- control keys,
- key-operated switches, Rated auxiliary voltage (power supply, binary inputs)
- function keys, 24 to 48 V DC, binary input threshold 17 V3) 2
- numerical keys, 60 to 125 V DC2), binary input threshold 17 V3) 4
- PC interface 110 to 250 V DC2), 115 V AC, binary input threshold 73 V3) 5

Binary/ Indication/ Fast High-speed Power Flush- Flush- Surface-


indica- command relay4) trip outputs relay5) mounting mounting mounting
tion- outputs incl. housing/ housing/ housing/
inputs live status screw-type plug-in screw-type
contact terminals terminals terminals
For 7SA631
13 10 7 n A 6
13 10 7 n E
13 10 7 n J
13 9 3 5 n M
13 9 3 5 n N
13 9 3 5 n P
20 9 4 n B
20 9 4 n F
20 9 4 n K

For 7SA632
21 18 7 n A
21 18 7 n E
21 18 7 n J
21 17 3 5 n M
21 17 3 5 n P
21 17 3 5 n R
29 26 7 n B
29 26 7 n F
29 26 7 n K
29 25 3 5 n N
29 25 3 5 n Q
29 25 3 5 n S
33 12 8 n C
33 12 8 n G
33 12 8 n L

1) Rated current can be selected by means of jumpers.


2) Transition between the two auxiliary voltage ranges can be selected by means of jumpers.
3) The binary input thresholds are selectable in three stages by means of jumpers, exception:
versions with power relays have some binary inputs with only two binary inputs thresholds.
4) Fast relays are identified in the terminal connection diagram.
5) Power relay for direct control of disconnector actuator motors.
Each pair of contacts is mechanically interlocked to prevent simultaneous closure.

Siemens SIP · 2004 6/29


6 Distance Protection / 7SA6

Selection and ordering data Description Order No.


7SA64 distance protection relay for all voltage levels
Housing, number of LEDs
7SA64¨¨-¨¨¨¨¨-¨oo¨
123
see pages 6/31
LSA2540-agpen.eps

Housing width 1/2 19", 14 LEDs 1


to 6/34
Housing width 1/1 19", 14 LEDs 2

Measuring input (4 x V, 4 x I)
IPH = 1 A1), Ie = 1 A (min. = 0.05 A) 1
IPH = 1 A1), Ie = sensitive (min. = 0.003 A) 2
Units with IPH = 5 A1), Ie = 5 A (min. = 0.25 A) 5
detached operator panel with IPH = 5 A1), Ie = sensitive (min. = 0.003 A) 6
- backlit graphic display
- control keys
Rated auxiliary voltage (power supply, binary inputs)
- key-operated switches
24 to 48 V DC, binary input threshold 17 V3) 2
- function keys
60 to 125 V DC2), binary input threshold 17 V3) 4
- numerical keys
110 to 250 V DC2), 115 V AC, binary input threshold 73 V3) 5
- PC interface
Binary/ Indication/ Fast High-speed Power Flush- Flush-
indica- command relay4) trip outputs relay5) mounting mounting
tion- outputs incl. housing/ housing/
inputs live status screw-type plug-in
contact terminals terminals
For 7SA641
6 13 10 7 n A
13 10 7 n J
13 9 3 5 n M
13 9 3 5 n P
20 9 4 n B
20 9 4 n K

For 7SA642
21 18 7 n A
21 18 7 n J
21 17 3 5 n M
21 17 3 5 n R
29 26 7 n B
29 26 7 n K
29 25 3 5 n N
29 25 3 5 n S
33 12 8 n C
33 12 8 n L

1) Rated current can be selected by means of jumpers.


2) Transition between the two auxiliary voltage ranges can be selected by means of jumpers.
3) The binary input thresholds are selectable in three stages by means of jumpers, exception:
versions with power relays have some binary inputs with only two binary inputs thresholds.
4) Fast relays are identified in the terminal connection diagram.
5) Power relay for direct control of disconnector actuator motors.
Each pair of contacts is mechanically interlocked to prevent simultaneous closure.

