Manual
1.
Introduction
1.1
1.2
1.3
2.
Handling Cautions
2.1
2.2
2.3
2.4
2.5
2.6
2.7
3.
Mounting................................................................... 15
Mounting the Diaphragm Seals ............................... 15
Diaphragm Seals Installation Consideration............ 16
Affixing the Teflon Film ............................................. 17
Rotating Transmitter Section.................................... 18
Changing the Direction of Integral Indicator............. 18
Impulse Piping Installation Precautions ................... 19
Impulse Piping Connection Examples ..................... 21
Process Piping Installation Precautions................... 22
Wiring
5.1
5.2
5.3
5.4
5.5
6.
5.
Operation
6.1
6.2
7.
8.
Parameter Summary
IM 01C22A01-01E
Yokogawa Electric Corporation
3
4
Installation
3.1
3.2
3.3
3.4
3.5
3.6
4.
2nd Edition
5
6
7
8
<1. Introduction>
1.
Introduction
Document No.
Style
IM 01C21B01-01E
S1
IM 01C21C01-01E
S1
IM 01C21D01-01E
S1
IM 01C21F01-01E
S2
IM 01C22H01-01E
S2
IM 01C22J01-01E
S2
EJA115
IM 01C22K01-01E
S3
IM 01C22T01-01E
IM 01C22T02-01E
IM 01C22T03-00E
NOTE
For FOUNDATION Fieldbus, PROFIBUS PA and HART
protocol versions, please refer to manuals in the
attached CD-ROM, in addition to this manual.
The following safety symbol marks are used in this
manual:
WARNING
Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
IM 01C22A01-01E
1
Introduction
<1. Introduction>
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may
also be used to alert against unsafe practices.
IMPORTANT
Indicates that operating the hardware or software in
this manner may damage it or lead to system failure.
NOTE
Draws attention to information essential for
understanding the operation and features.
Direct current
1.1
(a) Installation
The instrument must be installed by an expert
engineer or a skilled personnel. The procedures
described about INSTALLATION are not permitted for
operators.
In case of high process temperature, care should
be taken not to burn yourself because the surface of
body and case reaches a high temperature.
The instrument installed in the process is under
pressure. Never loosen the process connector bolts
to avoid the dangerous spouting of process fluid.
During draining condensate from the pressure
detector section, take appropriate care to avoid
contact with the skin, eyes or body, or inhalation of
vapors, if the accumulated process fluid may be toxic
or otherwise harmful.
When removing the instrument from hazardous
processes, avoid contact with the fluid and the interior
of the meter.
All installation shall comply with local installation
requirement and local electrical code.
(b) Wiring
The instrument must be installed by an expert
engineer or a skilled personnel. The procedures
described about WIRING are not permitted for
operators.
Please confirm that voltages between the power
supply and the instrument before connecting the
power cables and that the cables are not powered
before connecting.
(c) Operation
Wait 10 min. after power is turned off, before opening
the covers.
(d) Maintenance
Please do not carry out except being written to
maintenance descriptions. When these procedures
are needed, please contact nearest YOKOGAWA
office.
Care should be taken to prevent the build up of drift,
dust or other material on the display glass and name
plate. In case of its maintenance, soft and dry cloth is
used.
(f)
Modification
1.2
Warranty
IM 01C22A01-01E
<1. Introduction>
1
Introduction
IM 01C22A01-01E
<1. Introduction>
1.3
ATEX Documentation
SK
CZ
DK
LT
LV
EST
NL
PL
SF
SLO
P
F
BG
D
RO
GR
IM 01C22A01-01E
2.
Handling Cautions
Process
connections
1, 2, 3, and 4
EJA118W
Mounting bracket
A, B, C, and D
Mounting bracket
E and F
Option code /T
Option code /T
Part name
Qty
Process connector
Process connector
gasket
Process connector bolt
Process connector
Process connector
gasket
U-bolt
U-bolt nut
Mounting bracket
Plate (Flat type)
Teflon film
Adapter
Fluorinated oil
U-bolt (L)
Mounting bracket
(L or flat type)
Transmitter mounting
bolt
Mounting bracket
(L or flat type)
Plate
Adapter
Teflon film
Fluorinated oil
Teflon film
Fluorinated oil
U-bolt (S)
U-bolt nut (L)
F0202.ai
Figure 2.1
2.1
F0203.ai
Figure 2.2
EJA110A
1
A
EJA120A
EJA130A - 2 - B
3
C
EJA310A
4
D
EJA430A
EJA440A
2.2
1
EJA210A
2
- -
EJA220A
3
4
Name Plate
EJA118
A
- - -
EJA438
B
A
B
EJA115 - -
C
D
EJA510A
E
- -
EJA530A
F
F0201.ai
IM 01C22A01-01E
Handling Cautions
EJA210A
EJA220A
EJA310A
EJA430A
EJA440A
EJA210A
EJA438W
Mounting bracket
(L type)
U-bolt nut
Suffix code
Process
connections
1, 2, 3, and 4
EJA510A
EJA530A
Mounting bracket
(Flat type)
EJA110A
EJA120A
EJA130A
EJA110A
EJA120A
EJA130A
EJA310A
EJA430A
EJA440A
EJA118
EJA438
EJA115
Bolt
Process connector
Process connector
Gasket
U-bolt
2.3
2.4
NOTE
Pressure Connection
WARNING
Installation of Explosion
Protected Type
CAUTION
This instrument is tested and certified as intrinsically
safe type or explosionproof type. Please note that the
construction of the instrument, installation, external
wiring, maintenance or repair is strictly restricted, and
non-observance or negligence of this restriction would
result in dangerous condition.
