Professional Documents
Culture Documents
(,i
If . I v m
G U I D E L
I N
E S
Mft"
FOR H L X H N I N G
AND
i^fl'-
n n EI i ( A i
RESEARCH
LABORATORY
FACILITIES i
The American Institute of Architects
Center for Advanced Technology Facilities Design
2 mm%
TECHNPLOGfC^kCHALLENGE
G U I D E L I N E S
FOR
PL A N N I N G
AND
o F
IBIOMEDICAU
(RESEARCH
LABORATORY
iFACILITIES
The American Institute of Architects
Center for Advanced Technology Facilities Design
TABLE OF CONTENTS
PREFACE
ACKNOWLEDGMENTS
INTRODUCTION
vii
viii
xi
1
1
2
3
4
4
4
4
5
5
6
11
11
12
13
13
14
15
17
19
19
19
20
20
20
20
21
21
21
21
22
22
22
23
23
23
24
SPACE DESCRIPTIONS
B.l Laboratories
B.2 Wet Laboratories
B.2.1 Biochemistry/Pathology
B.2.2 Molecular Biology
B.2.3 Cell Biology
B.2.4 Organic Chemistry
B.2.5 Physical Chemistry
B.3 Dry Laboratories
B.3.1 Electrophysiology/Biophysics
B.3.2 Electron Microscope
B.3.3 Laser
B.3.4 Magnetic Resonance Imaging (MRI)
B.3.5 X-Ray Crystallography...
B.3.6 Mass Spectrometry (MS)
B.4 Laboratory Support
B.4.1 Autoclave Room
B.4.2 Glasswash
DESIGN CRITERIA
C.l Equivalent Linear Measurement (ELM)
C.2 Area Allowances
C.3 The Laboratory Module
C.4 Laboratory Furniture and Equipment
C.4.1 Casework
C.4.2 Chemical Fume Hoods and Biological Safety Cabinets
C.4.3 Equipment
C.5 Architectural Finishes and Materials
C.5.1 Floors
C.5.2 Walls
C.5.3 Ceilings
C.5.4 Windows and Window Treatment
C.5.5 Doors
C.6 Structural
C.6.1 Vibration
C.6.2 Module/Bay Size
C.6.3 Floor Slab Depressions
C.6.4 Equipment Pathway
24
25
25
25
26
26
26
27
27
27
27
27
28
28
28
28
28
29
29
29
29
30
30
30
31
31
31
32
32
32
32
33
34
34
34
35
35
35
35
35
36
37
37
37
37
38
38
39
39
41
41
41
42
43
44
44
45
45
45
46
47
47
47
47
48
48
48
48
49
49
49
49
50
50
50
50
51
53
57
57
60
61
61
63
65
VI
66
66
61
61
69
69
70
70
71
71
73
75
77
78
81
A-l
PREFACE
This document is the first publication by the American Institute of Architects (AIA) of
material developed to assist with the tasks of planning and designing biomedical research laboratories. The decision to develop the document was based on the recognition that biomedical research is rapidly becoming more complex and far reaching, and
that facilities designed to support work in the life sciences must themselves be correspondingly more sophisticated to meet research requirements today and tomorrow.
The original basis for this document was the set of design guidelines for biomedical
research facilities that was developed by the National Institutes of Health (NIH). The
NIH material has been amended by a multidisciplinary task group charged with creating a more broadly generic and updated set of guidelines that are not specific to one
type of public or private sector biomedical research. These guidelines should therefore be viewed as an introductory point of entry into a complicated subject. It is anticipated that this first edition will be steadily expanded and refined in an open, public
review and comment process conducted at periodic intervals in the future.
vii
ACKNOWLEDGMENTS
The American Institute of Architects (AIA) has been privileged to work with a
multidisciplinary task group of distinguished and dedicated experts involved in biomedical research laboratory facilities as researchers, facilities designers, and constructors, representatives of professional organizations and public agencies.
These experts were convened as a formal task group and they devoted many hours of
concentrated work during 1997-98 to represent the latest and best thinking about biomedical research from the viewpoints of their respective fields. Their deliberations
began with a thorough review of earlier guidelines that were developed specifically for
the National Institues of Health (NIH), and that the NIH generously made available to
the AIA in a modified form as a starting point for this document. The process benefited
further from the thoughts of numerous others, including Mr. Robert Guy, AIA, of Earl
Walls Associates, and Mr. Lloyd Siegel, FAIA, Director of the Facilities Quality Office, Department of Veterans Affairs, Washington, D.C. Every effort was made to craft
guidelines language that expressed a balanced and broad-based consensus.
Executive Committee
Frank Battistello
Branch Chief
Research Facilities Branch
National Cancer Institute
Bethesda, MD
Janet Baum, AIA
Principal
Health Education +
Research Associates, Inc.
St. Louis, MO
William R. Brader, PE
Principal
Kling Lindquist
Philadelphia, PA
Alfred Ferruggiaro
Senior Industrial Hygienist and
Acting Chief
Technical Assistance Section,
Division of Safety
National Institutes of Health
Bethesda, MD
viii
Daniel L. Hightower, RA
Associate Director
Management Control and Policy Office
Division of Engineering Services
National Institutes of Health
Bethesda, MD
Todd S. Phillips, Ph.D., AIA
Director
Center for Advanced Technology
Facilities Design
American Institute of Architects
Washington, DC
P. Richard Rittelmann, FAIA
Executive Vice President
Burt Hill Kosar Rittelmann Associates
Butler, PA
James Mulshine, MD
Head
Intervention Section
Medicine Branch
National Cancer Institute
Rockville, MD
John Pallas
Manager of Engineering
National Cancer Institute
Frederick Cancer Research
Development Center
Frederick, MD
Leo A. Phelan
Director
Standards Service
Office of Facilities Management
Department of Veterans Affairs
Washington, DC
David Westreich
Vice President
Gilbane Building Company
Laurel, MD
Joseph J. Wisnewski, FAIA
Wisnewski Blair & Associates
Alexandria, VA
Special thanks are due to Daniel L. Hightower, RA, of the NIH for his initiative in
making it possible for the AIA to work in concert with NIH experts and others to
undertake the development of this document. The initial task of converting NIH guidelines material into a basic manuscript that could serve as the starting point for this
document was conducted by the following key persons at the NIH:
Frank Battistello
Terry Christensen, PE
Charles Coulter, Ph.D.
Rassa Davoodpour
Alfred Ferruggiaro, CIH
Ricardo Herring, AIA
Daniel Hightower, RA
Jean Khoshbin, RA
Thomas Ligis
Dr. Farhad Memarzadah, PE
James Mulshine, MD
John Pavlides, PE
Judit Quasney, RA
Cyrena Simons
Thanks are owed as well to the many persons who are responsible for the NIH Design
Policy and GuidelinesResearch Laboratories:
Dave Berry
Joseph M. Bladen
Charles E. Blumberg, FIIDA
Martin D. Borenstein
Nancy Boyd
Benjamin Buck, PE
Christine M. Campbell, PE
James Carscadden, PE
Dr. Alan L. Chedester
Terry L. Christensen, PE
Rassa Davoodpour
Mehryar Ebrahimi, PE
David H. Epley, PE
Alfred J. Ferruggiaro, CIH
Shawn Googins
Paul Hawver
Ricardo C. Herring, AIA
John K. Hollingsworth
Herbert B. Jacobi
Frankie R. Kelly
Jean Khoshbin, RA
Byung Kim
Louis Klepitch
Frank M. Kutlak, RA
Dr. RandolfLarsen
James S. Lewis, PE
Thomas Ligis
Kristy Long, RA
Johnny Madlangbayan
Athanasia Mantzouranis, PE
Phillip Marcus
John McCabe, PE
Dr. Farhad Memarzadeh, PE
Mark F.Miller
Rand M. Mortimer
Nga Nguyen
Albert Parrish
Arvind Patel
Daryl E. Paunil, PE
John Pavlides, PE
Edward A. Pfister
Leon F. Pheder, PE
Judit A. Quasney, RA
Solange Rangel, RA
Shahriar Saleh
Donald A. Sebastian, RA
Cyrena G. Simons
William Strine
Peter W. Sweeney
Dr. James F. Taylor
Esmail Torkashvan, PE.
Gary Zackowitz, RA
INTRODUCTION
General
The puipose of this document is to provide information to the design and research
communities on the planning and design of biomedical research laboratories. These
guidelines reflect the judgment of a multidisciplinary group of experts in research
laboratory design and operation. They encompass the majority of current best practices today, but they are neither universal solutions nor detailed enough to answer
every question that may arise in the course of a specific planning and design project.
It is not the intent of this document to specify construction techniques, to prescribe
facilities quality or cost criteria, or to serve as code requirements. The intent instead is
to identify issues and approaches that deserve careful thought when undertaking biomedical research facilities projects. Such facilities are complex and require these special and specific design considerations.
As highly changeable environments, biomedical research laboratories and their support spaces must be flexible and able to readily accommodate a wide range of current
and future requirements and hazards. To achieve satisfactory results from the planning
and design, it is important that the project owner supply for each project a functional
program for the facility that describes the purpose of the project, the projected demand
or utilization, staffing patterns, departmental relationships, space requirements, and
other basic information relating to fulfillment of the organization's objectives. This
program may include a description of each function or service; the operational space
required for each function; the number of staff or other occupants of the various spaces;
the equipment required in each space; the numbers, types, and areas (in net square
meters) of all spaces; the special design features; the systems of operation; and the
interrelationships of various functions and spaces.
The functional program should also include a description of those services necessary
for the complete operation of the facility, and it should address future expansion of
essential services that may be needed to accommodate increased demand for technological change. The approved functional program shall be made available for use by
all members of the design team in the development of project design and construction
documents.
A total "environmental approach," including attention to site, structure, massing, circulation, visual harmony, open areas, existing conditions, and construction logistics, as
well as operational sustainability, is the most effective strategy when planning biomedical research facilities. A design approach that responds to these specific issues will
serve to create a product that is functional, aesthetic, flexible, and reliable. Design professionals must consider all these criteria to meet the needs that are identified by users,
dictated by functional relationships, and imposed by specific existing conditions.
xi
It is extremely important to recognize that the end users (researchers, facility managers, administrators, etc.) are integral parts of this process, and their involvement is
essential to the project success from the outset. The most effective method by which
to integrate scientific, administrative, and facility requirements is through a "partnership" interaction whereby design professionals and end users share a clearly defined
goal. Accomplishing such a shared vision through the entire design, construction, and
operations process ensures the operational functionality, sustainability, and reliability
of these sophisticated facilities.
A hazard assessment must be conducted for each investigative and research function.
The assessment becomes a critical determining factor in design and throughout the
full life cycle of the facility. A main purpose of these guidelines is to assist in the
design of "safe space" to support research.
In response to this purpose, all laboratories are assumed in design to contain chemical,
radiological, and biological hazards, since all of these scientific activities may occur
within the space during its life cycle. Containment devices and researcher procedures
are used in concert with the facility to manage these hazards. Architectural and engineering features are also essential to maintain proper safety for workers and visitors.
Every research facility shall provide and maintain a safe environment for personnel
and the public. When chemical fume hoods are required, even to handle small quantities of hazardous material, then the laboratory space must have air pressure negative in
relation to adjacent egress and circulation corridors. In addition, the exhaust system
requires redundancy to establish reliable containment. Radioisotopes, usually used
only in trace amounts, must be secured and shielded. Biohazards are assumed to be at
Biosafety Level 2.
xii
having primary responsibility for resolution should be consulted as early in the design
process as possible.
