SHANTA PROPERTIES LTD

REVISED ELECTRICAL LOAD CALCULATION (WITH ELECTRIC GEYSERS)


FOR 13 STORIED WITH 2 BASEMENTS RESIDENTIAL BUILDING-JALALABAD
AT HOUSE NO. 21, ROAD NO. 47, BLOCK - CWN (A), GULSHAN 2, DHAKA

Electrical Consultant

Revised By

Md. Lutfor Rahman


B.Sc. Engg. Electrical

Nayan Kumar Das


B.Sc. Engg. Electrical

273713865.xls

1 of 14

Load Calculation Summary


Transformer Load:
Total No. of Apartments is 18 and the summation of demand of 18 units is 374 kW (with Electric Geyser)
For 18 apartments, diversity 85% amongst the Apartments is considered, thus the total demand after Diversity is 319.9 kW
say 318 kW. Demand for Common Service Areas including roof is 65 kW
Total Demand of the Project with Electric Geysers is 383 kW, equivalent to 403.15 kVA,
say 403 kVA (at P.F. 0.95). 500 kVA Substation/Transformer will have 97 kVA (19.4%) spare capacity.
Immediate next size of Substation is 630 kVA, which will have 227 kVA spare capacity.
Therefore, with Electric Geyser, 500 kVA Substation Proposed

Generator Load:
Total demand of Project after Diversity (85%) amongst apartments is 383 kW equivalent to 478.75 kVA
at 0.80 P. F. Considering 10% spare capacity, it is 526 kVA
Therefore proposed for 525 kVA or nearest higher commercial size Stand-by capacityDiesel Generator.

Unit wise Load


Units

Unit Load

N0.

Total load, kW

Duplex Unit at 2nd Floor

27

27

Duplex Unit at 4th Floor

27

27

Duplex Unit at 7th Floor

27

27

Duplex Unit at 11th Floor

27

27

Simplex Units at 1st, 3rd, 5th, 6th,


8th, 9th & 10 th Floors

19

14

266

18

374

Total

273713865.xls

2 of 14

1. Load Calculation for Common Service Areas, SDB-S


(Basement 1 & 2, Gr Fl and Stair/lift lobby of all floors)
Sl.
No.
1

Description of Load

Watt per
Unit

No.

Connected
Load, watt

Demand,
Watt

Remark

Light points:
Wall Bracket with 2x23 W CFL (B)

46

11

506

1x4 ft Tube light, (T)

50

Ceiling mounted Light (CL)

23

96

2208

2208

2' F/T Light over Mirror (M)

25

175

175

Gate light (GT)

23

46

46

Water Proof Garden Light (GL)

23

20

460

460

Ceiling mounted Light in Stair, Fire


Escape & Lift lobby (CL)

23

84

1932

1932

Water Proof Light Fittings for Water


Body (WL)

50

200

200

Ceiling Fan (F)

70

24

1680

1680

Exhaust Fan (EX)

70

70

70

Wall Fan (WF)

60

5A/6A 2 Pin Socket (TP/PB)

200

600

600 Average watts

10/15 A 3 Pin socket (P)

300

12

3600

3600 Average watts

10/15 A 3 Pin+ 2pin socket (R)

500

500

500 Average watts

5 A 2 Pin socket (CP) for CC


Camera

25

19

475

475

Water Pump, 10 HP, 2 nos,


-1 is stand-by

7460

7460

10

Sump Pump, 1 HP

746

746

11

Lift

15000

15000

15000

12

Stretcher Lift

18000

18000

18000

2000

2000

2000

4000

8000

4000

2000

2000

65658

60912

25 A 3 Pin Socket (QA) for Split Air


Conditioner (1.5TR)
25 A 3 Pin Socket (QA) for Split Air
Conditioner (3.0TR)
13

Misc/Extra
Total
Total

14

Fire Fighting Pump, 45 HP

273713865.xls

Say 65 kW
33570

3 of 14

33570

506 (Warm Colour Lamp)

7460 One is considered to


calculate the demand
0 Not Considered in Demand

Say 61 kW
0 Not Considered in Demand
& FF Panel is connected
directly to LT Panel

15

Jocky Pump, 5 HP

3730

Not Considered in Demand


& FF Panel is connected
0 directly to LT Panel

3730

Note:
Load of FF Pump & Jockey Pump & Water Pump were received from the Designer

2. Load Calculation for Gym at Roof


Sl.
Description of Load
Watt per
No.
Unit
1 Light points:

No.

