You are on page 1of 8

Vari-Airbox

Variable air-flow extractor boxes


with integrated speed controller
Centrifugal double inlet fans with external rotor
motor of low noise level.
Vari-Airbox
General description

A complete range of ventilation units of variable air-flow volume, equipped with centrifugal fans with
external rotor motor, designed to satisfy the most demanding up-to date installations. It is Very silent, solid,
versatile and easy to mount.
Air flow control integrated with two regulation possibilities, manual and by centralized digital device.

Characteristics

Centrifugal double inlet fans and variable air flow, The speed control is obtained through an
equipped with external rotor motor protected electronic selector and a 5 stage converter,
through thermal contact. integrated within the box.
Radial impellers of high Manual speed control panel of
performance balanced 5 stages of functional design.
statically and dynamically, Connection through
type 2, 5 according to telephonic type connectors
DIN/ISO 1940. RJ45. Ready for digital
Extremely silent and communication to a PLC or
vibrations free. DDC.

Casing made of extrusion aluminium profiles, To make the installation easier there are available
ensemble by plastic corner of high resistance a wide range of accessories: flexible gaskets,
against impacts. shutters, grills, circular and rectangular hoppers,
All panels can be registered and exchangeable protection visors, dampers, duct silencers,
The use of screws of electrical heating and water
metallic metric thread (not coils, hot or cold, filtration
auto-threadable) makes it modules, mounting consoles
easy a quick and and other special accessories
professional service. on request.

The standard series is supplied with galvanized The sound levels indicated on the characteristic
steel panels with the internal part coated with 25 panels correspond to the noise level pressure in
mm of fibber glass insulation of high sound ponder "A", taken at a distance of 1 meter with the
absorber capacity. suction and discharge connected to the duct.
On request there can be
mounted sandwich panels
and acoustic panels with 50
mm insulation of high
density fibber glass. The
sizes of the boxes with
acoustic panels can be
different from the indicated
in the dimensions sheet.
Please consult us.

We reserve the right to make changes on the characteristics and the prices without previous information. 2
It is forbidden the total or partial reproduction of this documentation without our express authorization.
7/7-4 7/7-6

Vari-Airbox 7/7 4 - 5 Speed Vari-Airbox 7/7 6 – 5 Speed


Voltage V 230 Frequency Hz 50 Voltage V 230 Frequency Hz 50
Power kW 0,32 Intensity A 1,4 Power kW 0,17 Intensity A 0,75
Speed rpm 1080 Condenser 6µF Speed rpm 760 Condenser 2,5µF
Max. Temp. 50ºC Motor protection IP 44 Max. Temp. 70ºC Motor protection IP 44
∆ pst min. 80Pa Connection ∆ pst min. - Connection

7/9-4K 7/9-4

Vari-Airbox 7/9 4K - 5 speed Vari-Airbox 7/9 4 – 5 speed


Voltage V 230 Frequency Hz 50 Voltage V 230 Frequency Hz 50
Power kW 0,44 Intensity A 2,0 Power kW 0,57 Intensity A 2,6
Speed rpm 1050 Condenser 8µF Speed rpm 1240 Condenser 12µF
Max. Temp. 50ºC Motor protection IP 54 Max. Temp. 70ºC Motor protection IP 54
∆ pst min. - Connection ∆ pst min. - Connection

3
9/9-4 9/9-6

Vari-Airbox 9/9 4 - 5 speed Vari-Airbox 9/9 6 – 5 speed


Voltage V 230 Frequency Hz 50 Voltage V 230 Frequency Hz 50
Power kW Intensity A Power kW 0,17 Intensity A 0,75
Speed rpm Condenser Speed rpm 760 Condenser 2,5µF
Max. Temp. Motor protection Max. Temp. 70ºC Motor protection IP 44
∆ pst min. 80Pa Connection ∆ pst min. - Connection

10/10-4 10/10-6

Vari-Airbox 10/10 4 - 5 speed Vari-Airbox 10/10 6 – 5 speed


Voltage V 230 Frequency Hz 50 Voltage V 230 Frequency Hz 50
Power kW 0,44 Intensity A 2,0 Power kW 0,57 Intensity A 2,6
Speed rpm 1050 Condenser 8µF Speed rpm 1240 Condenser 12µF
Max. Temp. 50ºC Motor protection IP 54 Max. Temp. 70ºC Motor protection IP 54
∆ pst min. - Connection ∆ pst min. - Connection

4
12/12-6

Vari-Airbox 12/12 6 - 5 speed


Voltage V 230 Frequency Hz 50
Power kW 0,44 Intensity A 2,0
Speed rpm 1050 Condenser 8µF
Max. Temp. 50ºC Motor protection IP 54
∆ pst min. - Connection

Dimensions

Model A B C D E
Vari-Airbox 7/7 424 464 424 208 230
Vari-Airbox 7/9 424 464 424 208 299
Vari-Airbox 9/9 539 594 539 261 299
Vari-Airbox 10/10 634 634 634 291 330
Vari-Airbox 1212 764 764 764 341 396

5
Operating control and regulation

5 speed Standard controller.


This controller provides a 5-stage speed regulation by
voltage modulation totally interference free, motor
noises and vibrations free.
All connections, both the input and the control, are
placed outside the equipment.
For a simple connection free of errors, between the
controller and the equipment there is used a
telephonic type cable with connectors RJ45, what
reduces sensibly the installation time.
The digital communication with the controller
increases the protection against interferences and
allows long distances (till 300m) between the
controller and the equipments.
With a single controller there can be commanded till
12 different equipment placed in series.
Standard controller functions
External ON/OFF: Contact normally open and power
free that permit to turn on and off the equipment
through any external device, timer, PLC or centralized
management system.
Memory: It optionally preserves the order of the
selected speed in case of voltage shutdown.

Manual/Automatic Controller
It allows the standard manual or automatic operation.
The automatic controller permits to set a different
speed through an open free potential contact placed
inside the controller.
This way we can modify the operating of the
equipment according to the state of any type of
connector, sensor, pressure switch or any other
device.
Switch: Permits to open or close any device or
accessory connected to the equipment from a switch
placed in the controller. We can control the electro-
valve, turn on and off batteries, air shutters, etc…

6
Operating control and regulation

Electrical heating 5 speed controller


Besides the standard controller functions, It allows to
regulate the heating in 3 stages.
There can be limited the power of the heating stages
according to the fan’s speed. (Air-flow).

Interface box to a centralized controller


The CT-PLC-NE interface connects the digital
controller of the equipment to a centralized digital
management
DDC, PLC, BMS, etc. type.
With the direct programming we can control all the
equipment functions.

7
Conca de Barberà 6 – Pla de la Bruguera
08211 – CASTELLAR DEL VALLÈS (Spain)
Tel.: +34 93 7159988 Fax +34 93 7159989
e-mail:airtecnics@airtecnics.com
http://www.airtecnics.com