6/30 Siemens SIP · 2004


6 Distance Protection / 7SA6

Selection and ordering data Description Order No. Order code


7SA6 distance protection relay for all voltage levels 7SA6¨o¨-¨¨¨¨¨-¨oo¨ ¨¨¨
1)
123
Region-specific default settings / language settings see pages
Region DE, language: German; selectable A 6/32 to 6/34
Region World, language: English (GB); selectable B
Region US, language: English (US); selectable C
Region FR, French (on request) D
Region World, Spanish E
Region World, Italian (on request) F

Port B
Empty 0
System interface, IEC 60870-5-103 protocol, electrical RS232 1
System interface, IEC 60870-5-103 protocol, electrical RS485 2
System interface, IEC 60870-5-103 protocol, optical 820 nm, ST connector 3
System interface, PROFIBUS-FMS Slave2), electrical RS485 4
System interface, PROFIBUS-FMS Slave2), optical 3), double ring 3), ST connector 6
2 analog outputs, each 0.....20 mA 7
System interface, PROFIBUS-DP, electrical RS485 9 L 0 A
System interface, PROFIBUS-DP, optical 820 nm, double ring 3), ST connector 9 L 0 B
System interface, DNP 3.0, electrical RS485 9 L 0 G
System interface, DNP 3.0, optical 820 nm, ST connector3) 9 L 0 H
System interface, IEC 618504), 100 Mbit Ethernet, electrical, duplicate, 6
RJ45 plug connectors 9 L 0 R

1) Definitions for region-specific default settings and functions:


Region DE: preset to f = 50 Hz and line length in km, only IEC
inverse characteristic can be selected, directional earth (ground)
fault protection: no logarithmic inverse characteristic, no direction decision
with zero-sequence power Sr; distance protection can be selected with
quadrilateral or circle characteristic.
Region US: preset to f = 60 Hz and line length in miles, ANSI inverse
characteristic only, directional earth (ground) fault protection:
no logarithmic inverse characteristic, no direction decision
with zero-sequence power Sr, no U0 inverse characteristic.
Region World: preset to f = 50 Hz and line length in km, directional earth (ground) fault
protection: no direction decision with zero-sequence power Sr,
no U0 inverse characteristic.
Region FR: preset to f = 50 Hz and line length in km, directional earth (ground)
fault protection: no U0 inverse characteristic, no logarithmic inverse
characteristic, weak infeed logic selectable between French specification
and world specification.
2) For SICAM energy automation systems.
3) Optical double ring interfaces are not available with surface mounting housings.
4) Available approx. as of mid 2004.

Siemens SIP · 2004 6/31


6 Distance Protection / 7SA6

Selection and ordering data Description Order No. Order code


7SA6 distance protection relay for all voltage levels 7SA6¨o¨-¨¨¨¨¨-¨oo¨ ¨¨¨
123
Port C and port D see pages
Port C: DIGSI/modem, electrical RS232, 6/33 and 6/34
Port D: empty 1
Port C: DIGSI/modem, electrical RS485,
Port D: empty 2
Port C and Port D installed 9 M oo

Port C
DIGSI/modem, electrical RS232 1
DIGSI/modem, electrical RS485 2

Port D
Protection data interface: optical 820 nm, two ST connectors, FO cable length up to 1.5 km
For direct connection via multi-mode FO cable or communication networks 1) A
Protection data interface: optical 820 nm, two ST connectors, FO cable length up to 3.5 km
For direct connection via multi-mode FO cable B
Protection data interface: optical 1300 nm, two ST connectors, FO cable length up to 10 km
For direct connection via mono-mode FO cable C
Protection data interface: optical 1300 nm, two FC connectors, FO cable length up to 35 km
For direct connection via mono-mode FO cable D
Two analog outputs, each 0...20 mA K
6
New FO options2)
Protection data interface: optical 1300 nm, LC-Duplex connector
FO cable length up to 25 km for direct connection via mono-mode FO cable3) G
Protection data interface: optical 1300 nm, LC-Duplex connector
FO cable length up to 60 km for direct connection via mono-mode FO cable3) H
Protection data interface: optical 1550 nm, LC-Duplex connector
FO cable length up to 100 km for direct connection via mono-mode FO cable3) J

1) For suitable communication convert-


ers 7XV5662 (optical to G703.1/X21/
RS422 or optical to pilot wire or opti-
cal to ISDN) see "Accessories".
2) Available approx. 10/2004.
3) For surface -mounting housing appli-
cations an internal fiber-optic module
820 nm will be delivered in combina-
tion with an external repeater.

6/32 Siemens SIP · 2004


6 Distance Protection / 7SA6

Selection and ordering data Description Order No.


