You are on page 1of 43

Roads and Transport Authority

DUBAI METRO
Operation of Kiosks / Shops
at Dubai Metro Stations
(Red & Green Lines)

FIT-OUT GUIDE
Revision 01

DUBAI METRO
Roads and Transport Authority (RTA)
Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
(Revision 01 23 March 2011)

TABLE OF CONTENTS
CLAUSE NO.
1

PAGE

Requirements of Fitting-out Designs ........................................................................

1.1
1.2
1.3
1.4
1.5
1.6
1.7

Introduction ...................................................................................................
Station provision and site inspection.............................................................
Statutory requirements..................................................................................
Formal contacts..............................................................................................
Discussion before design submission .............................................................
Before fitting-out work begins.......................................................................
Fitting-out Submission for Approval ............................................................

1
1
1
2
2
2
2

Shop front Design ......................................................................................................

2.1
2.2
2.3
2.4
2.5

5
5
6
6
7

Introduction ...................................................................................................
Demise line .....................................................................................................
Standard shop frontage .................................................................................
Roller shutters................................................................................................
Other requirements........................................................................................

Signage and Graphics Design....................................................................................

3.1
3.2
3.3

Introduction ...................................................................................................
Shop signage...................................................................................................
Tenant signage ...............................................................................................

8
8
8

Interior Design Guidelines ......................................................................................

10

4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9

Introduction .................................................................................................
Integrity of fire compartment......................................................................
Glass and glazing..........................................................................................
Suspended false Ceiling ...............................................................................
Furniture and heavy loads...........................................................................
Fire precautions ...........................................................................................
Lighting ........................................................................................................
Facades and aisles ........................................................................................
Colour and material.....................................................................................

10
10
10
11
11
12
13
14
14

Fire Services Installation.........................................................................................

17

5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8

17
17
17
17
18
19
19
19

Portable Fire Extinguisher ..........................................................................


Fire Roller Shutter.......................................................................................
Emergency Exit Door and Route.................................................................

Requirements of Installing Sprinkler System


Additional Smoke Detectors or Sprinklers .................................................
Alterations to FSI.........................................................................................
Important .....................................................................................................
Other Requirements.....................................................................................

DUBAI METRO
Roads and Transport Authority (RTA)
Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
(Revision 01 23 March 2011)

Electrical Services Installation................................................................................

21

6.1
6.2
6.3
6.4

21
21
21
22

No Alterations to Stations Equipment .......................................................


Electrical Installations .................................................................................
Electrical Equipment ...................................................................................
Important .....................................................................................................

Air Conditioning and Mechanical Ventilation System.............

23

7.1
7.2
7.3
7.4
7.5

Air conditioning ...........................................................................................


Equipment and Material..............................................................................
Mechanical Ventilation................................................................................
Smoke Control .............................................................................................
Ventilation and Air Conditioning Control..................................................

23
23
24
24
24

Plumbing and Drainage Installation.......................................................................

25

8.1
8.2
8.3

Plumbing installations .................................................................................


Drainage Installations..................................................................................
Important .....................................................................................................

25
25
26

Communication Services Installation .....................................................................

27

Appendix A: Typical Station Provision of Kiosk / Shop.............................................................

28

Appendix B: Shop front Perspective Design ....................................................................................

30

Appendix C1: Specifications and Requirements for Motorized Transparent Security Shutters

31

Appendix C2: Technical Specification and Requirements for Shop Signage

34

Appendix D: Stainless Steel Shop Demarcation Line ..

37

Appendix E: Power Supply Schedule .

38

ii

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Requirements of Fitting-out Designs

1.1

Introduction
1.1.1

1.1.2

1.2

1.1.1.1

Tenants;

1.1.1.2

Fit-Out Contractors employed by tenants.

The Fit-out Guide must be followed by all tenants in their


fitting-out designs and works.

Station provision and site inspection


1.2.1

1.3

The Fit-out Guide is provided by Roads and Transport


Authority (RTA) to enable the following parties with
requirements and guidelines to design and fit out their kiosks /
shops to a high standard and in a safe manner.

Typical stations provision of kiosk / shop shall refer to Appendix A.


However Tenants have an obligation to carry out site inspection,
measurement and validation to establish actual site conditions and asbuilt provisions before commencing preliminary design work.

Statutory requirements
1.3.1

Tenants are responsible for obtaining and satisfying all


necessary statutory requirements from all jurisdictional
Authorities

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

1.4

1.5

1.6

Formal contacts
1.4.1

All formal contact for the fitting-out and occupancy of


kiosk/shop should be directed to the Representative of RTA.

1.4.2

Tenant shall provide RTA with a single point contact name with
details on the design proposal for necessary coordination and
follow up during design and fit out approval

Discussion before design submission


1.5.1

All designs are subject to the approval of the Representative of


RTA, tenants are required to discuss specific design ideas or
concepts with the Representative of RTA before commencing
preliminary design work.

1.5.2

Tenant to submit Pre-qualification document for proposed


Consultant/ contractor for RTA approval during the tenant
briefing session. The proposed consultant / contractors shall be
registered with the relevant statutory bodies within the country

Before fitting-out work begins


1.6.1

1.7

FIT-OUT GUIDE
Rev 01

Before any fitting-out work begins, tenants must submit the fitting-out
designs to the Representative of RTA for examination and approval. The
designs must be appropriate to the location and trade. The Representative
of RTA reserves the right to reject a submission that appears to be
unsuitable for any reason.

