38AK007, 38AKS013-024, 38ARD012-024, 38ARS008-012

38ARQ008-012, 38ARZ007-012, 38AQS012-016


48/50HJ,TF,TJ,TM004-014
50HJQ,TFQ,TJQ004-012
Accessory Motormaster I Head Pressure Controller
50/60 Hz

Installation Instructions
Part Numbers: 32LT900301, 32LT900611
PACKAGE CONTENTS
ITEM
Motormaster I Controller
No. 10 Sheet Metal Screws
Star Lockwashers
3/ -in. Lg, 4-40 Screws
4
Plate Washers
4-40 Nuts
Wirenuts
Sensor Assembly

INSTALLATION
QUANTITY
1
4
4
2
2
2
2
1

NOTE: The 32LT900301 Motormaster I device is rated at 8 amps, and the 32LT900611
Motormaster I device is rated at 4 amps.

GENERAL
Motormaster I solid-state head pressure control regulates
fan speed. A temperature sensor, mounted on a return bend of
the condenser (outdoor) coil, activates the device. The Motormaster I controller controls the speed of approved condenser
(outdoor) fan motors in order to maintain a constant head pressure in the condenser (outdoor) coil. When properly installed,
the control will maintain the appropriate head pressure at low
ambient temperatures down to 20 F. Usage is shown in
Table 1.

1. Disconnect power to the unit.


2. Disconnect condenser (outdoor) fan motor (OFM) wires
at the contactor and capacitor. Note position of fan blades
in relation to fan orifice.
NOTE: 38ARD012, 38ARQ008-012, 38ARS008-12,
and 38ARZ007-012 units require 2 OFMs.
3. Remove OFM(s) from the unit (except 38AKS013-024,
38ARD014-024, and 38AQS012-016 units with voltages
220-3-50, 208/230-3-60, 400-3-50, and 460-3-60).
4. Remove fan blade(s) from motor(s).
5. Mount Motormaster I controller on the unit. See Fig. 1.
The controller must be mounted vertically with leads at
the bottom. Using the template supplied with the controller, drill 4 mounting holes. To ensure electrical ground,
insert star lockwashers (supplied with the controller) under the heads of the sheet metal screws.
For 38ARD,ARQ,ARZ007-012 units, a field-fabricated
mounting bracket is required (2 for 38ARD012 units).
See Fig. 2. The bracket is mounted under the unit control
box. Mounting holes are provided in the unit basepan.

Table 1 Motormaster I Controller Usage


UNIT

VOLTAGE
MOTOR PART NO.
MOTORMASTER I PART NO.
220-1-50
220-3-50
HC38GE231
32LT900301
208/230-1-60
48/50HJ004,005
208/230-3-60
and 50HJQ004,005
400-3-50
HC36GE461
32LT900611
460-3-60
575-3-60
220-1-50
48/50HJ006-014*;
HC40GE233
220-3-50
32LT900301 (1 required)
50HJQ006-012*;
(1 or 2 required)
208/230-1-60
48/50TF004-014*, 50TFQ004-012*;
208/230-3-60
48/50TJ004-014*;
400-3-50
50TJQ004-012*; and
HC40GE463
32LT900611 (2 required)
460-3-60
48/50TM004-014*
(1 or 2 required)
575-3-60
208/230-1-60
HC42GE230
32LT900301
208/230-3-60
38AK007
575-3-60
460-3-60
HC42GE460
32LT900611
208/230-3-60
HC40GE233 (2 required)
32LT900301 (2 required)
575-3-60
HC40GE463 (2 required)
32LT900611 (2 required)
38ARD012
400-3-50
HC40GE463 (2 required)
32LT900611 (2 required)
460-3-60
208/230-3-60
HC40GE233 (2 required)
32LT900301
575-3-60
HC40GE463 (2 required)
32LT900611
38ARS008-012
400-3-50
HC40GE463 (2 required)
32LT900611
460-3-60
208/230-3-60
HC40GE233 (2 required)
32LT900301
38ARQ008-012
460-3-60
HC40GE463 (2 required)
32LT900611
208/230-3-60
HC38GE231 (2 required)
32LT900301
575-3-60
HC36GE461 (2 required)
32LT900611
38ARZ007
400-3-50
HC36GE461 (2 required)
32LT900611
460-3-60
208/230-3-60
HC40GE233 (2 required)
32LT900301
575-3-60
HC40GE463 (2 required)
32LT900611
38ARZ008-012
400-3-50
HC40GE463 (2 required)
32LT900611
460-3-60
208/230-3-60
Motor
change
not
required
32LT900301
220-3-50
38AKS013-024
38ARD014-024
460-3-60
Motor change not required
32LT900611
38AQS012-016
400-3-50
575-3-60**
HC44VL852
32LT900301
*A capacitor (P/N HC91CA010) and strap (P/N HC98ZZ071) are required for single-phase, 48/50HJ006 and 50HJQ006 and 3-phase 48/50TF,TJ,TM004-006 and 50TFQ,TJQ004-006 units. A
capacitor (P/N HC98KA048) and strap (P/N 317739-303) are required for single-phase 48/50TF,TM,TJ004-006 and 50TJQ004-006 units.
Field-fabricated bracket required for mounting.
**HT01AH852 transformer is required.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Catalog No. 533-80099 Printed in U.S.A. Form 38/48/50-21SI
Pg 1
6-03
Replaces: 38/48/50-13SI
Book 1 1 1 1 4 4 4 4
Tab 1a 1b 3a 5a 2a 5a 6a 6b

