Professional Documents
Culture Documents
PLANT DETAILS
2.0
OBJECTIVE
3.0
PROPOSAL
4.0
SERVICES REQUIRED
5.0
SAFETY PERECAUTIONS
6.0
EMERGENCY PROCEDURE
7.0
8.0
METHOD
9.0
COMPLETION CRITERIA
Sheet 1 of 19
Sheet
2 of 19
STATUS
1.0
PLANT DETAILS
1.1
1.2
1.2.1
Mechanical system:
Precipitator Casing made of pre-fabricated panels. The casing is
provided with inspection doors with gas tight seal construction. The roof
carries the precipitation internals, insulation housing transformer etc.
The Casing support allows for free thermal expansion of the casing
during operation.
1.2.2
Hoppers: The hoppers are adequately sized to hold the ash. Baffles are
provided in each hopper to avoid gas leakage. Thermostatically
controlled heating elements are arranged at the bottom of hopper portion
to ensure free flow of ash.
1.2.3
Gas distribution system: Even distribution of gas over the entire cross
section of ESP is achieved by guide vanes, splitters and screens
provided in the inlet funnel of the ESP.
1.2.4
Signatures
NTPC
BHEL
Sheet
3 of 19
STATUS
1.2.5
1.2.6
1.2.7
1.3
ELECTRICAL SYSTEM
1.3.1
Signatures
NTPC
BHEL
Sheet
4 of 19
STATUS
After the ionized gases are cleared and the dielectric strength restored,
the controller will quickly restore the power to a preset value and raise
it to the original non sparking level. The EC ensures adequate power
input to the precipitator while reckoning the electrical disturbances
within the precipitator. Regulated ac power from EC is fed to the
primary of the transformer precipitator, which is stepped up and
rectified to give a full wave power output. The transformer-rectifier is
mounted on roof of the precipitator which the EC is located in an air
conditioned control room.
1.3.2
1.3.3
1.4
1.5
Signatures
NTPC
BHEL
Sheet
5 of 19
STATUS
OBJECTIVE :
To commission ESP and make it available for Unit operation.
3.0
PROPOSAL :
ESP will be commissioned through the following proposals
3.1
3.2
4.0
SERVICE REQUIRED:
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
Signatures
NTPC
BHEL
Sheet
6 of 19
STATUS
5.0
SAFETY PRECAUTIONS:
5.1
5.2
5.3
Always ensure before entering any field the connected HV/LT supply is
isolated proper earthing of emitting electrode is done.
5.4
5.5
Ensure line clearance from the concerned boiler staff before entering
ESP.
5.6
The agencies working in ESP area are informed about ESP charging
activity.
5.7
ESP door interlock system is fully available and the master key should
be with designated person in the test team.
6.0
EMERGENCY PROCEDURE:
6.1
Keep a person always outside the field to extend necessary help in case
of Emergency during internal checking of ESP fields.
6.2
6.3
Mechanical
checking/Electrical
Signatures
NTPC
BHEL
Sheet
7 of 19
STATUS
7.0
7.1
7.2
7.3
L.T switch board, EC, ACP and disconnecting switches are off and fuses
are removed
7.4
7.5
7.6
7.7
All safety aspects as given in safety instructions are taken care off.
(Refer O & M)
7.8
7.9
No hole in the wall, roofs and hopper plates are left open.
7.10
7.11
Signatures
NTPC
BHEL
Sheet
8 of 19
STATUS
Ensure the following Critial dimensions / checks, (Machanical)
completed.
(To be verified through Erection log sheets)
-
Ensure the gap between Gas distribution screen and bottom of in let
funnel of ESP is 100+10 mm
Ensure Gas entry front casing wall and emitting electrode shock bar
is 350+10 mm
Ensure the distance between roof beam and emitting frame top is
195+5 mm minimum
Ensure support insulator bottom tip to emitting electrode frame top
is maintained as per drawing
Ensure the central line of collecting rapping drive shaft centre to
shock bar centre 310+5mm. If not available maintain it with proper
shims.
Emitting electrode support screen tube edge to emitting frame top
edge distance is maintained as per drawing.
Distance between centre of emitting system suspension point to first
hook with collecting electrode frames maintained as per drawing.
Emitting frames to collecting electrode distance maintained as per
drawing
Deflection plate to Emitting electrode suspension screen tube
dimension is maintained as per drawing
Confirm the suspension rod is centrally located with respect to
support insulator.
Confirm the shock pad and tumbling hammer face are in the same
vertical plane. If necessary confirm the same with chalk test by
running the collecting rapping of each field.
Set rings are in position.
Clearance between shock bar edge to shock bar guide is (40mm)
and shock bars are moving freely.
Signatures
NTPC
BHEL
Sheet
9 of 19
STATUS
-
7.13
Ensure shock bar guides and link rods are aligned properly.
Clearance between collecting electrode and hopper deflection plate
in the vertical plane as per drawing.
Straightness of shock bar and guide to be ensured.
The distance between emitting electrode and collecting electrode is
as per drawing.
The pitch distance of emitting electrode as per drawing.
Randomly check the spring back of emitting electrode
Verticality of all collecting electrode at all level to be ensured,
otherwise to be corrected.
Ensure deflection plates and throttling plates are arrested by
welding
Distribution screen manhole doors are locked in position.