These guidelines assume that the design professionals who are selected for biomedical research facilities projects are knowledgeable about the attributes of these facilities. It is the design professionals' responsibility to comply with established codes,
regulations, and current practices. These guidelines do not relieve design professionals of such responsibilities. Rather, they are intended to supplement the design process
by offering consolidated practical knowledge and experience based on commonly accepted operational sustainability and safety practices. By incorporating such knowledge, greater consistency,flexibility,reliability, and safety within biomedical research
facilities can be achieved.
Facilities shall be designed to meet the requirements of applicable building codes,
including the most current editions of the following:
Insofar as practical, these guidelines have been established to obtain a desired performance result. Limitations, when given, such as dimensions or quantities, describe a
condition that is commonly recognized as a practical standard for normal operation.
In all cases where specific limits are described, equivalent solutions will be acceptable
if the authority having jurisdiction approves them. Nothing in this document shall be
construed as restricting innovations that provide an equivalent level of performance
with these guidelines in a manner other than that which is prescribed by this document, provided that no other safety element or system is compromised in order to
establish equivalency.
Metric standards of measurement are the norm for most international commerce and
are being used increasingly in the United States. Where measurements are a part of
this document, "hard" metric units are given as the basic standard, with "hard" English units in parentheses. It should be noted that these units are not usually arithmetically equivalent.
Various codes and standards have been referenced in whole or in part in sections of
this document. Care must be taken to use current editions of the applicable codes and
standards as accepted by the regulating authorities.
xiii
a.
The intent of these guidelines is to provide the designer with information that
will yield state-of-the-art biomedical research facilities either by constructing new
facilities or by renovating older facilities to meet ever-changing biomedical research
needs. It is essential that the end users of the research laboratory be involved during
the programming and design stages to meet the various specific needs of the laboratory occupants. The following goals and objectives define the recommended considerations necessary to maintain proper functionality of the facility as well as good
productivity of the end user. For specific requirements see section C, Design Criteria.
b.
In planning and designing laboratory facilities, the designer needs to fully
analyze and understand the unique organizational and operating culture of the client,
including spatial relationships, flexibility, efficiency, security, and other requirements.
What works for one client is not necessarily applicable to all clients. Client organizational and operational cultures will vary widely; thus, the laboratory space diagrams
provided in this document must be considered in that light.
'',
e.
Where possible, laboratory staff shall be provided with low bench
desk space that is physically separated from the laboratory bench. This work
space shall be outside yet could be adjoining the laboratory. The reasons for
separating the office work space from the lab are to remove the occupant
from any potential hazards within the lab, to facilitate compliance with good
laboratory practice, and to realize possible cost reductions. In doing so, however, it is important to provide for a good visual connection into the lab.
strumentation as required to meet ever-changing needs without compromising laboratory health and safety.
e.
Expansion: In the context of master planning, future expansion is
an important consideration in laboratory facilities. State-of-the-art research
institutions must be designed to accommodate expansion. Establishing a
framework for building systems that can be easily expanded and be consistent with the local master plan is essential.
Quality of Life
Quality of life in laboratories is a major concern of the occupants. Researchers stated in a survey conducted by the National Institutes of Health, Division of Engineering Services, that views to the outdoors, both from their
laboratories and offices, are highly desirable. The laboratory should be designed for people, providing them with a pleasant work environment that
leads to increased productivity. Introduction of natural light into laboratories, giving researchers some visual relief, is an important element in creating a comfortable work environment. Adequate work space, color, a coordinated and well-organized layout, and attractive casework are some of the
design features that will enhance the quality of life. The use of visually interesting features such as natural material, art work, etc., and amenities such
as exercise facilities, bank teller machines, etc., that can help to attract and
retain scientific staff is highly desirable.
a.
Natural Light and Visual Relief: Introduction of natural light into
laboratories by allowing researchers the opportunity for visual relief is an
important element in creating a comfortable work environment. This presents design challenges with significant planning and functional implications in large, multifloor facilities.
Where possible, and unless in conflict with functional requirements, laboratories should be located in such as way as to optimize natural day lighting.
Laboratories utilizing photographic and optical diagnostic techniques must
have blackout capability. Natural light is less important in laboratory support areas because occupancy is more intermittent than in the labs.
b.
Lighting: Laboratory research requires high-quality lighting for close
work, both in terms of brightness and uniformity. Fixtures should be positioned to provide shadow-free illumination of the laboratory work bench.
Consideration should be given to control of glare, brightness contrast ratios,
accurate color rendition, and task lighting at the bench.
c.
Interaction Areas: These should be dedicated, neutral spaces specifically designed to encourage staff to encounter one another and promote
A.3.1
Noise
Noise is a critical factor in determining the quality of the work
environment. Noise levels in laboratories are difficult to control
because room finishes are often non-sound absorbent. Equipment
such as chemical fume hoods, centrifuges, and vacuum pumps
contributes to the high noise levels within the laboratory. Consideration should be given to minimizing the total impact of noisy
equipment or other noise generators. Planning should isolate
noise-sensitive areas from noise sources wherever possible.
A.3.2
Wayfinding
Graphics and signage will help employees and visitors find their
way through a laboratory building. Directional graphics/signage
shall be functional and integrated with the architecture of the
building.
A.3.3
Artwork
Artwork should be not only in the form of photographs, paintings, etc. It could be designed by using different forms of lighting, color, texture, and materials.
A.3.4
Other Amenities
Consideration during the programming and planning stages should
be given to the inclusion of other amenities such as cafeterias,
lounges, bank machines, credit unions, shower and locker facilities, and child care.
Planning Modules
a.
Many researchers have special laboratory design requirements. One of the initial goals in the design of a laboratory is to
establish an idealized common space denominator capable of
meeting the required variety of research needs while also allowing circulation, service, structural, mechanical/electrical/plumbing (MEP), partition, and laboratory casework systems to be provided as required. The laboratory module is the basic conceptual
facility design building block that provides regularity and repetitiveness of area and services for the building. It must be carefully organized on a modular basis and, to the maximum extent
possible, be free of interruptions such as stairwells, chases, shafts,
shear walls, elevators, and other obstructions.
b.
The planning module must be properly sized so that larger
units can be created by assembling a number of modules. This
permits the rational creation of space and allows, to the extent
possible, the standardization of MEP systems' design and accessibility. Laboratory buildings are usually designed based on a
planning module that is regular and repetitive, such as the unit
shown in Diagram No. 1. These typical modules are shown only
for the purpose of illustrating a modular approach and are not
universally applicable. The identification of modules for both
laboratory and nonlaboratory support functions allows the rational creation and organization of spaces to accommodate the wide
variety of laboratory and support spaces typically found in these
facilities.
X
1/3 MODULE
(
X
SINGLE
MODULE
213 MODULE
Diagram No. 1
c.
The building's structural system, whether existing or new,
must relate to the planning module. Structural columns should
be considered in the module design to minimize impact on function and beams designed to interface with MEP distribution systems. The structural system, in concert with other building systems, should be designed to maximize the building efficiency
given existing conditions and the needs of research. Because of
the sensitive research functions and equipment typically found
in these facilities, laboratory building designs generally include
considerations for the control of vibrations. This topic is discussed
further in the appendix to these guidelines.
A.4.2
yji_w
7s
BORATORlEi
'r
SUPP\>RT
SUPPORT %
SUPPORTJ/p
SUPPORT A
SUPPORT
Tzffimm.
Diagram No. 2
Support very conveniently located relative to laboratories
Very adaptable to partial interstitial space over support areas
Limited office area will work for some institutions but not
others
Fixed relationship of support to laboratory will somewhat limit
future flexibility
LABOR\TORIE^
llENT stORAGd
SERVICE
>IAE CORRIDOR
CORF&I
/
\LABORhoRIEd
Diagram No. 3
Excellent laboratory/support space relationship
Service corridor can run on either side of support area and can serve as
equipment storage area and provide a second exit from all laboratories
Offices can be on separate heating, ventilation, and air conditioning (HVAC)
system and enjoy perimeter wall
Labs sacrifice some natural light because of comdor
Excellent future flexibility
J-U
55
\LABOR\TORIES\
SUPPORT
V.ABOR\TORIES\
Diagram No. 4
\*F
JffC
LABORATORIES^
| ty////M/#//y//y//y//}///y//zm |
\
SUPPORT
2.
SUPPORT
JMBon/jrofflesj
i
I
I
i
Diagram No. 5
Offices and laboratories enjoy perimeter wall
Support space can be utilized for laboratories if desired
Offices conveniently separate from laboratories
Offices can be on separate HVAC system
Corridor would probably have to be a service corridor as well as an access
corridor
]LABOR\TORIE^
i
T
SUPPORT % SUPfORT
mMm.
t*
i | -1
jA
SUffORT )0 SUPPORT]
$ I & i
w/XsKm
FAICES
Diagram No. 6
Support between offices and laboratories
Support central to and well distributed through laboratories
Offices can be on separate HVAC system
Excessive corridor reduces floor efficiency
Typical of teaching institutions. Students can visit offices without entering
laboratory area
Entry to and exit from laboratories somewhat restricted
1
j
! 1
LABOR,
ircw/ESJ.
j
OFFICES
OFFICE
f Y///A
1
OFFICES
///yy//MW//W)y//A
SUP >ORT
1
i
sc
i
OFfjfCES
i
i
1
j
1
|
V//YA
1
j :
i .
1 1
i
Diagram No. 7
Very simple layout
Offices embedded in layout, which makes them expensive
Laboratories and support areas somewhat remote from each other
Offices have no natural light
Laboratories difficult to enter and exit
Used for research laboratories in teaching institutions
Reasonably efficient for large floorplate
Most often used in retrofit for buildings with a narrow floorplate
i
M l
i i
Diagram No. 8
Excellent laboratory/support relationship
Offices spread throughout plan, which makes them expensive
Efficient for a large floorplate but inefficient for a small floorplate
Can be difficult to enter/exit laboratories
Excellent for "laboratory neighborhoods" concept
Diagram No. 9
A.4.3
Security
Laboratory buildings are typically occupied 24 hours per day, and access by
visitors and employees must be delineated and controlled to minimize disruption and maintain security of operations. Zones of security within the
building, at the loading dock, and at dedicated building systems will also be
generally required. Electronic security such as card access and closed-circuit
television may be planned for the facility.
A.4.4
Loading Docks
vice corridor and interstitial space. These diagrams are merely examples of
typical layouts.
A.5.1
Disadvantages
"V^
^r
LABORATORY
LABORATORY
LABORATORY
LABORATORY
LABORATORY
LABORATORY
LABORATORY
LABORATORY
Diagram No. 10
A.5.2
13
Advantages
Relatively short horizontal runs are necessary that require smaller ducts or
pipes
Access to shutoff valves is more convenient and less disruptive than when
located in ceilings
Requires minimal floor-to-floor height in new facilities
Suitable for alterations to existing facilities with low floor-to-floor heights
Disadvantages
Diagram No. 11
A.5.3
Disadvantages
It is difficult to add utilities
Multiple shafts decrease the planning efficiency and raise the
grossing factor
The exterior appearance of the building is strongly influenced
Access for servicing is limited to the common wall between
shaft and building
Piped services are subject to temperature differentials, so insulation of the shaft may be required
Flexibility of planning for future laboratory configurations may
be reduced
Reduces potential window area
L-"WAFT^-J
L-sIS^^-J
L-^-^F?-^
\g^^SHAFT"<J
\e^SH4FT*--J
W-"SHAFT^-^-J
Diagram No. 12
Service Corridors
In this system, laboratory spaces adjoin an accessible and occupiable service corridor that houses horizontal utility spaces above
head height and distributes horizontally into the laboratories via
the ceiling or directly to the lab bench through the wall of the
service corridor. Vertical shafts from mechanical equipment
spaces are required at strategic locations. The service corridor
should be a minimum of 1,500 mm (5' 0") in width, plus any
utility and storage areas. (See Diagram No. 13.)