WARNING
To preserve the safety of explosionproof equipment
requires great care during mounting, wiring, and
piping. Safety requirements also place restrictions on
maintenance and repair activities. Please read the
following sections very carefully.
CAUTION
2.4.1 FM Approval
Maximum working pressure of the model EJA120A
differential pressure transmitter is 50 kPa
{0.5 kgf/cm2}.
Should the pressure exceed 50 kPa {0.5 kgf/cm2}, it
is possible to break the sensor. Proceed with caution
when applying pressure.
a.
IM 01C22A01-01E
Note 3. Installation
Barrier must be installed in an enclosure that meets
the requirements of ANSI/ISA S82.01.
Control equipment connected to barrier must not use
or generate more than 250 V rms or V dc.
Installation should be in accordance with ANSI/ISA
RP12.6 Installation of Intrinsically Safe Systems for
Hazardous (Classified) Locations and the National
Electric Code (ANSI/NFPA 70).
The configuration of associated apparatus must be
FMRC Approved.
Dust-tight conduit seal must be used when installed in
a Class II, III, Group E, F and G environments.
Associated apparatus manufacturers installation
drawing must be followed when installing this
apparatus.
The maximum power delivered from the barrier must
not exceed 0.9 W.
Note a warning label worded SUBSTITUTION OF
COMPONENTS MAY IMPAIR INTRINSIC SAFETY,
and INSTALL IN ACCORDANCE WITH DOC. No.
IFM012-A12 P.1 and 2.
[Intrinsically Safe]
Hazardous Location
Non-hazardous Location
Safety Barrier
+
+
General
Purpose
Equipment
+
[Nonincendive]
Hazardous Location
Non-hazardous Location
2
General
Purpose
Equipment
Not Use
Safety Barrier
F0204.ai
b.
FM Explosionproof Type
Caution for FM explosionproof type.
IM 01C22A01-01E
Handling Cautions
Note 3. Installation
All wiring shall comply with Canadian Electrical Code
Part I and Local Electrical Codes.
The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation and Yokogawa Corporation
of America is prohibited and will void Canadian
Standards Intrinsically safe and nonincendive
Certification.
c.
[Intrinsically Safe]
Hazardous Location
Non-hazardous Location
Safety Barrier
+
+
General
Purpose
Equipment
+
[Nonincendive]
Hazardous Location
Non-hazardous Location
General
Purpose
Equipment
Not Use
Safety Barrier
F0205.ai
b.
42 V DC Max.
4 to 20 mA DC
Signal
Sealing Fitting
Conduit
EJA Series
42 V DC Max.
4 to 20 mA DC
Signal
a.
50 cm Max.
Sealing Fitting
EJA Series
F0206.ai
IM 01C22A01-01E
2
Handling Cautions
Note 3. Operation
Keep the CAUTION label attached to the transmitter.
CAUTION: OPEN CIRCUIT BEFORE
REMOVING COVER.
OUVRIR LE CIRCUIT AVANT DNLEVER LE
COUVERCLE.
Take care not to generate mechanical sparking when
accessing to the instrument and peripheral devices in
a hazardous location.
c.
10
Marking
Note 4. Operation
WARNING:
WHEN AMBIENT TEMPERATURE 55C,
USE THE HEAT-RESISTING CABLES 90C.
Note 5. Special Conditions for Safe Use
WARNING:
IN THE CASE WHERE THE ENCLOSURE OF
THE PRESSURE TRANSMITTER IS MADE OF
ALUMINUM, IF IT IS MOUNTED IN AN AREA
WHERE THE USE OF ZONE 0 IS REQUIRED,
IT MUST BE INSTALLED SUCH, THAT, EVEN IN
THE EVENT OF RARE INCIDENTS, IGNITION
SOURCES DUE TO IMPACT AND FRICTION
SPARKS ARE EXCLUDED.
[Intrinsically Safe]
Hazardous Location
Non-hazardous Location
IECEx certified
Safety Barrier
+
+
General
Purpose
Equipment
+
[type n]
Hazardous Location
Non-hazardous Location
Not Use
Safety Barrier
F0208.ai
b.
IM 01C22A01-01E
11
Safety Barrier *1
Supply
F0209.ai
b.
