You are on page 1of 10

TELECOM IMPLEMENTATION

External Alarms (BTS Eltek)


Telecom Implementation
p
On this document you can find:
- External Alarms Cable - Routing
g
- External Alarms - Pin Connection / Electrical Connection
- Eltek Commissioning Snapshots (External Alarm)
- BTS Commissioning Snapshots (External Alarm)

Slide 1 of 10 DN606081 TI.03 03.October.2006 by Stevan Picolli

TELECOM IMPLEMENTATION

External Alarms Cable Routing

Note the Eltek External Alarms go to the BTS 900 only in both cases.
Check BTS Installation Hand Book for location in the Entry Cable Kit.

Slide 2 of 10 DN606081 TI.03 03.October.2006 by Stevan Picolli

TELECOM IMPLEMENTATION

Slide 3 of 10 DN606081 TI.03 03.October.2006 by Stevan Picolli

TELECOM IMPLEMENTATION

External Alarms Pin Connection

BTS Connector

Eltek Interface Card

Alarm Cable

(Ext. Alarms Input / Control


Out)

External Alarms Output

12-Pair (2 x 0.5mm)

BTS Input

Pin

Description

Pin

BTS Alarm Input 1

Relay 1

5 (B1)

GND

26

Relay 1 Common

6 (B1)

BTS Alarm Input 2

Relay 2

8 (B1)

GND

27

Relay 2 Common

9 (B1)

BTS Alarm Input 3

Relay 3

9 (B2)

GND

28

Relay 3 Common

10 (B2)

BTS Alarm Input


p 4

10

Relayy 4

12 ((B2))

GND

29

Relay 4 Common

13 (B2)

BTS Alarm Input 5

11

Relay 5

15 (B2)

GND

30

Relay 5 Common

16 (B2)

BTS Alarm Input 6

12

Relay 6

18 (B2)

GND

31

Relay 6 Common

19 (B2)

Signal / Alarm

Pair

Mains Fail Alarm

Orange
Orange/White

High Battery Voltage

Low Battery Voltage

Load/Battery Fuse Fail

Rectifier Module Fault

MCU Common Alarm

There are 2 banks in External Alarms Output Card of Eltek. Refer to Electrical connection for more details.

Slide 4 of 10 DN606081 TI.03 03.October.2006 by Stevan Picolli

Pair Colour

Green
Green/White
Brown
Brown/White
Greyy
Grey/White
Blue
Blue/White
Orange
Orange/White

TELECOM IMPLEMENTATION

External Alarms Electrical Connection

Slide 5 of 10 DN606081 TI.03 03.October.2006 by Stevan Picolli

TELECOM IMPLEMENTATION

External Alarms Commissioning Eltek


Alarm Output Selection

Slide 6 of 10 DN606081 TI.03 03.October.2006 by Stevan Picolli

TELECOM IMPLEMENTATION

External Alarms Commissioning Eltek


Battery Voltage/Temperature Settings
Adjust the Voltage limits according with the figure below.

Check which temperature sensor is correct

Check the setting below.

Slide 7 of 10 DN606081 TI.03 03.October.2006 by Stevan Picolli

TELECOM IMPLEMENTATION

External Alarms Commissioning BTS


Alarm Input Selection

Attention All the alarms normal state is closed. Before clicking next make sure the Input is closed

Slide 8 of 10 DN606081 TI.03 03.October.2006 by Stevan Picolli

TELECOM IMPLEMENTATION

External Alarms Testing the Alarms


BTS
Eltek
Normal state of the alarms are showed below. When simulating the alarms, check if the status of the alarm is changed in both cabinets

Slide 9 of 10 DN606081 TI.03 03.October.2006 by Stevan Picolli

TELECOM IMPLEMENTATION

External Alarms Where to Buy in Iran

DB37 Male: Contact 021-66726785


Cable: Contact 021-33946677-8

Slide 10 of 10 DN606081 TI.03 03.October.2006 by Stevan Picolli