IfEarthFaultPersistsinaDCDBhowtoPredictit'soccurenceand
HowtoremovetheDCDBEarthFault.DearAll,Yourexpriences
sharingwillbeappreciatedtoundertandtheconcept....
fault.dearfault.dear
fault.dear
Ashish
LikeComment(5)ShareApril24,2014
Comments
5comments

AsifE.
Manager(Engineering)atAlstomGrid
Asif

EarthfaultinDCcircuitisdetectedbysensingtheresistancebetweenpositivenegative
terminals&earth.BettertocallitDCearthleakageasDCsystemisusuallyunearthed.Settable
parameterinthisprincipleofdetectioncanberesistanceaswellascurrentbecauseearth
leakagecurrentalwaysdependsontheresistancevaluebetweenrespectiveterminals,therefore,
highertheresistance,loweristheleakagecurrentandviceversa.ManualofAlstomrelayCAEM
21canbechecked.Thereareothermakerelayisalsoavailableforsamepurpose.Youcan
consultyourDCDBmanufacturer.
AshishA.
SeniorElectricalEngineeratSTEAGEnergyServicesGmbH
@AsifEqbal

Ashish
IfthereisaDCEarthFaultinsomeFeeder.HowtoProceedfurtherforCheckingtheEarthfault
andRectifyit.KindlyClarifyit.....
2ndlyWhyDCSystemisusuallyUnearthed????
WhatisLinkedIn?

JoinToday

SignIn

AsifE.
Manager(Engineering)atAlstomGrid
Groundingcanbeeithersystemgroundorsafetyground.Incaseofsafetyground,equipment
groundconductorusuallydoesnotcarrycurrent.Itconnectstheexposedmetalsurfacetogether
andthenconnectedtogroundsothatincaseofleakagetheearthleakagecurrentcanfindthe
leastresistancepathtogroundpreventinganyhazardofelectricshock.Thisgroundingisdonein
bothACandDC.
Asfarassystemgroundingisconcernedpleasenotethatsystemgroundconductornormally
carriescurrentandisconnectedtoearthatanyonepointofthepowersystemlikeneutral
conductorinACsystemgroundedattransformerneutral.Thispointinpowersystemiscalled
systemground.IncaseifyouwanttodosystemgroundinginDCthanyouneedtogroundanyof
thepositiveornegativeconductors.WedonotdothisinDCbecause:
Ifyouhavethesamefaultinanungroundedsystemyouwillnottripanybreakers/fuses/other
things,thisisbecausethecurrentcannotgetbacktothepowersource.Therefore,thesystem
doesn'tgettripped.IfyouhavefaultyDCwiringorsomeotherfaultthathappenstogroundthe
system,itceasestobeanungroundedDCsystemandbecomesagroundedDCsystemthatwill
workjustfinebecauseafteroccurrenceoffirstgroundfaultsystemcontinuityismaintained.DC
systemismeantforauxiliarycontrolsupplysoitscontinuityisveryimportant.Theusualreason
Feedback

Asif

https://www.linkedin.com/groups/DCDBEarthFault2073290.S.5865120760556695573

1/2

5/4/2015

DCDBEarthFault|LinkedIn
tomakeaDCsystemungroundedisthisreason.Ifforsomereasonsomethinggoeswronganda
conductorgetsgroundedalsothennoproblem,youjusthaveagroundedsystemandeverything
keepsrunning.ThisiswhyalotofheavyindustrythatusesDCsystemswilluseanungrounded
system.ACungroundedsystemexperiencerepeatedarchinggroundforcingACungrounded
systemtoadopthigherinsulationlevelbutinDCdistributionof220Vto250Vminimum650Vor
1.1kVinsulationisusedsonoproblemonthataccountalso.
Bymeasuringtheleakagecurrentyoucancheckthatsomeunwantedgroundedconnectionhas
beenmade.RestpleasecheckrelaymanualandalsogetfeedbackfromO&Mpeopleas
checkingandrectificationcanbebetterexplainedbyoperationandmaintenancepersonnel.
EngrS.
CommissioningengineeratSiemens(3rdpartycontract)

Engr

DearIhavetwoDcSource.SourceAandSourceBwheniconnectedSourceBwithmySystem
theEarthfaultisoccurbutwithSourceASystemworkingnormal...Source_A226DCand
source_b228DC.....
PeterC.
Owner/ManageratControlSMART

Peter

Signup

HighpoweredDCsystemssuchasrailwayandtramwaysystemsandelectrolysingprocesses
(e.g.aluminium)areoftengroundedusuallyonthenegativesidealthoughthatispurelytraditional
andhastothebestofmyknowledgenotechnicalreason.ButthankyouAsifforyourexcellent
anddetailedexplanationofwhylowpowerDCsystemsarenotgrounded.

HelpCenter

LinkedInUpdates
2015

About

Careers

LinkedInInfluencers
UserAgreement

Advertising
LinkedInJobs

PrivacyPolicy

TalentSolutions
Directories

SalesSolutions

Members

CommunityGuidelines

Jobs

SmallBusiness

Pulse

CookiePolicy

https://www.linkedin.com/groups/DCDBEarthFault2073290.S.5865120760556695573

Mobile

Companies
CopyrightPolicy

Groups

Language

SlideShare

Universities

Titles

GuestControls

2/2

You might also like