Connected
Load, Watt

Demand,
Watt

Remark

Wall Bracket with 2x23 W CFL (B)

46

2' F/T Light over Mirror (M)

25

50

50

Ceiling Light (CL)

23

138

138

Tube Light (T)

50

50

50

238

Total
2

Ceiling Fan (F)

70

210

Exhaust Fan (EX)

70

210

Total

0 (Warm Colour Lamp)

420

5A/6A 2 Pin Socket (TP/PB)

200

10/15 A 3 Pin socket (P)

300

1500

25 A 3 Pin Socket (QA) for Split Air


Conditioner

3000

3000

3000

SDB-Swimming Pool

5000

5000

4000

20 A 3 Pin Socket (QG) for 15


Gallons Elect Geyser

1500

3000

1500 One is considered in demand


calculation

Total

Average watts
900 Average watts &
60% Diversity

13158
Say 13 kW

10058
Say 10 kW

3. Load Calculation for Swimming Pool at Roof ,Only Design purpose


Sl.
Description of Load
No.
1 Light points:

Watt per
Unit

Water Proof Light Fittings for Water


Body (WL)

No.

Connected
Load, Watt

50

10

500

5A/6A 2 Pin Socket (TP/PB)

200

10/15 A 3 Pin socket (P)

300

1200

Swimming Pool Load

3000
4700

Total

273713865.xls

4 of 14

Demand,
Watt

Remark

500

Average watts
720 Average watts &
60% Diversity
3000
4220

Say 5 kW

Say 4 kW

Revised Load Calculation is based with Electric Geyser

4. Load Calculation for Duplex Unit (SDB 2F1+SDB 2F2) at 2nd Floor, 1 Unit
Sl.
No.
1

Description of Load

Watt per
Unit

No.

Connected
Load, Watt

Demand,
Watt

Remark

Light points:
Wall Bracket with 2x23 W CFL (B)

46

24

1104

2' F/T Light over Mirror (M)

25

150

150

Ceiling Light (CL)

23

36

828

828

Tube Light (T)

50

100

100

Chandelier (CH)

300

1200

1200

Ceiling mounted Spot light with


23 W CFL (SP)

23

11

253

253

Ceiling mounted Pendant light with


23 W CFL (PD)
Ceiling mounted Traction light with
50 W Halogen Lamp (TR)
Water Proof garden light with
23
W CFL (GL)

23

161

161

50

300

300 Average 6 nos lamp in each

23

23

23

96

3796

1499

Total
2

Ceiling Fan (F)

70

20

1400

Exhaust Fan (EX)

70

490

Total

27

1104 (Warm Colour Lamp)

1050

5A/6A 2 Pin Socket (TP/PB)

200

32

6400

Average watts

10/15 A 3 Pin socket (P)

300

11

3300

Average watts

10/15 A 3 Pin+ 2pin socket (R)

500

11

5500

Average watts

Total

54

5000

25 A 3 Pin Socket (QA) for Split Air


Conditioner

3000

9000

20 A 3 Pin Socket (QA) for Split Air


Conditioner

2000

12000

9
9

20 A 3 Pin Socket (QG) for 15


Gallons Elect Geyser

1500
Total

273713865.xls

5 of 14

14700 Average 21 tr connected &


70% diversity considered
10500

4500

52386

26749

Say 51 kW

Say 27 kW

Revised Load Calculation is based with Electric Geyser

5. Load Calculation for Duplex Unit Right Side (SDB 2F2) at 2nd Floor, to Design SDB-2F2 only
Sl.
Description of Load
Watt per No. Connected Demand,
Remark
No.
Unit
Load,
Watt
Watt
1 Light points:
Wall Bracket with 2x23 W CFL (B)

46

13

598

2' F/T Light over Mirror (M)

25

75

75

Ceiling Light (CL)

23

16

368

368

Tube Light (T)

50

50

50

Chandelier (CH)

300

600

600

Ceiling mounted Spot light with


23 W CFL (SP)

23

115

115

Ceiling mounted Pendant light with


23 W CFL (PD)

23

92

92

Ceiling mounted Traction light with


50 W Halogen Lamp (TR)

50

200

Water Proof garden light with


23
W CFL (GL)

23

48

1898

1025

Total
2

Ceiling Fan (F)

70

630

Exhaust Fan (EX)

70

210

Total

12

598 (Warm Colour Lamp)

200 Average 6 nos lamp in each

490

5A/6A 2 Pin Socket (TP/PB)

200

21

4200

Average watts

10/15 A 3 Pin socket (P)