6. Route sensor wire from bottom of Motormaster I control to


sensor location as specified in Fig. 3-7. Fasten sensor with
3/ -in. 4-40 screws, plate washers, and 4-40 nuts provided.
4
8.
9.
Sensor assembly is delicate. Handle with care.
7. Replace the OFM(s), if required, with the motor(s) shown
in Table 1. Rewire the motor connections as shown in
Fig. 8-21. Two wirenuts are included in package, if needed.
NOTE: A capacitor is needed on 48/50HJ006 and
50HJQ006 single-phase units; 48/50TF,TJ004-006 units;
and 50TJQ004-006 units.
On single-phase 48/50HJ006 and 50HJQ006 units, use the
capacitor (HC91CA010) as an additional capacitor in parallel. Use the capacitor strap to hold the capacitor in place.
On single-phase and 3-phase 50TFQ,TJQ004-006 and
48/50TF,TM,TJ004-006 units, replace the capacitor with

10.

11.
12.

a field-supplied capacitor (HC98KA048, HC91CA010


respectively). Use the capacitor strap to hold the capacitor
in place.
Coil up all excess wire and secure it next to the controller.
Winter start control is required on all units except
condensing unit heat pumps. On units equipped with a
low-pressure switch on the suction line, disconnect
low-pressure switch and replace it with Carrier part
no. HK02ZB038. Locate the new switch on the access
port located on the liquid line (small rooftop units only).
Wind baffles are required to prevent wind cross currents
from causing abnormally low condensing temperatures.
Fabricate sheet metal baffles as shown in Fig. 22-25. Use
20-gage sheet metal.
Re-install fan blade. Ensure that fan blade is properly located in the orifice. Refer to the base unit installation instructions for further details.
Reconnect power to the unit.

38AK007 UNITS
CONDENSER
COIL

COMPRESSOR

48TJ004-007 UNITS

CONDENSER
COIL

MOTORMASTER --I
CONTROLLER

MOTORMASTER --I
CONTROLLER (38ARD012 ONLY)

48HJ,TF,TJ008-014 UNITS

NOTE: Field-fabricated bracket required for Motormaster I controller mounting.

38ARD012, 38ARS008-012, 38ARQ008-012


AND 38ARZ007-012 UNITS

38AKS013-024, 38ARD014-024, 38AQS012-016 UNITS

Fig. 1 Motormaster I Controller Location


2

50HJ,HJQ,TF,TFQ,TJ,TJQ008-014 UNITS WITH


SINGLE POINT BOX
50TJ004-007 UNITS WITHOUT
SINGLE POINT BOX

50TJ004-007 UNITS WITH


SINGLE POINT BOX

48HJ,TF,TM004-007 UNITS

50HJ,HJQ,TF,TFQ,TJ,TJQ008-014 UNITS WITHOUT


SINGLE POINT BOX

48HJ,TF,TM008-014 UNITS

Fig. 1 Motormaster I Controller Location (cont)

