You are on page 1of 2

Platform Power System, NetSure 701 Series

DC Power Solution
TM
forBusiness-Critical Continuity

-48 VDC, up to 19.2 kW


NetSure 701 A61 (PS48300-4/2900-Y6 and PS48300-4/2900-W6 )

Introduction
Platform Power System NetSure 701 A61 is Emerson next generation
system for medium exchanges, rural telecom networks and access
networks, 2G and 3G base station, transmission relay station,
microwave/satellite communication stations as well as other applications
requiring the power up to 19.2 kW.
The system can be optimized cost-effectively to meet initial requirements,
whilst allowing for easy expansion in the future. Configurable distribution
and number of rectifier modules are available to meet various demands

NetSure 701 A61


Configuration
Item

PS48300-4/2900-Y6 or PS48300-4/2900-W6
Model: R48-3200 or R482900U Optional configuratio

Rectifier

2piece

Monitoring module
AC input

AC input mode:3P+N+PE/380V+SPD

DC distribution

Optional parts

< High flexible configuration to meet various customer


requirements, easy for fast construction of communication
sites

Mechanical Parameter

Size (W D H)
(mm)

< Perfect lightning protection at perfect lightning protection


at both AC side and DC side
< The high power density rectifier uses the active Power
Factor Compensation (PFC) technology, raising the power
factor to 0.99

(12V/165Ah) or 3 4

(12V/100Ah)

Temperature sensors, modem

Cabinet

600 600 1800 (SFA)

Rectifier

85.3

600 600 500 (W6)


272 87.9

540 545 350


(accommodating 4 165Ah battery)

Battery compartment

< Two over-voltage protection methods for options:


hardware protection and software protection.

< The monitoring module can save up to 200 pieces of


historical alarm records, and 10 sets of battery test data
records

32A/1P, 6 63A/1P MCB

600 600 2000 (Y6)

< Compliant with global standards delivers quality,


performance and dependability

< Perfect battery management includes the LLVD,


temperature compensation, auto voltage regulation,
stepless current limiting, battery capacity calculation and
on-line battery test, etc

63A/1P, 2 32A/1P, 2 10A/1P MCB

9LLVD routes: 3

Maximum configuration: 3

Features

< Safety EN60950

6 BLVD routes:2

Battery MCB:3 100A/1P(SFA)

Battery routes

< Hot swap rectifier and controller, high power density

6pieces Standard configuration: 5 pieces

Model: M520S Standard configuration: 1 piece

Weight (kg)

540 545 280

Cabinet(excludingrectifiers,

(Accommodating 4 100Ah battery)


2000mm cabinet 140

Monitoring module and

1800mm cabinet 130

Batteries)

500mm cabinet

Rectifier

50

2.0

Technical specifications -Environmental Parameter


o

Operating Temperature

-5 C

Storage Temperature

-40oC

70oC

Relative Humidity

5%RH

95%RH

Elevation

45 C

2000m (derating is necessary above 2000m)

Platform Power System, NetSure 701 Series


-48 VDC, up to 19.2 kW
NetSure 701 A61 (PS48300-4/2900-Y6 and PS48300-4/2900-W6 )

DC Power Solution
for Business-Critical Continuity TM

Rectifier Module R48-2900 ,R48-3200


Features
Input voltage

nominal 200 to 240 Vac

Input voltage

permitted variation 85 to 290 Vac

Power factor

0.99

THD

<5% from 50 to 100% of rated load

Output voltage

-42 to -58 Vdc

Output power

3200 W

Max output current

67A

Efficiency

92% or 96% for HE R48-3200


o

Temperature range

-40 to +75 C for R48-3200 and -40 to +65 C for R48-2900U

RH (non-condensing)

0 to 95%

EMC

EN 300 386:2001, class B & FCC part 15, class B

Safety

IEC / EN / UL 60950

Dimensions

(H W

Weight

3.5 kg, 7.7 lbs

D) 132 85.3 287 mm, 5.20 3.36 11.3 inches

Controller: M520S
Intelligent battery management Latest 200 alarm history log
Display LCD with 4 16 characters
Language: English, Chinese
External Communication: RS232(modem) or TCP/IP
Protocol: YDN23
Inputs: 8 Digital Inputs Alarms/Events
Outputs: 8 Relay Outputs 1A, max 60V
Examples of Alarms: DC Power Plant Alarms AC mains failure, Rectifier failure, DC/DC converter failure, High voltage shut-down,
Fan failure, Thermal derating

Battery Cabinet (rack)


See separate datasheet for the detailed cabinet (rack) information

Emerson Network Power


A global leader for critical business continuityTM

Emerson Network Power Co., Ltd.


Address:No.1 Ke Fa Road, Science & IndustryPark,
Nanshan District,518057 Shenzhen, China Telep
hone: 86-755-86010808
Postcode: 518057

Emerson Network Power and the Emerson


Network Power Logo are trademarks and
service marks of Emerson Electric Co.
2009 Emerson All Rights Reserved
2009.11

You might also like