>
Advantages
Disadvantages
i l l l l l p
///
<yy
Y/y~~^
i 1I I I 1 J
Diagram No. 13
A.5.5
Interstitial Space
Interstitial space is essentially an unobstructed open area with
structural columns placed where they favorably relate to the planning module. Horizontal distribution of utility systems is housed
in an accessible space above the ceiling plane. The services drop
vertically from the interstitial space into the laboratory. Vertical
shafts at the perimeter or in a central core connect the interstitial
space with the entire building. Interstitial space should be carefully designed in zones. The vertical zones consist of the following: structural zone, branch distribution zone (for utilities that
are distributed through the floor, such as waste lines), main distribution zone, branch distribution zone (for utilities that are distributed through the ceiling), and lateral distribution zone. The
horizontal distribution zones consist of the following: electrical/
communications zone, air supply zone, exhaust zone, plumbing
zone, and access zone. (See Diagram No. 14.)
Advantages
The labs enjoy unobstructed floor plan and enhanced adaptability of space
Minimum disruption occurs in the lab during routine maintenance and alterations
Service is available from above or below at any point on the
planning module
The system is generally cost effective over the life of the building
Construction time can be reduced
Allows flexibility in faster, less costly upgrading of laboratories
Disadvantages
17
STRUCTURAL BAY
STRUCTURAL
MECHANICAL
LIGHT FIXTURE
RESEARCH
AREA
LAB MODULE
Diagram No. 14
(This diagram represents only one of many approaches to the design of
interstitial space.)
SPACE DESCRIPTIONS
Laboratories
a.
Laboratory buildings may be designed with generic laboratory space
whereby the future users would adapt the generic laboratory to suit their
requirements by placing equipment and work zones according to their individual needs. Generic laboratory design could be used to accommodate a
variety of biomedical research. With minor adaptations and well-designed
support space, research such as virology, immunology, physiology, cell biology, and clinical research could be accomplished in generic laboratories.
b.
Biomedical laboratories in general are classified as wet or dry. A wet
laboratory requires working with solutions utilizing benches, sinks, etc., with
fully piped services. A dry laboratory involves working with electronics and
large instruments with few piped services; however, more special electrical
services may be required than in wet labs.
c.
Wet Laboratories
Wet laboratories house functions that include working with solutions and
utilize benches, sinks, and chemical fume hoods. Generally, a wet lab is
fitted out with a full range of services: purified water, potable water, lab cold
Space Descriptions
19
and hot water, lab waste/vents, carbon dioxide (C0 2 ), vacuum, compressed
air, eyewash, safety showers, natural gas, telephone, local area network
(LAN), and power.
B.2.1
Biochemistry/Pathology
Equipment generally includes a large number of refrigerators and
freezers (-20C (-4F), -70C (-94F), and -135C (-211F)), and
a large number of centrifuges. Access to chemical fume hoods,
BSCs, and cold rooms is generally required.
B.2.2
Molecular Biology
Equipment generally includes refrigerators and freezers (-20C
(-4F), -70C (-94F)), and bottled liquid nitrogen) and centrifuges. Access to chemical fume hoods, BSCs, bacteriological
incubators, shakers, and darkroom is generally required.
B.2.3
One 120V outlet per 600 mm is required. Dry and liquid chemical and waste storage with radioactive shielding may be required
Cell Biology
Equipment includes refrigerators and freezers. Access to BSCs
with high/low C0 2 incubators, autoclave, cold room, and bottled
liquid nitrogen is required.
B.2.4
Organic Chemistry
A chemical fume hood for each investigator is highly desirable.
Cleanup sinks and acid-resistant waste piping are required.
Areas for storage and distribution of gas cylinders easily accessible to the laboratory through a central or manifolded system
are required.
Standby electric power for critical HVAC systems and containment equipment shall be provided
Piped services may include steam and other gases
Provision should be made for storage and distribution of cylinder gases within the laboratory or from outside the laboratory
Corrosion-resistant waste piping and materials for laboratory
furnishings should be used
Flammable liquid storage is required
Space Descriptions
B.2.5
Physical Chemistry
The quantity and range of services and electrical power distinguish chemistry laboratories. Due to instrumentation, heavy structural loading and high ceiling clearance may be required.
Dry Laboratories
Dry laboratories involve work with electronics and large instruments with few
piped services. These laboratories are analytical laboratories that utilize and house
sophisticated equipment: highly calibrated electronic apparatus in spaces that
require accurate temperature and humidity control, stable structure and vibration control, shielded space, clean power, andfilteredchilled water. These laboratories do not require extensive piped services and built-in casework. Floor
loading and ceiling heights are also a consideration. Access must be planned for
routine maintenance, repair, or calibration of equipment.
B.3.1
Electrophysiology/Biophysics
Laboratories require a large number of electronic racks and very
little fixed bench space.
B.3.2
Electron Microscope
Electron microscope suites may include imaging, a darkroom, a
print darkroom, a graphics layout room, and a sample preparation area with a chemical fume hood. A stable, vibration-free
structure is required. Use of vibration-damping tables, variable
room lighting, and humidity control may also be required.
Note: Air distribution around the microscope column is critical
to equipment performance. Laminar air flow is preferred; other
methods may be used as long as air is not directed toward the
column.
Space Descriptions
21
B.3.3
Laser
The laser suites must be isolated from vibration and be light-tight,
with a sample preparation space and chemical fume hood. Filtered chilled water for lasers and heavy floor loads are also a
consideration. Specialty gases may be needed.
B.3.4
Provision should be made for storage and distribution of cylinder gases within the laboratory or from outside the laboratory
High-voltage electric services may be needed
B.3.5
X-Ray Crystallography
The X-ray crystallography suites must be isolated from vibration
and have light, temperature, and humidity controls. A darkroom,
computer graphic/modeling rooms, a purification and crystal
growing room, tape storage, and computer work areas may be
required for these laboratories.
22
Space Descriptions
B.3.6
B.4
Laboratory Support
Laboratory support space should be on the same planning module as the
laboratory. It shall provide for activities that are not housed directly in the
laboratory but are critical to the efficient operation of the laboratory. This
space is often shared by multiple laboratories. Such areas include autoclave
rooms, constant-temperature rooms, cold rooms, computer rooms, darkrooms,
developing rooms, equipment areas, glasswash, bench support, radioactive
work areas, storage, and tissue culture laboratories.
B.4.1
Autoclave Room
a.
An autoclave is an industrial appliance that uses pressurized steam to sterilize laboratory instruments, glassware, other
Space Descriptions
23
B.4.2
Glasswash
The glasswash provides space for glasswashing, drying appliances, and carts, and has counters on legs, a sink, and overhead
exhaust. All areas in the room shall be thoroughly caulked and
sealed, and have a fixed ceiling, epoxy floors, and cleanable walls
to withstand moisture and prevent pest infestation. Space must
be provided for staging clean and dirty glassware. Utilities include HVAC with supplemental cooling, electricity, cold water,
purified water, DWV, vacuum, telecommunications, and equipment alarm system.
B.4.3
24
Space Descriptions
equipment alarm. Cold rooms that are used for storage only do
not have sinks and require minimal air changes compared with
cold labs.
A warm room is an environmentally controlled prefabricated unit
used for growing cultures at a constant temperature. The warm
room has counters, wire shelves, and sink. Electricity, HVAC,
filtered water, plumbing, and vacuum are required.
B.4.4
Cold room condenser shall be located in a serviceable location without disruption of cold room internal functions
Alarm temperature sensor shall be provided within room
Weather-proof electric outlets and lighting fixtures shall be
provided
B.4.5
Darkroom
This area will have casework, counters, work tables, and sink.
All doors, walls, ceilings, and penetrations must be light-tight.
Utilities include HVAC, electricity, hot/cold and chilled water,
DWV, compressed air, gas, vacuum, spot exhaust, telecommunications, and purified water. Requirements for compressed air, gas,
silver recovery system, and vacuum shall be verified during programming. Darkroom-in-use indicators must be provided outside of this space.
B.4.6
Space Descriptions
25
B.4.7
B.4.8
Radioisotope Laboratory
This area provides space for isolated radiation work. It will have
a dedicated radioisotope fume hood, sink, eyewash, emergency
shower, and flammable solvent storage cabinet. Utilities needed
include HVAC, normal and standby power, vacuum, compressed
air, gas, hot/cold water, DWV, nitrogen, telecommunications, and
purified water.
B.4.9
26
Space Descriptions
Each Class II, type B, BSC shall be hard duct connected to the
laboratory exhaust system through an individual independent
terminal unit
Provision should be made for secure storage of cylinders and
distribution of carbon dioxide gas within the laboratory or from
outside the laboratory
Space Descriptions
27
Offices
Offices should be positioned to achieve close proximity to the
occupant's laboratory work space. Ergonomic furniture should
be used in the office. If feasible, offices will be provided with
natural light. Consideration may be given to clustering offices in
order to have potential for sharing support staff. Storage requirements must be considered for records/files, copiers, and mail areas. The growth of automated procedures within the laboratory
highlights the need for high-bandwidth data connectivity to each
office.
B.5.2
Work Areas
Work areas with computers require HVAC, supplemental cooling, electricity, standby or uninterruptable power, telecommunications/LAN, and space for computer equipment.
B.5.3
Collaboration Areas
a.
Interaction Areas: In addition to scheduled formal meeting rooms, lab buildings need a variety of informal interaction
areas distributed on every floor and every research wing to facilitate connectivity between researchers. These spaces can be
small and may have some accommodations for coffee/tea breaks
and physical relaxation. Convenient locations of interaction areas are critical to their success.
b.
Conference Rooms: Conference rooms should be provided for meetings of the laboratory staff. All conference facilities will be shared. Requirements for each space, such as
whiteboards, audiovisual and projection equipment (35 mm and
overhead), light control, and blackout, as well as telecommunications/LAN capabilities, shall be verified during programming.
B.5.4
Break Rooms
Break rooms shall permit the safe consumption of food and bev-
28
Space Descriptions
B.5.5
B.6.1
Materials Management
For laboratory facilities, the issue of materials management concerns the storage of laboratory materials and supplies and the
handling, storage, and disposal of chemical and biohazardous
waste. Material handling zones should be designed adjacent to
dedicated service elevators for purposes of staging, dispensing,
and disposal of laboratory materials and supplies. Within each
building zone, separate areas for chemical and hazardous waste
storage must be provided that meet Occupational Health and
Safety Administration (OSHA) standards, codes, and other appropriate regulations.
B.6.2
Space Descriptions
29
B.6.3
Materials Handling
Movement of materials from loading dock facilities to multiple
points of use must be carefully considered and evaluated in development of the overall building circulation system. Materials
movement from loading dock to various points of use should be
provided in separate corridors to dedicated service elevators. Once
in the laboratory research areas, materials movement will occur
in common public corridors with limited and controlled movement. Material handling zones should be designed adjacent to
dedicated service elevators for purposes of staging, dispensing,
and disposing of laboratory materials, supplies, and equipment.
B.6.4
B.6.5
Circulation
Circulation shall promote separate flows of people and materials. Vertical circulation must be simple and direct without being
restrictive. Stairways and transition ramps shall be studied at connections between buildings with different floor-to-floor heights.
A freight elevator will be located and sized to handle the transportation of materials from the loading dock to the point of use.
Freight elevators require floor containment to prevent contamination of the elevator shaft in the event of a chemical spill. A
heavy-duty passenger elevator shall be accessible as a backup to
the freight elevator. Both shall be readily accessible to the loading dock.
