Professional Documents
Culture Documents
Experiment No-1.
Aim of the Experiment: To Study the static V-I characteristics of SCR.
Apparatus Required: 1. Static characteristic SCR Module.
2. Multi meters - 3 numbers.
3. Patch Chords.
Circuit Diagram:
When cathode is more positive with respect to anode with switch S open, then
SCR is told to be in reverse blocking mode.
In this mode, junction J1 & J3 are reverse biased & junction J2 is forward biased.
When reverse voltage is more than a critical value known as V BR, then J1 & J3
junction will be forced fully breakdown & a huge amount of current flow. So high power
loss in SCR occurs & heat will generate which will damage the SCR. Hence reverse
voltage < VBR.
In this mode anode is made positive with respect to cathode with switch S open.
In this mode, junction J1 & J3 are forward biased & junction J2 is reverse biased.
When forward voltage increases then at certain voltage VBO, J2 junction will
breakdown & conduction takes place.
When Va < VBO, the SCR offers high impedance & acts as open circuit.
Forward Conduction Mode:
When gate pulse is applied then SCR conducts at certain voltage less than V BO &
gate current (Ig) is inversely proportional to VBO.
Voltage drop across SCR is very small & SCR offers low impedance i.e. short
circuit.
VAK
IA(amp)
Result Analysis:
1.
2.
3.
4.
5.
Questions:
1.
2.
3.
4.
5.
6.
Circuit Diagrams:
B2
Eta-point
RB2
Eta-point
p-type
RB1
n-type
RB2
B2
Ve
VBB
RB1
Ie
VBB
-
B1
B1
(a)
(b)
B1
(c)
VBB RB1
RB1
VBB
RB1 RB 2
RB1 RB 2
is intrinsic stand-off ratio of UJT and ranges between 0.51 and 0.82. Resistor RB 2 is
between 5 to 10K.
Operation:
When voltage VBB is applied between emitter E with base 1 B1 as reference and the
emitter voltage VE is less than VD VBE the UJT does not conduct. VD VBB is
V
Cutoff e
region
VBB
Vp
Saturation
region
R load line
Peak Point
Valley Point
Vv
0 Ip
Iv
Ie
Resistance triggering:
LOAD
R1
R2
vS=Vmsint
VT
Vg
Vm
I gm , where I gm is the maximum or peak gate
R1
Vm
.Also with R2 0 , we need to ensure that the
I gm
Vm R
R1 R
Vgm R1 Vgm R Vm R
Vgm R1 R Vm Vgm
R
Vgm R1
Vm Vgm
Operation:
Case 1: Vgp Vgt
Vgp , the peak gate voltage is less then Vgt since R2 is very large. Therefore, current I
flowing through the gate is very small. SCR will not turn on and therefore the load
(since Vgp reaches its peak at 900 only). The waveforms shows that the load voltage is
zero till 900 and the voltage across the SCR is the same as input voltage till it is triggered
at 900 .
Case 3: Vgp Vgt , R2 small value.
The triggering value Vgt is reached much earlier than 900 . Hence the SCR turns on earlier
than VS reaches its peak value. The waveforms as shown with respect to Vs Vm sin t .
At
Therefore
sin 1
But
Vgp
Therefore
sin 1
Vgt
V
gp
Vm R
R1 R2 R
Vgt R1 R2 R
Vm R
vO
LOAD
D2
vS=Vmsint
VC
VT
-
D1
10
vs
Case 2: R Small
-/2 0
-/2 0
0
a
vo
vc
Vmsint
Vgt
vs
V gt
vc
vo
t
vT
vc
Vm
vc
Vm
t
vT
Vm
-Vm
-Vm
DESIGN EQUATION From the circuit VC Vgt Vd1 . Considering the source voltage and
the gate circuit, we can write vs I gt R VC . SCR fires when vs I gt R VC that is
vS I g R Vgt Vd1 . Therefore R
vs Vgt Vd1
I gt
T
that is maximum firing angle for power frequencies is empirically gives as RC 1.3 .
2
11
12
Measured Vload
Calculated Vload
Result Analysis:
1. Check how the firing angle in each triggering is controlled.
2. Trace load voltage, thyristor voltage and gate-cathode voltage in each triggering
case.
3. Check whether for same firing angle for each triggering circuit load voltage
changes or not.
4. Check in which triggering gate loss is minimum.
Questions:
1.
2.
3.
4.
5.
6.
13
Circuit Diagram:
14
Theory:
15
16
(
)
) , X = wL.
