You are on page 1of 30

UNIT PRICE (SR)

ITEM

DESCRIPTION

UNIT

QTY

FCU-2 / ACCU-2: @ Basemetn M.P.Room


Airflow = 1600 CFM, Total Cooling / Heating Capacity= 4.0 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

11,500.00

FCU-4 / ACCU-4: @ Basemetn BUFIA


Airflow = 1200 CFM, Total Cooling / Heating Capacity= 3 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

9,000.00

FCU-3 / ACCU-3: @ 1st, 2nd & 3rd Floor Enterance Hall both side flats
Airflow = 1400 CFM, Total Cooling / Heating Capacity= 3.5 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

10,000.00

FCU-2 / ACCU-2: @ 1st, 2nd & 3rd Floor Family Dining Both side flats
Airflow = 1600 CFM, Total Cooling / Heating Capacity= 4.0 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

11,500.00

Div.15A

MECHANICAL- HVAC

15-A.01

DUCTED SPLIT CONCEALED UNITS DX-TYPE

AMOUNT IN
NUMBERS

Supply and installation of ducted split concealed units DX type complete with
referegerant pipes, filters valves and all related accessories,Indoor and outdoor units
shall be installed with hangers and supports and vibration isolators, room thermostat
control wires condensate drainage connections as per drawings and specification.

FCU-5/ACCU-5:@1st,2nd&3rd floor Bedroom & Maids room Both side flats, Airflow =
1000 CFM, Total Cooling / Heating Capacity= 2.5 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

SUB-TOTAL:

NO

8,500.00

Div.15A

MECHANICAL- HVAC (Continuation)

FCU-6/ACCU-6:@1st,2nd & 3rd Double Bedroom Both side flats


Airflow = 800 CFM, Total Cooling / Heating Capacity= 2.0 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

8,000.00

FCU-6A/ACCU-6A:@1st,2nd&3rd Floor Master Bedroom Both side flats


Airflow = 800 CFM, Total Cooling / Heating Capacity= 4.0 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

11,500.00

FCU-1 / ACCU-1: @ Fourth Floor Enterance Hall


Airflow = 2000 CFM, Total Cooling / Heating Capacity= 5.0 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

13,000.00

FCU-1A / ACCU-1A: @ Fourth Floor Studip


Airflow = 2000 CFM, Total Cooling / Heating Capacity= 5.0 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

13,000.00

FCU-1A / ACCU-1A: @ Fourth Floor Main Reception ORom


Airflow = 2000 CFM, Total Cooling / Heating Capacity= 5.0 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

13,000.00

FCU-2 / ACCU-2: @ Fourth Floor Guest Dining Room


Airflow = 1600 CFM, Total Cooling / Heating Capacity= 4.0 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

11,500.00

FCU-4 / ACCU-4: @ Fourth Floor Corridor/stairs


Airflow = 1200 CFM, Total Cooling / Heating Capacity= 3 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

SUB-TOTAL:

NO

9,000.00

Div.15A

MECHANICAL- HVAC (Continuation)

FCU-6/ACCU-6:@ Fourth floor Kitchen


Airflow = 800 CFM, Total Cooling / Heating Capacity= 2.0 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

8,000.00

FCU-3 / ACCU-3: @ Fifth Floor Dressing Room


Airflow = 1400 CFM, Total Cooling / Heating Capacity= 3.5 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

10,000.00

FCU-3A / ACCU-3A: @ Fifth Floor Master Bed Pavilion


Airflow = 1400 CFM, Total Cooling / Heating Capacity= 3.5 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

10,000.00

FCU-4 / ACCU-4: @ Fifth floor Bedroom/Dressing Room


Airflow = 1200 CFM, Total Cooling / Heating Capacity= 3 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

9,000.00

FCU-4A / ACCU-4A: @ Fifth floor Corridor


Airflow = 1200 CFM, Total Cooling / Heating Capacity= 3 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

9,000.00

SUB-TOTAL:

Div.15A

MECHANICAL- HVAC (Continuation)

15-A.02

WALL MOUNTED SPLIT UNITS DX-TYPE

Supply and installation of Wall mounted split units DX type complete with referegerant
pipes, filters valves and all related accessories,Indoor and outdoor units shall be
installed with hangers and supports and vibration isolators, room thermostat, control
wires and condensate drainaige connections as per drawings and specification.

