You are on page 1of 34

LAMDA ELECTRIC

PT. Lamda Teknologi Indonesia

EARTHING AND LIGHTNING PROTECTION

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

LAMDA ELECTRIC
Earthing and Lightning Protection

Copper Bond Electrode Rod (Threaded)


They are made from a low carbon, high tensile strength (600m/mm 2 minimum) steel core with a coating
of molecular bonded 99.9% pure electrolytic copper.
The minimum thickness of this coating is 100 micro (0.1 mm), 200 micro (0.2 mm), 250 micro (0.25 mm).
Extensible type rods have a rolled thread (UNC2A at each end).
Rolled threads have a higher strength than cut threads and also preserve the copper coating at the
treads roots.
Special size and copper thickness can be supplied on request.
Length

Thread Size

ft

mm

Rod Dia
mm

ERT 1112

4'

1200

11

1/2"

12.5

ERT 1115

5'

1500

11

1/2"

12.5

ERT 1118

6'

1800

11

1/2"

12.5

ERT 1212

4'

1200

12.5

9/16"

14.2

ERT 1215

5'

1500

12.5

9/16"

14.2

ERT 1218

6'

1800

12.5

9/16"

14.2

ERT 1412

4'

1200

14.2

5/8"

15.8

ERT 1415

5'

1500

14.2

5/8"

15.8

ERT 1418

6'

1800

14.2

5/8"

15.8

ERT 1424

8'

2400

14.2

5/8"

15.8

ERT 1430

10'

3000

14.2

5/8"

15.8

ERT 1712

4'

1200

17.2

3/4"

19

ERT 1715

5'

1500

17.2

3/4"

19

ERT 1718

6'

1800

17.2

3/4"

19

ERT 1724

8'

2400

17.2

3/4"

19

ERT 1730

10'

3000

17.2

3/4"

19

Part No.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

in

mm

LAMDA ELECTRIC
Earthing and Lightning Protection

Copper Bond Electrode Rod (Un-Threaded)


They are made from a low carbon, high tensile strength (600m/mm 2 minimum) steel core with a coating
of molecular bonded 99.9% pure electrolytic copper.
The minimum thickness of this coating is 100 micro (0.1 mm), 200 micro (0.2 mm), 250 micro (0.25 mm).
Special size and copper thickness can be supplied on request.

Part No.

Length

Rod Dia

ft

mm

in

mm

ER 101

4'

1200

1/2"

12.5

ER 102

5'

1500

1/2"

12.5

ER 103

6'

1800

1/2"

12.5

ER 144

4'

1200

9/16"

14

ER 145

5'

1500

9/16"

14

ER 146

6'

1800

9/16"

14

ER 201

4'

1200

5/8"

16

ER 202

5'

1500

5/8"

16

ER 203

6'

1800

5/8"

16

ER 204

8'

2400

5/8"

16

ER 205

10'

3000

5/8"

16

ER 301

4'

1200

3/4"

19

ER 302

5'

1500

3/4"

19

ER 303

6'

1800

3/4"

19

ER 304

8'

2400

3/4"

19

ER 305

10'

3000

3/4"

19

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

LAMDA ELECTRIC
Earthing and Lightning Protection

Driving Head
Suitable for Rod Dia

Part No.

In

mm

DH 12

1/2"

12.5

DH 14

9/6"

14

DH 16

5/8"

16

DH 19

3/4"

19

Driving studs are made from high tensile steel with a


socket head cap screw.

Coupling
Part No.

Length
(mm)

CC 12

Suitable for Rod Dia


in

mm

60

1/2"

12.5

CC 16

60

9/6"

14

CC 19

70

5/8"

16

CC 14

70

3/4"

19

Couplers are counter bored to completely enclose threads


& protect from damage and corrosion

Driving Tip

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

Part No.

Length (mm)

DS 12

Suitable for Rod Dia


in

mm

60

1/2"

12.5

DS 14

60

9/6"

14

DS 16

70

5/8"

16

DS 19

70

3/4"

19

LAMDA ELECTRIC
Earthing and Lightning Protection

Solid Copper Grounding Rod


Part No.

Rod Dia (mm)

Length

SCR-512

15

1200 mm or 4'

SCR-515

15

1500 mm or 5'

SCR-520

20

1200 mm or 6'

SCR-521
20
1500 mm or 5'
Solid copper earth rod are made from 99.9% pure
electrolytic copper. Solid copper rods offers greater
resistance to corrosion. They are ideally used in applications
where soil condition are very aggressive, for eg. Solid with
high salt content.

Driving Head
Part No.

Length (mm)

Thread Dia (mm)

Material

DH 16

40

10

DH 20

42

10

Hardened
steel

Driving Heads are made from hardened and tempered


steel. It is used protect the internal thread and the top of
the earth electrode when being driven into the ground.

Coupling Dowel
Part No.

Length

Thread Dia (mm)

Material

CD 10

40

10

CD 10

40

10

Stainless
steel

Coupling dowels for stainless steel earth rods are made


from stainless steel or brass. It used to join either the solid
copper and stainless steel rods.

Driving Spike
Part No.

Length

Thread Dia (mm)

Material

DS 10

40

10

DS 10

40

10

Stainless
steel

Driving spikes are made from case hardened steel. It is used


to enable the earth. Electrode to be driven into the ground
more easily and stops the earth electrode from being
damage.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

LAMDA ELECTRIC
Earthing and Lightning Protection

Solid Copper Earth Rod


Solid copper earth rod are made from 99.9% pure electrolytic copper.
Solid copper earth rod offers greater resistance to corrosion. They are ideally used in applications where
soil conditions are very aggressive, foreg, soil with high salt content.

Part No.

Length

Rod Dia

ft

mm

in

mm

CR 101

4'

1200

1/2"

12.5

CR 102

5'

1500

1/2"

12.5

CR 144

4'

1200

9/16"

14

CR 145

5'

1500

9/16"

14

CR 201

4'

1200

5/8"

16

CR 202

5'

1500

5/8"

16

CR 203

6'

1800

5/8"

16

Mechanically Claded Earth Rod


Mechanically cladded copper earth rod is made from 99.9% electrolytic grade copper tube with wall
thickness of 0.25 mm (25 micro) is cladded to a low carbon steel rod.

Part No.

Length

Rod Dia

ft

mm

in

mm

ER 101

4'

1200

1/2"

12.5

ER 102

5'

1500

1/2"

12.5

ER 144

4'

1200

9/16"

14.2

ER 145

5'

1500

9/16"

14.2

ER 201

4'

1200

5/8"

16

ER 202

5'

1500

5/8"

16

ER 203

6'

1800

5/8"

16

ER 302

5'

1500

3/4"

19

ER 303

6'

1800

3/4"

19

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

LAMDA ELECTRIC
Earthing and Lightning Protection

Rod to Tape Clamp


Part No.