IM 01C22A01-01E
2
Handling Cautions
*1:
Non-hazardous Location
12
[Installation Diagram]
Hazardous Location
(Zone 2 only)
Transmitter
Non-hazardous Location
Supply
c.
WARNING
When using a power supply not having a nonincendive
circuit, please pay attention not to ignite in the
surrounding flammable atmosphere.
In such a case, we recommend using wiring metal
conduit in order to prevent the ignition.
Applicable Standard: EN60079-15
Referential Standard: IEC60079-0,
IEC60079-11
Type of Protection and Marking Code: Ex nL IIC T4
Temperature Class: T4
Enclosure: IP67
Process Temperature: 120C max.
Ambient Temperature: 40 to 60C
Note 1. Electrical Data
Ui = 30 V
Effective internal capacitance; Ci = 22.5 nF
Effective internal inductance; Li = 730 H
Note 2. Installation
All wiring shall comply with local installation
requirements. (refer to the installation diagram)
Power Supply
F0210.ai
Marking
(3) Installation
WARNING
All wiring shall comply with local installation
requirement and local electrical code.
There is no need of the conduit seal for both of
Division 1 and Division 2 hazardous locations
because this product is sealed at factory.
In case of ANSI 1/2 NPT plug, ANSI hexagonal
wrench should be applied to screw in.
IM 01C22A01-01E
13
(4) Operation
WARNING
OPEN CIRCUIT BEFORE REMOVING COVER.
INSTALL IN ACCORDANCE WITH THIS USERS
MANUAL
Take care not to generate mechanical sparking
when access to the instrument and peripheral
devices in hazardous locations.
The third figure from the last shows the last one figure of
the year of production. For example, the production year
of the product engraved in NO. column on the name
plate as follows is 2001.
12A819857
132
WARNING
*2:
2.5
EN61326-2-3
Name plate
CAUTION
This instrument is a Class A product, and it is designed
for use in the industrial environment. Please use this
instrument in the industrial environment only.
NOTE
YOKOGAWA recommends customer to apply the
Metal Conduit Wiring or to use the twisted pair Shield
Cable for signal wiring to conform the requirement
of EMC Regulation, when customer installs the EJA
Series Transmitters to the plant.
2.6
(1) General
F0212.ai
IM 01C22A01-01E
Handling Cautions
14
2.7
PS*1
(bar)
V(L)
PS-V
(bar-L)
Category*2
160
0.01
1.6
Article 3,
paragraph 3 (SEP)
EJA120A
0.5
0.01
0.005
Article 3,
paragraph 3 (SEP)
EJA130A
420
0.01
4.2
Article 3,
paragraph 3 (SEP)
EJA130A
With code /PE3
420
0.01
4.2
III
EJA310A
160
0.01
1.6
Article 3,
paragraph 3 (SEP)
EJA430A
160
0.01
1.6
Article 3,
paragraph 3 (SEP)
EJA440A
500
0.01
50
Article 3,
paragraph 3 (SEP)
EJA440A
With code /PE3
500
0.01
50
III
EJA510A
500
0.01
50
Article 3,
paragraph 3 (SEP)
EJA510A
With code /PE3
500
0.01
50
III
EJA530A
500
0.01
50
Article 3,
paragraph 3 (SEP)
EJA530A
With code /PE3
500
0.01
50
III
*1:
*2:
(3) Operation
CAUTION
The temperature and pressure of fluid should be
applied under the normal operating condition.
The ambient temperature should be applied under
the normal operating condition.
Please pay attention to prevent the excessive
pressure like water hammer, etc. When water
hammer is to be occurred, please take measures
to prevent the pressure from exceeding PS by
setting the safety valve, etc. at the system and the
like.
When external fire is to be occurred, please take
safety measures at the device or system not to
influence the transmitters.
IM 01C22A01-01E
15
<3. Installation>
3.
Installation
IMPORTANT
Pipe
(Open to atmosphere)
Zero-adjustment screw
Measurment span code
F00301.ai
Figure 3.1
Mounting
F0302.ai
Figure 3.2
Transmitter Mounting
(Horizontal Impulse Piping Type)
Plate
U-bolt nut (S)
U-bolt (L)
Mounting bracket
50 mm(2-inch) pipe
F0304.ai
Figure 3.4
3.2
Mounting
bracket
Transmitter
mounting bolt
F0303.ai
Figure 3.3
Transmitter Mounting
(Vertical Impulse Piping Type)
IM 01C22A01-01E
Installation
3.1
Adapter
U-bolt (S)
16
<3. Installation>
3.3
Gasket
Nut
F0305.ai
3.2.2 EJA118
and EJA438
Bolt
IMPORTANT
When measuring the liquid level of the tank, the
minimum liquid level (zero point) must be set to a
level at least 50 mm above the center of the high
pressure side diaphragm seal (see Figure 3.2.3).
Correctly install the diaphragm seals on the high
and low pressure sides of the process, checking
the label on each seal.