50TM008-014 UNITS WITHOUT


SINGLE POINT BOX
50HJ,HJQ,TF,TFQ,TM004-007 UNITS WITHOUT
SINGLE POINT BOX

50TM008-014 UNITS WITH


SINGLE POINT BOX
50HJ,HJQ,TF,TFQ,TM004-007 UNITS WITH
SINGLE POINT BOX

Fig. 1 Motormaster I Controller Location (cont)

NOTE: Dimensions are in millimeters.

Fig. 2 Field-Fabricated Mounting Bracket (38ARD,ARQ,ARZ007-012 Units Only)


4

SIZES 014-024

TOP OF COIL

SIZE 013

SENSOR LOCATION
ON HAIRPIN/RETURN
BEND
(7th FROM TOP)

COIL HAIRPIN END

HEADER END

38AKS013-024
HEADER END
38AK007

RETURN BEND
END

Fig. 3 Motormaster I Sensor Mounting Location 38AK,AKS Units

SEE DETAIL B

SEE DETAIL A

LOCATION FOR
MOTORMASTER
SENSOR

LOCATION FOR
MOTORMASTER
SENSOR

DETAIL A

38ARZ007 UNIT

DETAIL B

38ARQ008, 38ARZ008 AND 38ARS008 UNITS

NOTE: Route and bundle Motormaster wires with control box harness assembly.

Fig. 4 Motormaster I Sensor Mounting Locations 38AR Units


5

LOCATION FOR
MOTORMASTER
SENSOR

SEE DETAIL D

LOCATION FOR
SECOND
MOTORMASTER
SENSOR (FOR
38ARD012 ONLY)

DETAIL D

SEE DETAIL C

DETAIL C

38ARZ012, 38ARQ012, 38ARS009,012 AND 38ARD012 UNITS


NOTE: 38ARD012 requires (2) Motormaster sensors. Use both locations in detail C and D.

38ARD014-024 UNITS

Fig. 4 Motormaster I Sensor Mounting Locations 38AR Units (cont)

Fig. 5 Motormaster I Sensor Mounting Locations


38AQS012,016 Units

SENSOR
LOCATION

48/50HJ004

48/50TF,TM004

48/50TJ004

Fig. 6 Motormaster I Sensor Mounting Locations 48/50HJ,TF,TJ,TM Units


7

SENSOR
LOCATION

48/50HJ005

48/50TF,TM005

48/50TJ005

SENSOR
LOCATION

48/50HJ006

48/50TF,TM006

48/50TJ006

Fig. 6 Motormaster I Sensor Mounting Locations 48/50HJ,TF,TJ,TM Units (cont)


8

SENSOR
LOCATION

48/50TF007

48/50HJ007
(units with serial numbers lower than 0702G);
48/50TM007

SENSOR
LOCATION

48/50TJ007

48/50HJ007
(units with serial numbers 0702G and higher)

Fig. 6 Motormaster I Sensor Mounting Locations 48/50HJ,TF,TJ,TM Units (cont)

SENSOR

48/50TF,TJ008

48/50HJ,TM008

48/50HJ009
(units with serial numbers lower than 0903G)

48/50TF,TJ,TM009

Fig. 6 Motormaster I Sensor Mounting Locations 48/50HJ,TF,TJ,TM Units (cont)

10

SENSOR

48/50HJ009
(units with serial numbers 0903G and higher);
48/50HJ012

48/50TF,TJ,TM012

48/50HJ,TF,TJ,TM014

Fig. 6 Motormaster I Sensor Mounting Locations 48/50HJ,TF,TJ,TM Units (cont)

11

SENSOR

SENSOR

50TFQ004 AND 50TJQ004

50HJQ004

SENSOR

SENSOR

50TFQ005 AND 50TJQ005

50HJQ005

Fig. 7 Motormaster I Sensor Mounting Locations 50HJQ,TFQ,TJQ Units

12

SENSOR

SENSOR

50HJQ006

50TFQ006 AND 50TJQ006

SENSOR
SENSOR
SENSOR
LOCATION

50HJQ007
(with serial numbers lower than 0902G)