. Where
output
(
voltage
Vor
)
17
Firing
angle
Calculated Avg
output Voltage
Measured Avg
output Voltage
%error
Result Analysis:
1. Verify that the Avg output voltage of R-load and R-L with FD is same for all firing
angles.
2. Verify that the continuity of load current depends on load inductance.
3. Verify that FD improves Avg output voltage for R-L Load.
4. Trace the output voltage, thyristor voltage, load current for different load at a
constant firing angle.
Questions:
1.
2.
3.
4.
5.
6.
7.
18
19
Theory:
Self commutation or load commutation or class A commutation:
In this type of commutation the current through the SCR is reduced below the holding
current value by resonating the load. i.e., the load circuit is so designed that even though
the supply voltage is positive, an oscillating current tends to flow and when the current
through the SCR reaches zero, the device turns off. This is done by including an
inductance and a capacitor in series with the load and keeping the circuit under-damped.
This type of commutation is used in Series Inverter Circuit.
Expression for current
At t 0 , when the SCR turns ON on the
application of gate pulse assume the current
in the circuit is zero and the capacitor
voltage is VC 0 .
Vc(0)
+ -
Load
20
s 2 2
A
Taking
i t
inverse
e
Laplace
C
L
Current i
inverse
0
sin t
/2
2V
Capacitor voltage
t
2
1
R
2L LC
That is
Gate pulse
V
t
sin
But
L
LC
1
LC
t
V
V
t
C
t
Therefore i
LC sin
V
sin
L
L
LC
LC
Current commutation:
Mode-1:
&
).
Capacitor again recharged to opposite polarity with -VS. The moment capacitor
is recharged to opposite polarity the auxiliary thyristor will turn off.
PE-LAB Manual of Department Of Electrical Engineering
21
Mode-2:
Now the capacitor voltage forward bias the diode D2 and IC flows through the
path C-L-D2-Tm-C.
V0 = VS + VTm.
This capacitor current opposes the thyristor current.
When the capacitor current value becomes equal to thyristor current main
thyristor will turn off.
Unless Tm is not turn off D1 cant conduct as voltage drop across Tm reverse bias
the D1.
The moment Tm will turn off IC flows through the path C-L-D2-D1-C and load
current through the path VS-C-L-load-VS. ID1 = IC I0. V0 = VS + VD1.
When capacitor current decreases to I0 then ID1 becomes 0. And D1 will off.
Then I0 = IC till capacitor is not recharged to original polarity.
The moment capacitor charges to original polarity up to VS. IC = 0 and I0 will
circulate through FD.V0 = 0.
V0 fluctuation is almost negligible.
Design:
(
(
)
(
)
22
Complementary-commutation: In complementary
commutation the current can be transferred between
two loads. Two SCRs are used and firing of one
SCR turns off the other. The circuit is shown in
figure 3.31.
IL
R1
R2
ab
iC
C
T1
T2
23
Where V f is the final voltage, Vi is the initial voltage and is the time constant.
At t tc , vc t 0 ,
0 V 2Ve
tc
R1C
R1C , V f V , Vi V ,
tc
R1C
tc
R1C
ln 0.5
tc
R1C
Therefore 0 V V V e .
tc
. tc 0.693R1C .
R1C
T1 . Similarly when T2 is
commutated tc 0.693R2C
And this time should be greater than t q of T2 . Usually R1 R2 R .
Voltage / Auxiliary-commutation:
24
25
26
1.
2.
3.
4.
5.
6.
Experiment No-5:
Aim of the Experiment:
To trace the output voltage waveform of Three Phase full wave fully
controlled and semi controlled converter with R, R-L, R-L-E Load with & without FD.
Apparatus Required:
CRO & CRO Probe.
3-Phase Converter module.
50/5A Rheostat.
120mH/4A Inductive load.
Patch cords.
Multimeter.
Circuit
Diagram:
Theory:
It consists of 6 SCRs.
The odd number SCRs are positive group SCRs, even number SCRs are negative group
SCRs,
The difference between each arm SCR is 3.
Supply is given through transformer to provide isolation.
There are 3-arms, each arm consists of two SCRs.
T1, T3 and T5 are called positive group SCRs. T2, T4 and T6 are called negative group
SCRs.
Each arm SCR should be fired after 1800 from each other.
PE-LAB Manual of Department Of Electrical Engineering
27
(900 + ) < wt < (1500 + ) ---- T1 & T2 are conducting. The load current flows through
the path a-T1-load-T2-c.
(
(1500 + ) < wt < (2100 + ) ---T3 & T2 are conducting. The load current flows through
the path b-T3-load-T2-c.