Fitting-out Submission for Approval


1.7.1

The Tenants are required to follow the requirements of the Fit-out


Guide to prepare fitting-out submission for approval. The fitting-out
submission shall include, at least but not limited to the following:

1.7.1.1

Fitting-out drawings
a.

The Tenants shall submit nine sets of hardcopies and


softcopies, of all fitting-out drawings prior to
commencing the fitting-out works. The proposed
design drawings shall be submitted on Auto Cad
release-14 / compatible software only

b. Every fitting-out drawings shall be dimensioned


in millimeter (mm) and to scale.
2

FIT-OUT GUIDE

DUBAI METRO
Roads and Transport Authority (RTA)

Rev 01

Request for Operation of Kiosks / Shops


At Dubai Metro Stations (Red & Green Lines)

c. Every fitting-out drawings submission shall include the

following:
- drawing number, revision letter, scale and title

- basic layout plans, flooring layouts, furniture layouts,


detailed drawings, sections, all internal and external
elevations, reflected ceiling with setting out dimensions
- types of materials and kinds of colours to be used in the
fitting-out works
- layout, type, rating and location of electrical and mechanical
equipment and installation details
- layout and types of lighting, power socket outlets/electrical
equipment/telephone outlets/ data outlets, etc. with numbered
positions indicated on the fitting-out drawings

- layout and types of air conditioning units, ventilation fans,


air curtains, exhaust hoods, ductworks, air grilles/diffuser,
pipeworks (including condensate drain pipe), isolation
valves, balancing valves, etc.
- fittings attached to station walls or soffits
- types and positions of actual fastenings
- details of false ceiling and Fire Services Installation (FSI)
- details of access panels to station services, drainage, airconditioning, etc.
- details of storage cupboards and furniture
- details of equipment installations and supports, services
penetration through wall / ceiling / floor of kiosk or shop
- existing and proposed FSI, e.g. smoke detectors and
sprinkler heads
- schematic diagram of E&M works, and
- combined service drawings
- Existing services layout to be also provided by tenant
- Details of the used anchors used for installing MEP, false
ceiling, interior walls showing the Drilling depth inside the
structural elements (floors, walls, columns) ( Max allowed
drilling inside the structure shall be 40mm)
- Submit details for the proposed water proofing of wet areas
3

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

1.7.1.2

FIT-OUT GUIDE
Rev 01

Materials and samples submission


a.

The tenants shall submit three sets of each of


the samples which are proposed/intended to be
used in the fitting-out works, and they shall
have been approved prior to ordering

b. The samples submitted shall comprise materials


and finishes in their final form.
c.

The submitted samples shall be with full technical


certificate and documentation to prove their
compliance with the specification and requirement.

1.7.1.3

Artist impression submission


a.

The tenants shall submit three copies of each artist


impressions to illustrate the concept, theme and design
approach of fitting-out design.

b. Each artist impressions shall be in color and


printed A3 size paper.
c.

1.7.1.4

The artist impressions shall be included the


following:
- drawing title and date
-

external perspective for shop front design


and tenants signage

internal perspective for kiosk/shop and


furniture layout

shop front signage of tenants logo and shop


name.

All Documents should have a unique number for


easy referencing and quality control.
Example: RLM-R01- C- 40.1- ABC
(Metro ref- Stn ref- Concourse / Pod Ref- Retail Unit RefTenant ref)

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

2
2.1

Shop front Design


Introduction
2.1.1

2.2

FIT-OUT GUIDE
Rev 01

The Shop front Design covers the following:


2.1.1.1

Demise line

2.1.1.2

Standard shop frontage

2.1.1.3

Roller shutter

2.1.1.4

Shop front sign

2.1.1.5

Other requirements.

Demise line
2.2.1

The demise line for all kiosk/shop areas is defined as the


maximum extent to which display/merchandise can be placed
without jeopardising the Fire Safety Strategy.
2.2.1.1

No objects are allowed to be placed beyond this line


at any time, as they will jeopardize the overall safety
of the station.

2.2.1.2

No display, promotion counter or any other retail


activities shall cause obstruction to passenger circulation.

2.2.1.3

A 20mm wide hairline stainless steel channel to be


provided by Tenant at demise line for shop demarcation.
Please refer to Appendix C2-B for reference.

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

2.3

2.4

FIT-OUT GUIDE
Rev 01

Standard shop frontage


2.3.1

Unless prior approval is obtained from the Representative of


RTA, no alteration is to be made to the standard shop frontage.
All the structural fixing details of any shop front alteration
works shall be designed and certified by a qualified Structural
Engineer in order to ensure structural safety. Additional shop
front glass panels/entrance glass door shall be subject to the
approval of the Representative of RTA.

2.3.2

Shop front design may be rejected if it is considered incompatible with


the station architecture and aesthetic appearance.

Roller shutters
2.4.1

A fire rated shutter will be provided by the Station and the


security shutter will be provided by the Tenant as follows:
2.4.1.1

A fire rated roller shutter of 2 hours fire resistance


period to meet the Fire Safety Strategy is provided
and a security shutter shall be provided by the tenant
if required

2.4.1.2

The security shutter provided by the Tenant will be a


transparent type to allow for a high degree of
visibility to maximize passenger awareness even
when the unit is closed. The technical specification
and requirements shall refer to Appendix C1.
The security shutter is required to be provided with
a manual operation device to allow the tenant to
close or open the shop in case of power failure.