7SA6 distance protection relay for all voltage levels 7SA6¨¨¨-¨¨¨¨¨-¨oo¨
Functions 1
Trip mode Thermal overload BCD-coded output
protection (ANSI 49) for fault location
3-pole 0
3-pole n 1
3-pole n 2
3-pole n n 3
1/3-pole 4
1/3-pole n 5
1/3-pole n 6
1/3-pole n n 7

Functions 2
Distance protection Power swing de- Parallel line
pickup (ANSI 21, 21N) tection (ANSI 68, 68T) compensation
I> A
V< / I> B
Quadrilateral (Z<) C
Quadrilateral (Z<), V< / I> / ϕ D
Quadrilateral (Z<) n F
Quadrilateral (Z<), V< / I> / ϕ n G 6
V< / I> n 1) J
Quadrilateral (Z<) n 1) K
Quadrilateral (Z<), V< / I> / ϕ n 1) L
Quadrilateral (Z<) n n 1) N
Quadrilateral (Z<), V< / I> / ϕ n n 1) P

Functions 3
Auto-reclosure Synchro- Breaker failure pro- Over/undervoltage protection
(ANSI 79) check (ANSI 25) tection (ANSI 50BF) V>, V< (ANSI 27, 59)
Over/underfrequency protection
(ANSI 81)
A
n B
n C
n n D
n E
n n F
n n G
n n n H
n J
n n K
n n L
n n n M
n n N
n n n P
n n n Q
n n n n R

Functions 4
Directional earth- Earth-fault Measured values
fault protection, detection extended
earthed networks compensated/ Min, max, mean
(ANSI 50N, 51N, isolated
67N) networks
0
n 1
n2) 2
n2) n 3
1) Only with position 7 of
Order No. = 1 or 5. n 4
n n 5
2) Only with position 7 of
Order No. = 2 or 6. n n2) 6
n n2) n 7
Siemens SIP · 2004 6/33
6

n
n
n
n
n

6/34
Tr
ip

n
m
od

Functions 1
Tr e,
ip 3-

n
n
n
n
n
m po
le
od
Pi e1

Preferential types
ck

n
n
n
n
up or
I> 3-
Pi po
ck le

n
n
up
V
Z </
< I>
Selection and ordering data

V< (qua

n
n
/I> dri
6 Distance Protection / 7SA6

/ϕ late
Po ra
we l)

n1)

2) Only with position 7 of Order No. = 2 or 6.


1) Only with position 7 of Order No. = 1 or 5.
rs
wi
Pa ng
ra de
co llel tec
m lin tio

n
n
pe e
ns n
Description

Au a tio
to n

n
n
-re
Sy clo
nc su

n
n
n
n
hr re
o-
Br ch
ea ec
k
pr ker
ot fai

n
n
n
n
n
ec lu
tio re
Vo n
lta
Fr ge
eq pr

n
n
n
n
ue ot
nc ect
Ea y p io
rth ro n
dir -fa tec
ec ult tio
t
ne ion ro p n
7SA6 distance protection relay for all voltage levels

tw al te

n2)
n2)
or fo cti
ks r e on
Ea ar
rth th
fo -fa ed
r c ul
ne omp dir t

n
n
n
n tw en ec
or sa tio
ks te na
Ov di l
so

n
n
n
n
n

erl
oa lat
M d pr
ed
ea ot
Order No.

ten resu e cti


de d v on
d, alu
m es
in , e
. m x-
ax
.m
ea
n

5
4
5
4
7
6
7
1

6
0

7 PR¨
3 GH¨
3 BM¨
3 B D¨
1 A B¨
7SA6¨¨¨-¨¨¨¨¨-¨oo¨

Siemens SIP · 2004


6 Distance Protection / 7SA6

Accessories Description Order No.


DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows (version Windows 95 and higher)
device templates, Comtrade Viewer, electronic manual included
as well as “Getting started” manual on paper, connecting cables (copper)

Basis
Full version with license for 10 computers, on CD-ROM
(authorization by serial number) 7XS5400-0AA00
Demo
Demo version on CD-ROM 7XS5401-0AA00
Professional
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00

SIGRA
(generally contained in DIGSI Professional, but can be ordered additionally)
Software for graphic visualization, analysis and evaluation of fault records.
Can also be used for fault records of devices of other manufacturers
(Comtrade format). Running under MS Windows 95/98/ME/NT/2000/XP Professional. 6
Incl. templates, electronic manual with license for 10 PCs.
Authorization by serial number. On CD-ROM. 7XS5410-0AA00

Connecting cable (copper)


Cable between PC/notebook (9-pin connector) and protection unit (9-pin connector)
(contained in DIGSI 4, but can be ordered additionally) 7XV5100-4
Voltage transformer miniature circuit-breaker
Rated current 1.6 A; thermal overload release 1.6 A;
overcurrent trip 6 A 3RV1611-1AG14
Manual for 7SA6
English C53000-G1176-C156-1

Siemens SIP · 2004 6/35


6 Distance Protection / 7SA6

Accessories Description Order No.


