Electrical Transient Analyzer Program


Short-Circuit Analysis
IEC 60909 Standard
3-Phase, LG, LL, & LLG Fault Currents
Short-Circuit Current Based on User-Defined c Factor

Swing

V-Control

Number of Buses:

Number of Branches:

System Frequency:
Unit System:

50 Hz
Metric

Total

XFMR2

XFMR3

Synchronous

Power
Grid

Synchronous

Generator
Number of Machines:

Load

Reactor

Motor

11

Line/Cable

Impedance
1

Machines
0

Induction

Tie PD
0

Lumped

Load
0

Total
0

Project Filename:

sanjen 42

Output Filename:

E:\hydro\sanjen 42\Untitled.SI2

Adjustments
Apply
Adjustments

Individual
/Global

Transformer Impedance:

Yes

Individual

Reactor Impedance:

Yes

Individual

Overload Heater Resistance:

No

Transmission Line Length:

No

Cable Length:

No

Tolerance

Apply
Adjustments

Individual
/Global

Transmission Line Resistance:

Yes

Individual

Cable Resistance:

Yes

Individual

Temperature Correction

Percent

Degree C

Bus Input Data

Bus
ID

Type

Initial Voltage
Nom. kV
Sub-sys

Base kV
%Mag.
Ang.

Bus4

Load

11.000

10.476

100.00

-30.00

Bus5

Load

0.400

0.381

100.00

-60.00

Bus6

Gen.

11.000

10.476

100.00

-30.00

Bus7

Load

135.300

135.300

100.00

0.00

Bus11

Load

0.400

0.381

100.00

-60.00

Bus12

Load

11.000

10.476

100.00

-30.00

Bus13

Gen.

11.000

10.476

100.00

-30.00

Bus14

Load

0.400

0.381

100.00

-60.00

Bus15

Load

11.000

10.476

100.00

-30.00

Bus16

Gen.

11.000

10.476

100.00

-30.00

Bus17

SWNG

135.300

135.300

100.00

0.00

11 Buses Total
All voltages reported by ETAP are in % of bus Nominal kV.
Base kV values of buses are calculated and used internally by ETAP.

Line/Cable Input Data


Ohms or Siemens per 1000 m per Conductor (Cable) or per Phase (Line)
Length

Line/Cable
ID

Library

Line1

Line / Cable resistances are listed at the specified temperatures.

Size

356

Adj. (m)
% Tol.
2000.0

#/Phase
0.0

T (C)
1

R1

X1
75

Y1
1.41045

R0

X0
0.86507

2-Winding Transformer Input Data

Transformer
ID

Rating
MVA

Prim. kV

Sec. kV

Z Variation
%Z

X/R

+ 5%

- 5%

% Tap Setting
% Tol.

Prim.

Adjusted

Sec.

%Z

T3

0.300

11.000

0.400

4.00

3.09

T4

17.250

11.000

135.300

8.00

18.60

T7

17.250

11.000

135.300

8.00

18.60

T8

0.300

11.000

0.400

4.00

3.09

T9

17.250

11.000

135.300

8.00

18.60

T10

0.300

11.000

0.400

4.00

3.09

2-Winding Transformer Grounding Input Data


Grounding
Transformer
ID

Rating
MVA

Prim. kV

Conn.
Sec. kV

Type

Primary
Type

kV

Secondary
Amp

Ohm

T3
0.300

11.000

0.400

D/Y

Solid

17.250

11.000

135.300

D/Y

Solid

17.250

11.000

135.300

D/Y

Solid

0.300

11.000

0.400

D/Y

Solid

17.250

11.000

135.300

D/Y

Solid

0.300

11.000

0.400

D/Y

Solid

T4

T7

T8

T9

T10

Type

Branch Connections
CKT/Branch
ID
T3

T4

T7

T8

T9

T10

Line1

Connected Bus ID
Type

2W XFMR

2W XFMR

2W XFMR

2W XFMR

2W XFMR

2W XFMR

Line

From Bus
Bus4

Bus6

Bus13

Bus12

Bus16

Bus15

Bus17

% Impedance, Pos. Seq., 100 MVAb


To Bus

Bus5
441.41

1363.94

2.74

50.91

2.74

50.91

441.41

1363.94

2.74

50.91

441.41

1363.94

1.54

0.95

Bus7

Bus7

Bus11

Bus7

Bus14

Bus7

CB8

Tie Breakr

Bus6

Bus4

CB15

Tie Breakr

Bus13

Bus12

CB18

Tie Breakr

Bus16

Bus15

Power Grid Input Data

Power Grid

Connected Bus

ID

ID

U1

% Impedance
100 MVA Base

Rating
MVASC

Bus17

1200.000

kV

135.300

1.80775

X"

R/X"

8.13489

Groundin
g
Type

0.22 Wye - Solid

Total Connected Power Grids ( = 1 ): 1200.000 MVA

Synchronous Generator Input Data


% Impedance in Machine Base
Synchronous Generator
ID

Xd"

Rating
Type

MVA

kV

RPM

% PF

Grounding
Adj.

Tol.

R/X

Xd, sat

Gen2

Hydro w/o Damping

16.847

11.000

600

85.00

1.000

19.00

0.0

0.05

155.00

Gen4

Hydro w/o Damping

16.847

11.000

600

85.00

1.000

19.00

0.0

0.05

155.00

Gen5

Hydro w/o Damping

16.847

11.000

600

85.00

1.000

19.00

0.0

0.05

155.00

Total Connected Synchronous Generators ( = 3.00 ) : 50.541 MVA

SHORT- CIRCUIT REPORT

Fault at bus

Bus7

Nominal kV

135.30

1.10 (User-Defined)

Line-To-Ground Fault
% Voltage at From Bus

Contribution
From Bus

To Bus

ID

ID

Va
Mag.