To avoid measuring error duets temperature
difference between the two diaphragm seals,
capillary tube must be bound together. The
capillary tube must be securely fixed to the tank
wall to prevent movement by wind or vibration.
If the capillary tube is too long, loosely coil the
excess and secure using suitable clamps.
Stud bolt
Figure 3.5
IMPORTANT
Install the sealed diaphragm
so that the shank positions
downward.
Nut
High
pressure
side
d
Gasket
The product is
shipped with these
parts assembled.
Low
pressure
side
Minimum
liquid level
50mm minimum
Figure 3.6
Figure 3.7
IM 01C22A01-01E
17
<3. Installation>
Low
pressure side
IMPORTANT
The transmitter should be installed below the high
pressure (HP) process connection to ensure a
positive head pressure of fill fluid. The recommended
height between the HP process connection and the
transmitter is show in the following table. Pay special
attention to vacuum applications.
Model
Height (h)
600 mm
EJA118
EJA438W Wetted parts material code S,
700 mm
T, U, EJA438N
EJA438W Wetted parts material code H 1,300 mm
P
h
(+)
0
()
High
pressure side
F0308.ai
Figure 3.8
(PP0)dHg
ds
3.4
7.5103 [mm]
3178
3596
6074
4711
T, U
5254
6980
13019
EJA438
Wetted parts material
code
P0: Minimum working
pressure limit
C, E
1.07
0.94
1.09
D
1.90 to
1.92
Teflon film
PART No.
EJA210A F9347YD
2B
(50A)
EJA118W
EJA438W
3B(80A)
F9347YA
F9347XA
Diaphragm
Gasket area
F0309.ai
Figure 3.9
IM 01C22A01-01E
3
Installation
18
<3. Installation>
3.5
Mounting screw
IMPORTANT
90
90
Shrouding bolt
Figure 3.11
Pressure-detector section
Rotate 90o or 180o segments
Conduit connection
Transmitter section
F0310.ai
Figure 3.10
3.6
IMPORTANT
The terminal box cover is locked by an Allen head
bolt (a shrouding bolt) on CENELEC and IECEx
flameproof type transmitters. When the shrouding bolt
is driven clockwise by an Allen wrench, it is going in
and cover lock is released, and then the cover can be
opened by hand.
When a cover is closed it should be locked by a
shrouding bolt without fail. Tighten the shrouding bolt
to a torque of 0.7 Nm.
1) Remove the cover.
2) Supporting the integral indicator by hand, loosen its
two mounting screws.
3) Dismount the LCD board assembly from the CPU
assembly. When doing this, carefully pull the LCD
board assembly straight forward so as not to damage
the connector pins between it and the CPU assembly.
IM 01C22A01-01E
19
4.
4.1
Process connection
Process connector
Bolt
Figure 4.1
F0401.ai
Impulse piping
Nipple
Vent plug
(optional)
3-valve
manifold
Stop valve
(low pressure side)
Equalizing valve
(balancing)
Pipe
Pipes
Stop valve
(high pressure side)
Ball head
lock nut
Nipple
Process
connector
50 mm(2-inch) pipe
57 mm
54 mm
51 mm
F0402.ai
Figure 4.2
Ball head
lock nut
Process connector
bolts
Figure 4.3
F0403.ai
IM 01C22A01-01E
20
Impulse
piping
3-valve
manifold
Equalizing
valve
Equalizing valve
Stop valve
Impulse
piping
Figure 4.4
Bolts
Stop valve
[Gas]
45 45
[Liquid]
[Steam]
45
45
45
45
F0405.ai
Stop valve
Stop valve
Gasket
Process
connector
NOTE
3-valve manifold
F0404.ai
3-Valve Manifold
(Direct-Mounting Type)
Figure 4.5
IM 01C22A01-01E
21
IMPORTANT
Liguid
Orifice
Tap valve
Union
or flange
Steam
Gas
Condensate pot
Tee
3-valve
manifold
Drain valve
Drain plug
F0406.ai
Figure 4.6
Open Tank
Tap valve
Union or flange
Vent plug
Tee
Pipe (opened to
atmosphere at low
pressure side)
4.2
Drain valve
Drain plug
F0407.ai
Figure 4.7
Liquid
Gas
Tap valve
Steam
Union or flange
Union or flange
Tap valve
Drain plug
Drain valve
Union or
flange
Tee
Tee
Tee
Union or flange
Tap valve
Drain valve
Drain plug
Drain valve
Drain plug
F0408.ai
Figure 4.8
IM 01C22A01-01E
22
4.3
Manifold
NOTE
If the process fluid is a gas, then as a rule the
manifold must be located at the downside of the
pressure-sensing assembly.
If the process fluid is a liquid, then as a rule the
manifold must be located at the upside of the
pressure-sensing assembly.
Process connector
(high pressure side)
F0409.ai
Figure 4.9
Union or flange
Stop valve
Manifold
Process piping
Liquid flow measurement
Manifold
Union or flange
Process piping
Figure 4.10
Stop valve
F0410.ai
IM 01C22A01-01E
23
<5. Wiring>
5.