Opto-electric communication converters
Optical to X21/RS422 or G703.1 7XV5662-0AA00
Optical to pilot wires 7XV5662-0AC00
Optical to ISDN 7XV5662-0AB00

Additional interface modules


Protection data interface FO 5, OMA1, 820 nm, multi-mode FO cable,
ST connector, 1.5 km C53207-A351-D651-1
Protection data interface FO 6, OMA2, 820 nm, multi-mode FO cable,
ST connector, 3.5 km C53207-A351-D652-1
Protection data interface FO 7, OMA3, 1300 nm, mono-mode FO cable,
ST connector, 10 km C53207-A351-D653-1
Protection data interface FO 8, OMA4, 1300 nm, mono-mode FO cable,
FC connector, 35 km C53207-A351-D654-1

New modules (available approx. 10/2004)


Protection data interface FO 17, 1300 nm, mono-mode FO cable,
LC-Duplex connector, 25 km C53207-A322-B115-3
Protection data interface FO 18, 1300 nm, mono-mode FO cable,
LC-Duplex connector, 60 km C53207-A322-B116-3
Protection data interface FO 19, 1550 nm, mono-mode FO cable,
LC-Duplex connector, 100 km C53207-A322-B117-3

6 New optical repeaters (available approx. 6/2004)


Serial repeater (2-channel), opt. 1300 nm, mono-mode FO cable,
LC-Duplex connector, 25 km 7XV5461-0BG00
Serial repeater (2-channel), opt. 1300 nm, mono-mode FO cable,
LC-Duplex connector, 60 km 7XV5461-0BH00
Serial repeater (2-channel), opt. 1550 nm, mono-mode FO cable,
LC-Duplex connector, 100 km 7XV5461-0BJ00

Description Order No. Size of Supplier Fig.


package
LSP2089-afpen.tif

Connector 2-pin C73334-A1-C35-1 1 Siemens 6/32


3-pin C73334-A1-C36-1 1 Siemens 6/33
2 1)
Crimp CI2 0.5 to 1 mm 0-827039-1 4000 AMP
1)
Fig. 6/31 Mounting rail for 19" rack connector 0-827396-1 1 AMP

CI2 1 to 2.5 mm 2 0-827040-1 4000 AMP 1)


0-827397-1 1 AMP 1)
LSP2091-afpen.eps
LSP2090-afpen.eps

Type III+ 0.75 to 1.5 mm 2 0-163083-7 4000 AMP 1)


0-163084-2 1 AMP 1)
1)
Crimping For Type III+ 0-539635-1 1 AMP
1)
Fig. 6/32 Fig. 6/33 tool and matching female 0-539668-2 AMP
1)
2-pin connector 3-pin connector for CI2 0-734372-1 1 AMP
1)
and matching female 1-734387-1 AMP

19"-mounting rail C73165-A63-D200-1 1 Siemens 6/31


LSP2093-afpen.eps

LSP2092-afpen.eps

Short-circuit links For current terminals C73334-A1-C33-1 1 Siemens 6/34


For other terminals C73334-A1-C34-1 1 Siemens 6/35

Safety cover for terminals large C73334-A1-C31-1 1 Siemens 6/4


Fig. 6/34 Fig. 6/35 small C73334-A1-C32-1 1 Siemens 6/4
Short-circuit link Short-circuit link
for current con- for voltage contacts/ 1) AMP Deutschland GmbH Tel.: +49 6103 709-0
tacts indications contacts Amperestr. 7–11 Fax +49 6103 709-223
63225 Langen
Germany

6/36 Siemens SIP · 2004


6 Distance Protection / 7SA6

Connection diagram
LSA2532-agpen.eps

Fig. 6/36
Connection diagram

Fig. 6/37
Serial interfaces

Siemens SIP · 2004 6/37


6 Distance Protection / 7SA6

Connection diagram
LSA2532-agpen.eps

Fig. 6/38
Connection diagram

Note: For serial interfaces see Fig. 6/37.

6/38 Siemens SIP · 2004


6 Distance Protection / 7SA6

Connection diagram
LSA2545-agpen.eps

Fig. 6/39
Connection diagram

1) Version with 3-pole tripping.


2) Version with 1/3-pole tripping.
3) Time advantage with fast relay approx. 3 ms.
4) High-speed trip outputs in versions 7SA6*1*-*M, 7SA*1*-*N, 7SA*1*-*P.
Note: For serial interfaces see Fig. 6/37.

Siemens SIP · 2004 6/39


6 Distance Protection / 7SA6

Connection diagram
LSA2545-agpen.eps

Fig. 6/40
Connection diagram

1) Version with 3-pole tripping.


