Introduction
Adapt PM Smart IDC Power System is a new generation uninterruptible power supply and integrated
smart distribution management system developed by Emerson with its more than 40 years of experiences
in large UPS production, advanced IDC power solutions and smart power management technologies.

Application scope
Medium IDCs of enterprises, medium-small IDCs in the fields of Finance, Security and Government

New Technical Features


Superior energy saving and environment-friendly: Efficiency > 96% at 50%-75% rated
load, and > 95% at 25% rated load; Input PF close to 1, input THDi<3%

System features:
Online double conversion
DSP control and IGBT
Modular UPS with each module of 30KVA
Both UPS and battery system use the aesthetics IT-style
rack
Embedded with the most delicate 30kVA rack-mounted
UPS in the world with weight < 35kg and 3U height; Up
to 5 UPS units can be paralleled inside one cabinet
Embedded with hot swappable 150 kW bypass module
Embedded with input/output distribution switch and
manual maintenance bypass
Embedded with Server Power Management System
(SPM) to detect the switch status, voltage, current, PF,
harmonics, and energy consumption of each branch
circuit, and 2-level current pre-alarm settable
Equipped with optional plug-and-play distribution
module with 18 circuit breakers, so capacity can be
expanded anytime and output distribution can be
modified flexibly
Equipped with optional ABB plug-and-play circuit
breakers, the circuit breaker capacity expansion or load
phase modulation can be realized without cutting the
input power
Both UPS power supply and load distribution can be
configured dynamically. The UPS capacity and number
of load circuits can be increased with the increase of
user's IT systems

Optional parts:
SPM (smart power management unit)
ABB distribution modules (18 PCS)
ABB hot swappable distribution modules (18PCS)
Nader distribution modules (18PCS)
UPS SIC / SNMP card, ModBUS card, relay I/O control
card, EnviroProbe, SNMP hub
UPS dry contacts
SiteMonitor UPS monitoring software
Load Bus Synchronization (LBS) cable and extension kit
Temperature and humidity sensor
Rack battery cabinet

Superior capability of powering load: Output PF close to 1, no need of power deration


with load of leading or lagging PF
Easy-to-install: Top or bottom cabling, no need of input cabling cabinet, with UPS and
smart distribution integrated into one cabinet
Easy-to-maintain: Full front access, UPS, bypass and distribution can be replaced within
2mins
Easy-to-modify: Parallel systems can share the batteries. The number of battery cells can
be configured flexibly, so the original batteries can be used when modifying the legacy
system; moreover, the battery cell can be replaced in time when it fails without interrupting
the normal operation of UPS.

Adapt PM Smart IDC Power System

AC Power Systems
TM
for Business-Critical Continuity

Adapt PM Smart IDC Power System


Model
Power (kVA/kW)
Physical parameters
Width X Depth X Height (mm)
Weight (kg)
Input specications (rectier)
Rated input voltage
Rated operating frequency
Input voltage range
Input frequency range
Input PF
Input current harmonic distortion (THDi)
Input power soft-start function
DC specications
Output voltage regulation of charger
Low DC ripple voltage
Output specications (inverter)
Inverter output voltage
Output PF
Voltage Steady state
stability Transient state
Steady state response time
Inverter overload capability
With 100% balance load
Phase
shift
With 100% imbalance load
100% linear load
THDv
100% nonlinear load
Bypass
Bypass input voltage
Bypass voltage range
Bypass overload capability
System
Frequency
Mains synchronization range
Actual frequency precision (internal clock)
System efciency
SPM Smart Power Management System
Number of branch circuit breakers
Number of branch circuit breakers
Monitoring functions
Operating environmental
Operating temperature range
Storage temperature
Relative humidity
Altitude
Noise (1m)
Protection level
Standard

Adapt PM150
306090120150
60011002000
450kg
380/400/415VAC3-phase 4-wire
50/60Hz
228V476V20%25% Full loadlinear derating at -25% - -40%; can take
70% load at -40%
40Hz70Hz
Full load0.99Half load0.98
3%
Yes, 5 30s settable
1%
1%
380/400/415VAC3-phase 4-wire
1(kW=kVA)
1% Typical value
5 Typical value
20ms
110%1h125%10mins150%1mins150%200ms
1
1

Adapt PM Smart IDC Power System

1%
3%
380/400/415VAC3-phase 4-wire
Default value is -20%-+15%, -40%, -30%, -10% - +10%, other ranges can be set via
software
135%long time170%1h1000%100ms
50Hz/60Hz (Settable)
2Hz(Default value)adjustable with step of 0.5Hz within range of +/- 0.5Hz - 3Hz
50Hz/60Hz0.02%
>96% at load above 50%, >95% at load above 25%

Hot swappable and capacity expandable


18-way distribution circuit breaker module

18 ways X 3
25A standard conguration, 10-63A optional
Status of mains input and branch circuit breakers, voltage, current, PF, harmonics,
energy consumption and 2-level current pre-alarm
040 (See user manual for details)
2570 (Without battery)
095% No condensation
not more than 1000m, derated by 1% for every increase of 100m between 1000m and 2000m
5562dBAdjusted with load
IP20(Internal dust lter)
SafetyIEC60950-1IEC62040-1-1/ AS 62040-1-1EMCIEC62040-2 / AS
62040-2/EN50091-2 CLASS ADesign and testIEC62040-3 / AS 62040-3

Emerson Network Power Co., Ltd.


Address: No.1 Kefa Road, Science & Industry Park,
Nanshan District, 518057 Shenzhen, China
Telephone: 86-755-86010808
Postcode: 518057

Large LCD screen display with


Chinese language available

2011

E-X6216294 0111

You might also like