50HJQ007
(with serial numbers 0902G and higher)

50TFQ007 AND 50TJQ007

Fig. 7 Motormaster I Sensor Mounting Locations 50HJQ,TFQ,TJQ Units (cont)

13

SENSOR

SENSOR

50HJQ008

50TFQ008 AND 50TJQ008

SENSOR

SENSOR

SENSOR

50TFQ009 AND 50TJQ009

50HJQ012

50TFQ012 AND 50TJQ012

Fig. 7 Motormaster I Sensor Mounting Locations 50HJQ,TFQ,TJQ Units (cont)

14

Fig. 8 Wiring Details


(38AK007 and 48/50HJ,TF,TJ,TM004-007 Units)
SENSOR

Fig. 11 Wiring Details


(38AKS013-024 Units Except 575-V)

ED

BL

*Use control part no. 32LT900301 for all unit voltages except 400 V
and 460 V. Use control part no. 32LT900611 for 400 V and 460 V
units.

MOTORMASTER

CAP
CLO
COMP
OFM

LEGEND
Contactor
Capacitor
Compressor Lockout
Compressor
Outdoor Fan Motor

Fig. 12 Wiring Details


(38AKS013-024 Units 575-V)

Fig. 9 Wiring Details


(38ARZ007-012 Units)
SENSOR

ED

BL

*Use control part no. 32LT900301 for all unit voltages except 400 V
and 460 V. Use control part no. 32LT900611 for 400 V and 460 V
units.

MOTORMASTER

Fig. 13 Wiring Details


(38AQS012-016 Units Except 575-V)

CAP
COMP
OFM
OL

LEGEND
Contactor
Capacitor
Compressor
Outdoor Fan Motor
Overload

Fig. 14 Wiring Details


(38AQS012-016 Units 575-V)

Fig. 10 Wiring Details


(38ARS008-012 Units)

15

W1 W2

ORN

ORN

ORN

ORN

HR

RVR1
ORN

ORN

1 RVR2 3

WHT
WHT
WHT

C TRAN2
3 CR3
3 RVR2

WHT

WHT
WHT

3 HR
C TB2

RVR3

ORN
1 RVR3 3

NOTE: Isolation Relay (R) (field supplied) HN61KQ120 or


equivalent.

WHT

RVR1

Fig. 15 Isolation Relay Wiring Details (38AQS012-016 with Isolation Relay)

MOTORMASTER

C
CAP
CH
CLO
COMP
OFM
OFR
QT

LEGEND
Contactor
Capacitor
Crankcase Heater
Compressor Lockout
Compressor
Outdoor-Fan Motor
Outdoor-Fan Relay
Quadruple Terminal

Fig. 16 Wiring Details (38ARD014-024 Units)


16

SENSOR

MOTORMASTER

BLU D
RE

TO OFC ON
DEFROST
BOARD BLK

ED

BL

(MOTORMASTER
CONTROL NO. 1)

BLK MOTORMASTER

SENSOR
BLK

BLK
WHT

23

13

YEL

BRN

RVS
O

C
R

C
OFC
R
RVS

LEGEND
Contactor
Outdoor-Fan Contactor
Relay
Reversing Valve Solenoid

NOTE: R HN61KJ250 (normally closed contacts)

CAP
CH

CLO
COMP
OFM

Fig. 19 Wiring Details


(50HJQ,TFQ,TJQ004-007 Units)

LEGEND
Contactor
Capacitor
Crankcase Heater
Compressor Lockout
Compressor
Outdoor-Fan Motor
SENSOR

ED

BL

MOTORMASTER

(MOTORMASTER
CONTROL NO. 2)

LEGEND
C Contactor

NOTE: Two Motormaster


controls are required on
38ARD012 units.