2.4.1.3

The roller shutter path shall not be obstructed by the


tenants fixtures and fittings. Display fixtures/items
should be set back from any part of the guide rail by
100 mm.

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

2.5

FIT-OUT GUIDE
Rev 01

Other requirements
2.5.1

No opaque portion of the Tenants shop front shall exceed 20%


of the shop front width

2.5.2

Sales promotion material such as flyers, advertisement, stickers should


not be allowed on any part of the shop front. Poster stands or notice
boards should be designed for the purpose. The design of the said
stand/notice boards shall be submitted for approval.

2.5.3

Stickers/logos/silk screening is not allowed on any part of the


shop front panels/glass door/glazed panels/roller shutters.

2.5.4

Showcases and display cabinets should be adequately lit and


ventilated.

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

3
3.1

Signage and Graphics Design


Introduction
3.1.1

3.2

FIT-OUT GUIDE
Rev 01

The Signage and Graphics Design cover the following:


3.1.1.1

Shop signage

3.1.1.2

Tenant signage

Shop signage
3.2.1

The light box for the shop sign shall be provided by the
landlord. The technical specification and requirements shall
refer to Appendix C2-A.
3.2.1.1 The electrical connection /conduiting for the shop sign
(light box) till the isolator shall be responsibility of the
tenant; to implement DEWA and IEE regulations which
shall be the guide for all wiring works
3.2.1.2 The tenant shall install the sticker with their name /logo
on the shop front sign box and remove the same
subsequently when their tenancy contract has been
completed

3.2.2

The provision of shop signs for kiosks / shops are described below:
3.2.2.1

3.3

The Tenant shall provide a shop numbering sign (size


90mmW x 84mmH) at the side of the shop front to indicate
the shop number. The technical specification and
requirements shall refer to Appendix C2.

Tenant signage
3.3.1

Rules pertaining to tenant signs for retails are described below


3.3.1.1

Railway signage always has the highest priority.


Tenants signs must not compromise the visibility
nor compete with these signs.

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

3.3.1.2

Tenants are encouraged to use their corporate logo,


trading name and colour, which are provided and
maintained by the tenants.

3.3.1.3

Notwithstanding 3.3.1.2 above, shop sign letters shall be


backlit in white colour only. Tenants are allowed to choose
only one colour as the background colour for the shop sign.
Please refer to Appendix B for reference.

3.3.1.4

Appendix B1 shall be followed for shop sign letter size.

3.3.1.5

The logo and shop name shall preferably be positioned in the


centre of the shop front, subject to RTA approval.

3.3.1.6

Tenants shall submit their proposed shop front


signage arrangement with tenants logo and shop
name to the Representative of RTA for the approval.

3.3.1.7

Cloth, paper, flashing lights, formed plastic, noise


making stickers or decals, moving or rotating signs
and exposed labels of sponsors are not permitted.

3.3.1.8

No displays or signs are permitted outside the demise line.

3.3.1.9

The luminance of all commercial facility signs shall


2
not exceed 500 candela / square metre (cd/m ).

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

4
4.1

Interior Design Guidelines


Introduction
4.1.1

4.2

The interior design guidelines cover the following:


4.1.1.1

Integrity of fire compartment

4.1.1.2

Glass and glazing

4.1.1.3

Ceiling

4.1.1.4

Furniture and heavy loads

4.1.1.5

Fire precautions

4.1.1.6

Lighting

4.1.1.7

Facades and aisles

Integrity of fire compartment


4.2.1

4.3

FIT-OUT GUIDE
Rev 01

Tenants must ensure that:


4.2.1.1

The fire compartmentation of the retail unit does not


infringe the Fire Safety Strategy.

4.2.1.2

No damage is done to openings, floors, walls,


columns, or roof of retail units.

Glass and glazing


4.3.1

Tenants must ensure that:

10

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

4.4

4.3.1.1

All glass partitions or screens are tempered glass and


can either withstand or be protected from impact by
passengers, baggage or trolleys, etc.

4.3.1.2

They have conclusive proof of safety in terms of


impact and abrasion resistance in accordance with
BS8200 & BS3900

4.3.1.3

Full height clear glazing is permanently marked to


indicate the presence of glass, e.g. by using dots or
bands at average of eye level (1500mm above FFL) to
the approval of the Representative of RTA.

Suspended false Ceiling


4.4.1

4.5

FIT-OUT GUIDE
Rev 01

Tenants must ensure that:


4.4.1.1

The suspended false ceiling design within their areas will


not infringe the requirements of the Fire Safety Strategy

4.4.1.2

The suspended false ceiling should be readily


demountable type for maintenance and inspection.

4.4.1.3

All materials used at or above suspended false ceiling


level are non-combustible and all wiring is installed
in metal ducting, conduit or trunking.

4.4.1.4

Proper, safe and convenient access to all valves,


switches and other mechanical equipment requiring
maintenance is provided.

4.4.1.5

All equipment within the ceiling void is supported by a


suitable suspension system independent of the ceiling.

4.4.1.6

No supports for false ceilings or any other tenant equipment


above false ceiling void including ducts shall be hanged from
the main building services supports /supporting structure

Furniture and heavy loads


11

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

4.5.1

4.6

FIT-OUT GUIDE
Rev 01

Tenants must ensure that:


4.5.1.1

All furniture is manufactured from non-combustible


components.