Current at From Bus (kA)

Vb
Ang.

Mag.

Vc
Ang.

Mag.

Ia
Ang.

Mag.

Ib
Ang.

Mag.

Ang.

Bus7

Total

0.00

0.0

99.34

-116.3

94.47

117.6

5.584

-74.2

0.000

0.0

Bus17

Bus7

20.49

-28.7

95.87

-114.7

94.49

114.8

4.231

-70.6

0.513

99.5

Bus6

Bus7

61.70

-48.2

64.10

-130.5

94.72

89.7

0.462

-85.0

0.171

-80.5

Bus13

Bus7

61.70

-48.2

64.10

-130.5

94.72

89.7

0.462

-85.0

0.171

-80.5

Bus16

Bus7

61.70

-48.2

64.10

-130.5

94.72

89.7

0.462

-85.0

0.171

-80.5

U1

Bus17

100.00

0.0

100.00

-120.0

100.00

120.0

4.231

-70.6

0.513

99.5

Gen2

Bus6

95.24

-30.0

95.24

-150.0

95.24

90.0

2.132

-86.8

2.177

92.3

Bus5

Bus4

84.56

-73.9

47.81

-178.1

86.33

73.6

0.000

0.0

0.000

0.0

Gen4

Bus13

95.24

-30.0

95.24

-150.0

95.24

90.0

2.132

-86.8

2.177

92.3

Bus11

Bus12

84.56

-73.9

47.81

-178.1

86.33

73.6

0.000

0.0

0.000

0.0

Gen5

Bus16

95.24

-30.0

95.24

-150.0

95.24

90.0

2.132

-86.8

2.177

92.3

Bus14

Bus15

84.56

-73.9

47.81

-178.1

86.33

73.6

0.000

0.0

0.000

0.0

Bus6

Bus4

61.70

-48.2

64.10

-130.5

94.72

89.7

0.000

0.0

0.000

0.0

Bus13

Bus12

61.70

-48.2

64.10

-130.5

94.72

89.7

0.000

0.0

0.000

0.0

Bus16

Bus15

61.70

-48.2

64.10

-130.5

94.72

89.7

0.000

0.0

0.000

0.0

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer

Short-Circuit Summary Report


3-Phase, LG, LL, LLG Fault Currents
Bus
ID

3-Phase Fault
kV

I"k

ip

Line-to-Ground Fault
Ik

I"k

ip

Ib

Line-to-Line Fault
Ik

I"k

*Line-to-Line-to-Ground
ip

Ib

Bus7
135.300
All fault currents are in rms kA. Current ip is calculated using Method C.
* LLG fault current is the larger of the two faulted line currents.

5.243

10.642

4.901

5.584

11.335

5.584

Sequence Impedance Summary Report


Bus
ID
Bus7

Positive Seq. Imp. (ohm)


kV

Resistance
135.300

Reactance

Impedance
4.82684

Negative Seq. Imp. (ohm)


Resistance

Reactance
15.66336

Impedance

Zero Seq. Imp. (ohm)


Resistance
16.39021

Reactance

Impedance
4.87082

Fault Zf (ohm)
Resistance
15.53456

015

678

mal

Total
3

10

Y0
0.0000055

2.08094

2.90175

0.000003

Phase Shift
Type

Angle
0

4.0000 Std Pos. Seq.

-30.000

5.000

8.0000 Std Pos. Seq.

30.000

5.000

8.0000 Std Pos. Seq.

30.000

4.0000 Std Pos. Seq.

-30.000

5.000

8.0000 Std Pos. Seq.

30.000

4.0000 Std Pos. Seq.

-30.000

Secondary
kV

Amp

Ohm

nce, Pos. Seq., 100 MVAb


Z

1433.59

50.99

50.99

1433.59

50.99

1433.59

1.81

0.2029036

Excitation
Conn.

Type

Amp

Wye

3.00 Sal-pole 160%

Wye

3.00 Sal-pole 160%

Wye

3.00 Sal-pole 160%

Type

Ic
Mag.

Sequence Current (kA)


Ang.

I1

I2

I0

0.000

0.0

1.861

1.861

1.861

0.530

97.8

1.587

1.576

1.071

0.177

-82.2

0.095

0.098

0.270

0.177

-82.2

0.095

0.098

0.270

0.177

-82.2

0.095

0.098

0.270

0.530

97.8

1.587

1.576

1.071

0.057

-125.7

1.227

1.262

0.000

0.000

0.0

0.000

0.000

0.000

0.057

-125.7

1.227

1.262

0.000

0.000

0.0

0.000

0.000

0.000

0.057

-125.7

1.227

1.262

0.000

0.000

0.0

0.000

0.000

0.000

0.000

0.0

0.000

0.000

0.000

0.000

0.0

0.000

0.000

0.000

0.000

0.0

0.000

0.000

0.000

*Line-to-Line-to-Ground
Ik

5.584

I"k

4.556

ip

9.247

Ib

4.556

Ik

4.556

5.564

11.294

5.564

5.564

Fault Zf (ohm)
Reactance
15.53456

Impedance
16.28028

2.89730

13.21325

13.52717

0.00000

0.00000

0.00000

0.00000