Fig. 20 Wiring Details


(48/50HJ,TF,TJ,TM008-014 Units)

Fig. 17 Wiring Details


(38ARD012 Units)

SENSOR

ED

BL

MOTORMASTER

BLU D
RE

RED

MOTORMASTER

SENSOR
BLK

BLK
WHT

C
YEL

BRN

BLK
RVS
O

C
R

CAP
CH

CLO
COMP
MMR
OFM

WHT
BRN

LEGEND
C
Contactor
R
Relay
RVS Reversing Valve Solenoid

LEGEND
Contactor
Capacitor
Crankcase Heater
Compressor Lockout
Compressor
Motormaster Relay
Outdoor-Fan Motor

Fig. 21 Wiring Details


(50HJQ,TFQ,TJQ008-012 Units)

Fig. 18 Wiring Details


(38ARQ Units)
17

NOTE: Dimensions in ( ) are millimeters.

UNIT
38AK
007

UNIT
38ARZ/S/D/Q
007-012

DIMENSIONS (in.)

DIMENSIONS (mm)

LEFT BAFFLE

LEFT BAFFLE

291/4

303/16

31

27

10

18

26

22 223/4

231/4 27 21/4 91/4

161/4

231/4

UNIT
38AK
007

743

767

787

686

51

254

457

660

UNIT
38ARZ/S/D/Q
007-012

559

578

591

686

57

235

413

591

REAR BAFFLE
UNIT
38AK
007

UNIT
38ARZ/S/D/Q
007-012

REAR BAFFLE

361/2

373/8

381/4

27

10

18

26

30

31

32

27 21/4 91/4

161/4

231/4

UNIT
38AK
007

927

949

972

686

51

254

457

660

UNIT
38ARZ/S/D/Q
007-012

762

787

813

686

57

235

413

591

FRONT BAFFLE
UNIT
38ARZ/S/D/Q
007-012

FRONT BAFFLE

25

26

27

27 21/4 91/4

161/4

231/4

UNIT
38ARZ/S/D/Q
007-012

635

660

686

686

57

235

413

591

RIGHT BAFFLE

RIGHT BAFFLE

UNIT
A
B
C
D
E
F
G
H
38ARZ/S/D/Q
301/2 311/2 321/2 27 21/4 91/4 161/4 231/4
007-012

UNIT
38ARZ/S/D/Q
007-012

775

800

826

686

57

235

413

591

Fig. 22 Wind Baffle Mounting Details, 38AK,ARD,ARQ,ARS,ARZ007-012 Units

18

DIMENSIONS (ft-in.)
BAFFLE LOCATIONS
Right-Hand Side*
Back
Left-Hand Side*

A
2-511/16
5-81/2
3-07/16

*As viewed from access panel side.

Fig. 23 Wind Baffle Mounting Details, 38AKS,ARD013-024 and 38AQS012-016 Units


19

NOTE: Dimensions in ( ) are millimeters.

DIMENSIONS (in.)
FRONT BAFFLE
SIDE BAFFLE
D
E
F
G
H
A
B
C
D
E
48/50TF,TJ,TM004-007 4213/16 4313/16 4413/16 1921/32 315/16 77/8 1125/32 153/4 263/4 273/4 283/4 1921/32 315/16
48/50HJ004-007
341/2 359/32 361/16 273/8 23/32 93/32 163/32 233/32 2213/16 2319/32 243/8 273/8 23/32
and
50HJQ,TJQ004-007
211/2 221/4 23
273/8 13/32 93/32 173/32 253/32 253/32 253/4 265/32 273/8 45/16
50TFQ004,005
317/8 325/8 337/16 273/8 13/32 93/32 173/32 253/32 253/32 253/4 265/32 273/8 45/16
50TFQ006,007
UNIT

F
G
H
77/8 1125/32 153/4
93/32 163/32 233/32
115/16 185/16 255/16
115/16 185/16 255/16

DIMENSIONS (mm)
UNIT
48/50TF,TJ,TM004-007
48/50HJ004-007
and
50HJQ,TJQ004-007
50TFQ004,005
50TFQ006,007

FRONT BAFFLE
D
E
F
499 100
200

A
1087

B
1113

C
1138

876

896

916

695

52.9

546
810

565
829

584
849

695
695

28
28

G
299

H
400

A
679

B
705

C
730

SIDE BAFFLE
D
E
F
499 100
200

230.7

408.5

586.3

579

599

619

695

52.9

231
231

434
434

637
637

637
637

654
654

664
664

691
691

110
110

G
299

H
400

230.7

408.5

586.3

287
287

465
465

643
643

Fig. 24 Wind Baffle Mounting Details, 48/50HJ,TF,TM,TJ004-007 and 50HJQ,TFQ,TJQ004-007 Units

20

NOTE: Dimensions in ( ) are millimeters.