4.5.1.2

The furniture and cupboards must be provided with doors


and in sufficient quantity to contain all envisaged needs of
the tenants so that only items intended for sale or display are
visible to the general public.

4.5.1.3

Any upholstery is fully fire retardant in accordance with


BS 7176 and meets all necessary statutory requirements.

4.5.1.4

Heavy loads bear on either an independent structure


or the partition adjacent to any demise wall.

Fire precautions
4.6.1

Tenants must ensure that:


4.6.1.1

Emergency exit doors and routes are kept free of


obstruction at all times.

4.6.1.2

No gas or flammable liquids are used or stored.

4.6.1.3

All fittings, fixtures and displays do not restrict the free


circulation of ventilation and air conditioning supply.

4.6.1.4

Fire Safety Strategy, e.g Close Cabin Concept shall be taken


into consideration and should comply with DCD (Dubai Civil
Defence) regulations.

12

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

4.7

FIT-OUT GUIDE
Rev 01

Lighting
4.7.1

Tenants must ensure that:


4.7.1.1

No glare from their fittings affects the public areas


or the adjacent Station signage.

4.7.1.2

The following criteria for Display Lighting (Shop


front Window Zone) are met:
a.

Lighting source shall have a colour rendering


index of 85 or better.
b. No exposed or coloured lamps shall be used.
c.

No flashing strobe, spinner, or chase type


lighting shall be used.

d.

High intensity discharge lamps which do not meet the


colour rendering criteria shall not be used.

e.

A level of lighting in excess of 500 lux measured


vertically at eye level; in the shop front window zone
shall be maintained throughout opening hours of the
Station. Tenants are advised to shut down the lights
during the closing hours of the Station.

4.7.1.3

The following criteria for Interior Lighting (all other


areas of the retail open to public view) are met:
a.

All light fittings shall be of the low brightness type.

b.

All light sources (lamps, bulbs) for direct fittings


(downlights, track lights, soffit lights, etc) or indirect
fittings (coves, etc.) shall be shielded.

c.

Fluorescent fitting shall have low brightness


parabolic diffusers, metal or aluminized plastic,
lampshade type.
d. No lensed fittings shall be used.
e.

Recessed downlights shall have specular or


semi-specular aluminum reflectors or other low
brightness shielding devices.
13

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

4.7.1.4

4.8

f.

Self-contained interior emergency lighting shall


be provided to maintain 10 lux over the
emergency exit routes.

g.

Emergency EXIT signs shall be provided and


shall be conformed to the design guideline and
be installed to meet all necessary statutory
requirements. Back up electrical supply to the
signage should also be provided.

Use energy saving light fittings. Apply CIBSE


standard for lux level

Facades and aisles


4.8.1

4.9

FIT-OUT GUIDE
Rev 01

Tenants must ensure that:


4.8.1.1

Open facades are designed so as to facilitate


passenger flow and visibility.

4.8.1.2

Aisle widths are adequate, wherever possible, for


persons in wheelchairs and passengers with baggage.

Colour and material


4.9.1

Colour Requirements
4.9.1.1

Colours used should generally follow and be in


harmony with the soffit/station colours. Certain
neutral colours may also be used subject to the
approval by the Representative of RTA.

4.9.1.2

External ducting and piping installed above the


kiosk/shop and public area should be painted in a
colour matched with the soffit/station colours as
appropriate or agreed by the Representative of RTA.

14

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

4.9.2

No alterations to panel
4.9.2.1

Alterations, paintings, etc. are prohibited on the


following panels:
a.

4.9.3

The floor material chosen should be:


a.
b.
c.

4.9.5

Station wall panels

Floor material
4.9.3.1

4.9.4

FIT-OUT GUIDE
Rev 01

non-flammable
hard-wearing, and
non-slippery

Painting on timber surface


4.9.4.1

In general, painting on timber surface should be


avoided and laminates should be used. If timber
surfaces that are not clad with Class 1 flame
retardant laminates, they should be coated with 2
layers of an approved Class 1 flame retardant paint.

4.9.4.2

On completion of the painting work, painting details list


should be submitted to the Representative of RTA.

Prohibited materials
4.9.5.1

The following materials are prohibited from being


used in the fitting-out works of kiosk/shop:
a.
b.
c.

acrylic and inflammable plastics


foam cushions, and
other untreated inflammable materials.

15

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

4.9.6

FIT-OUT GUIDE
Rev 01

Carpet requirements
4.9.6.1

When carpets are to be installed, the following


requirements should be fulfilled:
a.

pile depth must not exceed 10mm, and

b.

gross floor area covered by pure wool carpet


must not exceed 10%

c.

If the carpeting area exceeds 10%, the carpet must


either be pure wool with fibres pre-treated by the
ZIRPO process, or pure wool post-treated with a
fire retardant solution to achieve a Class 1 spread of
flame according to BS476 : Part 7 : 1987 (1993).

16

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

5
5.1

Fire Services Installation


Portable Fire Extinguisher
5.1.1

5.2

5.3

The portable fire extinguisher is to be provided by the Tenant and its


location should be clearly shown on the fitting out drawing and the
position of it must be prominent and easily accessible. Standard provision
of type and size of portable fire extinguisher should be stated on fit out
design by tenants as advised by Retail Consultant; and should be
approved by DCD (Dubai Civil Defense).