(
(2100 + ) < wt < (2700 + ) ---T3 & T4 are conducting. The load current flows through
the path b-T3-load-T4-a.
(
(2700 + ) < wt < (3300 + ) ---T5 & T4 are conducting. The load current flows through
the path c-T5-load-T4-a.
(
(3300 + ) < wt < 3900 + ) ---T5 & T6 are conducting. The load current flows through the
path c-T3-load-T4-b.
(
) (
28
( )
( )
Procedure:
1.
Connect as per the circuit diagram.
2.
Connect the converter power circuit as shown in figure.
3.
Connect resistive load (lamp-load) across the output terminals of the power circuit.
4.
Keep the MCB in off position.
5.
In control unit side, one firing angle pot is provided. Keep it in minimum position.
6.
Connect the firing pulses terminals to gate-cathode terminals of respective SCRs.
7.
After connection over, give the3-phase supply to the power circuit through the auto
transformer and keep it in minimum position. Then switch on the MCB.
8.
Observe the output and thyristor wave forms on CRO by giving a supply voltage
for different firing. And also trace those waveforms.
9.
Measure the average output voltage and also calculate the average output voltage
and find the error.
29
Average Vo in
volt(Measured)
Average Vo in
volt(calculated)
Calculation:
Calculation should be done using this formula
Average load voltage is:
) (
Result Analysis:
Check the firing gap of the thyristors, trace the wave forms of thyristor voltage , load
voltage .
Questions:
1. In 3-phase full converter, what is the interval of firing the three SCRs Pertaining to
one group?
o
2. In a 3-phase semi-converter, for firing angle less than or equal to 60 , what is the
conduction angle of each diode & thyristors.
0
0
3. In a 3-phase semi-converter how many output pulses exit for >=60 & <60 .
4. In 3-phase full converter output voltage ripple reduces or increases in comparison
to 1-phse .
0
5. For >=90 what is the average output voltage for R-L load.
30
Theory:
Jones Chopper:
Jones chopper is one kind of voltagecommutated chopper.
Some times in voltage commutated
chopper capacitor does not get
sufficient energy from L to turn-off the
Tm. So commutation failure occurs.
To avoid this type of commutation
failure we have to use coupled coil
instead of single coil.
31
o VC =
(
o Thyristor current is ITm = I0 + IC.
Since load current always flowing through L2 and induces an e.m.f in L1. So the
capacitor recharges to a potential (Vc + E)>Vs with lower plate positive. Where E=
induced e.m.f.
The moment capacitor recharged to opposite polarity IC = 0, VC = -(VS+E), ITm =
I0 .
When auxiliary thyristor is fired the capacitor voltage reverse bias the Tm and turn
it off.
Then capacitor discharges through the path C-Ta-L2-load-Vs and again recharge to
original polarity.
Advantages:
We can use higher voltage and lower mF capacitors because the trapped energy in
the inductor L2 can be forced in to the commutating capacitor C rather than simply
charging the capacitor by supply voltage.
On time and off time can be varied individually. So there will be greater flexibility
in control.
Procedure:
1. Switch on the power ON/OFF switch.
2. Power on the switch SW1.
3. Power on the switch SW2.
4. Change the duty cycle keeping frequency constant and measured the average
output voltage of output.
5. Change the frequency keeping duty cycle constant and measured the average
output voltage of output.
PE-LAB Manual of Department Of Electrical Engineering
32
Frequency
Duty Cycle
Measured
Vo
Calculated
Vo
%error
Calculation:
Average load voltage
(for R and R-L load)
T = Ton + Toff.
To calculate the Ton time we have to take the period from the instant load voltage equal
to the source voltage and end at the instant the load voltage is 33% of the peak value.
Result Analysis:
Trace the thyristor and load voltages and capacitor voltage, check the peak value of load
voltage, also verify that it is a modified voltage commutation circuit. Find the circuit
turns off time of each SCR
Questions:
1.
2.
3.
4.
5.
6.
33
Theory:
Series inverter:
Since the commutating components are permanently
connected in series with the load so these inverters are
known as series inverter. The circuit should be underdamped in nature. As current attains zero value due to
PE-LAB Manual of Department Of Electrical Engineering
34
35
Tabulation:
SL NO
Output frequency
36
37
Cycloconverter Module.
CRO & CRO Probe.
Patch Chords.
Circuit Diagram:
Theory:
Output frequency is less than the input frequency. Forced commutation is not required. It
requires only natural commutation. Midpoint Transformer is in the ratio 1:1:1. P 1, P2 are
positive group thyristors because they can only operate when supply is positive. Similarly
N1, N2 are negative group thyristors because they can only operate when supply is
negative.