Wiring
5.2
NOTE
For FOUNDATION Fieldbus and PROFIBUS PA
communication types, please refer to manuals in the
attached CD-ROM.
5.1
Connections of External
Wiring to Terminal Box
Wiring Precautions
+
Power supply
IMPORTANT
Shrouding Bolt
Shrouding Bolt
F0501.ai
F0502.ai
Figure 5.1
+
Power supply
250 to 600
Ignore the polarity
since it is AC-coupled
to the terminal box.
BT200 etc.
Figure 5.2
5.3
F0503.ai
Wiring
CAUTION
IM 01C22A01-01E
5
Wiring
24
<5. Wiring>
Drain plug
F0506.ai
Figure 5.5
Non-hazardous Location
Distributor
(Power supply unit)
F0504.ai
Figure 5.3
Flameproof packing
adapter
Apply a non-hardening
sealant to the threads for
waterproofing.
Wiring metal
conduit
Tee
Non-hazardous Location
Wiring metal
conduit
Apply a non-hardening
sealant to the threads for
waterproofing.
Tee
Drain plug
F0507.ai
Receiver
instrument
Safety barrier
Figure 5.4
F0505.ai
Figure 5.6
Optional
Code
G11
G12
8 to 10
10.1 to 12
16
16
Part
Number
8-10
G9601AM
10-12
IM 01C22A01-01E
25
<5. Wiring>
2) Insert the cable through the union cover, the union
coupling, the clamp nut, the clamp ring, the gland,
the washer, the rubber packing, and the packing
box, in that order.
3) Insert the end of the cable into the terminal box.
4) Tighten the union cover to grip the cable. When
tightening the union cover, tighten approximately
one turn past the point where the cable will no
longer move up and down.
Proper tightening is important. If it is too tight, a
circuit break in the cable may occur; if not tight
enough, the flameproof effectiveness will be
compromised.
5) Fasten the cable by tightening the clamp nut.
6) Tighten the lock nut on the union cover.
7) Connect the cable wires to each terminal.
Apply a non-hardnening
sealant to the threads for
waterproofing.
O-ring
Adapter body
Lock nut
Wrench
Packing box
Rubber packing
Washer
Gland
Clamp ring
5.4
Grounding
WARNING
For TIIS flameproof type and intrinsically safe,
grounding should satisfy Class D requirements
(grounding resistance, 100 or less).
Transmitter terminal box
Ground terminal
(Inside)
Clamp nut
Union coupling
Lock nut
Ground terminal
(Outside)
F0610.ai
Wrench
Figure 5.9
Union cover
Ground Terminals
Cable
F0508.ai
Hazardous area
Flameproof
heavy-gauge
steel conduit
Tee
Drain plug
600
Flameproof flexible
metal conduit
Apply a non-hardening
sealant to the threads
of these fittings for
waterproofing
External
load
resistance
R ()
R=
E10.5
0.0236
Communication
applicable range
BRAIN and HART
250
Seal fitting
After wiring, impregnate the fitting
with a compound to seal tubing.
F0509.EPS
Figure 5.8
5.5
Wiring
Figure 5.7
10.5
16.4
24.7
42
Figure 5.10
IM 01C22A01-01E
26
<6. Operation>
6.
Operation
Output Status Setting at CPU Failure
NOTE
For FOUNDATION Fieldbus and PROFIBUS PA
communication types and for the transmitter operating
confirmation and zeroing by any communication
method, refer to manuals in the attached CD-ROM for
further information.
6.1
CPU assembly
Burn-Out
Direction
Output at
Burn-Out
HIGH
110% or higher
LOW
-5% or lower
H L
H L
F0602.ai
Figure 6.1
Slide switch
F0601.ai
L
Y
NOTE
If any of the error indications above appears on the
display of the integral indicator, refer to Chapter 7 for
corrective action.
L
Y
Burn-out Direction
H
N
H
N
L
Y
HIGH
H
N
LOW
L
Y
H
N
NO
L
Y
H
N
YES
F0603.ai
Figure 6.2
IM 01C22A01-01E
<6. Operation>
6.2
27
IMPORTANT
Do not turn off the power to the transmitter
immediately after a zero adjustment. Powering off
within 30 seconds after a zero adjustment will return
the adjustment back to the previous settings.
Zero-adjustment screw
F0604.ai
6
Operation
IM 01C22A01-01E
28
7.
For FOUNDATION Fieldbus and PROFIBUS PA communication types, please refer to manuals in the attached CD-ROM.
The table below shows a summary of error messages for BRAIN and HART protocols.
Table 7.1
Integral
Indicator
Display
Cause
Countermeasure
None
GOOD
---
ERROR
Er. 01
Capsule problem.*1
Er. 02
Amplifier problem.
Replace amplifier.
Er. 03
OUT OF RANGE
Input is outside
measurement range limit
of capsule.
Check input.