Rod Dia

Max. Conductor

in

mm

RTC 10

1/2"

12.5

26 x 12 mm2

RTC 10

5/8"

16

26 x 12 mm2

RTC 10

3/4"

19

26 x 10 mm2

RTC 30

5/8"

16

40 x 12 mm2

RTC 40

5/8"

16

51 x 8 mm2

RTC 50

3/4"

19

51 x 12 mm2

RTC 60

1/2"

12.5

26 x 20 mm2

RTC 60

5/8"

16

26 x 18 mm2

RTC 60

3/4"

19

26 x 10 mm2

RTC 60

1"

25

26 x 10 mm2

The clamps are used to join various sizes of conductor tape to


the earth electrode, which have a high resistance to
corrosion and are mechanically strong to ensure a lasting
connection.

Rod to Cable Clamp


Part No.

Rod Dia

Max. Conductor

in

mm

RCC 9

3/8"

9.5

6-35 mm2

RCC 12

1/2"

12.5

16-50 mm2

RCC 16

5/8"

16

16-70 mm2

RCC 20

3/4"

19

16-95 mm2

RCC 25

1"

25

70-120 mm2

The clamps are used to join various sizes of cable to the earth
electrode, which have a high resistance to corrosion and are
mechanically strong to ensure a lasting connection.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

LAMDA ELECTRIC
Earthing and Lightning Protection

U-Bolt Rod to tape Clamp (Single Plate)


Part No.

Rod Dia
in

Mm

URC-1-16

5/8"

16

URC-1-20

3/4"

20

Material

Copper/Brass

URC-1-25
1
25
The clams are used to join various sizes of conductor
tape to earth electrode / rebar.

U-Bolt Rod to tape Clamp (Double Plate)


Part No.

Rod Dia
in

Mm

URC-2-16

5/8"

16

URC-2-20

3/4"

20

URC-2-25

25

Material

Copper/Brass

The clams are used to join 25 x 3 mm conductor tape to


earth electrode / rebar, without the need to drill the
tape.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

LAMDA ELECTRIC
Earthing and Lightning Protection

U-Bolt Rod to Cable Clamp

URCC 16

Rod Dia
(mm)
14.2-17.2

Conductor
(mm2)
16-70

URCC 70

18-25

70-185

Part No.

Material
Copper/Brass

U-Bolt Rod Clamp


Rod/Pipe Dia
in

mm

No. of
Conductors

UC 301

5/8"-3/4"

16-19

50-95

UC 302

5/8"-3/4"

16-19

50-70

UC 303

5/8"-3/4"

16-19

50-70

UC 304

5/8"-3/4"

16-19

50-70

UC 305

5/8"-3/4"

16-19

70-120

UC 306

5/8"-3/4"

16-19

50-70

UC 307

5/8"-3/4"

16-19

70-120

UC 308

5/8"-3/4"

16-19

1 or 2

UC 309

30

1 or 2

UC 310

40

Part No.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

Conductor Size
(mm2)

No. of Copper Tape

LAMDA ELECTRIC
Earthing and Lightning Protection

Tape Clip
Part No.

Conductor Size
(mm)

TCC 203

20 x 3

TCC 253

25 x 3

Material
Copper/Brass

These Metal Clip Hold the Tape Flush to the Surface


and Fixed Using Two Screws

Tape Clip
Part No.

Conductor Size
(mm)

TCA 203

20 x 3

TCA 253

25 x 3

Material
Aluminium

DC Tape Clamp
Part No.

Tape Size (mm)

ADC 203

20 x 3

ADC 253

25 x 3

ADC 256

25 x 6

ADC 506

50 x 6

Material

Aluminium

DC Tape Clamp
Part No.

Conductor (mm)

CDC 203

20 x 3

CDC 253

25 x 3

CDC 256

25 x 6

CDC 503

50 x 3

CDC 504

50 x 4

CDC 506

50 x 6

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

Material

Copper/Brass

LAMDA ELECTRIC
Earthing and Lightning Protection

Square Tape Clamp


Part No.

Conductor Size
(mm2)

Material

ASC 253

25 x 3

Aluminium

CSC 253

25 x 3

CSC 256

25 x 6

CSC 506

50 x 6

Copper/Brass

Square clamps are made form cooper and aluminium,


it is used for four ways connection and suitable for
crossing over taps, straight through joints or t
connections to from a continuous network of tapes.

Square Conductor Clamp


Part No.

Conductor Size
(mm2)

SCC 50

50

SCC 50

70

SCC 50

95

Material

Copper

Square clamps for copper and aluminium circular


conductor used for a four ways connection and
suitable for crossing over taps, straight through joints
or t connections to from a continuous network of
tapes.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

10

LAMDA ELECTRIC
Earthing and Lightning Protection

Bi-Metallic Connector
Part No.

Conductor Size
(mm2)

Material

BMC 253 A

25 x 3

Aluminium Tape to

25 x 3

Copper Tape

Part No.

Conductor Size
(mm2)

Material

BMC 253 B

25 x 3

Aluminium Tape to

25 x 3

Copper Tape

Bimetal Clamps are used to connect Aluminium conductor to Copper Earth Conductor

Adhesive Base DC Clip


Part No.

Conductor Dia
(mm)

Conductor Type

OH 8 C

Copper

OH 8 A

Aluminium

OH 10 C

Copper pvc covered

OH 10 A

Aluminium pvc covered

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

11

LAMDA ELECTRIC
Earthing and Lightning Protection

C-Copper Clamp
Dimensions (mm)

Part
No.

Conductor
(mm2)

CCA-1

25-35

25

15

22

10

CCA-2

50-70

34

21.5

25

11

CCA-3

95-95

41

25

29

14.5

CCA-4

120-120

47.5

29

30

16

Note
Can be
produced
according to
customer's
drawing

Dimensions (mm)

Part No.