FCU-9 / ACCU-9: @ Basement floor Driver Rooms


Airflow = 600 CFM, Total Cooling / Heating Capacity= 1.5 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

6,000.00

FCU-8 / ACCU-8: @ Ground Floor Enterance Hall


Airflow = 800 CFM, Total Cooling / Heating Capacity= 2.0 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

8,000.00

FCU-9 / ACCU-9: @ Ground floor Driver Rooms


Airflow = 600 CFM, Total Cooling / Heating Capacity= 1.5 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

7,000.00

FCU-9 / ACCU-9: @ Fourth Floor Maids Room


Airflow = 600 CFM, Total Cooling / Heating Capacity= 1.5 Tons
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Trane or Approved equivalent

NO

7,000.00

SUB-TOTAL:

Div.15A

MECHANICAL- HVAC (Continuation)

15-A.03

EXHAUST& VENTILATION FANS

Supply and installation of exhasut fans Inline and Ceiling type complete with flexible
ducts, back draft dmapers and disc valves, the internal construction as shown drawings
and specification.

EF-1 : Inline Type@ Basement floor Toilets M.P. Room & Driver room
Airflow = 150 CFM, ESP= 0.5 inch wg
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Green Heck or Approved equivalent

NO

1,500.00

CEF-1 : Celing exhust fan cassete Type@ Ground floor


Airflow = 75 CFM, ESP= 0.25 inch wg
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Green Heck or Approved equivalent

NO

1,000.00

CEF-1 : Celing exhust fan cassete Type@ 1st,2nd & 3rd floor toilets
Airflow = 75 CFM, ESP= 0.25 inch wg
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Green Heck or Approved equivalent

NO

36

1,000.00

EF-2 : Inline Type@ Fourth floor ditrty Kitchen


Airflow = 225 CFM, ESP= 0.5 inch wg
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Green Heck or Approved equivalent

NO

1,800.00

EF-1 : Inline Type@ Fourth floor ditrty Kitchen


Airflow = 150 CFM, ESP= 0.5 inch wg
Power Supply 220 V- 1 Ph - 60 Hz
Manfacturer - Green Heck or Approved equivalent

SUB-TOTAL:

NO

1,500.00

Div.15A

MECHANICAL- HVAC (Continuation)

15-A.04

Supply Linear Diffuser with Plenum box (SLD)


Supply linear diffuser, aluminum steel complete w/ deflectors, dampers,hangers,
support, insulated plenum box, accessories, etc.

a
b
c
c
15-A.05

SLD 2 Slot
SLD 3 Slot
SLD 4 Slot
SLD 5 Slot

LM
LM
LM
LM

36
135
17
5

600.00
650.00
700.00
760.00

LM
LM
LM

62
135
27

600.00
650.00
700.00

NO
NO
NO

10
6
6

450.00
400.00
400.00

NO

12

250.00

ReturnLinear Diffuser (RLD)


Return linear diffuser, aluminum steel complete,hangers, support, accessories, etc.

a
b
c
15-A.06

RLD 2 Slot
RLD 3 Slot
RLD 4 Slot
Supply Ceiling Diffuser with Plenum Box (SCD)
Supply ceiling diffuser, square face type, aluminum steel complete w/ deflectors,
dampers, insulated plenum box, hangers, support, accessories, etc.

a
b
c
15-A.06
a

SCD 300 mm
SCD 300 x 300 mm
RCD 300 x 300 mm
Exhsut Air Diffursers (EAD)
EAD 150 x 150

15-A.06
a
b
c

Exhaust Grille (EG)


EG 200 x 200
EG 250 x 150
EG 150 x 150

SUB-TOTAL:

NO
NO
NO

3
1
39

200.00
200.00
200.00

Div.15A

MECHANICAL- HVAC (Continuation)

15-A.07

Sheet Metal Duct Work( Supply / Return Air Duct )

Supply and Install galvanized steel duct according to SMACNA specifications


fabrication - including all formers, hangers fasteners, flanges, sealant, Volume dampers
and all accessories shall be included, access doors etc. as per drawings and
specifications. Including Air Balancing & Testing commissioning

Supply / Return Air Duct Gauge-24 & 22

M2

750

Exhaust Air duct of Gauge -24

M2

120

M2

900

35.00

M2

200

45.00

15-A.08

15-A.09

15-A.10

Fiber Glass Insulation


Supply and Install insulation for HVAC ducts by fiber glass wall (density 24 kg/m) and
thickness 25mm according to the specification and as shown on drawings, complete
with all accessories.
Accoustic Lining
Supply and Install Acoustic linning for internal HVAC duct by fiber glass wall (density
48 kg/m) and thickness 25 mm according to the specification , and it fixed from inside
by a stick pin
Item include testing commissioning.
Flexible Duct
Flexible duct as per required diameter with minimum of 1.5 meters long.Complete with
fittings and accessories.

a
b
c
15-A.11

FD
FD
FD

250 mm
200 mm
150 mm

TESTING, ADJUSTING, BALANCING & COMMISSIONING

SUB-TOTAL:

LM
LM
LM

60
50
160

LS

75.00
65.00
60.00

UNIT PRICE (SR)


AMOUNT IN WORDS

TOTAL

22 sr per kg
22 sr per kg

20% of all cost

You might also like