General view
Power Turbo-Systems
Plants
COMBINED-CYCLE PLANT
MAIN FEATURES
Location :
France
Customer :
DK6
Consultant Engineer :
LAHMEYER
Scope of supply
Full Turnkey
Contract in force :
07/06/02
First synchronisation
1st GT :
13/04/04
Steam and water diagram
Generators
GT
ST
Type
210
0.85
50
15.75
Static
Air
Yes,
for GT starting
283
0.85
50
18
Static
Air
No
GT13E2
172
Rating (MVA)
Power factor
Frequency (Hz)
Terminal voltage (kV)
Excitation system
Cooling system
Static frequency converter
GT
Model
Rating ISO (MW)
conditions (open cycle) (MW)
Rating at nominal
temperature combined cycle (C)
Fuel
Cooling system
Exhaust temperature
(combined cycle) (C)
NOx control system
164
Natural gas
Closed cooling water
529
Dry, Lean combustion
technology
Condensing plant
- Water temperature (C)
- Condenser pressure (mbar)
- Tube material
Feedwater tank
Main pumps configuration
- Condensate extraction
- HP / LP feedwater pumps
- BP / LP feedwater pumps
- Circulating water pumps
14
35
Titanium
3 x 50 %
2 x 100 %
Na
2 x 50 %
HRSG
Electrical and C&I
Type
Number of pressure levels
HP / LP (bar abs.) / temperature (C)
Mean flow HP / LP (t/h)
Exhaust gas by pass and damper
Suplementary Firing
Steam turbine
Rating (MW)
Number of pressure stage
Main steam pressure (bar abs.)
/ steam temperature (C)
LP exhaust type
240
3
140 / 564.7
02/07/04
Lateral
Main transformer
465
- Rated output (MVA)
236 / 18
- Transformation ratio (kV)
Unit auxiliary transformer
2
Number
26
- Rated output (MVA)
18 / 6.9
- Transformation ratio (kV)
Instrumentation and control system
ABB EGATROL
- GT controler
ALSTOM
- ST controler
ALSTOM MICOM
- Protection
ALSTOM P320
- DCS
PWER / BPROS / DUNK04 / eng / PPS / 09.04 / FR / 5287 - - ALSTOM - 2004. ALSTOM, the ALSTOM logo and any alternatine version there of are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies.
The technical and other data contained in this document is provided for information only. Neither ALSTOM, its officers and employees accept responsibility for or should be taken as making any representation or warranty (whether express or implied) as to the accuracy or completeness
of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. Big Bang Communication RC Besanon
ALSTOM Power Centrales - 2 quai Michelet / 4 Avenue Andr Malraux 92309 Levallois Perret Cedex France - Phone + 33 141 49 20 00 - Fax + 33 141 49 24 85
ALSTOM (Switzerland) Ltd - Brown Boveri Strasse 7- CH 5401 Baden - (Switzerland) - Phone + 41 56 205 70 58 - Fax + 41 56 205 28 88
ALSTOM Power Generation Inc. - 2800 Waterford Lake Drive - Midlothian, Virginia 23112 - United States of America - Phone + 1 804 763 70 00 - Fax + 1 804 763 73 95
ALSTOM Power Asia Pacific Sdn Bhd - 20 th Floor, WISMA Genting - 28, Jalan Sultan Ismail - 50250 Kuala Lumpur, Malaysia - Phone + 60 3 2163 60 71 - Fax + 60 3 2161 77 88
www.power.alstom.com