30 Space Descriptions
DESIGN CRITERIA
The following paragraphs describe the architectural and engineering design criteria
that are important in planning a laboratory building.
Desk Space
Lab Support
b.
These values are only guidelines and are not absolute. Specific user
programming is required to verify actual requirements.
c.
Current trends in laboratory design are toward the use of a volumetric measure rather than linear measures for work space. This trend derives
from the use of stacked instrumentation.
Design Criteria 31
Casework
a.
Choice of casework system directly relates to the function and the budget assigned for the laboratory. Fixed casework
shall be sealed to walls and floors during installation. Racked
equipment, mobile casework on "wheels," or other options which
minimize costs and maximize flexibility shall be considered due
to the tremendous changes in research requirements. Wherever
possible, casework should be designed such that plumbing services can be installed prior to casework installation utilizing
wall-mounted racks or other means.
b.
Countertops materials will vary depending upon usage of
the laboratory. Typically, chemical-resistant plastic laminates will
be used. Epoxy resin will apply for most applications where corrosive chemicals are used or where sinks or heavy water usage
occurs. (Do not use epoxy resin in a laboratory that uses dry ice.)
Stainless steel is usually used for radioisotopes, perchloric acid,
glassware washing, cold rooms, and solvent usage. Several other
materials can be used, based on the functions of the lab and the
budget of the project.
C.4.2
32 Design Criteria
Equipment
a.
Equipment Within a Lab: A wide variety of equipment is
used in laboratories. The goal is to create adaptability in laboratory
space so that instruments can be relocated without altering the space,
or the attendant supportive utility systems, or without compromising the operation of the instruments, or safety of the users.
Design Criteria 33
b.
Common Equipment Rooms: Some instrumentation
rooms, electron microscopy suites, MRI, mass spectroscopy
suites, X-ray crystallography suites, and mass spectrometry rooms
require special utilities and environmental controls.
c.
Noise: Noise levels in laboratories can become extreme
for a number of reasons, including mechanical systems, fume
hoods, pumps, compressors, non-sound-absorbing surfaces, etc.
Consideration should be given to designing common equipment
rooms to house most commonly used equipment. This would concentrate high noise-generating equipment into one space to be
shared by a number of labs where it could be controlled.
C.5.1
Floors
Floor materials must be nonabsorbent, skidproof, resistant to wear,
and resistant to the adverse effects of acids, solvents, and detergents. Materials may be monolithic (sheet flooring) or have a
minimal number of joints such as vinyl composition tile (VCT)
or rubber tile. The base may be vinyl or rubber material (if readily
cleanable) with an integral cove base when sheet vinyl flooring
is used. Material selection relates directly to the biosafety level
of the laboratory and the level of cleanliness required for the
functions performed within the space.
C.5.2
Walls
Wall surfaces shall be free from cracks, unsealed penetrations,
and imperfect junctions with ceiling and floors. Materials must
be capable of withstanding washing with strong detergents and
disinfectants and be capable of withstanding the impact of normal traffic. Corner guards and bumper rails shall be provided to
protect wall surfaces in high traffic/impact areas.
Design Criteria
C.5.3
Ceilings
Ceilings such as washable lay-in acoustical tiles shall be provided
for most laboratory spaces. Ceiling heights in a laboratory and laboratory support shall accommodate biosafety cabinet and fume hood
installation. Gypsum board with epoxy paint and equipped with access panels is usually provided in glassware washing and autoclave
rooms, where the potential for high moisture exists.
C.5.4
C.5.5
Doors
The choice of door for laboratories varies from a minimum 1,070
mm (3' 6") to doors 1,200 mm (4' 0") wide with 900 mm (3' 0")
active leaf and 300 mm (V 0") inactive leaf. Doors shall be at
least 2,100 mm (6' 8") high. In laboratories where the use of larger
equipment is anticipated, wider/higher doors or removable transoms shall be considered to allow for entry and exit of larger
equipment. Laboratory doors shall be recessed and swing outward in the direction of egress. They shall be provided with locks
and closers for security/safety.
Structural
C.6.1
Vibration
a.
Because vibration can interfere significantly with sensitive laboratory instruments, designers must take appropriate opportunities to control vibration and to locate vibration sources
away from activities sensitive to vibration. Steel structures are
feasible subject to the results of the vibration analysis. A thorough vibration analysis is suggested prior to selection of a steel
structure system.
b.
An analysis of vibration response of the structure should
be made. Consideration must be given to vibration of floor-framing
systems as well as slab-on-grade and ground transmission caused
Design Criteria 35
The structural system shall be relatively stiff so that any vibration that is transmitted occurs at high frequencies. Vibrations
occurring at higher frequencies are more easily dampened with
instrumentation vibration dampening systems and isolation
tables than vibrations occurring at lower frequencies
The structural system shall have relatively short column
spacing
Laboratory spaces shall be isolated from sources of vibration
Vibration-sensitive equipment shall be located on
grade-supported slabs
On framed floors, vibration-sensitive equipment shall be located near columns
On framed floors, the combining of corridors and laboratory
spans in the same structural bay shall be avoided
C.6.2
Module/Bay Size
a.
The dimension of the structural bay, both vertical and horizontal, must be carefully evaluated with respect to the laboratory
planning module, utility distribution, vibration criteria, and future expansion plans. Due to the importance of the laboratory
planning module to functional and safety issues, the laboratory
planning module shall be considered as the primary building
module in multi-use facilities.
b.
The horizontal dimension of the structural bay should be
a multiple of the laboratory-planning module dimension to provide for flexibility and regular fenestration, and to allow uniform
points of connection for laboratory services with respect to the
laboratory planning module.
c.
Columns should not fall within the laboratory planning
module to prevent interference with laboratory layouts and inefficient use of valuable laboratory space.
36 Design Criteria
d.
Close coordination between structural and mechanical disciplines is critical to minimize interference of piping and ventilating systems with the structural framing.
C.6.3
C.6.4
Equipment Pathway
The potential routing or pathway for the addition or relocation of
heavy equipment shall be reviewed and identified during the schematic design phase.
C.7.1
Energy Conservation
a.
Applicable local, state, and federal codes shall be utilized
to regulate the design and construction of the exterior envelopes
and the selection of HVAC, service water heating, electrical distribution, lighting systems, and equipment required for the pur-
Design Criteria
37
pose of effective use of energy, and shall govern all buildings and
structures erected for human occupancy.
b.
Minimum system insulation thicknesses shall be as required by the energy conservation code and ASHRAE recommendations. The minimum thickness in all applications shall be
sufficient to prevent condensation.
c.
The quality of the building environment shall maintain
the health and safety of building occupants. Opportunities for
conserving energy resources shall not compromise health and
safety issues nor hinder research functions.
d.
Effective energy management requires close, consistent
control of all energy-consuming systems and components. Evaluations of heat reclamation alternatives shall be compared to systems employing no heat recovery or energy conversation components.
C.7.2
C.7.3
38 Design Criteria
Air Quality
a.
HVAC systems must maintain a safe and comfortable
working environment and be capable of adapting as appropriate
to new research initiatives. In addition, they must be easy to maintain, energy efficient, and reliable to minimize lost research time.
b.
Adequate access shall be provided for periodic maintenance and cleaning of coils, humidifiers, and drain pans. Drain
pans shall be designed and installed for proper and immediate
drainage of condensed water. A proper hydraulic head shall be
provided for drains within positive and negative air plenums to
maintain drainage and prevent overflow.
c.
Prevailing winds, adjacent buildings, and discharge velocities must be taken into account so that discharge is not entrained within an outdoor air intake. Outdoor air intakes shall be
located as far as practical (usually on directionally different exposures) but not less than 9,000 mm (30' 0") from exhaust outlets
of combustion equipment stacks, cooling towers, ventilation exhaust outlets from the building or adjoining buildings, vacuum
systems, plumbing vent stacks, or areas that may collect vehicular exhaust and other noxious fumes. The bottom of outdoor air
intakes serving central systems shall be located as high as practical above the roof or ground level.
d.
Exhaust outlets shall be located away from occupied areas or from doors and windows. The preferred location for exhaust discharge is above roof level. Care must be taken in locating highly contaminated exhausts and discharges from engines,
fume hoods, BSCs, kitchen hoods, and paint booths.
Design Criteria 39
e.
If fume hood exhaust systems interconnect with other ventilation duct systems, appropriate engineering equipment, principles, and controls are necessary so that cross-contamination of
the general ventilation does not occur.
f.
Laboratories containing harmful substances shall be designed and field balanced so that air flows into the laboratory
from adjacent (clean) spaces, offices, and corridors. This requirement for directional airflow into the laboratory is to contain odors,
toxic chemicals, and inadvertent biological aerosols with negative pressurization. Air supplied to the corridor and adjacent clean
spaces must be exhausted through the laboratory to achieve effective negative pressurization. Laboratory HVAC systems usually utilize 100% outdoor air, conditioned by central station
air-handling systems of sufficient capacity to provide the necessary balance with exhaust air requirements. Laboratory supply
air is not usually recirculated or reused for other ventilation needs.
g.
The use of exposed fiberglass or any fibrous material that
allows fibers to break off into the airstream for interior duct lining or insulation is usually not allowed for ductwork and
air-handling units. Sound attenuators with suitable linings or other
approved means of noise control shall be used where required.
Insulation and a vapor barrier shall be installed on the outside of
ductwork to prevent condensation.
h.
The architect/engineer shall develop in the design phase
a formal start-up and commissioning procedure that addresses
indoor air quality requirements.
i.
The filtration necessary for supply air depends on the activity in the laboratory. Conventional chemistry and physics laboratories commonly have 85% efficient filters, based on ASHRAE
Standard 52-76 Test Method. Biomedical laboratories usually
require 85% to 95% efficient filters. HEPA filters shall be provided in special laboratories where research materials are particularly susceptible to contamination from external sources.
HEPA filtration of the supply air is considered necessary in only
the most critical applications, such as environmental studies,
dust-sensitive work, and electronic assemblies. In many instances,
BSCs (which are HEPA filtered), rather than HEPA filtration for
the entire room, are satisfactory.
j.
Supply air for all laboratory systems shall befilteredon the
upstream side of fans with prefilters and high-efficiency afterfilters.
40
Design Criteria
k. T Exhaust air in general does not require filtration or scrubbing. However, in special laboratories using radioisotopes, or
certain hazardous chemicals or in biocontainment laboratories,
exhaust air may require special scrubbing or filtration before entering the combined laboratory exhaust system or discharging to
the atmosphere.
Air Distribution
Air supplied to a laboratory space must keep temperature gradients and air turbulence to a minimum, especially near the face of
the laboratory fume hoods and BSCs. Air outlets must not discharge into the face of fume hoods. Also, cross-flows that impinge on the side of a hood more seriously alter airflow than do
cross-flows in front of the hood.
Relative Pressurization
a.
Laboratories in general should remain at a negative air
pressure in relation to the corridors and other nonlaboratory
spaces. Laboratory air shall flow from low-hazard to high-hazard
use areas. In general, laboratories shall be maintained negative
relative to nonlaboratory spaces. Administrative areas in laboratory buildings must always be positive with respect to corridors
and laboratories. The entire building must be maintained at an
air pressure above atmospheric to reduce or eliminate unwanted,
unfiltered air and water infiltration.
b.
Corridor supply air distribution shall be sized to offset
transfer air to laboratories while maintaining an overall positive
building pressure. Loading and receiving docks must be maintained as positive to prevent the entrance of vehicle fumes.
c.