Conductor
(mm2)

CCT-10

7.5-14

9.5

6.3

6.2

12

1.6

CCT-16

14.5-16

11.8

7.8

7.8

13

CCT-20

16.5-20

12.8

8.6

9.7

13

5.4

2.9

CCT-26

21-26

14.7 10.2

10

16

6.5

3.2

CCT-44

27-44

19

13.4 14.4

20

8.5

CCT-60

45-60

21

15.4 15.4

22

9.7

CCT-76

61-75

24.4 17.3 17.6

22

10.8

CCT-98

77-98

27.8 20.8 18.8

25

12.8

CCT-122

99-122

29.8 22.1 21.2

26

13.5

5.5

CCT-154

123-154

34

25.7 24.4

28

17

CCT-190

155-190

37

28.5 25.4

35

17.4

CCT-240

191-240

40

30.2 28.5

40

19

Material : 99.9% Pure coppen


Surface : Tin Plating on request

Split Bolted Connector


L

Weight
(kg)

T/J-16

Applicable
Conductor
(mm2)
16

26

10 x 1

5.3

13.9

0.023

T/J-25

25

29

14 x 1.5

18.5

0.034

T/J-35

35

34

18 x 1.5

20.8

0.057

T/J-50-70

50-70

42

24 x 2

12

27.7

0.108

T/J-90-120

90-120

50

24 x 2

14.5

30

0.142

T/J-150-185

150-180

63

24 x 2

18

34.6

0.250

T/J-200-240

200-240

72

31 x 2.5

20

32

0.301

Part No.

Dimensions (mm)

Material : Brass
Surface : Tin Plated or Copper Plated on request.
It is used to branch or connect aerial hard copper conductor or insulated copper conductor.
PT. Lamda Teknologi Indonesia
Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

12

LAMDA ELECTRIC
Earthing and Lightning Protection

B Bond
Part No.

Conductor
(mm)

Material

BBC

25 x 3

Copper/Brass

BBA

25 x 3

Aluminium

Bond connections are used to bond either


Copper of Aluminium to flat metal surfaces.

Pipe Bond
Part No.

Conductor
(mm)

Material

PBC

25 x 3

Copper/Brass

PBA

25 x 3

Aluminium

Pipe bond connections are used to connect flat


conductor objects i.e. Pipe work and hand rails
etc.

Rod to Cable Lug Clamp


Part No.

Rod Dia
in

mm

CLUG 10

3/8"

9.5

CLUG 16

5/8"

16

CLUG 20 S

20

Material

Copper/Brass

Rod to cable lug clamps are used to join


various sizes of compression lugs to the earth
electrode.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

13

LAMDA ELECTRIC
Earthing and Lightning Protection

Tee Clamp
Part No.

Conductor Dia
(mm)

Material

TC 08

Copper/Brass

TA 08

Aluminium

Tee clamps for copper and aluminium circular conductor, the


clamps are used for three ways connection.

Flat to Circular Square Clamp


Part No.

Tape Size
(mm)

Conductor Rang
(mm/mm2)

SCC 25350

25 x 3

50

SCC 25370

25 x 3

70

SCC 25395

31 x 3

95

Material

Copper/Brass

Square clamps for copper tape to circular conductor, the base


has a countersunk hole in the middle for fixing the clamp.

Test ClampCable
Part No.

Conductor Dia (mm)

TC 50

50

TC 70

70

TC 95

95

Material

Copper/Brass

Test clamps are manufactured from copper, it used to form a


disconnecting joint between the down conductor system and
the earthing system.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

14

LAMDA ELECTRIC
Earthing and Lightning Protection

Oblong Test Clamp


Part No.

Conductor (mm)

Material

OTCA 253

25 x 3

Aluminium

OTCC 253

25 x 3

OTCC 316

31 x 6

OTCA 405

40 x 5

Copper/Brass

Oblong Test Clamps are used to join conductor tape to


facilitate in the annual testing of the lightning protection
system.

Copper Test Clamp


Part No.
CTC 08

Conductor Dia Conductor Size


Material
(mm)
(mm)
8
25 x 3
Copper/Brass

Copper test clamp are used to form a disconnecting joint


between either conductor (8 mm + 0.8 mm dia) or 25 x 3 m
conductor.

Earth Bonding Point

EBP 2

Length
(mm)
500

EBP 4

500

EBP 2P

500

EBP 2P-08

500

Part No.

Material

Gunmetal casting with 70


mm2 pvc copper cable

Earth bond points are used to provide earthing continuity and


a multi-bonding point. The bonding points are available with
2 or 4 holes connections and cover plate.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

15

LAMDA ELECTRIC
Earthing and Lightning Protection

Screw Down Test Clamp


Part No.

Conductor (mm)

Material

STDC 253

25 x 3

Copper/Brass

Screw down test clamp are used to join 25 x 3 mm conductor


tape to facilitate in the annual testing of the lightning
protection system.

Plate Test Clamp


Part No.

Conductor (mm)

Material

PTC 253

25 x 3

Gunmetal

Plate type test clamps, made of brass or aluminium, which


can be used as to joints or straight through joints of tapes
being joints, these can also effectively be used as testing
points for the network. By disconnecting the joints, plate test
clamp can also be used for heavy duty up to 50 x 6 tape
connections.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

16

LAMDA ELECTRIC
Earthing and Lightning Protection

Air Rod
Part No.

Rod Length
(mm)

Rod Dia
(mm)

Thread Dia
(mm)

CAR 0515

500

15

16

CAR 1015

1000

15

16

CAR 1515

1500

15

16

CAR 2015

2000

15

16

TAR 515 T

500

15

16

TAR 1515 T

1000

15

16

TAR 2015 T

1500

15

16

TAR 051 T

2000

15

16

AAR 0515 A

500

15

16

AAR 1015 A

1000

15

16

AAR 1515 A

1500

15

16

AAR 2015 A

2000

15

16

AAR 0510

500

10

10

AAR 1010

1000

10

10

AAR 0510 A

500

10

10

AAR 1010 A

1000

10

10

Material

Copper

Tinned Copper

Aluminium

Copper
Aluminium

The air rods made from Electrocytic Grade Copper, one side tapper pointed and the other side with
suitable threads for fixing to saddles /air terminal bases. Rods made from also can be supplied against
specific requirements. Rods can be installed with or without multiple points. However, researches
conducted in this regards suggest use or multiple points with taper pointed air rods are more effective
than taper pointed air rods.

Air Rods Base


Part No.