RAPPING SYSTEM
-
Signatures
NTPC
BHEL
Sheet 10 of 19
STATUS
-
7.14
Ensure that doors are swinging freely and latches are engaging
properly with doors, Gaskets are air tight
Earthing cable is connected properly.
Interlocks and keys are matching properly
8.0
METHOD:
8.1
Signatures
NTPC
BHEL
Sheet 11 of 19
STATUS
- Confirm the cable size, proper cable glanding, earthing of shielded
input cables and output cables as per drawing
- Megger IR value of the input cables to the panel from incomer-A to
panel
bus section -A and the input cables to the panel from
incomer-B to panel bus section-B independently with respect to earth
by keeping open their respective ACBs open.
- Megger the panel power supply control supply buses, heater control
supply and 240 bus bar.
- Confirm the availability of DC 220V and match both the sources for
+ and . Close one of the DC-IS switches and establish control DC
power supply bus for energizing ACBs. Similarly isolate the first DCIS and energies the second source and establish 220 V DC control
supply bus to ACBs.
- Confirm the two source of power supply from LTMSB, three phases
are having the same voltage with respect to earth. Measure phase to
phase voltage also and confirm equal. Check and correct phase
sequence of both source.
- Check the relay setting of ACB1, ACB2 and ACB3as per
recommendations.
- Charge the ACP bus section-A by ACB1 closing.
- Confirm the voltage reading in all the three phases are reading
correctly. Check the 240V bus voltage with respect to Neutral bus
bar, Similarly check 110V bus voltage with respect to Neutral bus bar
for both motor control supply and heater control supply. Similarly
Change the TPDT SW of control transformer and repeat checking all
bus bar voltages as earlier
- Repeat the same for ACP BUS SECTION-B as 8.49 to 8.50
- The interconnecting ACB3 has to be kept opened, match the phase
sequence of the both the panel buses.
- Open ACB2, CloseACB3 check the output bus voltage of entire
ACP.
- Open out ACB1, ACB3 opens out. Close ACB2, close ACB3
reconfirm the output bus voltages.
Signatures
NTPC
BHEL
Sheet 12 of 19
STATUS
Collecting and emitting Rapping System Commissioning :
Geared motors :
-
8.3
Heating Elements :
-
Signatures
NTPC
BHEL
Sheet 13 of 19
STATUS
-
8.4
Disconnecting switches
-
8.5
INSULATOR HOUSING
-
8.6
Ensure flange ioints are provided with gasket and earthing cables.
Copper tubes are straight and tightly connected
Signatures
NTPC
BHEL
Sheet 14 of 19
STATUS
8.7
8.8
8.9
Signatures
NTPC
BHEL
Sheet 15 of 19
STATUS
e)
Signatures
NTPC
BHEL
Sheet 16 of 19
STATUS
Oil temperature indicator: Check the indicator for visual damage, for
proper wiring for alarm and trip.
Completion of job: Check the oil level and top it upto requirement with
dry oil. Check the complete wiring for various alarm/trip contacts tank
and HIV positive terminal is completed.
IR value of transformer windings : 8.98 Measure the IR value
which should be typical to the one given H-E = 200Mohm; L-E =
200Mohm: H-L = 200Mohm.
Open circuit Test :
a). Magnetising Curent Test: Prepare a circuit diagram as shown in
the instruction manual of HVR in page C-12. In this test, the primary of
HVR is fed from a two phase variac 500V/10A, and the magnetizing
current drawn by HVR is measured. This may be compared with the test
result of HVR.
b).Output voltage measurement : The measurement of HV open
circuit output voltage should be done in conjunction with EC and this
should be of the order of rated output DC KV. ( 70KV Peak).
Field IR VALUE measurement: Keep the HVR FIELD ISOLATOR
SWITCH in middle position measure the IR of the field and confirm no
shorting.
Commissioning the field.
Connect the transformer rectifier as per drawing
a)
b)
Signatures
NTPC
BHEL
Sheet 17 of 19
STATUS
c)
Signatures
NTPC
BHEL
Sheet 18 of 19
SL.NO
STATUS
PREPARATIONS :
This air load test has to be carried out at a time with one ESP
consisting of eight fields.
Remove all temporary earth connection made with discharge rods
Confirm that rapping system/EC-HVR system of all the fields
which are to be air load tested are commissioned and ready for
operation.
If necessary for reconfirming the IR value of the field, meggering
may be carried out by between earthing and emitting electrode at
disconnecting switch by keeping open the moving blade in between
the two fixed contacts. Close the disconnecting switch after IR
value measurement.
Close all insulator housing, disconnecting switch and inspection
doors adopting interlock sequence and return the key to the
electronic controller.
Confirm from the concerned personnel that nobody having any
inspection work in the concerned ESP ducts and get clearance for
charging the ESP.
POCEDURE :
Make supply available to ACPs and Ecs.
Switch on all rapping motors on continuous mode.
Switch on EC and slowly raise the current. Note the meter reading
for each interval of 50 mA. Raise upto rated current. Look for
flashover if any and record.
The rapping motors are to be changed to intermittent rapping mode
after taking voltage & current readings.
Keep all the fields energised for a period of 8 hours.
Log air load readings at every one hour interval.
Switch off the ECs, ACPS AND L.T. Board.
Signatures
NTPC
BHEL
Sheet 19 of 19
STATUS
COMPLETION OF ESP COMMISSIONING:
ESP Commissioning completed by completing the proposals given in
Section 3.0.
Signatures
NTPC
BHEL