Some laboratories, such as biohazard containment laboratories and tissue culture laboratories, require control of relative pressurization. The HVAC system must be capable of achieving these special relative pressure requirements, which are discussed in the Centers for Disease Control/National Institutes of
Health (CDC/NIH) publication Biosafety in Microbiological and
Biomedical Laboratories.
Air Balance
a.
Control of airflow direction in research laboratories controls the spread of airborne contaminants, protects personnel from
Design Criteria
41
toxic and hazardous substances, and protects the integrity of experiments. In these facilities, the once-through principle of airflow is applied based on (1) exhausting 100% of the supplied air;
(2) maintaining the required airflow with all exhaust units operating at capacity; and (3) providing directional flow of air from
areas of least contamination to those of greatest contamination.
Determinants for air pattern control are (1) the type of research
materials handled or generated in each space; (2) the type, size,
and number of laboratory fume hood, BSCs, and auxiliary exhaust equipment in each space; and (3) permissibility of air transfer into or out of spaces.
b.
For critical air-balance conditions, a personnel entry or
exit airlock provides a positive means of air control. An airlock
is an anteroom with airtight doors between a controlled and uncontrolled space. The air pattern in the airlock suits the foregoing laboratory space air-balance requirements.
c.
Supply air quantities are not fully established by the
room-cooling requirements and load characteristics. Additional
supply air required to make up the differences between room
exhaust requirements and primary supply may be designated (1)
infiltrated supply, if induced indirectly from the corridors and
other spaces or (2) secondary supply, if conducted directly to the
room.
C.7.9
Ventilation Rates
a.
The ventilation rate for laboratory HVAC systems is driven
by three factors: fume hood demand, cooling loads, and removal
of fumes and odors from the general laboratory work area. The
minimum air-change rate for laboratory space is often dependent
on fugitive fume and odor emissions anticipated. Some laboratories may require significantly higher rates to support fume hood
demand or to cool high instrument heat loads in equipment laboratories.
b.
Implementation of a recirculative-type HVAC system for
administrative areas may be utilized for energy conservation.
Recirculating air systems shall provide ventilation conforming
to ASHRAE standards and must not affect the pressurization and
balance between laboratory and administrative zones.
c.
In the design of HVAC systems for laboratory areas and
the use of recirculating systems for administrative areas, the ques-
42
Design Criteria
tion of future flexibility becomes an ever-increasing and important question. It is imperative that the design architect/engineer
do in-depth programming and planning and that the research personnel be informed that administrative areas do not have flexibility for conversion into soft lab space unless this is a planned
function and the area is designed accordingly.
Design Criteria
43
Plumbing
a.
The plumbing systems shall be coordinated with the laboratory planning module. A piping distribution method, including mains, risers, and
branch lines, shall be designed to accommodate easy service isolation and
system maintenance while minimizing disruption to laboratory functions.
Emergency isolation valves must be conveniently located on branch lines so
that segments can be taken off line quickly in the event of failures.
b.
Piping systems shall be designed for flexibility and have redundant
components to provide reliable and continuous operation. Adequate fluid
temperature, pressure, and volume must be delivered to required laboratory
Design Criteria
functions through conservatively sized pipe mains. Future capacity allowances need to be considered in building designs.
c.
Floor penetrations in laboratory areas shall be avoided. All required
penetrations shall use raised sleeved openings sealed and caulked to prevent
leakage and maintain the fire rating of the slab.
&.
Gas piping systems shall comply with the latest edition of National
Fire Protection Association (NFPA) 54, National Fuel Gas Code.
Electrical
C.9.1
Normal Power
a.
The following load figures in volt-amperes per square
meter shall be used in calculating and sizing the overall building
load. These figures are connected load and shall be used in the
early design stages. Actual design loads shall be used in the later
part of the design. The range provided allows for varying intensity of usage. A few factors that influence usage are density of
occupancy in the laboratories and type of research conducted.
The mechanical loads do not include chilled water or steam generation, which are produced centrally. The engineer shall use
sound judgment in applying these numbers.
Load
Lighting
Receptacle
HVAC
Lab Equipment
Elevators
Miscellaneous
Total Range
VA/M2
27-38
48-215
97-108
43-86
11-16
11-22
237-485
(VA/sf)
2.5-3.5
4.5-20
9-10
4-8
1-1.5
1-2
22^5
b.
Because of the proliferation of computer-based equipment
and the nature of its power consumption, the designer should
investigate the impact of the resulting harmonics on power circuitry and the sizing of neutrals.
C.9.2
\
Standby Power
a.
The following load figures in watts per square meter shall
be used in sizing the generator. These figures are connected load
and shall be used in the early design stages. Actual design loads
shall be used in the later part of the design. The range allows for
Design Criteria
45
varying intensity of usage. The engineer shall use sound judgment in applying these numbers.
Load
Lighting
Receptacles
HVAC
Lab equipment
Elevators*
W/m2
1-5
1-2
1-32
20-43
2-2
Total Range
25-84
C.9.3
One light fixture per module with one light switch per lab
BSCs
Supply and exhaust fans for BL3 and BL4 labs
Ventilated animal cages and cage systems
Lab equipment alarm-monitoring system
Fume hood exhaust fans
High-value specimen refrigerators, freezers, cold rooms, warm
rooms, etc.
Incubators
Lighting
a.
Laboratories generally require 100 foot-candles at
benchtop level, with a minimum of 75 foot-candles being acceptable with minimum glare and maximum efficiency. Where
the correct identification of color is important, special
color-corrected lamps may be necessary.
b.
Illumination design shall be based on the Illuminating Engineering Society of North America (IESNA) Lighting Handbook for recommended values.
c.
Undershelf-mounted, fluorescent task-lighting fixtures are
sometimes used. Where utilized, under-shelf fluorescent fixtures
shall have lenses over the lamps. Industrial-type fluorescent lighting fixtures shall have wire guards.
46 Design Criteria
C.9.4
Monitoring
a.
Lab equipment, such as freezers, incubators, environmental rooms, etc., often needs to be monitored for alarm conditions.
b.
New buildings or wholesale renovation of existing buildings should have empty conduit with pull lines installed for monitoring of lab equipment.
C.9.5
Telecommunications/LAN
Voice, data, and video are often important systems needed in the
laboratory and shall be prewired using accessible cable trays and
conduit and provided with standby power as required. The location and number of telecommunications/LAN closets in research
buildings must be carefully considered during the design phase.
Telecommunications/LAN rooms require adequate space for circulation around the equipment for repair and maintenance. Consideration shall be given to alternatives to surface-mounted raceways since they can harbor pests.
C.9.6
Grounding System
A suitably designed isolated grounding system should be provided for laboratory instrumentation.
c.
While many of the requirements for health and safety engineering
are incorporated in these guidelines, it is impossible to cover all concerns. It
is recommended that a health and safety professional be part of every design
team.
Design Criteria
47
48 Design Criteria
C.10.6 Electrical
Shunt trip breakers may be required for labs with high-voltage
electrical equipment. A ground fault circuit interrupter is required
within 600 mm of a water source.
C.10.7 Flammables
Incorporate flammable storage cabinets in all laboratories using
flammable chemicals. Limitations on flammable storage and use
in laboratories should be determined by code.
Design Criteria
49
C.11.1
Background
"i
50 Design Criteria
<^
Design Criteria 51
g.
Decontamination Requirements: OSHA requires the use
of "EPA [Environmental Protection Agency] registered tuberculocidal hospital disinfectants" for the decontamination of
biohazardous spills. These disinfectants may include
halogen-containing compounds (hypochlorite, iodine), phenols,
alcohols, aldehydes, and quaternary ammonium compounds. Selection of a specific disinfectant depends on a number of criteria,
which could be different for different laboratories. Personnel must
choose appropriate disinfectants that are compatible with the surfaces on which the spill may have occurred.
Materials for laboratory finishes shall be as resistant as possible
to the caustic chemical activity of disinfectants and other chemicals used in the laboratory.
h.
Medical Pathological Waste (MPW) Storage Areas:
Sufficient kneehole space must be provided in each laboratory
module to accommodate the MPW containers as well as other
waste receptacles. Design consideration must be made for accommodation of these containers.
There must be space provided in the area of the loading dock for
the collection and storage of MPW. A cold box capable of holding a minimum of 30 MPW boxes overnight must be supplied in
close proximity to the loading dock.
Space must also be provided for MPW collection stations on each
floor of laboratory buildings.
i.
Autoclaves: For maximum flexibility, autoclave space
shall be provided on each floor where microbiological research
is performed. Actual installation of autoclaves and their use is an
operational decision. Since quality control considerations may
require separate autoclaves for clean and dirty procedures, space
must be considered for both "clean" autoclaves (for sterilization
of microbiological media and clean instruments, etc.) and "dirty"
autoclaves (for decontamination purposes). Architects/engineers
shall review the requirements of the building personnel when
designing and specifying autoclave space.
Autoclave space must be of sufficient size to accommodate carts
and other equipment necessary for the handling of materials to
be sterilized.
52 Design Criteria
Design Criteria 53
b.
Containment Requirements: BL3 laboratories require
all of the design considerations for BL2 laboratories plus specific requirements for the additional containment of those
biohazardous materials used in the laboratory. No compromise
of the integrity of the containment of the BL3 laboratory is allowed.
c.
Restricted Access: BL3 laboratories must be separated
from areas with unrestricted traffic flow by passage through two
sets of "self-closing" doors. There must be a ventilated airlock
designed to separate the common corridor(s) from the BL3 containment laboratory.
The purpose of a BL3 laboratory facility is to ensure containment of agents used in this laboratory. It is recommended that
airlock doors be interlocked to prevent simultaneous opening of
doors between the outside corridor and containment areas. Interlocks, when present, shall be provided with a manual override
for use in case of emergency. Final determination on the design
of airlocks for these facilities shall be made in consultation with
facility safety personnel.
d.
Sinks: A sink for hand-washing is to be located near the
exit door in each BL3 laboratory (not in the airlock). Sink faucets must be foot, elbow, or automatically operated.
e.
Interior Surfaces: Interior surfaces of walls, floors, and
ceilings must be water resistant (i.e., epoxy paint, caulking, etc.),
gas tight (i.e., capable of containing decontamination gas during
decontamination process), and easily cleanable.
f.
Ceilings: All BL3 facilities must have a ceiling with a
smooth, sealed finish. In all new construction, all access to critical mechanical equipment (ventilation ducts, fans, piping, etc.)
must be provided outside of the containment facility. (See paragraph h, HVAC System/Mechanical Equipment, below.)
g.
HVAC/Airflow: Ventilation must be single-pass air, and
all BL3 space must be kept negative with respect to outside corridors and laboratories. Exhaust ducts must be under negative
pressure until the air is discharged outside the building.
Note: HEPA filtration of BL3 space may, in some cases, be required. (See paragraph o, Filtration of Laboratory Exhaust, below.) If the BSC cabinet exhaust system is connected to the build-
54 Design Criteria
Design Criteria
55
k.
Windows: Laboratory windows, where present, must be
designed not to open. All interior windowsills must be sloped,
and the seams around the windows must be sealed as are other
seams in the laboratory.
1.
Autoclaves: Decontamination equipment (preferably autoclave) shall be available in the BL3 laboratory. Autoclave space
shall meet specifications as provided in section B.4.1 of this document.
m.
Vacuum Systems: Vacuum systems in BL3 laboratories
must be protected by filtration. (See section C.10.3.)
n.
Alarms: BL3 facilities must be designed to ensure notification of inappropriate directional airflow. Both visual (gauges)
and audible local alarms are acceptable. In addition, alarms indicating the potential failure of BL3 containment shall be tied to a
central system at the Building Engineer's office, where possible.