300

1500

Average watts

10/15 A 3 Pin+ 2pin socket (R)

500

1500

Average watts

Total

29

2500

25 A 3 Pin Socket (QA) for Split Air


Conditioner

3000

3000

20 A 3 Pin Socket (QA) for Split Air


Conditioner

2000

10000

6
9

20 A 3 Pin Socket (QG) for 15


Gallons Elect Geyser

1500
Total

273713865.xls

6 of 14

9800
6000

4500

28938

18315

Say 29 kW

Say 18 kW

Revised Load Calculation is based with Electric Geyser

6. Load Calculation for Duplex Unit (SDB 4F1+SDB 4F2) at 4th Floor, 1 Unit
Sl.
Description of Load
No.
1 Light points:

Watt per
Unit

No.

Connected
Load, Watt

Demand,
Watt

Remark

Wall Bracket with 2x23 W CFL (B)

46

24

1104

2' F/T Light over Mirror (M)

25

125

125

Ceiling Light (CL)

23

42

966

966

Tube Light (T)

50

100

100

Chandelier (CH)

300

1500

1500

Ceiling mounted Spot light with


23 W CFL (SP)

23

11

253

253

Ceiling mounted Pendant light with


23 W CFL (PD)

23

161

161

Ceiling mounted Traction light with


50 W Halogen Lamp (TR)

50

250

250 Average 6 nos lamp in each

Water Proof garden light with


23
W CFL (GL)

23

23

23

101

4209

1602

Total
2

Ceiling Fan (F)

70

26

1820

Exhaust Fan (EX)

70

560

Total

34

1104 (Warm Colour Lamp)

1260

5A/6A 2 Pin Socket (TP/PB)

200

25

5000

Average watts

10/15 A 3 Pin socket (P)

300

14

4200

Average watts

10/15 A 3 Pin+ 2pin socket (R)

500

12

6000

Average watts

Total

51

5000

25 A 3 Pin Socket (QA) for Split Air


Conditioner

3000

9000

20 A 3 Pin Socket (QA) for Split Air


Conditioner

2000

12000

273713865.xls

7 of 14

14700 Average 21 tr connected &


70% diversity considered

20 A 3 Pin Socket (QG) for 15


Gallons Elect Geyser

1500

Total

9000

4500

51789

27062

Say 52 kW

Say 27 kW

Revised Load Calculation is based with Electric Geyser

7. Load Calculation for Duplex Unit Right Side (SDB 4F2) at 4th Floor, to Design SDB 4F2 only
Sl.
No.
1

Description of Load

Watt per
Unit

No.

Connected
Load, Watt

Demand,
Watt

Remark

Light points:
Wall Bracket with 2x23 W CFL (B)

46

11

506

2' F/T Light over Mirror (M)

25

50

50

Ceiling Light (CL)

23

24

552

552

Tube Light (T)

50

50

50

Chandelier (CH)

300

300

300

Ceiling mounted Spot light with


23 W CFL (SP)

23

115

115

Ceiling mounted Pendant light with


23 W CFL (PD)

23

46

46

Ceiling mounted Traction light with


50 W Halogen Lamp (TR)

50

150

Water Proof garden light with


23
W CFL (GL)

23

49

1619

955

Total
2

Ceiling Fan (F)

70

14

980

Exhaust Fan (EX)

70

210

Total

17

506 (Warm Colour Lamp)

150 Average 6 nos lamp in each

700

5A/6A 2 Pin Socket (TP/PB)

200

15

3000

Average watts

10/15 A 3 Pin socket (P)

300

2100

Average watts

10/15 A 3 Pin+ 2pin socket (R)

500

1500

Average watts

Total
7

25 A 3 Pin Socket (QA) for Split Air


Conditioner

273713865.xls

25
3000

8 of 14

2500
3000

20 A 3 Pin Socket (QA) for Split Air


Conditioner
20 A 3 Pin Socket (QG) for 15
Gallons Elect Geyser

2000

1500

5
3

Total

8000

4500

8600
4500

24909

17255

Say 25 kW

Say 17 kW

Revised Load Calculation is based with Electric Geyser

8. Load Calculation for Duplex Unit (SDB 7F1+SDB 7F2) at 7th Floor, 1 Unit
Sl.
No.
1

Description of Load

Watt per
Unit

No.