Rod Dia
(mm)

Thread Dia
(mm)

DC 312

12

12

Max.
Conductor
width (mm)
25

DC 515

15

16

25

DA 312

12

12

25

DA 515

15

16

25

Material
Copper/Brass
Aluminium

Copper and Aluminium Air Rod Base are used for supporting taper
pointed or air Rods with tapes, four fixing holes are provided on it.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

17

LAMDA ELECTRIC
Earthing and Lightning Protection

Air Termination
Part No.
ATC 3142
ATC 5142
ATC 10142
ATC 20142
ATC 31558-16
ATC 51558-16
ATC 101558-16
ATC 201558-16
ATC 31658-16
ATC 51658-16
ATC 101658-16
ATC 201658-16
ATC 5172
ATC 10172
ATC 20172
ATA 3142
ATA 5142
ATA 10142
ATA 15142
ATA 20142
ATA 31558-16
ATA 51558-16
ATA 101558-16
ATA 151558-16
ATA 201558-16
ATA 31658-16
ATA 51658-16
ATA 101658-16
ATA 151658-16
ATA 201658-16
ATA 5172
ATA 10172
ATA 20172

Rod Length
(mm)
300
500
1000
2000
300
500
1000
2000
300
500
1000
2000
500
1000
2000
300
500
1000
1500
2000
300
500
1000
1500
2000
300
500
1000
1500
2000
500
1000
2000

Rod Dia
(mm)
14.2
14.2
14.2
14.2
15
15
15
15
16
16
16
16
17.2
17.2
17.2
14.2
14.2
14.2
14.2
14.2
15
15
15
15
15
16
16
16
16
16
17.2
17.2
17.2

Thread Dia
(mm)
5/8"
5/8"
5/8"
5/8"
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
3/4'
3/4'
3/4'
5/8'
5/8'
5/8'
5/8'
5/8'
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
5/8' or 16 mm
3/4'
3/4'
3/4'

Material

Copper/Brass

Copper/Brass

Copper/Brass

Aluminium

Aluminium

Aluminium

Aluminium

Tapper pointed air rods ate made from copper/base. One side tapper pointed and the other side with
suitable for fixing to saddles/air terminal bases. Rods made of aluminium alco can be supplied against
specific requirements. Rod can be use of multiple points with taper points with taper pointed air rods
are more effective than taper pointed air rods.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

18

LAMDA ELECTRIC
Earthing and Lightning Protection

Air Termination
Part No.

Dimensions (mm)
H

H1

H2

H3

ATC 01-A

380

250

130

90

100

ATC 01-B

550

420

130

140

100

ATC 01-C

1000

870

130

300

100

Part No.

Dimensions (mm)
H

H1

H2

H3

ATC 02-A

380

250

130

90

100

ATC 02-B

550

420

130

140

100

ATC 02-C

1000

870

130

300

100

Part No.
ATC 03-A

Part No.
ATC 03-B

Dimensions (mm)
H

H1

H2

H3

750

400

250

100

100

Dimensions (mm)
H

H1

H2

H3

1500

250

200

700

150

200

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

19

LAMDA ELECTRIC
Earthing and Lightning Protection

Earth Plate Solid Copper


Part No.

Size (mm)

SCEP 615

600 x 600 x 1.5

SCEP 630

600 x 600 x 3

SCEP 915

900 x 900 x 1.5

SCEP 930

900 x 900 x 3

Material

Copper

Solid copper earth plates are used as part of earthing network,


which provide a log lasting solution where earth rods are unsuitable
and also used as an electrode where significant amounts of fault
current can be encountered.

Earth Mat Copper Tape


Part No.

Size (mm)

LCEM 630

600 x 600 x 3

LCEM 930

900 x 900 x 3

Material
High conductivity copper

The Copper Earth Mat are used where step potential could cause
problems, which provide a long lasting earthing solution and used
as an electrode where significant amounts of fault current can be
encountered.

Solid copper plate arrangement

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

Lattice copper mat arrangement

20

LAMDA ELECTRIC
Earthing and Lightning Protection

Rod To Tape Coupling


Part No.

Conductor Dia
(mm)

Conductor Size
(mm)

Material

RBCC 16

16

25 x 3

Copper/Brass

Rod To Tape Couplers are made from copper and used in


conjunction with Side Mounted Brackets.

Air Rod Bracket


Part No.

Conductor Dia
(mm)

Conductor Size
(mm)

Material

APK 15

15

16

Copper

APK 15 A

15

16

Aluminium

APK 15 T

15

16

Tinned Copper

Air Rod Brackets are to be installed to the side of the building were
it is not possible to fit a conventional air terminal base. The brackets
are to be used in conjunction with the rod to tape coupling.

Puddle Flanges
Part No.

Dimension (mm)

Material

PFC

150 x 150 x 600

Copper

PFA

150 x 150 x 600

Aluminium

Made from copper or Aluminium, used where the roof termination


or down conductors have to pass through water proof couering,
roff, etc.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

21

LAMDA ELECTRIC
Earthing and Lightning Protection

Compression Clamp
Part No.

Suitable Conductor (mm2)

BC-119-50

50-70

BC-119-70

70-95

BC-119-95

95-120

Inspection Pit
Part No.

Overall (mm)

Description

Material

IP 5

300 x 25 x 6

5 Hole pit bar

IP 7

300 x 25 x 6

7 Hole pit bar

Hard drawn
copper bar

These are suitable for most types of earthing & lightning protection installations.
Not suitable for use in areas where high load, small wheel vehicles are used.

Product Introduction

Part No.

Diameter of lamp

Height of Lamp

Length of screw

Material

IP 5
160 mm
185 mm
200 mm
M16
The obstruction lamp is a product applied by the communication base stations up to date since a long
time ago. It is based on DC or AC power as its power supply system with the light emitting tube as its
light source. Its outside case is made of polycarbonate and engineering plastic materials, controlled with
the light sensitive resistance. It flashes by itself at the night time and turns off automatically at the day
time.

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

22

LAMDA ELECTRIC
Earthing and Lightning Protection

Earth Bars
Part No.
EBAR 6
EBAR 8
EBAR 10
EBAR 12
EBAR 14
EBAR 16
EBAR 18
EBAR 20
EBAR 22
EBAR 24
EBAR 26
EBAR 28
EBAR 30

Dimension (mm2)
300 x 90 x 90
450 x 90 x 90
450 x 90 x 90
520 x 90 x 90
650 x 90 x 90
650 x 90 x 90
800 x 90 x 90
800 x 90 x 90
900 x 90 x 90
1050 x 90 x 90
1050 x 90 x 90
1250 x 90 x 90
1250 x 90 x 90

Material
6 ways earth bar disconnect link
8 ways earth bar disconnect link
10 ways earth bar disconnect link
12 ways earth bar disconnect link
14 ways earth bar disconnect link
16 ways earth bar disconnect link
18 ways earth bar disconnect link
20 ways earth bar disconnect link
22 ways earth bar disconnect link
24 ways earth bar disconnect link
26 ways earth bar disconnect link
28 ways earth bar disconnect link
30 ways earth bar disconnect link