PE-LAB Manual of Department Of Electrical Engineering
38
Operating
thyristor.
P1
Output
voltage Vo
Vs
Period.
Operating
thyristor.
N2
(4 + )to(5 +
)
( + )to(2 +
P2
-Vs
(5 + )to(6 +
N1
)
)
(2 + )to(3 +
P1
Vs
(6 + )to(7 +
N2
)
)
(3 + )to(4 +
P2
-Vs
(7 + )to(8 +
N1
)
)
For discontinuous mode operation the firing scheme is given in the table:
Period.
Operating
thyristor.
Output
voltage Vo
Period.
to
P1
Vs
to ( + )
none
( + )to( +
+ )
( + +
)to(2 + )
(2 + )to(2 +
+ )
(2 + +
)to(3 + )
P2
-Vs
none
P1
Vs
none
(4 + )to(4 +
+ )
(4 + + )to(5
+ )
(5 + )to(5 +
+ )
(5 + + )to(6
+ )
(6 + )to(6 +
+ )
(6 + + )to(7
+ )
Output
voltage Vo
-Vs
Vs
-Vs
Vs
Operatin
g
thyristor.
N2
Output
voltage Vo
none
N1
Vs
none
N2
-Vs
none
-Vs
39
P2
-Vs
none
(7 + )to(7 +
+ )
(7 + + )to(8
+ )
N1
Vs
none
Tabulation:
Firing angle
Output
Frequency
Measured
voltage
Calculated
voltage
% error
Result Analysis:
Trace the load voltage, thyristor voltage. Check whether the rms value of output changes
with frequency change or not for a particular firing angle.
Questions:
1.
2.
3.
4.
5.
40
Circuit Diagram:
41
Assumptions:
1. Each switch is considered
as ideal switch.
2. Load is star connected.
3. IGBTs are preferred for
switches.
Each switch conducts for 1800.
There is 1800 firing gap between the arm switches.
42
between S1, S3 and S5 is 1200. Similarly the firing gap between negative group switches
S2, S4 and S6 is 1200.
(0 < wt < 600):
S1, S6 and S5 are conducting. Load current flows through the path VsS1-a-R-n-R-b- S6-Vs and also along the path Vs- S5-c-R-n-R-b- S6-Vs.
43
.
(1200 < wt < 1800):
S1, S3 and S2 are conducting. Load current flows through the path VsS1-a-R-n-R-c- S2-Vs and also along the path Vs- S3-b-R-n-R-c- S2Vs.
.
(180 < wt < 240 ):
0
S3, S4 and S2 are conducting. Load current flows through the path VsS3-b-R-n-R-a- S4-Vs and also along the path Vs- S3-b-R-n-R-c- S2-Vs.
.
(2400 < wt < 3000):
S4, S3 and S5 are conducting. Load current flows through the path
Vs- S3-b-R-n-R-a-S4-Vs and also along the path Vs- S5-c-R-n-R-aS4-Vs.
PE-LAB Manual of Department Of Electrical Engineering
44
.
0
.
The rms value of phase voltage is given by:
Assumptions:
4. Each switch is considered
as ideal switch.
5. Load is star connected.
6. IGBTs are preferred for
switches.
PE-LAB Manual of Department Of Electrical Engineering
45
46
.
(2400 < wt < 3000):
S4 and S5 are conducting. Load current flows through the path Vs- S5-cR-n-R-a- S4-Vs.
.
(3000 < wt < 3600):
47
Procedure:
1.
2.
3.
4.
5.
6.
Result Analysis:
Trace the load phase and line voltages, trace the phase currents, measure the voltages and
compare with calculated values and verify the line voltage in 180 0 is more than 1200
mode.
Questions:
1.
2.
3.
4.
5.
6.
48
Circuit Diagram:
Theory:
49
As it can conduct in both direction the terms A & K are not applicable to
TRIAC. Its three terminals are MT1 (Main terminal 1), MT2 (Main terminal 2)
& Gate.
When a +ve gate voltage w.r.t MT1 is applied in ve half it conducts from MT1
to MT2.
When a +ve gate voltage w.r.t MT2 (or -ve voltage w.r.t MT1) is applied in -ve
half it conducts from MT1 to MT2.
50
Measured load
voltage
Calculated load
voltage
% error
Result Analysis:
Trace the load voltage, TRIAC voltage, for both R and R-L load and observe that in R-L
load the output voltage is not regulated till the firing angle is greater than power factor
angle. Measure the voltages and compare with calculated values.
Questions:
1.
2.
3.
4.
5.
51