Er. 04
OUT OF SP RANGE
Er. 05
Capsule temperature
is outside range (-50 to
130C).
Er. 06
Amplifier temperature
is outside range (-50 to
95C).
Er. 07
OVER OUTPUT
Er. 08
OVER DISPLAY
Displayed value is
outside high or low range
limit value.
Er. 09
ILLEGAL LRV
Er. 10
ILLEGAL URV
Er. 11
ILLEGAL SPAN
Er. 12
*1:
*2:
*3:
This error code appears at a capsule problem or when an illegal overpressure is applied to the pressure sensor.
If the normal pressure is regained, the Er.01 will disappear according to the setting of the parameter of E50AUTO RECOVER.
When the E50AUTO RECOVER is set to ON, the Er.01 will disappear automatically. The default setting for this parameter is
ON. When the E50AUTO RECOVER is set to OFF, restart the transmitter to cancel Er.01. If no error code appears then, perform
necessary adjustments such as zero-adjustment to continue the operation. If the error code still appears, replace the capsule
assembly.
For Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.
IM 01C22A01-01E
29
8.
Parameter Summary
IMPORTANT
NOTE
1
2
3
4
5
6
7
Pressure
Percent Range
Analog Output
Sensor Temperature
Static Pressure
Engineering Unit
Engineering Display
2 DIAGNOSTICS
AND SERVICE
1 TEST/STATUS
2 Loop Test
Hot Key
1 Keypad Input
1
2
3
4
5
6
LRV
URV
Unit
LSL
USL
Min Span
1
2
3
4
Write protect
Enable wrt 10 min
New password
Software seal
1 Self Test
2 Status
1 RERANGE
1 Keypad Input
2 Apply Values
2 TRIM ANALOG
OUTPUT
1 Digital-to-Analog Trim
2 Scaled Digital-to-Analog Trim
1 Tag
2 Unit
3 BASIC SETUP
1
2
3
4
5
3 SENSOR TRIM
3 RERANGE
1 Keypad Input
2 Apply Values
4 DEVICE INFO
1
2
3
4
Online Menu
5 Transfer Function
DEVICE SETUP
Pres
A01 Out
LRV
URV
6 Damp
7 Low Cut
Date
Descriptor
Message
Write Protect
4 DETAILED
SETUP
2 SIGNAL
CONDITION
1 Pressure Sensor
2 Temperature
Sensor
1 Snsr temp
2 Amp temp
3 Sensor temp Unit
3 Static Pressure
Sensor
1 Static Pressure
2 Static Pressure Unit
1 PROCESS
VARIABLES
1 Pressure
2 Percent Range
3 Sensor Temperature
2
3
4
5
6
7
8
9
1 Keypad Input
2 Apply Values
RERANGE
Unit
Transfer Function
Damp
Low Cut
Cut Mode
Bi-dir Mode
H2O Unit Select
Pressure
Percent Range
Analog Output
Sensor Temperature
Static Pressure
Engineering Unit
Engineering Display
1
2
3
4
5
6
Loop Test
Digital-to-Analog Trim
Scaled D/A Trim
Auto recover
AO lower limit %
AO upper limit %
4 HART OUTPUT
1
2
3
4
Poll Address
Number of Request Preambles
Burst Mode
Burst Option
1 Display Mode
2 Display Function
3 Engineering
Display Range
1
2
3
4
Engineering Unit
Engineering Display LRV
Engineering Display URV
Engineering Display Point
1 PROCESS
VARIABLES
3 Analog Output
Alarm
5 REVIEW
5 DEVICE
INFORMATION
Zero Trim
Pressure
Lower Sensor Trim
Upper Sensor Trim
Sensor Trim Point
Clear snsr trim
1
2
3
4
5
6
7
2 ANALOG
OUTPUT
4 DISPLAY
CONDITION
Percent Range
Pressure
Unit
Sensor Trim
1
2
3
4
5
6
7
8
Parameter Summary
3 OUTPUT
CONDITION
Zero Trim
Pressure
Lower Sensor Trim
Upper Sensor Trim
Sensor Trim Points
Clear snsr trim
1
2
3
4
8 Cut Mode
1 SENSORS
1
2
3
4
5
6
3 CALIBRATION
IM 01C22A01-01E
30
Item
MODEL
TAG NO.
SELF CHECK
DISPLAY
OUTPUT (%)
ENGR. OUTPUT
AMP TEMP
CAPSULE TEMP
STATIC PRESS
A40 INPUT
A60 SELF CHECK
B
B10
B11
B20
B21
B30
B40
B60
SENSOR TYPE
MODEL
STYLE NO.
LRL
URL
MIN SPAN
MAX STAT.P.
SELF CHECK
Description
Rewritability
Model+capsule type
Tag number
Self-diagnostic result
Measured data display
Output (in %)
Output (in engineering units)
Amplifier temperature
Capsule temperature
Static pressure
16 alphanumerics
GOOD/ERROR
Menu name
5 to 110%*3
19999 to 19999
Unit specified in D30
Unit specified in D30
Unit specified in D31*1
32000 to 32000
Sensor type
Model+span
Style number
Lower range-limit
Upper range-limit
Minimum span
Maximum static pressure*6
C SETTING
C10 TAG. NO.