Notification devices shall indicate the failure to maintain a negative pressure differential between a noncontaminated area and
potentially contaminated areas.
All alarm systems must be validated prior to occupancy of the
containment space by research personnel.
o.
Filtration of Laboratory Exhaust: While HEPA filtration of room exhaust from BL3 laboratories is seldom necessary,
an evaluation of the need for specific filtration shall be performed
during the initial planning and design stages of the project. The
need for HEPA filtration shall be determined on a case-by-case
basis in consultation with the facility safety personnel and shall
be based on a hazard assessment of the materials in use and the
procedures to be performed.
p.
Autoclave Exhaust Filtration: The exhaust from an autoclave contains a significant amount of moisture, and exhaust
ductwork should be designed accordingly. Filtration of this exhaust, when necessary (as determined above in Filtration of Laboratory Exhaust), must be through a moisture-resistant (hydrophobic) filter such as a 0.2 micron filter or equivalent. Filtration of
moist exhaust through a cold filter housing containing a paper
HEPA filter will result in the destruction of the HEPA filter and a
break in integrity.
56 Design Criteria
q.
HEPA Filter Housings: When installed, HEPA filter exhaust housings must be constructed in such a manner as to allow
for appropriate particulate testing (i.e., DOP or equivalent) and
must be capable of being isolated from the ventilation system for
gas decontamination and testing (i.e., gas-tight dampers and housings). Facility safety personnel must be consulted with regard to
the suitability of the decontamination mechanism design and
approve of the system prior to the finalization of the design.
Design Criteria 57
58 Design Criteria
Design Criteria
59
1.
Class II, Type B3 Cabinets: Type B3 cabinets function
in the same manner as Type A cabinets but have been redesigned
to provide a negative-pressure zone around all positive-pressure
contaminated plenums. They have the same limitations as the
Type A cabinets. If a small amount of volatile is used in this
cabinet, the exhaust is hard ducted to the building exhaust system and thimble connection is not allowed.
m.
Requirements for BSC Installation: All BSCs must
meet NSF Standard 49 requirements. Selection of cabinets is to
be based on the evaluation of the work to be performed and the
specific safety requirements necessary to protect personnel, research, and the environment.
n.
Air supply diffusers, or exhaust vents, shall not be placed
directly over or in front of BSCs where the movement of air can
affect the airflow of the cabinet.
o.
The safe operation of BSCs depends upon the air curtain
formed by incoming and downflow air in the cabinet. Disruption
of the air curtain will result in potential compromise of the operation of the cabinet and possible contamination of personnel or
work. Personnel traffic results in air pattern disruption in BSCs.
Therefore, these cabinets must be placed toward the rear of the
laboratory module and out of the direct traffic pattern of the laboratory. Some codes dictate the placement of BSCs relative to exits.
p.
A gas-tight valve must be provided on the Class II, Type
B1 cabinet exhaust. This valve is required in order to facilitate
decontamination and pressure testing of the cabinets.
q.
The design of the HVAC systems must allow for the maximum exhaust capacity for all BSCs which may be required in the
facility.
2 Radiation Safety
a.
Work performed at biomedical research laboratories may involve the
potential for occupational exposure to radioactive materials and other sources
of ionizing and non-ionizing radiation. While laboratory procedures identified as good radiation safety practices and techniques are essential to minimize exposures, the implementation of good facility design in security, engineering controls, and shielding are important elements to enhance safety.
Design Criteria
b.
The intent of this section is to provide the architect/engineer and construction contractor with a working knowledge of facility design parameters
associated with facilities using a variety of radiation sources and radioactive
materials in the biomedical research environment.
c.
The designer should be aware that all sources of ionizing and
non-ionizing radiation may not be licensed by a single regulatory authority.
Radioactive materials and various radiation sources may be subject to regulations from the Nuclear Regulatory Commission (NRC), state regulatory
agencies, the Food and Drug Administration (FDA), and/or by policies and
guidance of the facility's radiation safety personnel. Contact should be made
early on in the design process with the facility's safety personnel to avoid
confusion and possible design issues related to regulatory authority.
d.
In addition to the protection of the occupationally exposed, good
facility design translates into adequate protection of the environment as well
as members of the general public who work and reside near such facilities.
b.
All radioactive materials and/or sources of radiation that
are in storage or in use shall be secured when unattended in conformance with requirements of the applicable regulations. This
may be implemented with locking containers, storage cabinets,
or possibly key card access.
Design Criteria 61
62 Design Criteria
Liquids
( aqueous waste
solvents/other hazardous chemical constituents (mixed
waste)
Dry or solid waste (dry active waste)
disposable labware, gloves, absorbent paper, etc.
sharps (may be categorized as medical pathological waste
(MPW) if also contaminated with pathogens/body fluids)
Liquid scintillation cocktail and vials
MPW
animal carcasses/tissues
animal bedding/excreta
other radioactive waste containing pathogens
c.
The location of the radioactive waste in each laboratory shall
be standardized to assist emergency response personnel in the event
of a fire or accident. It is recommended that this storage be located
near the laboratory door, particularly if a service corridor exists, to
facilitate easy access and collection by radioactive waste collection
personnel. This will reduce or avoid the need to transport waste
Design Criteria 63
All laboratories shall have the ability to be locked against unauthorized access
All radioactive materials use and storage areas shall be capable
of being secured when unattended
Laboratories and waste storage and accumulation areas shall
be sized appropriately for the anticipated workload and to reduce unnecessary accumulation
Appropriate spill containment shall be included in all storage
and accumulation areas
The space required for shielding waste containers shall be considered
Potential shielding requirements for adjoining or adjacent laboratory benches shall be considered for laboratories using
high-energy beta-emitting radionuclides. This may be accomplished through the use of 0.95 to 1.27 cm (3/8" to 1/2") plastic
sheets (Lucite)
Potential shielding requirements shall be considered for laboratories using high-energy photo-emitting radionuclides. The design
may need to consider loading of countertops and chemical fume
hoods due to the addition of appropriate lead shielding
Corridors and public space shall not be designated and used
for storage of radioactive materials or to house equipment such
as refrigerators/freezers, liquid scintillation counters, gamma
counters, centrifuges, lyophilizers, water baths, or other equipment that houses, contains, or may be contaminated with radioactive materials
Secure equipment alcoves or rooms are required for equipment such as refrigerators/freezers, liquid scintillation counters,
gamma counters, centrifuges, lyophilizers, water baths, or other
equipment that houses, contains, or may be contaminated with
radioactive materials. Secure rooms are required for
radiation-producing equipment such as irradiators, X-ray machines, etc.
Epoxy coatings, laminates, floor coverings, and protective coatings shall be utilized for ease of decontamination of surfaces
64 Design Criteria
Sinks shall be either plastic composite, stainless steel, or nonporous surfaces suitable for the laboratory environment
Chemical fume hoods used for radioactive materials shall have
a minimum face velocity of 0.5 m/s (100 lfpm)
A typical chemical fume hood designed for chemicals/hazardous materials is acceptable for use with radioactive materials.
The hood design shall include smooth, nonporous surfaces for
ease of decontamination
e.
Additional design guidance for chemical fume hoods used
for radionuclides is available from the following references:
All systems used to exhaust air potentially containing radioactive materials shall have the ability to sample the effluent being discharged (primarily gases and vapors) and shall be prominently marked for ease of identification
This sampling point shall be located inside an accessible mechanical room at a point downstream from any exhaust treatment systems (filtration, etc.). This location shall be provided
with a 120V, 20A grounded receptacle to power an air sampling
pump, or sufficient house vacuum to be used to pull samples
Design Criteria 65
Where radioactive iodination is performed in specific laboratories, the exhaust system serving those laboratories shall be
equipped to accept appropriate charcoal filtration systems
Airborne radioactive effluent sampling systems shall be designed in accordance with ANSI Standard N13.1, Guide to Sampling Airborne Radioactive Materials in Nuclear Facilities. A
single-nozzle sample probe shall be designed to accomplish
sampling of gases and vapors, as specified in ANSI Standard
N13.1
Due to the weight of such equipment, floor loads must be assessed for structural integrity
The available means for moving this equipment must be examined (e.g., structural loads and capacity of elevators and
floors when placing the equipment; structural floor loading limi-
66 Design Criteria
c.
For design purposes, the dose equivalent limit goal shall
be 10 mRem to members of the public and 500 mRem occupational exposure.
Design Criteria
67
c.
With respect to the use of lasers, specifically high-power
intensity lasers, the following regulations and design considerations apply:
d.
A Class III laser system is a medium-pulse system requiring control measures to prevent viewing of the direct beam.
Design and control measurers emphasize preventing direct access to the primary or reflected beam. Safety eyewear is necessary and required with this class of laser.
e.
High-power intensity lasers (e.g., C0 2 lasers) are classified as Class IV lasers in 21 CFR 1040. These lasers produce
radiation so powerful that they can cause injury with a direct or
reflected exposure, even when the beam is scattered or diffused
by a rough surface or smoke screens. Class IV radiation lasers
emit more than one-half watt continuous output.
f.
Laser facilities shall be designed to minimize the use of
reflective/refractive surfaces to provide additional protection to
personnel.
68 Design Criteria
Design Criteria
69
which serve only one fire area, or in fully sprinklered buildings. Where duct
smoke detectors are installed they shall be of the photoelectric type, connected to the building fire alarm system, and shall cause shutdown of the
associated air handler upon alarm.
i.
Fire Extinguishers: Laboratory fire extinguishers shall be located
in the corridors. The maximum travel distance to an extinguisher, from any
point, shall be 15,000 mm (50' 0").
j.
Fire Water Pumps: A pressure test shall be performed at the nearest hydrant/fire water source during the design phase to determine the need
for fire water pumps.
b.
Attention to environmental management issues and proper waste
handling is a key portion of the facility's overall goals of ensuring the health
and well-being of facility employees, visitors, and neighbors and maintaining the facility campus atmosphere.
C.14.1 Background
a.
These guidelines regarding environmental management
encompass the current federal regulations regarding environmental management issues. State and local requirements are not included and must be addressed.
b.
Federal laws applicable to environmental management
include
70 Design Criteria
Design Criteria 71
d.
Each building utilizing these hazardous substances shall
be designed with a receiving and storage area. This area shall be
located at or near the point of use of the materials and will be
used for long-term storage of hazardous materials.
e.
Hazardous substance storage areas shall be out of the
normal flow of personnel traffic. There shall be convenient access from the storage area to the freight elevator and/or the loading dock without having to traverse heavily traveled or public
corridors.
f.
The staging area shall be large enough to provide storage
of the hazardous substances and room for loading and unloading
the drums or containers. If multiple substances will be stored,
the design shall allow for incompatible materials to remain segregated while in storage.
g.
The storage area shall be designed to contain any spills
of hazardous substances that may occur due to handling. Spill
containment may be accomplished with a curb around the area,
secondary containment bins, shelving designed to contain spills,
or a combination thereof. A chemical-resistant coating shall be
applied to the walls and floor in this area to make it easier to
clean up spills. These areas shall be thoroughly caulked and sealed
to minimize pest harborage and exclude pests.
h.
Safety equipment shall be provided for each hazardous
substance staging area in accordance with the direction of facility safety personnel. This safety equipment shall consist of an
emergency eyewash and an emergency shower. Special consideration must be given to this area in the fire protection design if
flammable materials will be stored.
i.
All laboratory spaces shall be designed for the safe storage of hazardous substances while discouraging the storage of
excessive amounts of hazardous substances. Thus, the designer
needs to consider the function of the laboratory and the potential
use of hazardous substances to fulfill this function.
j.