Fire Roller Shutter


5.2.1

Kiosk/shop fitting-out must be at least 200mm clear in plan


from the path of any fire roller shutter

5.2.2

All fire roller shutter access panels must be visible and


accessible all the times

Emergency Exit Door and Route


5.3.1

5.4

FIT-OUT GUIDE
Rev 01

The emergency exit door must have a clear route equal to its
width, i.e. not less than 915mm and must be permanently
available to both customers and kiosk/shop staff

Requirements of Installing Sprinkler System


5.4.1

The table below tabulates the basic guidelines for installing


sprinkler system against various types of ceiling which shall
comply to NFPA 13 (2002 edition).
Ceiling type

Mounting height

No false ceiling

75-150mm from soffit

17

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Egg-crate type false ceiling with


dimensions 100mm (W) x
100mm (L) x 25mm (H)
Solid type false ceiling

5.4.2

75-150mm from soffit,


and minimum 800mm
above false ceiling
Beneath the false ceiling

The table below tabulates the horizontal spacing for installing the
sprinkler heads which shall comply to NFPA 13 (edition 2002).

Spacing between

Distance

sprinkler heads

3-4 metres

sprinkler head and wall

Maximum 1.5 metres perpendicular

sprinkler head and the further Maximum 2.1


metres corner
5.4.3

5.5

Other Requirements
a.
b.

Sprinkler head coverage is 12 square metres.


Sprinkler heads shall be of quick response type, general 68 C.

c.

Sprinkler distribution pipes shall be as close to the


perimeter as possible so as to maximise the area at the
centre of air conditioners and other services.

d.

Depending on the hood dimensions, additional sprinkler


head near or below shutter hood may be necessary.

Additional Smoke Detectors or Sprinklers


5.5.1

Any additional smoke detectors or sprinklers must be of a type


approved by the following authorities and comply to NFPA 72
(2002 edition) and NFPA 13 (2002 edition)
a.
b.

5.5.2

the Representative of RTA


Dubai Civil Defence Department

Installation of additional smoke detector(s) and relocation of


smoke detector(s) must be carried out by the assigned smoke
detectors supplier(s). It needs 4-6 weeks to check and approve
software modification for the Automatic Fire Alarm system.
18

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

5.5.3

5.6

Any alterations to the Fire Services Installation (FSI) must only


be undertaken by a registered fire services contractor of
appropriate class with the approval of both the Representative
of RTA and Dubai Civil Defence Department.

Important
5.7.1

5.8

The approval of additional smoke detector(s) is subject to the


capacity of station fire panel.

Alterations to FSI
5.6.1

5.7

FIT-OUT GUIDE
Rev 01

All FSI, modifications and application of flame retardant paint


MUST be undertaken by a registered fire services contractor of
appropriate class. He/She will submit all required duly endorsed
forms to local Authorities.

Other Requirements
5.8.1

Minimum one emergency light, complying with BS5266: Part 1,


shall be provided by the tenant. He/She will submit all required
duly endorsed forms to local Authorities.

5.8.2

For any escape door, exit sign shall be installed above the door
way. He/She will submit all required duly endorsed forms to
local Authorities for the installed emergency light.

5.8.3

Maintenance of the above-mentioned equipment shall be


responsible by the tenant and in compliance with requirements
of the local Authorities. A copy of duly signed form shall be
submitted to the Representative of RTA for record.

5.8.4

Each year, the complete electrical installation shall be checked and tested
by registered electrical contractor. A copy of such test report shall be
submitted to the Representative of RTA for record.

19

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

5.8.5

A copy of the approved design drawings, fire load assessment


form, test reports for electrical installations, duly signed forms
for all FSI modified or provided by the tenant shall always be
kept inside the shop and ready for inspection.

5.8.6

The tenant to obtain Dubai Civil Defence (DCD) approval and


related aspects of Dubai metro to comply the existing system as
it all one system

20

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

6
6.1

Electrical Services Installation


No Alterations to Stations Equipment
6.1.1

Alteration to existing Stations electrical and mechanical services and


equipment is NOT permitted and kiosk/shop fitting-out must:

a.

not be attached to or suspended from the existing


Stations equipment

b.

not obstruct access to those soffits and wall areas where


essential services, monitoring points and drainage of
Station are laid
not obstruct both the supply and return of conditioned air
not cover the fan coil unit
provide adequate access for equipment maintenance

c.
d.
e.
6.2

Electrical Installations
6.2.1

6.3

FIT-OUT GUIDE
Rev 01

The electrical installations of kiosks/shops are not exempted


from the provisions of the local Electricity Ordinance. For
making any changes of the power loading or modifications to
the existing kiosk/shop installations, tenants should:
When
Before implementation

What to do
Obtain the approval from the
Representative of RTA.

After completion

Submit
an
Electrical
Work
Completion Certificate certified by a
registered electrical contractor to the
Representative of RTA.

Electrical Equipment
6.3.1

All electrical equipment including light fittings, motors and machines,


transformers and neon signs within kiosk/shop should be rated at

21

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

230V or 400V, ranged from 30 amp single phase 50 Hz to 250 amp,

three-phase 50 Hz.
6.4

Important
6.4.1

All electrical works MUST be undertaken by a registered


electrical contractor of appropriate grade. He/She must submit
a duly endorsed copy of the following before/during the final
fitting-out inspection to the Representative of RTA
a.

Electrical Work Completion Certificate

b.

Insulation Resistance Test - Distribution Board (EL/TR/01)

c.