Connected
Load, Watt

Demand,
Watt

Remark

Light points:
Wall Bracket with 2x23 W CFL (B)

46

34

1564

2' F/T Light over Mirror (M)

25

150

150

Ceiling Light (CL)

23

36

828

828

Tube Light (T)

50

50

50

Chandelier (CH)

300

1200

1200

Ceiling mounted Spot light with


23 W CFL (SP)

23

11

253

253

Ceiling mounted Pendant light with


23 W CFL (PD)

23

161

161

Ceiling mounted Traction light with


50 W Halogen Lamp (TR)

50

200

200 Average 6 nos lamp in each

Water Proof garden light with


23
W CFL (GL)

23

23

23

103

4206

1602

Total
2

Ceiling Fan (F)

70

25

1750

Exhaust Fan (EX)

70

560

Total

33

1564 (Warm Colour Lamp)

1260

5A/6A 2 Pin Socket (TP/PB)

200

26

5200

Average watts

10/15 A 3 Pin socket (P)

300

13

3900

Average watts

10/15 A 3 Pin+ 2pin socket (R)

500

12

6000

Average watts

Total

273713865.xls

51

9 of 14

5000

25 A 3 Pin Socket (QA) for Split Air


Conditioner

3000

9000

20 A 3 Pin Socket (QA) for Split Air


Conditioner

2000

12000

9
9

20 A 3 Pin Socket (QG) for 15


Gallons Elect Geyser

1500

Total

10500

14700 Average 21 tr connected &


70% diversity considered
4500

53116

27062

Say 53 kW

Say 27 kW

Revised Load Calculation is based with Electric Geyser

9. Load Calculation for Duplex Unit Right Side (SDB 7F2) at 7th Floor, to Design SDB 7F2 only
Sl.
No.
1

Description of Load

Watt per
Unit

No.

Connected
Load, Watt

Demand,
Watt

Remark

Light points:
Wall Bracket with 2x23 W CFL (B)

46

19

874

2' F/T Light over Mirror (M)

25

75

75

Ceiling Light (CL)

23

16

368

368

Tube Light (T)

50

50

50

Chandelier (CH)

300

600

600

Ceiling mounted Spot light with


23 W CFL (SP)

23

115

115

Ceiling mounted Pendant light with


23 W CFL (PD)

23

46

46

Ceiling mounted Traction light with


50 W Halogen Lamp (TR)

50

150

Water Proof garden light with


23
W CFL (GL)

23

51

2128

1082

Total
2

Ceiling Fan (F)

70

13

910

Exhaust Fan (EX)

70

210

Total

16

874 (Warm Colour Lamp)

150 Average 6 nos lamp in each

630

5A/6A 2 Pin Socket (TP/PB)

200

12

2400

Average watts

10/15 A 3 Pin socket (P)

300

2100

Average watts

273713865.xls

10 of 14

10/15 A 3 Pin+ 2pin socket (R)

500

Total

2000

23

2500

25 A 3 Pin Socket (QA) for Split Air


Conditioner

3000

3000

20 A 3 Pin Socket (QA) for Split Air


Conditioner

2000

10000

1500

6
4

20 A 3 Pin Socket (QG) for 15


Gallons Elect Geyser
Total

Average watts

6000

9800
3000

28748

17012

Say 29 kW

Say 17 kW

Revised Load Calculation is based with Electric Geyser

10. Load Calculation for Duplex Unit (SDB 11F1+SDB 11F2) at 11th Floor, 1 Unit
Sl.
No.
1

Description of Load

Watt per
Unit

No.

Connected
Load, Watt

Remark

Light points:
Wall Bracket with 2x23 W CFL (B)

46

26

1196

2' F/T Light over Mirror (M)

25

150

150

Ceiling Light (CL)

23

38

874

874

Tube Light (T)

50

100

100

Chandelier (CH)

300

900

900

Ceiling mounted Spot light with


23 W CFL (SP)

23

11

253

253

Ceiling mounted Pendant light with


23 W CFL (PD)

23

69

69

Ceiling mounted Traction light with


50 W Halogen Lamp (TR)

50

200

Water Proof garden light with


23
W CFL (GL)

23

46

46

Water Proof Light Fittings for Water


Body (WL)

50

200

200

93

3542

1436

Total
2

Ceiling Fan (F)

70

24

1680

Exhaust Fan (EX)

70

560

Total
4

Demand,
Watt

5A/6A 2 Pin Socket (TP/PB)

273713865.xls

32
200

11 of 14

26

1196 (Warm Colour Lamp)

200 Average 6 nos lamp in each

1190
5200

Average watts

10/15 A 3 Pin socket (P)