Other sizes request

Earth Bars Insulators


Part No.
SM 10
SM 20
SM 25
SM 30
SM 35
SM 40
SM 45
SM 51
SM 60
SM 76

Size (mm)
M 10 x 35
M 5 x 20
M 6 x 25
M 8 x 30
M 8 x 35
M 8 x 40
M 8 x 45
M 8 x 51
M 8 x 60
M 10 x 71

Electrical :
Dielectric Strength
Resistance (normal)
Resistance (bolted)
Arc resistance
Tracking Index
Inserts:
Brass
(Torque can depend
on the Standoff
diameter)

Description
Insulator stand off type c/w 2 studs & 3 nuts
Insulator stand off type
Insulator stand off type
Insulator stand off type
Insulator stand off type
Insulator stand off type
Insulator stand off type
Insulator stand off type
Insulator stand off type
Insulator stand off type
: > 14 kV/mm
: > 10 M Ohms
: > 10 M Ohms
: > 180 secretary
: > 600

M6
M8
M10

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

9 Nm Torque
18 Nm Torque
35 Nm Torque
23

LAMDA ELECTRIC
Earthing and Lightning Protection

Copper Tape

Part No.

Dimension (mm2)

CT 203
CT 254
CT 304
CT 305
CT 404
CT 405
CT 505
CT 506

20 x 3
25 x 4
30 x 4
30 x 5
40 x 4
40 x 5
50 x 5
50 x 6

Stand No. / Diameter


(mm2)
60
100
120
150
160
200
250
300

Remark

Material : Oxygen-free copper

Bi-metal Earth Conductor

Part No.
SBCT 08
SBCT 10
SBCT 12
SBCT 14

Diameter (mm)
8
10
12
14

Length (m)
6
6
6
6

Remark
Thickness of copper layer 0.5 mm
Copper/steel

Flat Bi-metal Tape

Part No.
FBT 50
FBT 070
FBT 095
FBT 120
FBT 160
FBT 180
FBT 210

Dimensions
(mm)
6 X 14
6 X 20
7 X 22
7 X 27
7 X 32
7 X 37
8 X 37

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

Stand No. / dia (m)


6
6
6
6
6
6
6

Remark

Thickness of copper layer 0.5 mm


Copper/steel

24

LAMDA ELECTRIC
Earthing and Lightning Protection

Bi-metal Earthing Conductor

Barel (Cu/Steel) Bimetallic cable / Y/G PVC insulated (Cu/Steel) Bimetallic cableGalvanized technics.
Conductor Section
Conductor Dia
Weight / M
Part No.
Remark
(mm2)
(mm)
(kgs)
BC 16/IBC 16
16
7/1.70
0.126/0.156
BC 25/IBC 25
25
7/2.14
0.193/0.228
BC 35/IBC 35
35
7/2.50
0.273/0.323
BC 50/IBC 50
50
7/3.00
0.384/0.444
General packing : 100
meters
BC 50/IBC 50
50
19/1.80
0.384/0.444
BC 70/IBC 70
BC 95/IBC 95
BC 120/IBC 120
BC 150/IBC 150
BC 185/IBC 185

70
95
120
150
185

19/2.10
19/2.50
37/2.03
37/2.30
37/2.50

0.523/0.603
0.742/0.842
0.930/1.050
1.02/1.17
1.446/1.63

Voltage of Insulator :
450/750V

Copper Earth Conductor

Bare copper stranded cables / Y / G PVC insulated copper cables.

CC 16/ICC 16

Conductor Section
(mm2)
16

Conductor Dia
(mm)
7/1.68

Weight / M
(kgs)
0.14/0.17

Cc 25/ICC 25

25

7/2.11

0.22/0.255

Cc 35/ICC 35

35

7/2.49

0.306/0.356

Part No.

Remark

Cc 50/ICC50

50

7/2.97

0.438/0.498

Material : Oxygen-

Cc 70/ICC 70

70

19/2.14

0.618/0.698

free copper

Cc 95/ICC 95

95

19/2.49

0.838/0.938

tinned conductor

Cc 120/ICC 120

120

19/2.80

1.057/1.177

on request

Cc 150/ICC 150

150

37/2.25

1.34/1.49

Cc 185/ICC 185

185

37/2.49

1.65/1.834

Cc 240/ICC 240

240

37/2.84

2.14/2.371

Cc 300/ICC 300

300

61/2.49

3.564/2.854

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

25

LAMDA ELECTRIC
Earthing and Lightning Protection

Copper Braid Wire


The copper braided wire is used as flexible jointing wire of electric appliance, switch appliance, electric
stove and storage battery etc.
Model and Meaning

Technique Performance
Copper braided wire adopts super quality round copper wire or tinning soft round copper wire to be
braided in multiple thread one layer or many layers.
The DC electrical resistivity (20oC) of copper braided wire is lower than 0.022 .mm2/m, the DC electrical
resistivity (200C) of tinning copper braided wire is lower than 0.234 .mm2/m.

CBW20 and CBWX 20


Section
(mm2)
Standard Calculating
16
25
35
50
70
95
120
150
185
240
300
400
500
630

16.59
24.88
33.18
49.77
66.36
90.49
120.55
150.82
180.98
241.31
301.63
401.17
500.65
633.43

Number of skeins x
threads/diameter of a single thread
(mm)
24 x 22 x1/0.20
24 x 33 x1/0.20
24 x 44 x1/0.20
24 x 33 x2/0.20
24 x 44 x2/0.20
24 x 40 x3/0.20
24 x 40 x4/0.20
24 x 40 x 5/0.20
24 x 40 x 6/0.20
24 x 40 x 8/0.20
24 x 40 x 10/0.20
24 x 40 x 10/0.20 + 36 x 44 x 2/0.20
24 x 40 x 10/0.20 + 48 x 44 x 3/0.20
24 x 40 x 10/0.20 + 48 x 44 x 5/0.20

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

20 Direct Current
reistance /km no
Calculating
more than
weight
The width Thickness
(kg/km)
no more
for
CBW-20 CBWX-20
than
reference
16
3.0
1.30
1.36
166
18
3.5
0.87
0.91
249
20
4.0
0.65
0.68
331
22
5.0
0.43
0.45
198
24
6.5
0.32
0.33
664
20
0.24
0.25
905
22
0.18
0.19
1207
24
0.14
0.15
1508
26
0.12
0.13
1810
30
0.089
0.093
2413
35
0.071
0.075
3016
40
0.054
0.056
4004
45
0.043
0.045
5007
50
0.034
0.036
6334
Size
(mm)