Operation Check - Distribution Board (EL/TR/02)

22

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Air Conditioning and Mechanical Ventilation System

7.1

Air conditioning
7.1.1

The type of air conditioning system provision shall generally


include the following:
System Type
Provision
Chilled water fan coil Chilled water fan coil unit(s) to be
unit system
supplied and installed by tenant
7.1.1a

Chilled water temperature difference for FCU selection


should be 6.8 C in and 14.8 C out

7.1.1b 3 way control valve should be provided on FCU valve


package for temperature and water flow control
through FCU
7.1.2

7.2

Tenant shall submit justification including detailed cooling load


calculation if the tenant requires greater capacity of the air
conditioning than the allowed. The Representative of RTA does
not commit to accept the greater capacity subject to the site
conditions and technical feasibility.

Equipment and Material


7.2.1

NO combustible materials shall be used. Materials shall meet


the following requirements:
Material
Thermal insulation

Requirement
Approved by Dubai Civil Defence
Department. Comply with BS476
Class O fire property

Ductwork

Galvanized sheet metal

Pipework

Black mild steel or galvanized steel


of sufficient pressure rating

Air grille / diffuser

Aluminum or mild steel

23

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

7.3

FIT-OUT GUIDE
Rev 01

Mechanical Ventilation
7.3.1

Mechanical ventilation is provided for food and beverage


kiosk/shop. Depending on the site conditions, the provisions are
generally as below:
System type
Self contained
exhaust system within
the kiosk/shop

Provision
No main exhaust ductwork provided
by the Station and blank-off within
the kiosk/shop unit. Ventilation fans,
air grilles, ductworks and / or
exhaust hoods to be supplied and
installed by the tenant.

Primary / fresh air Complete the system provided by


supply system
the Station. Tenant to connect air
grilles and ductworks to the system.

7.3.2

7.4

Smoke Control
7.4.1

7.5

Emissions of steam, odor, or hot vapor from workplace or equipment of


the food and beverage kiosk / shop shall NOT be released to the station
areas. Tenants shall provide odor and / or vapor eliminators within the
kiosk/shop to avoid any smell or moist air to be released from the selfcontained exhaust system. Exhaust hood shall be provided to fully cover
and exhaust such emissions.

Closed cabin concept is adopted for the station kiosk / shop. Smoke
generated from the kiosk / shop shall be extracted out from the Station
through the station main smoke exhaust system.

Ventilation and Air Conditioning Control


7.5.1

For kiosks/shops in Station, the tenant shall connect the air conditioning
and mechanical ventilation (ACMV) equipment to a connection box
which provides a control signal to automatically switch off the tenants
ACMV equipment when fire is detected.

24

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

8
8.1

FIT-OUT GUIDE
Rev 01

Plumbing and Drainage Installation


Plumbing installations
8.1.1

Potable Water Supply


8.1.1.1

The type of potable water supply shall generally


include the following:

System Type
Potable water supply

8.2

Provision
A 15 mm diameter water pipe
connection from a meter box
comprising a water meter and
isolation valves on upstream &
downstream side provided by the
Station.
Tenant to extend the water pipe and
install internal piping and fittings
within the kiosk/shop.

8.1.2

All station water supply pipes are of PPR to standard ASTM


F2389. Use the same for retails.

8.1.3

Hot water where required shall be provided by means of local


electric hot water units branched from the potable water
supply. Hot water piping shall be suitably insulated.

Drainage Installations
8.2.1

Drainage system
8.2.1.1

The drainage system is an independently piped


drainage network used for drainage of the following
types of discharge: a.

Basins
25

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

b.
c.
d.
8.2.1.2

FIT-OUT GUIDE
Rev 01

Sinks
Condensate water from air conditioning units
Fire services test water

The drainage system shall generally include the following:

System Type
Potable water supply

Provision
One stub connection of 100mm
diameter drain pipe provided by the
Station.
Tenant to extend the drain pipe and
install internal piping and fittings
within the kiosk/shop.

8.2.1.3

All station drainage pipes are of uPVC to standard BS


4514 & BS 5520 & BS 5526. Use the same for retails.

8.2.1.4

Tenants are required to provide all local air-seal stainless


steel grease interceptors for any drainage from equipment
producing greasy waste and interconnecting pipework
within kiosk/shop. All greasy water drainage pipework
shall be of the same material as for drainage pipework.

8.3

Important
8.3.1

All plumbing and drainage works MUST be carried out by a


registered plumbing and drainage contractor of appropriate
grade. He/She must submit a duly endorsed copy of the
following before/during the final fitting-out inspection to the
Representative of RTA

26

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Communication Services Installation


9.1.1

Telephone and Data Installation


9.1.1.1

The communication services


generally include the following:

System Type

installation

shall

Telephone outlet

Provision
A cable shall be provided by the
station at boundary of kiosk /shop".
The tenant to extend the outlets
inside the retail from the terminal
box according to service provider

Data outlet

A cable shall be provided by the


station at boundary of kiosk /shop".
The tenant to extend the outlets
inside the retail from the terminal
box according to service provider

27

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Appendix A: Typical Station Provision of Kiosk / Shop


Type of Provision

Retail with food & beverage provision

Proposed Location

Concourse Level or Mezzanine Level or Ground Level;


Unpaid area
2

Floor Area
Fire Resistance Period

60 400 m
2 hours

Means of escape

Single means of escape for gross floor area of 280 m or less;

Two separate means of escape for gross floor area larger than
2

280 m
ABWF Provision
Flooring

Cement sand screeding (Approximately 50mm lower than


concourse finished level)

Wall

Blockwork or concrete wall

Ceiling

Concrete fairface surface

Others
E&M Provision

Shop front portal and fire shutter.