A flammable storage cabinet (FSC) shall be provided in
each laboratory. Additional FSCs shall be provided per NFPA 45
requirements. All FSCs shall be constructed of metal. The exterior of all FSCs shall be appropriately signed. The FSC shall be
located as remote as possible from the exit doors of the labora-
72 Design Criteria
tory. FSCs shall not be installed beneath fume hoods. FSCs shall
not be located in corridors. The integrity of the FSC shall not be
compromised by its mounting method. The FSC shall not be
vented. The size of these cabinets is based on the volume of flammable materials permitted by code that are used in the laboratory
and stored in the building.
k.
An additional storage area for nonflammable hazardous
substances shall also be provided. This storage area shall have at
least two physically separated sections to allow segregation of
incompatible materials. Each section of the storage area shall be
designed to contain a spill of at least 1 gallon of liquid. The configuration of the storage area shall be designed to facilitate spill
cleanup. Interior surfaces of the storage area shall be cleanable,
corrosion resistant, and nonreactive.
Design Criteria 73
74 Design Criteria
Thus, the designer needs to consider the function of the laboratory to determine the space necessary for hazardous waste storage. At a minimum, a 750 mm by 750 mm (21 6" by 2' 6") area
will be required.
1.
The designer must also recognize that some types of hazardous waste may be incompatible with other types and design
the hazardous waste storage area to accommodate multiple containers. The designer shall investigate the possibility of stacked
containers that will provide sufficient storage space while minimizing the footprint in the laboratory. Each storage container shall
be designed to provide secondary containment of the hazardous
wastes.
m.
The location of the hazardous waste storage area in the
laboratories shall be standardized to assist emergency response
personnel. It is recommended that this storage area be located
near the laboratory door for convenient access by the technician
collecting the hazardous waste. For laboratory modules with a
service corridor, it is recommended that this storage area be located near the service entrance rather than the hall entrance. This
will avoid the need for moving hazardous waste through the main
corridors of the laboratory building.
n.
The hazardous waste storage area shall have at least two
distinct segments to allow segregation of incompatible materials. Some laboratories may require three segments depending
upon the types of hazardous waste that will be generated. Each
segment of the storage area shall be designed to contain a spill of
at least 1 gallon of hazardous waste. The configuration of the
storage area shall be designed to facilitate spill cleanup. Interior
surfaces of the storage area shall be cleanable, corrosion resistant, and nonreactive.
Design Criteria 75
c.
Design considerations regarding the above-ground storage tanks include the location of the tanks to provide access for
delivery trucks. At the same time, the tanks shall be sufficiently
isolated and protected from traffic flow to minimize the risk of
accident. The tanks shall also be placed in a location to minimize
the aesthetic impact of the tank on the surroundings. This would
include the use of berms and landscaping to block the view of the
tanks.
d.
Spill Control: All bulk storage facilities and
above-ground storage tanks shall be equipped with secondary
containment to prevent discharge of the material in the event of a
spill or a leak. For single storage tanks, the secondary containment shall be large enough to contain the volume of the tank and
rainfall from the 10-year, 24-hour storm. For multiple storage
tanks, the secondary containment shall be large enough to contain the volume of the largest tank and rainfall from the 10-year,
24-hour storm.
e.
Materials used to provide the secondary containment shall
be impervious to the substance contained in the storage tank. The
containments shall be equipped with a normally closed and
locked/secured valve to prevent accidental discharge of the substance from the containment. This valve can be manually opened
to discharge accumulated rainwater after it has been determined
that the water is not contaminated.
f.
The other potential spill areas for hazardous substances
are the loading docks. Spills can occur at the loading docks during the loading and unloading of hazardous substances or hazardous wastes.
g.
Loading docks shall be designed to contain spills of hazardous substances and minimize the contamination of stormwater
runoff. One option that would accomplish this objective would
consist of a loading dock with a grate drain at the base that would
accumulate any spilled substances. This drain would be equipped
with a normally closed and locked/secured valve to prevent accidental discharge of spilled substances. Uncontaminated runoff
would be diverted from this drain by a second grate drain and a
small berm. An overhang would divert direct rainfall from the
base of the loading dock to the uncontaminated runoff drain. Alternative designs which meet this objective may be proposed by
the designer.
76 Design Criteria
h.
To maintain proper water quality, all drainage systems
which collect runoff from the parking areas shall be equipped
with oil water separators.
C.14.6 Wastewater
a.
Wastewater Discharge: Only uncontaminated stormwater runoff shall be discharged to a receiving stream. All wastewaters generated shall be discharged to the sanitary sewer. Typical wastewaters generated include domestic sewage from the lavatory facilities, nonhazardous waste discharged from laboratory
or research area sinks, waters used for cage washing and animal
care, waters used in cafeteria operations, and all floor drains.
b.
Wastewater Sampling: The wastewater sampling may
be a requirement of the local municipality or sanitation district.
c.
For new laboratory facility construction, the sanitary system shall be designed to allow for sampling at the discharge point
from the individual building. This will allow for testing and
troubleshooting of individual building wastewater streams.
d.
The sampling point shall be designed to allow for installation of a continuous pH monitor, installation of a programmable
sampler, and personnel access for grab sampling. Cage-washing
facilities shall be provided with a continuous pH monitor and
recorder.
e.
Wastewater Treatment: It may be necessary to provide
neutralization and equalization of wastewater streams from some
laboratory buildings to comply with local agency requirements.
f.
To allow for these circumstances, the sanitary system for
new laboratory buildings shall be designed with sufficient hydraulic gradient that an equalization or neutralization tank can
be installed at a later date without a redesign of the sewer system
or the installation of a pump station.
g.
Tanks used for equalization and neutralization of wastewaters can accumulate sludges and hazardous wastes, require
maintenance, and cause odor problems. Therefore, equalization
and neutralization tanks will not automatically be installed in new
construction. The designer shall investigate the potential use of
the building and attempt to characterize the potential wastewater
stream based upon this proposed use. Equalization and neutral-
Design Criteria
77
ization tanks shall be included in new construction if the anticipated characteristics of the wastewater stream indicate that these
facilities are likely to be required.
h.
Any facility being designed with darkrooms or
photoprocessing facilities shall have a processing facility for recovering silver from the wastewater stream from the
photoprocessing rooms.
78 Design Criteria
fied environmental engineer to identify hazardous waste materials specific to the laboratory in addition to those generally found
in building demolition. This site assessment shall include a review of records regarding the design, construction, and use of
the building to be demolished and the site; a review of records
regarding responses to hazardous substances spill incidents or
other emergencies; visual inspection of the building and site; and
sampling and analysis of suspect materials and areas to provide
quantitative data to back up the qualitative assessment.
Design Criteria 79
A
accelerators, 61
accessibility, 11, 12,22
ACGIH, see American College of
Governmental and Industrial Hygienists (ACGIH)
acid, 32, 33
actuators, 19
aerosol-producing equipment, 55
afterfilters, 40
AIA, see American Institute of Architects (AIA)
air pressure, negative, 41
air
balance, 41,42
conditioning, xii
distribution, 21,41
emissions, 70
flow, 21, 40, 51
quality, 39, 71
supply diffuser, 60
unfiltered, 41
airborne contaminants, 37
airlock, 42, 53, 54
alarms, 24, 25, 70
alcohol, 52
aldehyde, 52
alternate distribution systems, 12
amenities, 3, 4
American College of Governmental
and Industrial Hygienists (ACGIH),
32,48, 65
American Institute of Architects
(AIA), vii, viii, 31
American National Standards Institute
(ANSI), 32
American Society of Heating, Refrigerating, and Air-Conditioning
Engineers (ASHRAE), 32, 33, 37,
40,42
animals, 4, 30,43, 44, 46, 62, 63, 77
ANSI Standards
2136.1,68
N13.1, 66
Z 358.1,48
ANSI/ASHRAE Standard 110, 33,48
artwork, 3,4
ASHRAE Handbook of Fundamentals,
38,43
ASTM, 32
autoclave, 20, 27, 52, 53, 56
exhaust filtration, 56
rooms, 23, 24, 35, 44
autoradiography, 25
B
bank machines, 3, 4
benches, 2, 3, 15, 23, 26
benchwork, 26, 31
biohazard, see biological hazards
biological hazards, xii, 29,41,48, 50,
52,54
biological safety cabinet, 19, 20, 27,
30, 31, 32, 33, 35, 39, 40-42, 46, 48,
51,54,57-60
Biological Safety in Microbiological
and Biomedical Laboratories, 50
Biological Safety Levels
Level 1,24, 50
Level 2, xii, 24, 50, 51, 69, 74
Level 3, 24, 50, 53-56
Level 4, 24, 50, 57
biomedicine, 1
biophysics, 1, 21
biosafety, see Biological Safety Levels
biosafety cabinet, see biological safety
cabinet
Index 81
biotech room, 27
blackout capability, 3
BOCA, see Building Officials and
Code Administrators (BOCA)
break rooms, 1,4, 28
breakers, shunt trip, 49
BSC, see biological safety cabinet
Building Officials and Code Administrators (BOCA), xiii
bumper rails, 34
c
cafeteria, 30
cage-washing, 44, 77
calibration, 1
canopy hoods, 24, 53
capacity, 2
carbon dioxide, 20, 27, 61, 68
carcass disposal, 30
casework, 25, 32
caulking, 35, 51, 53, 54
CDC, see Centers for Disease Control/
National Institutes of Health (CDC/
NIH)
ceilings, 13, 14, 21, 24, 35,43, 51, 54,
55
Centers for Disease Control/National
Institutes of Health (CDC/NIH), vii,
viii, x, 3, 42
centrifuge, 4,20,26, 55, 64
chase areas, 2,4,71
chemical, xii
fume hood, 4, 21, 22, 32, 65
spill, 16,27,30,62
storage, 19,27,28
waste, 29, 62
chemistry, physical, 21
child care, 4
82 Index
D
darkroom, 20-23, 25, 44, 78
daylight, 6
decontamination, 52, 56
demolition, 78, 79
Department of Health, 30
design, 1,12,31,37
desk space, 2, 31
developing rooms, 23