Self-diagnostic
messages
Setting data
Tag number
C60
D
D10
D11
D15
D16
D20
Self-diagnostic messages
Auxiliary setting data 1
Low cut
Low cut mode
Lower output range-limit
Lower output range-limit
Display selection
SELF CHECK
AUX SET 1
LOW CUT
LOW CUT MODE
OUT LIMIT(L)
OUT LIMIT(H)
DISP SELECT
Remarks
Applicability
F
P
L
32000 to 32000
32000 to 32000
32000 to 32000
Same as A60
Menu name
16 alphanumerics
Selected from mmH2O,
mmAq,mmWG, mmHg,
Torr, Pa, hPa, kPa, MPa,
mbar, bar, gf/cm2, kgf/cm2,
inH2O, inHg, ftH2O, psi, or atm
32000 to 32000(but within
measurement range)
32000 to 32000(but within
measurement range)
Selected from 0.2*2, 0.5, 1.0,
2.0, 4.0, 8.0, 16.0, 32.0, or
64.0 sec.
Selected from OUT:LIN; DSP:
LIN, OUT:LIN; DSP:SQR,
OUT:SQR; DSP:SQR
Default Value
Same as A60
Menu name
0.0 to 20.0%
LINEAR/ZERO
5.0 to 110.0%
5.0 to 110.0%
NORMAL %/USER SET, USER
& %/INP PRES, PRES & %
8 uppercase alphanumerics
19999 to 19999
19999 to 19999
As specified when
ordered.
As specified when
ordered.
As specified when
ordered.
As specified when
ordered.
2.0 s
As specified when
ordered.
If not specified,
OUT: LIN; DSP: LIN.
10.0%
LINEAR
5.0%*7
110.0%
As specified when
ordered.
As specified when
ordered.
As specified when
ordered.
IM 01C22A01-01E
31
No.
Item
Description
Output reversal
SELF CHECK
AUX SET 2
DFS MODE
TEMP SELECT
TEMP ZERO
BI DIRE MODE
AUTO RECOVER
SELF CHECK
ADJUST
ZERO ADJ
ZERO DEV.
SPAN ADJ
EXT. ZERO ADJ
J30
J31
J60
K
K10
OUTPUT 4mA
OUTPUT 20mA
SELF CHECK
TEST
OUTPUT in %
K60
M
M10
M20
M30
M40
M50
M60
P
P10
P11
P12
P13
P60
SELF CHECK
MEMO
MEMO 1
MEMO 2
MEMO 3
MEMO 4
MEMO 5
SELF CHECK
RECORD
ERROR REC 1
ERROR REC 2
ERROR REC 3
ERROR REC 4
SELF CHECK
Self-diagnostic messages
Memo
Memo
Memo
Memo
Memo
Memo
Self-diagnostic messages
History of the errors
Last error
One time before
Two time before
Three time before
Self-diagnostic messages
*1:
*2:
*3:
*4:
*5:
*6:
*7:
Remarks
deg C/deg F
Selected from mmH2O,
mmAq, mmWG, mmHg, Torr,
Pa, hPa, kPa, MPa, mbar,
bar, gf/cm2, kgf/cm2, inH2O,
inHg, ftH2O, psi, or atm
NORMAL/REVERSE
NORMAL/REVERSE*4
HIGH/LOW, 5 to 110%*3
HOLD/HIGH/LOW, 5 to
110%*3
Same as A60
Menu name
OFF/ON*5
AMP. TEMP/CAP. TEMP*5
610.00*5
OFF/ON
OFF/ON
Same as A60
Menu name
32000 to 32000
32000 to 32000
Default Value
deg C
As specified when
ordered. If not
specified, MPa.
If not specified,
NORMAL.
NORMAL
Applicability
F
P
L
HIGH
HIGH
ON
CAP. TEMP
0.00
OFF
ON
Same as A60
Menu name
5 to 110.0%*3
10.00 to 10.00%
ENABLE/INHIBIT
0.00%
10.00 to 10.00%
10.00 to 10.00%
Same as A60
Menu name
5 to 110.0%*3 Displays
ACTIVE while executing
Same as A60
Menu name
8 uppercase alphanumerics
8 uppercase alphanumerics
8 uppercase alphanumerics
8 uppercase alphanumerics
8 uppercase alphanumerics
Same as A60
0.00%
0.00%
8
Parameter Summary
H60
J
J10
J11
J15
J20
Self-diagnostic messages
Auxiliary setting data 2
DFS mode
Reference temperature sensor
Zero shift conpensation setup
Bidirectional mode
Auto-recover from sensor
error
Self-diagnostic messages
Automatic setup
Automatic measurement
range lower range value setup
Automatic measurement range
higher range value setup
Self-diagnostic messages
Adjustment data
Automatic zero adjustment
Manual zero adjustment
Manual span adjustment
External zero adjustment
screw permission
4mA adjustment
20mA adjustment
Self-diagnostic messages
Tests
Test output % setting
Rewritability
In case of Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.