2) Each pair of contacts is mechanically interlocked to prevent simultaneous closure.
3) Version with 1/3-pole tripping.
Note: For serial interfaces see Fig. 6/37.

6/40 Siemens SIP · 2004


6 Distance Protection / 7SA6

Connection diagram

LSA2546-agpen.eps

1) Version with 3-pole tripping.


2) Version with 1/3-pole
tripping.
3) Time advantage with fast
relay approx. 3 ms.
4) High-speed trip outputs in
versions 7SA6*2*-*M, Fig. 6/41
7SA6*2*-*P, 7SA6*2*-*R. Connection diagram
5) 7SA613 is only available in a
2/3 x 19" flush-mounting housing.
Note: For serial interfaces see Fig. 6/37.

Siemens SIP · 2004 6/41


6 Distance Protection / 7SA6

Connection diagram

LSA2546-agpen.eps

1) Version with 3-pole tripping.


2) Version with 1/3-pole
tripping.
3) Time advantage with fast
relay approx. 3 ms.
4) High-speed trip outputs in
versions 7SA6*2*-*N,
7SA6*2*-*Q, 7SA6*2*-*S.
Time advantage: approx. 5 ms.
Note: For serial interfaces
see Fig. 6/37. Fig. 6/42 Connection diagram

6/42 Siemens SIP · 2004


6 Distance Protection / 7SA6

Connection diagram

LSA2546-agpen.eps

1) Version with 3-pole tripping.


2) Each pair of contacts is Fig. 6/43 Connection diagram
mechanically interlocked
to prevent simultaneous closure.
3) Version with 1/3-pole tripping.
Note: For serial interfaces see Fig. 6/37.

Siemens SIP · 2004 6/43


6 Distance Protection / 7SA6

Dimension drawings in mm / inch

Dimension drawings for SIPROTEC 4


1/3 x 19" housing (7XP20)

6 Side view Rear view 1 Rear view 2 Panel cutout


7SA610, 7SD61, 7SJ64 7SJ61, 7SJ62, 7UT612,
7UM611
Fig. 16/22
Housing for panel flush mounting/
cubicle mounting (1/3 x 19")

Front view Side view

Fig. 16/23
1/3 x 19” surface-mounting housing

6/44 Siemens SIP · 2004


6 Distance Protection / 7SA6

Dimension drawings in mm / inch

Dimension drawings for SIPROTEC 4


1/2 x 19" flush-mounting housings (7XP20)

6
Side view 1 Side view 2 Panel cutout

Rear view 1 Rear view 2 Rear view 3 Rear view 4


7SA61/63, 7UM621, 7SJ64 7SJ63, 7UM613 7SA522, 7SD52 7UT613

Fig. 16/24
1/2 x 19" flush-mounting housing

Siemens SIP · 2004 6/45


6 Distance Protection / 7SA6

Dimension drawings in mm / inch

Dimension drawings for SIPROTEC 4


2/3 x 19" flush-mounting housings (7XP20)

6 Side view

Rear view Panel cutout

Fig. 16/25
2/3 x 19" flush-mounting housing for 7SA613

6/46 Siemens SIP · 2004


6 Distance Protection / 7SA6

Dimension drawings in mm / inch

Dimension drawings for SIPROTEC 4


1/1 x 19" flush-mounting housings (7XP20)

Side view 1 Side view 2

* Terminals M and L additionally for 7UT635 only

Panel cutout Rear view 1


7SA6, 7UM622, 7SJ64, 7UT633, 7UT635

Rear view 2 Rear view 3


7SJ63, 7MD63 7SA522, 7SD52

Fig. 16/26
in 1/1 x 19" flush-mounting housing

Siemens SIP · 2004 6/47


6 Distance Protection / 7SA6

Dimension drawings in mm / inch

Dimension drawings for SIPROTEC 4


1/2 and 1/1 x 19" surface-mounting housings
(7XP20)

6
Front view Side view
1/2 x 19" surface-mounting
housing 7XP20

Front view
1/1 x 19" surface-mounting housing 7XP20
(without sloped FO case)

Fig. 16/27
1/2 and 1/1 x 19" surface-mounting housing

6/48 Siemens SIP · 2004


6 Distance Protection / 7SA6

Dimension drawings in mm / inch

Dimension drawings for SIPROTEC 4


1/2 and 1/1 x 19" housings
with detached operator panel

6
Detached operator panel (side view) Rear view Panel cutout

Fig. 16/28
Housing with detached
operator panel

Siemens SIP · 2004 6/49

You might also like