26

LAMDA ELECTRIC
Earthing and Lightning Protection

Copper Braided Shunt


These connectors manufactured from highly flexible, which are braided from annealed Cu. The best
alternative to cable, no cutting, no crimping, flexible, pre-punched, ready to use, quick and easy to
install.
Solidified pressed contact areas

Ametal Alloyed Leadfree Solder Solidified Contact Areas

Technical data
Braids
: 0.20 mm annealed Cu-ETP wires, uncoated or tinned
Insulation : Special vinyl compound
Max. working temperature 1050C
Self extinguishable: UL 94 VO
Dielectric strength : 20 kV/mm
Max. working voltage : 1000V AC 1500 V DC

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

27

LAMDA ELECTRIC
Earthing and Lightning Protection
Part No.
Red Copper
BS 025- 230- 10-8
BS 025- 330- 10-8
BS 025- 430- 10-8
BS 025- 530- 10-8
BS 025- 630- 10-8
BS 025- 230- 10-8
BS 035- 330- 10-8
BS 035- 430- 10-8
BS 035- 530- 10-8
BS 035- 630- 10-8
BS 035- 230- 10-8
BS 050- 330- 10-8
BS 050- 430- 10-8
BS 050- 530- 10-8
BS 050- 630- 10-8
BS 050- 230- 10-8
BS 070- 330- 10-10
BS 070- 430- 10-10
BS 070- 530- 10-10
BS 070- 630- 10-10
BS 070- 230- 10-10
BS 095- 330- 10-10
BS 095- 430- 10-10
BS 095- 530- 10-10
BS 095- 630- 10-10
BS 120- 330- 10-10
BS 120- 430- 10-10
BS 120- 530- 10-10
BS 120- 630- 10-10
BS 120- 730- 10-10
BS 120- 830- 10-10
BS 150- 330- 10-12
BS 150- 430- 10-12
BS 150- 530- 10-12
BS 150- 630- 10-12
BS 150- 730- 10-12
BS 150- 830- 10-12
BS 185- 330- 10-12
BS 185- 430- 10-12
BS 185- 530- 10-12
BS 185- 630- 10-12
BS 185- 730- 10-12
BS 185- 830- 10-12
BS 240- 330- 10-12
BS 240- 430- 10-12
BS 240- 530- 10-12
BS 240- 630- 10-12
BS 240- 730- 10-12
BS 240- 830- 10-12

Cross
secretary
Tinned Copper
(mm2)
BST 025- 230- 10-8
25
BST 025- 330- 10-8
25
BST 025- 430- 10-8
25
BST 025- 530- 10-8
25
BST 025- 630- 10-8
25
BST 025- 230- 10-8
25
BST 035- 330- 10-8
35
BST 035- 430- 10-8
35
BST 035- 530- 10-8
35
BST 035- 630- 10-8
35
BST 035- 230- 10-8
35
BST 050- 330- 10-8
50
BST 050- 430- 10-8
50
BST 050- 530- 10-8
50
BST 050- 630- 10-8
50
BST 050- 230- 10-8
50
BST 070- 330- 10-10
70
BST 070- 430- 10-10
70
BST 070- 530- 10-10
70
BST 070- 630- 10-10
70
BST 070- 230- 10-10
70
BST 095- 330- 10-10
95
BST 095- 430- 10-10
95
BST 095- 530- 10-10
95
BST 095- 630- 10-10
95
BST 120- 330- 10-10 120
BST 120- 430- 10-10 120
BST 120- 530- 10-10 120
BST 120- 630- 10-10 120
BST 120- 730- 10-10 120
BST 120- 830- 10-10 120
BST 150- 330- 10-12 150
BST 150- 430- 10-12 150
BST 150- 530- 10-12 150
BST 150- 630- 10-12 150
BST 150- 730- 10-12 150
BST 150- 830- 10-12 150
BST 185- 330- 10-12 185
BST 185- 430- 10-12 185
BST 185- 530- 10-12 185
BST 185- 630- 10-12 185
BST 185- 730- 10-12 185
BST 185- 830- 10-12 185
BST 240- 330- 10-12 240
BST 240- 430- 10-12 240
BST 240- 530- 10-12 240
BST 240- 630- 10-12 240
BST 240- 730- 10-12 240
BST 240- 830- 10-12 240

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

L
mm
230
330
430
530
630
230
330
430
530
630
230
330
430
530
630
230
330
430
530
630
230
330
430
530
630
330
430
530
630
730
830
330
430
530
630
730
830
330
430
530
630
730
830
330
430
530
630
730
830

L1
mm
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

L2
mm
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

L3
mm
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14

Dimensions
L4 L5 W T
mm mm mm mm
7 248 20 3.2
7 348 20 3.2
7 448 20 3.2
7 548 20 3.2
7 648 20 3.2
7 248 20 4.2
7 348 20 4.2
7 448 20 4.2
7 548 20 4.2
7 648 20 4.2
7 252 20 5
7 352 20 5
7 452 20 5
7 552 20 5
11 652 20 5
11 252 20 6.8
11 352 20 6.8
11 452 20 6.8
11 552 20 6.8
11 652 20 6.8
11 252 25 7.5
11 352 25 7.5
11 452 25 7.5
11 552 25 7.5
11 652 25 7.5
14 355 30 7.5
14 455 30 7.5
14 555 30 7.5
14 655 30 7.5
14 755 30 7.5
14 855 30 7.5
14 355 30 10
14 455 30 10
14 555 30 10
14 655 30 10
14 755 30 10
14 855 30 10
14 355 30 11
14 455 30 11
14 555 30 11
14 655 30 11
14 755 30 11
14 855 30 11
14 355 30 13
14 455 30 13
14 555 30 13
14 655 30 13
14 755 30 13
14 855 30 13

K
mm
7
7
7
7
7
7
7
7
7
7
7.5
7.5
7.5
7.5
7.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
12.5
12.5
12.5
12.5
12.5
12.5
15
15
15
15
15
15
15
15
15
15
15
15
17
17
17
17
17
17

G
mm
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
28
28
28
28
28
28
28
28
28
28
28
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34
34

D1
mm
10
10
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

D2
mm
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

28

LAMDA ELECTRIC
Earthing and Lightning Protection

Grounding Braid
Earthing Tapes With Solder Pressed Contact Areas

Earthing Tapes With Ametal Alloyed Leadfree Solder


Solidified Contact Areas

Part No.