disaster provisions, xii
distribution, 12, 13, 17, 22
DNA sequencers, 26
domestic sewage, 77
doors, 35, 54
drain, waste, and vent, 24-26, 39, 77
dry ice boxes, 26
duct smoke detection, 69, 70
ductwork, 24, 55
DWV, see drain, waste, and vent
E
earthquake, 28
electric, standby, 20, 27, 28, 43,45
electromagnetic field, 22
electron microscope, 21, 34
electronic
monitoring, 1
racks, 21
electrophysiology, 21
elevator, 2,4, 29, 30, 36,45,46, 62,
66, 72, 73
energy conservation, 37,42
Environmental Protection Agency
(EPA), 52, 78
environmental
approach, xi
management, 70
rooms, 47
EPA, see Environmental Protection
Agency (EPA)
epoxy paint, 35, 54
equalization, 77
equipment, 23, 24, 25, 32, 33
cooling loads, 44
pathway, 37
equivalent linear measurement (ELM),
31
exercise facilities, 3
exhaust, 56
exotic agents, 57
expansion, 3
F
facility safety, 30, 33, 53, 69
facility-specific construction, 47
FDA, see Food and Drug Administration (FDA)
fiberglass, 40
fibrous material, 40
filtration, 40, 56
fire
dampers, 69
extinguishers, 70
protective signaling systems, 69
safety, 69
water pumps, 70
fire-resistant materials and construction, 69
flammable liquid storage, 20
flammable storage cabinet, 49, 72, 73
floor-framing systems, 35
flooring, 51
material, 34
monolithic, 34
floors, 21, 23, 32, 34, 43, 52, 54, 55,
64,66
depressions, 37
penetrations, 45
fluorescence microscopy, 25
Food and Drug Administration (FDA),
37, 61, 68
foot-candles, 46
freestanding equipment areas, 25
freezers, 20, 25, 27,46, 47, 64
FSC, see flammable storage cabinet
fume hood, 19-23, 31, 33-35, 37, 3942, 46, 48, 59, 69, 74
Index 83
G
gamma counter, 64
gas cylinders, 11,20, 22, 23,26, 27,49
gas piping systems, 45
generators, 36
GFCI, see ground fault circuit interrupter
glassware, 23,24, 71
glassware washing, 24, 32, 35,44
gross area allowance, 31
ground fault circuit interrupter, 49
grounding system, 47
gypsum board, 35
H
hazard assessment, xii
hazardous materials, xii, 27, 70, 72, 78
Hazardous Materials Transportation
Act, 71
hazardous waste, 29, 70, 73-76, 78, 79
handling, 70, 73
storage, 63, 70, 73, 75
heat loads, 43,44
heating and cooling load calculation,
43
heating, ventilation, and air conditioning, 8,9, 11, 20,21, 24-26, 37-42,
44,45,46, 53-55, 60
HEPA filters, 40, 53-59
high-bench lab, 26
hood, kitchen, 39
humidity, 21,22, 37
HVAC, see heating, ventilation, and air
84 Index
conditioning
hydrophobic filters, 48
l
ICBO, see International Conference of
Building Officials (ICBO)
ice machines, 26
IESNA, see Illumination Engineering
Society of North America (IESNA)
Illumination Engineering Society of
North America (IESNA), 46
incubators, 20, 46, 47
Industrial Ventilation: A Manual of
Recommended Practice, 48, 65
information processing, 1
insecticidal dusts, 71
integrity of experiments, 42
interaction areas, 1, 3, 4, 28, 29
International Conference of Building
Officials (ICBO), xiii
interstitial space, 7, 9, 12, 13, 15, 16,
17,18
ionizing, 60, 61
irradiators, 61, 66, 67
K
kitchen, 30
L
laboratory
analytical, 21
biomedical, vii, xi, xiii, 1, 19, 31,
33,40
dry, 19,21
general, 5, 19 (
generic, 19
modules, 5, 18,32,75
neighborhoods, 6,10
physics, 40
space diagrams, 1,7-11, 13-16
staff, 2
support, 5, 6, 23, 31
support space, 2, 23
wet, 19
lasers, 22, 61,67, 68, A-2
facilities, 22, 68
high-power intensity, 67, 68
light, natural, 3, 8,10, 11, 16, 27
lighting, 3, 9, 22, 28, 29, 37,43-46, 74
liquid effluent monitoring, 65
liquid nitrogen, 20,26, 27
liquid scintillation, 63, 64
live loads, 12
loading dock, 11, 29, 30, 41, 52, 72-74,
76
local area network, see telecommunications/LAN
locker facilities, 4
Lucite, 64
lyophilizers, 64
M
magnetic resonance imaging, 22, 34,
61,67
^
mass spectrometry, 23, 34
materials
handling, 29, 30
storage, 11, 30
medical pathological waste, 52
MEP systems, 5, 6, 12
Metric standards of measurement, xiii
microscope, 21, 27, 34, A-l, A-3
electron, 21, 34
modules, planning, 5-7, 23
monitoring, 47
N
National Council on Radiation Protection (NCRP), 67
National Earthquake Hazards Reduction Program (NEHRP), xiii
National Fire Protection Association
(NFPA), 45, 69, 72, 75
National Fuel Gas Code, 45
National Sanitation Foundation (NSF),
57
NC 50, 37
NCRP, see National Council on Radiation Protection (NCRP)
NEHRP, see National Earthquake
Hazards Reduction Program
(NEHRP)
neutralization, 25, 71, 77
NFPA, see National Fire Protection
Association (NFPA)
NFPA 45, 69, 72
NIH, see Centers for Disease Control/
National Institutes of Health (CDC/
NIH)
noise, 2,4, 16,23,34,37,40
NRC, see Nuclear Regulatory Commission (NRC)
NRC Information Notice 90-09, 62, 63
NSF, see National Sanitation Foundation (NSF)
Nuclear Regulatory Commission
(NRC), 26, 61, 62, 63
Index 85
o
Occupational Health and Safety Administration (OSHA), 29, 32, 52
odors, 37, 42, 53, 71, 77
offices, 1,28,29
oil/water separators, 77
open areas, 15
optical diagnostic techniques, 3
organic chemistry, 20
OSHA, see Occupational Health and
Safety Administration (OSHA)
p
paint booths, 39
pathology, 20
peak system, 43
penetrations and joints, 55
perimeter wall, 8, 9, 11
pests, 11, 53
pH monitor, 77
phenols, 52
photography, micron, A-l
piped service, 15,19, 20, 21
piping systems, 37,44
planned zoning, 6, 7
plumbing, 17,32,44
postings, 67, 68
primary activities, 1
programmable sampler, 77
Q
quality control, 11
quaternary ammonium compounds, 52
86 Index
R
rack-washing, 44
radiation
non-ionizing, 60, 61, 67
safety, 60, 69
work, 26
radiation-producing equipment, 67
radioactive, 60-64, 66, 69
iodination, 66
shielding, 20
staging, 61, 62
waste, 61, 62, 63, 73
work areas, 23
radioisotopes, xii, 26, 32, 33,40
radiological, xii
radionuclides, 61, 64
recycling, 11,78
refrigerator, 20, 27, 29,46, 64
regulations
federal, 70
safety and health, 47
relative pressurization, 41
remodeling, 69
renovation, see remodeling
Resource Conservation and Recovery
Act, 70
restricted access, 54
reusable products, 78
robotics, 6
rooms
autoclave, 23, 24, 35,44
cold, 20, 22-25, 27, 32,46, 62
common equipment, 34,44
conference, 28
constant temperature, 23, 24
environmental, 47
general storage, 27
glassware washing, 24, 32, 35,44
warm, 25,46
s
Safe Drinking Water Act, 70
sampling port, 53
satellite building, 62
SBCCI, see Southern Building Code
Congress International (SBCCI)
scrubbing, 41
security, 1, 11
service corridor, 9, 12,13,15, 16
shafts
exterior, 12-14
multiple internal, 12, 13
shielding requirements, 68
shipping and receiving area, 29
shower, 19, 20, 26, 48, 72, 74
signage, 4, 67, 68
silver recovery unit, 25, 77
sinks, 19, 24-26, 29, 32, 48, 54, 65, 77
slab-on-grade, 35
smoke detectors, 69
Southern Building Code Congress
International (SBCCI), xiii
space requirements, xi
specimen, 1
spectroscopy, 34
spill containment, 27, 62, 64, 73, 76
splash guards, 51
sprinkler systems, 69
staff, support, 1
staffing patterns, xi
staging, 11,29,71,72,74
stairwells, 1,2,4, 30
steel structures, 35
sterilizer, ethylene oxide, 24
storage, 22, 23, 25, 27-29, 61, 69, 72,
74
areas, 11, 15,28,72,73,75
bulk, 70, 75
cabinet, 49, 72, 73
cabinets, 33, 57-60
chemical, 19, 27, 28
flammable, 20,49, 72, 73
flammable liquid, 27
laboratory materials, 29
lockable cubicles, 27
materials, 11, 30
medical pathological waste, 52
open, 69
personal effects, 29
radioactive waste, 61, 63
tanks, 75, 76
temporary, 11,71,73
stormwater runoff, 76, 77
structural, 35, 37, 66
Structural Shielding Design and
Evaluation for Medical Use ofXRays and Gamma Rays of Energies
uptolOMeV,61
Structural Shielding Design and
Evaluation Handbook, 67
structural
bay, 18,36
columns, 2, 6, 12
systems, 6, 12, 36
Suggested State Regulations for
Control of Radiation, Volume II:
Non-Ionizing Radiation, 68
surfaces
interior, 54
reflective, 68
refractive, 68
T
teaching institutions, 9
telecommunications/LAN, 20, 24-26,
28,47
temperature, 15, 22, 37
Index 87
U
utility
connection, 12
distribution, 12, 29, 31
services, 2,13,17
V
vacuum, 20, 24-26, 65
pump systems, 4, 23,48, 66
system, 48, 53, 66
VCT, see vinyl composition tile
ventilation, 8, 24, 37,40,42-44, 54,
59, 62, 74
vents, exhaust, 60, 74
vibration, 2, 6, 20-23, 35, 36, A-3
damping tables, 21
requirements, 12, A-3
vinyl composition tile, 34
visual connection, 2
volumetric measure, 31
w
walls, 2,4, 14, 15, 32, 34,43, 55, 71.
74
warning
placards, 67, 68
requirements, 68
waste
aqueous, 63
boxes, 50
chemical, 29, 62
disposal, 11
infectious, 23
88 Index
management, 61, 78
medical pathological, 52
mixed, 62
piping, 20
radioactive, 61, 62, 63, 73
solid, 63, 70, 77
storage, 20, 50, 75
water, 70,71,77,78
water
infiltration, 41
potable, 19, 48
waste, 70, 71,77, 78
windows, 15, 19, 35, 36, 56
work areas, 28
worker protection, 47
zone, 6,12, 17
APPENDIX A
VIBRATION CRITERIA FOR USE IN PLANNING
NEW FACILITIES
Description of Use
Criterion
Maximum Level
microinches/sec (dB)*
32,000 (90)
16,000 (84)
8,000 (78)
4,000 (72)
Vibration not detectable. ISO recommendation for operating theaters and critical
sleep areas. This standard is probably
adequate for bench-mounted microscopes
and other inspection systems of moderate
modification (20 through 100 times).
2,000 (66)
1,000(60)
500 (54)
250 (48)
125 (42)
*Reference: 1 microinch/sec.
NOTE: These limits should be applied to the highest one-third octave band within the
frequency range 5 Hz through 100 Hz. Equipment descriptions cover the equipment as
supplied by the manufacturer, including, in many cases, built-in vibration isolation.
BBN Criteria
100
micro inch/sec
90
^v
ISO Workshop
32,000
ISO Office
16,000
8,000
o
CD
80
o
o
E
o
70
v_
CO
"D
C
"0
>
0
4,000
BBN Criterion A
2,000
BBN Criterion B
1,000
X.
BBN Criterion C
N.
BBN Criterion D
60
50
40
500
250
I I I M I I I I I I I I I II
4
6.3
5
10 16
25
40
63 100
12.5 20 31.5 50
80 125
THE AUTHORS
Under the direction of the AIA, a multidisciplinary task group was convened to
develop these guidelines.This group met
during a two-year period to pull together the latest and best thinking about biomedical facility design.The task group
consisted of distinguished and dedicated
experts directly involved in biomedical
research facilities as researchers, designers, and constructors. It also included
representatives of professional organizations and public agencies. Under the
leadership of a seven-member executive
committee, the task group utilized not
only their own knowledge and experience, but that of their staffs and professional colleagues.The result is a balanced,
comprehensive overview of the challenges and opportunities you face, as well
as the ideas and solutions you need.
A B O U T THE AIA
The American Institute of Architects
(AIA) was created in 1857.Through education, government advocacy, community
redevelopment, and public outreach
activities, the AIA works toward a public
environment that is responsive to the
people it serves while representing the
professional interests of America's architects. In close concert with other members of the design and construction
team, the AIA also works to fulfill its
commitment to help coordinate the
building industry.
Jacket design by Max Brinkmann
mmmmm
ISBN l-fl7cB0M-c15-3
781879"304956
AIA