When Optional code /F1 is specified, substitute the value with 0.1.
When Optional code /F1 is specified, substitute the value 5 with 2.5.
Not applicable for Model EJA115.
Applicable only for Model EJA118W, EJA118N, EJA118Y, EJA438W, and EJA438N.
See MWP(max. working pressure) on the nameplate. B40 shows an approximate value of maximum pressure for the capsule.
Unless otherwise specified by order. When Optional code /F1 is specified, substitute the value 5 with 2.5.
IM 01C22A01-01E
32
3. Terminology
EX-A03E
33
CAUTION
If intrinsically safe apparatus and safety barriers require
maintenance service and checking, a gas detector shall be
used to ensure that there is no explosive gas in the location
(maintenance servicing shall be conducted in a nonhazardous location).
(3) Repair
Intrinsically safe apparatus and safety barriers shall be repaired
by manufacturers.
EX-A03E
34
3. Terminology
(1) Enclosure
An outer shell of an electrical apparatus, which encloses live
parts and thus is needed to configure explosion-protected
construction.
(2) Shroud
A component part which is so designed that the fastening of joint
surfaces cannot be loosened unless a special tool is used.
EX-B03E
35
(2) Repair
If the flameproof apparatus requires repair, turn off the power
and transport it to a safety (non-hazardous) location. Observe
the following points before attempting to repair the apparatus.
(a) Make only such electrical and mechanical repairs as will
restore the apparatus to its original condition. For the
flameproof apparatus, the gaps and path lengths of joints
and mating surfaces, and mechanical strength of enclosures
are critical factors in explosion protection.
Exercise great care not to damage the joints or shock the
enclosure.
(b) If any damage occurs in threads, joints or mating surfaces,
inspection windows, connections between the transmitter
and terminal box, shrouds or clamps, or external wiring
connections which are essential in flameproofness, contact
Yokogawa Electric Corporation.
CAUTION
Do not attempt to re-process threaded connections or refinish
joints or mating surfaces.
(c) Unless otherwise specified, the electrical circuitry and
internal mechanisms may be repaired by component
replacement, as this will not directly affect the requirements
for flameproof apparatus (however, bear in mind that the
apparatus must always be restored to its original condition).
If you attempt to repair the flameproof apparatus, companyspecified components shall be used.
(d) Before starting to service the apparatus, be sure to check all
parts necessary for retaining the requirements for flameproof
apparatus. For this, check that all screws, bolts, nuts, and
threaded connections have properly been tightened.
IMPORTANT
The cable glands (cable entry devices for flameproof type)
conforming to IEC Standards are certified in combination
with the flameproof apparatus. So, Yokogawa-specified cable
entry devices for flameproof type shall be used to meet this
demand.
References:
(1) Type Certificate Guide for Explosion-Protected Construction
Electrical Machinery and Equipment (relating to Technical
Standards Conforming to International Standards), issued by
the Technical Institution of Industrial Safety, Japan
(2) USERS GUIDELINES for Electrical Installations for
Explosive Gas Atmospheres in General Industry (1994),
issued by the Japanese Ministry of Labour, the Research
Institute of Industrial Safety.
EX-B03E
36
Revision Information
Title
Manual No.
Edition
Date
1st
Jan. 2008
2nd
Oct.2008
Page
Revised Item
New publication
12
13
28
29
2.4.4 Change explosion protection marking for type n from EEx to Ex.
2.5 Update EMC conformity standards.
7. Modify descriptions and notes for Er.01.
8. Add new parameters.
IM 01C22A01-01E
OS
CPU
RAM
Display
for Windows
Contents
This CD-R contains information in PDF format that is necessary for safe and effective operation of the product.
Trademarks
Microsoft, MS-DOS, Windows and Windows NT are either registered trademarks or trademarks of Microsoft
Corporation in the United States and/or other countries.
Other company and product names are trademarks or registered trademarks of their respective holders.
www.yokogawa.com/fld/
WARNING: This CD contains software, and is for use in a computer only. Do not play this on
an audio CD player, as the high volume may damage your hearing or audio speakers.
YOKOGAWA EUROPE B. V.
Databankweg 20 Amersfoort 3821 AL, THE NETHERLANDS
Phone : 31-33-464-1611 Fax : 31-33-464-1610
Branch Sales Offices / Wien (Austria), Zaventem (Belgium), Ratingen
(Germany), Madrid (Spain), Runcorn (United Kingdom), Milano (Italy),
Velizy-Villacoublay (France), Budapest (Hungary), Stockholm (Sweden), Sola
(Norway), Warszawa (Poland), Vila Nova de Gaia (Portugal), Bucharest
(Romania)
May 08
Printed in Japan