Tinned Copper

TZ 6 - 75/010/07
TZ 6 - 100/010/07
TZ 6 - 150/010/07
TZ 6 - 200/010/07
TZ 10 - 100/020/09
TZ 10 - 150/020/09
TZ 10 - 200/020/09
TZ 10 - 250/020/09
TZ 10 - 300/020/09
TZ 16 - 100/020/09
TZ 16 - 200/020/09
TZ 16 - 250/020/09
TZ 16 - 300/020/09
TZ 16 - 350/020/09
TZ 16 - 400/020/09
TZ 25 - 100/020/09
TZ 25 - 200/020/09
TZ 25 - 300/020/09
TZ 25 - 400/020/09
TZ 35 - 100/020/09
TZ 35 - 200/020/09
TZ 35 - 300/020/09
TZ 35 - 400/020/09
TZ 50 - 100/020/11
TZ 50 - 200/020/11
TZ 50 - 300/020/11
TZ 50 - 400/020/11
TZ 75 - 200/020/11
TZ 75 - 300/020/11
TZ 75 - 400/020/11
TZ 95 - 200/020/13
TZ 95 - 250/020/13
TZ 95 - 400/020/13
TZ 95 - 400/020/13

TZX 6 - 75/010/07
TZX 6 - 100/010/07
TZX 6 - 150/010/07
TZX 6 - 200/010/07
TZX 10 - 100/020/09
TZX 10 - 150/020/09
TZX 10 - 200/020/09
TZX 10 - 250/020/09
TZX 10 - 300/020/09
TZX 16 - 100/020/09
TZX 16 - 200/020/09
TZX 16 - 250/020/09
TZX 16 - 300/020/09
TZX 16- 350/020/09
TZX 16 - 400/020/09
TZX 25 - 100/020/09
TZX 25 - 200/020/09
TZX 25 - 300/020/09
TZX 25 - 400/020/09
TZX 35 - 100/020/09
TZX 35 - 200/020/09
TZX 35 - 300/020/09
TZX 35 - 400/020/09
TZX 50 - 100/020/11
TZX 50 - 200/020/11
TZX 50 - 300/020/11
TZX 50 - 400/020/11
TZX 75 - 200/020/11
TZX 75 - 300/020/11
TZX 75 - 400/020/11
TZX 95 - 200/020/13
TZX 95 - 250/020/13
TZX 95 - 400/020/13
TZX 95 - 400/020/13

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

Section
Wire
(mm2) Diameter
6
6
6
6
10
10
10
10
10
16
16
16
16
16
16
25
25
25
25
35
35
35
35
50
50
50
50
75
75
75
100
100
100
100

0.10
0.10
0.10
0.10
0.15
0.15
0.15
0.15
0.15
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20

A
B
mm mm
13
11
13
11
13
11
13
11
23
17
23
17
23
17
23
17
23
17
23
17
23
17
23
17
23
17
23
23
23
23
23
17
23
17
23
17
23
17
23
23
23
23
23
23
23
23
30
23
30
30
30
30
30
30
30
30
30
35
30
35
35
35
35
35
35
35
35
35

Dimensions
C
D
mm mm
5
7
5
7
5
7
5
7
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
10
9
15
11
15
11
15
11
15
11
15
11
15
11
15
13
15
13
15
13
15
13

S
L
mm mm
2.0 75
2.0 100
2.0 150
2.0 200
2.0 100
2.0 150
2.0 200
2.0 250
2.0 300
2.5 100
2.5 200
2.5 250
2.5 300
2.5 350
2.5 400
3.2 100
3.2 200
3.2 300
3.2 400
3.4 100
3.4 200
3.4 300
3.4 400
4.5 100
4.5 200
4.5 300
4.5 400
5.0 200
5.0 300
5.0 400
6.0 200
6.0 250
6.0 400
6.0 700
29

LAMDA ELECTRIC
Earthing and Lightning Protection

Round Flexible Copper Wire

20 Direct Current
Size (mm)
reistance /km no
Calculating
more than
external
Number of skeins x
diameter
threads/diameter
(mm)
Total
CBW-20 CBWX-20
of a single thread
(mm)
408
12 x 34/0.07
1.97
11.70
12.6

Standard
Section
(mm2)

Calculating
Section
(mm2)

1.5

1.57

2.5

2.49

646

19 x 34/0.07

2.35

7.41

7.96

23.7

4.03

513

19 x 27/0.10

3.08

4.58

4.79

38.3

6. 3

6.27

798

19 x 42/0.10

3.73

2.94

3.07

59.6

10

10.00

1273

19 x 67/0.10

4.73

1.85

1.93

95.1

16

15.83

2016

12 x 7 x 24/0.10

7.18

1.15

1.21

150

25

25.07

3192

19 x 7 x 24/0.10

8.55

0.736

0.769

238

(35)

34.47

4389

19 x 7 x 33/0.10

9.90

0.535

0.559

328

40

39.96

2261

19 x 7 x 17/0.15

11.03

0.462

0.483

380

(50)

49.36

2793

19 x 7 x 21/0.15

12.15

0.374

0.391

470

63

63.46

3591

19 x 7 x 27/0.15

13.50

0.291

0.304

604

(70)

70.51

3990

19 x 7 x 30/0.15

14.18

0.252

0.274

671

80

79.91

4522

19 x 7 x 34/0.15

15.08

0.231

0.241

760

(95)

94.01

5320

19 x 7 x 40/0.15

16.43

0.195

0.205

894

100

10.73

5700

19 x 7 x 25/0.15

18.27

0.183

0.191

958

(120)

120.87

6840

19 x 7 x 30/0.15

20.24

0.153

0.160

1150

125

127.59

7220

19 x 19 x 20/0.15

20.29

0.145

0.152

1214

160

159.49

9025

19 x 19 x 25/0.15

21.75

0.116

0.121

1517

(185)

185.00

10469

19 x 19 x 29/0.15

23.25

0.0997

0.104

1760

200

196.15

11100

37 x 12 x 25/0.15

25.58

0.0940

0.0982

1866

250

251.08

41208

37 x 12 x 32/0.15

28.57

0.0735

0.0768

2388

315

310.58

17575

37 x 19 x 25/0.15

30.45

0.0594

0.0621

2954

400

397.54

22496

37 x 19 x 32/0.15

34.13

0.0464

0.0485

3782

500

496.92

28120

37 x 19 x 40/0.15

38.06

0.0371

0.0388

4727

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

Calculating
weight
(kg/km)

14.8

30

LAMDA ELECTRIC
Earthing and Lightning Protection

Brailed Flexible Connector


Pressed copper connectors, tin coated on request.
Single wire diameter : 0.20 standard
0.10 on request