SIDE BAFFLE
DIMENSIONS (in.)
UNIT
48/50HJ,TF,TJ,TM008,009;
50HJQ008, 50TFQ,TJQ008,009
48/50HJ,TF,TJ,TM012,014; 50HJQ,TFQ,TJQ012

431/8

437/8

445/8

351/4

57/

147/8

221/4

301/2

431/8

437/8

445/8

431/4

57/8

147/8

221/4

301/2

381/8

DIMENSIONS (mm)
UNIT
48/50HJ,TF,TJ,TM008,009;
50HJQ008, 50TFQ,TJQ008,009
48/50HJ,TF,TJ,TM012,014; 50HJQ,TFQ,TJQ012

1096.0

1115.0

1134.0

894.0

150.0

377.0

566.0

774.0

1096.0

1115.0

1134.0

1098.0

150.0

377.0

566.0

774.0

967.6

FRONT BAFFLE
DIMENSIONS (in.)
UNIT
48/50HJ009; 48/50HJ,TF,TJ,TM008; 50HJQ,TFQ,TJQ008

A
415/8

B
423/8

C
431/8

D
351/4

E
11/4

F
91/4

G
171/4

H
251/4

J
331/4

48/50TJ,TM009; 50TJQ009

301/4

311/8

317/8

351/4

11/4

91/4

171/4

251/4

331/4

50TFQ009

165/8

173/8

181/8

351/4

11/4

91/4

171/4

251/4

331/4

48/50TF,TJ,TM012

151/2

161/4

171/8

431/4

11/4

91/4

171/4

251/4

331/4

411/4

50TJQ012

181/2

191/4

211/8

431/4

11/4

91/4

171/4

251/4

331/4

411/4

48/50HJ012,014; 48/50TF,TJ,TM014; 50HJQ,TFQ012

415/8

423/8

431/4

431/4

11/4

91/4

171/4

251/4

331/4

411/4

A
B
C
D
E
F
1058.0 1077.0 1096.0
894.0 32.0 235.2
796.0
789.0
809.0
894.0 32.0 235.2
422.2
441.3
460.4
894.0 32.0 235.2
393.0
413.0
433.0 1098.0 32.0 235.2
469.2
489.2
509.2 1098.0 32.0 235.2
1058.0 1077.0 1096.0 1098.0 32.0 235.2

G
438.4
438.4
438.4
438.4
438.4
438.4

H
641.6
641.6
641.6
641.6
641.6
641.6

DIMENSIONS (mm)
UNIT
48/50HJ009; 48/50HJ,TF,TJ,TM008; 50HJQ,TFQ,TJQ008
48/50TJ,TM009; 50TJQ009
50TFQ009
48/50TF,TJ,TM012
50TJQ012
48/50HJ012,014; 48/50TF,TJ,TM014; 50HJQ,TFQ012

J
844.8
844.8
844.8
844.8
844.8
844.8

1048.0
1048.0
1048.0

Fig. 25 Wind Baffle Mounting Details, 48/50HJ,TF,TM,TJ008-014 and 50HJQ,TFQ,TJQ008-012 Units

21

Copyright 2003 Carrier Corporation


Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Catalog No. 533-80099 Printed in U.S.A. Form 38/48/50-21SI
Pg 22
6-03
Replaces: 38/48/50-13SI
Book 1 1 1 1 4 4 4 4
Tab 1a 1b 3a 5a 2a 5a 6a 6b

Copyright 2003 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Catalog No. 533-80099 Printed in U.S.A. Form 38/48/50-21SI
Pg 24
6-03
Replaces: 38/48/50-13SI
Book 1 1 1 1 4 4 4 4
Tab 1a 1b 3a 5a 2a 5a 6a 6b

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE


CUT ALONG DOTTED LINE

CONTROLLER MOUNTING TEMPLATE

You might also like