Power (amps)

Shops shall be provided with isolators with ampere rating


according to appendix (E), and tenants shall not exceed the
max loads allowed to be connected

Emergency Lighting

Meet local authority requirement on emergency escape

Fire Services

To comply with requirements such as sprinklers, break glass unit,


alarm bell.

Air-Conditioning

Supplied chilled water to design temperature 24 deg C, designed


cooling capacity = 0.75kW/m2

Fresh Air

As per requirement of design factor of local Authority. Pre-cool


air intake by package air handling unit to prevent condensation

Condensate Drain

100 mm diameter waste pipe for condensate pipe connection

Communications

1 no. telephone cable, 1 no. data line cable


Cable communication provision to be distributed by tenant

Potable Water

15 mm diameter

Grease Trap

Under-sink stainless steel grease trap to be provided by tenants

28

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Appendix A
Typical Station Provision of Kiosk / Shop
Type of Provision

Retail

Proposed Location

Concourse Level or Mezzanine Level or Ground Level

Floor Area
Fire Resistance Period

20-650 m
2 hours

Means of escape

Single means of escape for gross floor area of 280 m or less;

Two separate means of escape for gross floor area larger than
2

280 m
ABWF Provision
Flooring

Cement sand screeding (50mm lower than concourse finished level)

Wall

Blockwork or concrete wall

Ceiling

Concrete fairface surface

Others
E&M Provision

Shop front portal and fire shutter.

Power supply

Shops shall be provided with isolators with ampere rating


according to appendix (E), and tenants shall not exceed the
max loads allowed to be connected

Emergency Lighting

Meet local authority requirement on emergency escape

Fire Services

To comply with requirements such as sprinklers, break glass unit,


alarm bell.

Air-Conditioning

Supplied chilled water to design temperature 24 deg C, designed


cooling capacity = 0.50kW/m2

Fresh Air

As per requirement of design factor of local Authority. Pre-cool


air intake by package air handling unit to prevent condensation

Condensate Drain

100 mm diameter waste pipe for condensate pipe connection

Communications
Potable Water

1 no. telephone cable, 1 no. data line cable


Cable communication provision to be distributed by tenant
15 mm diameter

29

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Appendix B
Shop Front Perspective Design

Note: The above image is only an indicative perspective of a typical shop front
of a metro retail outlet.

30

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Appendix B1
Shop Front Letter size

31

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Appendix C1
Technical Specification and Requirements for Motorized Transparent
Security Roller Shutters
The technical specification and requirements for motorized transparent security
roller shutters are given as follows:
1.

Shutter Curtain
Fabricated from 3.7mm thickness UV protected polycarbonate multiple
panels linked joint with Powder Coated Heavy Duty aluminium hinges.
Finishing: Powder coated in RAL 9003 (white)

2.

Greaseless Shutter Guide Rails


st

Both side shutter guide rails are roll formed from 1 grade BHP zincalume
steel U-channel with PVC strips both sides with internal locking catches for
the locking bars.
Finishing: Powder coated in RAL 9003 (white)
3.

Aluminum Bottom Bar


Heavy Duty Extruded aluminum with PVC Bottom seal and Nylon guided
ends. Finishing: Powder coated in RAL 9003 (white)

4.

Operating Counter Balance System


The system is fabricated from carbon steel pipe with roller ball bearing steel
wheels with high cartoon steel counter balance springs with adjustable
tensioning arrangement.

5.

Shutter Enclosure Box


The shutter enclosure box is formed from first grade steel plate with steel
hollow sections framing design and painted in black. A sliding maintenance
panels is provided for access of manual chain override device.

32

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

6.

FIT-OUT GUIDE
Rev 01

Electrical Power Supply


The Tenant shall provide isolators with the electrical cabling from the main
supply for the motorized transparent security roller shutters. The cabling
shall be enclosed by proper cable containments or conduits.

7.

Motorised Specifications and Features


a) Power Source: (i) 220V a.c., 60Hz, Single phase
(ii) 3-phase, 220V a.c., 60 Hz motor to shutters longer than 7 meters.
b) Insulation Class E
c) Manual Chain Override
d) One unit low voltage push button control switch integrated with lockable
metal housing

8.

Proposed Supplier and Shutter Model


It is proposed that all retail shopfronts use the same type of security shutter
to ensure a consistent appearance when shops are close while station is still
in operation.
Supplier:
Al Dosteen General Trading LLC
C-18 Al Naboodah Warehouse, near Tasjeel Al Qusais Industrial Area 5, Dubai
UAE P.O. Box 231002
Tel. No. 04 2582321
Fax No. 04 2582320

Shutter model numbers:


(i)

Standard Vision 7 motorized transparent roller shutter with PVC


silencer guide and;

(ii)

Vision7 LV10 (Light weight version) motorized transparent roller


shutter with PVC silencer guide.

33

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Appendix C1-A
Standard Design Drawings for Transparent Security Roller Shutters (For
Reference Only)

Note: Tenants shall use the horizontal pulling type shutter when the headroom
or site conditions do not allow the installation of the vertical shutters shown
above.

34

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Appendix C2
Technical Specification and Requirements for Shop Numbering Plate

1.