Red copper

Tinned
copper

CRS 100
CRS 150
CRS 200
CRS 250
CRS 300
CRS 400
CRS 500
CRS 600
CRS 800
CRS 1000
CRS 1200
CRS 1500
CRS 2000

CSS 100
CSS 150
CSS 200
CSS 250
CSS 300
CSS 400
CSS 500
CSS 600
CSS 800
CSS 1000
CSS 1200
CSS 1500
CSS 2000

Section
(mm)
100
150
200
250
300
400
500
600
800
1000
1200
1500
2000

A
(mm)
40
40
50
50
100
100
100
100
80
100
120

B
S
L
(mm) (mm) (mm)
40
5
200
40
7
250
50
7
350
50
9
350
50
10
400
50
12
400
50
16
400
60
16
400
80
16
400
100
17
450
120
17
450

Holes D
13
13
13
13
13
13
13
13
13
13
13

Terminal
Drill
W1
W1
W1
W1
W2
W2
W2
W2
W4
W5
W7

Current
flow
480
590
760
910
950
1020
1300
1500
1700
1900
2150

On request

Widths, lengths, cross-sections and bores are not included in table above, they are provided at request.
An information concerning current flow is not binding, the values.
Shown above are approximate values.

Standard drillings

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

31

LAMDA ELECTRIC
Earthing and Lightning Protection

Flexible Insulated Bars


Flexible insulated bars are made of high Flexibility laminated copper layers, coated with black coloured,
selfextinguishable insulating PUV compound.

Technical Characteristic Laminated Copper Strips


Electrolytic copper annealed Cu ETP (state): 99.9% Cu.
Resistivity : 1.78 cm2 / cm
Vickers hardness : < 50 HV
Maximum tensile strength > 200/MM2
Elongation > 30%

Dimensions
(mm)

Current-load
Current-load
Section
Dimensions Section
(mm) t 20C t 40C t 50C
(mm)
(mm) t 20C t 40C t 50C

15.5 x 0.8 x 2
15.5 x 0.8 x 3
15.5 x 0.8 x 4
15.5 x 0.8 x 6
15.5 x 0.8 x 8
15.5 x 0.8 x 10

24.8
37.2
49.6
74.4
99.2
124

125
160
195
225
165
300

175
210
265
320
380
420

200
240
295
360
430
480

20 x 1 x 2
20 x 1 x 3
20 x 1 x 4
20 x 1 x 5
20 x 1 x 6
20 x 1 x 8
20 x 1 x 10

40
60
80
100
120
160
200

170
230
270
300
330
400
420

240
320
380
430
470
560
580

270
360
440
490
530
620
650

24 x 1 x 2
24 x 1 x 3
24 x 1 x 4
24 x 1 x 5
24 x 1 x 6
24 x 1 x 8
24 x 1 x 10

48
72
96
120
144
192
240

200
250
280
330
360
420
500

280
360
410
170
510
590
700

320
410
460
530
570
670
790

32 x 1 x 2
32 x 1 x 3
32 x 1 x 4
32 x 1 x 5
32 x 1 x 6
32 x 1 x 5
32 x 1 x 10
32 x 1 x 10

64
96
126
160
192
256
320
320

230
280
320
390
440
510
600
600

320
410
460
550
620
720
840
840

360
460
520
610
700
800
930
930

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

40 x 1 x 2
40 x 1 x 3
40 x 1 x 4
40 x 1 x 5
40 x 1 x 6
40 x 1 x 8
40 x 1 x 10

80
120
160
200
240
320
400

240
330
400
450
480
600
670

330
450
560
630
680
830
920

380
540
630
710
750
920
1030

50 x 1 x 3
50 x 1 x 4
50 x 1 x 5
50 x 1 x 6
50 x 1 x 8
50 x 1 x 10

150
200
250
300
400
500

400
490
540
690
680
750

570
700
780
840
1000
1100

650
790
880
950
1130
1300

63 x 1 x 5
63 x 1 x 6
63 x 1 x 8
63 x 1 x 10

315
378
504
630

650
690
840
920

900
950
1200
1300

1000
1100
1350
1450

80 x 1 x 5
80 x 1 x 6
80 x 1 x 8
80 x 1 x 10

315
378
504
630

650
690
840
920

900
980
1200
1300

1000
1100
1350
1450

100 x 1 x 5
100 x 1 x 6
100 x 1 x 8
100 x 1 x 10
100 x 1 x 12
100 x 1 x 12

500
600
800
1000
1200
1200

860
950
1100
1220
1300
1300

1250
1380
1580
1710
1800
1800

1400
1530
1760
1920
2010
2010
32

LAMDA ELECTRIC
Earthing and Lightning Protection

Press Welded Flexible Connector


Press welding can only be performed on red copper and it depends on its dimensions and customers
specifications.
The laminated sections are compressed and reconstructed by block during the terminal phase. via use of
high currents. The contact resistance between each lamina is almost zero.
Contact areas : PWR press welded.
Copper strips : 0.1 mm thick witcover sheet 0.3 mm.
It is also possible to deliver contact areas with tinned or silvered design.

Red copper
PWR 200/180/40
PWR 200/230/40
PWR 320/230/40
PWR 400/230/40
PWR 250/250/50
PWR 400/250/50
PWR 500/250/50
PWR 480/300/60
PWR 600/300/60
PWR 640/300/80
PWR 800/300/100
PWR 960/300/80
PWR 800/350/100
PWR 1000/350/100
PWR 1200/350/120
PWR 1200/400/120
PWR 1440/400/120

Section
(mm)
200
200
320
400
250
400
500
480
600
640
800
960
800
1000
1200
1200
1440

A
(mm)
50
50
50
50
60
60
60
90
90
90
90
90
110
110
110
130
130

PT. Lamda Teknologi Indonesia


Komplek Ruko Taman Yasmin Sector VI No. 76
Jl. Ring Road Utara Taman Yasmin Bogor 16310
Telp/Fax : 0251-7155452 / 0251-8384529
Email
: lamdatek@yahoo.co.id

B
(mm)
40
40
43
45
45
48
50
70
70
70
70
70
80
80
80
80
80

S
(mm)
5
5
8
10
5
8
10
8
10
8
10
12
8
10
12
10
12

L
(mm)
180
230
230
230
250
250
250
300
300
300
300
300
350
350
350
400
400

Holes D
(mm)
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13

Terminal
drill
W1
W1
W1
W1
W1
W1
W1
W2
W2
W4
W4
W4
W5
W5
W5
W7
W7

Current
flow A
600
600
800
900
700
950
1100
1100
1200
1350
1500
1700
15550
1800
1900
2000
2200

33