300

14

4200

Average watts

10/15 A 3 Pin+ 2pin socket (R)

500

11

5500

Average watts

Total

51

5000

25 A 3 Pin Socket (QA) for Split Air


Conditioner

3000

9000

20 A 3 Pin Socket (QA) for Split Air


Conditioner

2000

12000

9
9

20 A 3 Pin Socket (QG) for 15


Gallons Elect Geyser

1500

Total

14700 Average 21 tr connected &


70% diversity considered
10500

4500

52182

26826

Say 51 kW

Say 27 kW

Revised Load Calculation is based with Electric Geyser

11. Load Calculation for Duplex Unit Right Side (SDB 11F2) at 11th Floor, to Design SDB 11F2 only
Sl.
No.
1

Description of Load

Watt per
Unit

No.

Connected
Load, Watt

Demand,
Watt

Remark

Light points:
Wall Bracket with 2x23 W CFL (B)

46

10

460

2' F/T Light over Mirror (M)

25

75

75

Ceiling Light (CL)

23

19

437

437

Tube Light (T)

50

50

50

Chandelier (CH)

300

300

300

Ceiling mounted Spot light with


23 W CFL (SP)

23

115

115

Ceiling mounted Pendant light with


23 W CFL (PD)

23

Ceiling mounted Traction light with


50 W Halogen Lamp (TR)

50

150

Water Proof garden light with


23
W CFL (GL)

23

23

23

Water Proof Light Fittings for Water


Body (WL)

50

200

200

43

1437

909

Total
2

Ceiling Fan (F)

70

13

910

Exhaust Fan (EX)

70

210

273713865.xls

12 of 14

460 (Warm Colour Lamp)

150 Average 6 nos lamp in each

Total

16

630

5A/6A 2 Pin Socket (TP/PB)

200

15

3000

Average watts

10/15 A 3 Pin socket (P)

300

2700

Average watts

10/15 A 3 Pin+ 2pin socket (R)

500

1500

Average watts

Total

27

3000

25 A 3 Pin Socket (QA) for Split Air


Conditioner

3000

3000

20 A 3 Pin Socket (QA) for Split Air


Conditioner

2000

10000

20 A 3 Pin Socket (QG) for 15


Gallons Elect Geyser

1500

6
4

6000

9800
3000

28757

17339

Total

Say 29 kW

Say 17 kW

Revised Load Calculation is based with Electric Geyser

12. Load Calculation for Simplex Units Left/ Right Side (SDB 1F1, SDB 1F2, SDB 3F1, SDB 3F2, SDB
5F1, SDB 5F2, SDB 6F1, SDB 6F2, SDB, 8F1, SDB 8F2, SDB 9F1, SDB 9F2, SDB 10F1 & SDB 10F2 at
2nd, 3rd, 5th, 6th, 8th, 9th & 10th Floors
Sl.
No.
1

Description of Load

Watt per
Unit

No.

Demand,
Watt

Remark

Light points:
Wall Bracket with 2x23 W CFL (B)

46

19

874

874 (Warm Colour Lamp)

2' F/T Light over Mirror (M)

25

125

125

Ceiling Light (CL)

23

22

506

506

Tube Light (T)

50

Chandelier (CH)

300

600

600

Ceiling mounted Spot light with


23 W CFL (SP)

23

184

184

Ceiling mounted Pendant light with


23 W CFL (PD)

23

46

46

Ceiling mounted Traction light with


50 W Halogen Lamp (TR)

50

0 Average 6 nos lamp in each

Water Proof garden light with


23
W CFL (GL)

23

58

2335

1134

13

910

Total
2

Connected
Load, Watt

Ceiling Fan (F)

273713865.xls

70

13 of 14

Exhaust Fan (EX)

70
Total

490

20

770

5A/6A 2 Pin Socket (TP/PB)

200

21

4200

Average watts

10/15 A 3 Pin socket (P)

300

12

3600

Average watts

10/15 A 3 Pin+ 2pin socket (R)

500

1500

Average watts

Total

36

2500

25 A 3 Pin Socket (QA) for Split Air


Conditioner

3000

9000

20 A 3 Pin Socket (QA) for Split Air


Conditioner

2000

8000

7
9

20 A 3 Pin Socket (QG) for 15


Gallons Elect Geyser

1500
Total

11900 Average 13.5 tr connected &


70% diversity considered
9000

3000

39035

19304

Say 38 kW
Revised Load Calculation is based with Electric Geyser

273713865.xls

14 of 14

Say 19 kW