The Shop Numbering Sign


The technical specification and requirements for the shop numbering sign
are given as follows:
1. Material: 1mm thick stainless steel with vertical hairline finish.
2. Finishing: Photo etching lettering of station abbreviation and shop
number filled with white ink.
3. Size: 90mm Wide x 84mm High x 1mm Thick
4. Setting out: Wall mounted at stainless steel column of shop front
portal and 200mm below soffit of shop front.

35

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Appendix C2-A
Standard Design Drawings for Shop Signage (For Reference Only)

LIGHT BOX
BY
LANDLORD

36

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Appendix D
Stainless Steel Shop Demarcation Line (For Reference Only)

37

DUBAI METRO
Roads and Transport Authority (RTA)
Request for Operation of Kiosks / Shops
At Dubai Metro Stations (Red & Green Lines)

FIT-OUT GUIDE
Rev 01

Appendix E
Power Supply Schedule
S/n
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Station Name
Rashidya
Rashidya
Rashidya
Rashidya
Rashidya
Rashidya
Emirates
Emirates
Emirates
Emirates
GGICO
GGICO
GGICO
GGICO
GGICO
Deiraa City Centre
Deiraa City Centre
Deiraa City Centre
Deiraa City Centre
Deiraa City Centre
Deiraa City Centre
Al Rigga
Al Rigga
Al Rigga
Al Rigga
Al Rigga
Union
Union
Union
Union
Union
Union
Union
Union
Khaleed Bin Al Walleed
Khaleed Bin Al Walleed
Khaleed Bin Al Walleed
Khaleed Bin Al Walleed
Khaleed Bin Al Walleed
Khaleed Bin Al Walleed
Khaleed Bin Al Walleed
Khaleed Bin Al Walleed

Shop No.
(RFP)

DURL Shop
No.

Isolator
rating (A)

1
2
3
4
R01A-1
R01A-2
1
2
R02A-1
RO2B-1
1
2
RO5A-1
RO5B-1
RO5B-2
1
2
3
4
5
6
1
2
3
4
5
1
2
3
4
5
6
7
8
1
3
4
5
6
7
8
9

R40.4
R40.3
R40.2
R40.1
R41
R41.1
R40.1
R40.2
R41
R41
R40.1
R40.2
R41
R41
R41.1
R40.1
R40.4
R40.2
R40.3
R40.6
R40.5
R40.1
R40.2
R40.3
R40.4
R40.5
R40.1
R40.2
R40.3
R40.4
R40.5
R40.6
R40.7
R40.8
R40.2
R40.1
R40.10
R40.9
R40.3
R40.4
R40.5
R40.6

32
63
32
100
32
32
32
32
32
100
32
32
32
100
32
32
100
100
63
63
32
32
100
63
63
63
100
32
32
63
100
32
NA
100
100
100
200
200
100
63
100
100

38

43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94

Khaleed Bin Al Walleed


Khaleed Bin Al Walleed
Khaleed Bin Al Walleed
Khaleed Bin Al Walleed
Khaleed Bin Al Walleed
Khaleed Bin Al Walleed
Al Karama
Al Karama
Al Karama
Al Karama
Al Jafiliya
Al Jafiliya
Al Jafiliya
World Trade Centre
World Trade Centre
World Trade Centre
Emirates Towers
Emirates Towers
Emirates Towers
Emirates Towers
Financial Centre
Financial Centre
Financial Centre
Financial Centre
Burj Dubai/Dubai Mall
Burj Dubai/Dubai Mall
Burj Dubai/Dubai Mall
Burj Dubai/Dubai Mall
Burj Dubai/Dubai Mall
Business Bay
Business Bay
Al Quoz
Al Quoz
Al Quoz
First Gulf Bank
First Gulf Bank
First Gulf Bank
Mall of Emirates
Mall of Emirates
Mall of Emirates
Sharaf DG
Sharaf DG
Dubai Internet City
Dubai Internet City
Dubai Internet City
Dubai Internet City
Dubai Internet City
Nakheel
Nakheel
Nakheel
Nakheel
Nakheel

11
12
Pod A
Pod B
Pod C
Pod D
1
2
R10A-1
R10B-1
1
2
R11A-1
1
2
R12A-1
1
2
R13A-1
R13B-1
1
2
R14A-1
R14B-1
1
2
R15A-1
R15B-1
R15B-2
1
R16A-1
1
2
R17A-1
1
2
R18A-1
1
2
R18aB-1
1
R19A-1
1
2
R20C-1
R20D-1
R20D-2
1
2
4
R21B-1
R21B-2
39

R40.8
R40.7
R40.11
R40.12
R40.13
R40.14
R40.1
R40.2
R41
R41
R40.1
R40.3
R41
R40.1, R40.3
R40.2
R41
R40.2
R40.1
R41
R41
R40.2
R40.1
R41
R41
R40.1
R40.2
R41
R41
R41.1
R40.3
R41
R40.1
R40.2, R40.3
R41
R40.1
R40.2, R40.3
R41
R40.2
R40.1
R41
R40.3
R41
R40.2
R40.1
R41
R41
R41.1
R40.3
R40.4
R40.2
R41
R41.1

100
200
63
32
63
63
32
32
100
100
32
32
100
32
32
100
32
32
32
100
32
32
100
NA
32
32
32
100
32
32
100
32
32
100
32
32
32
32
100
32
32
100
32
32
100
100
32
63
100
32
32
32

95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118

Dubai Marina
Dubai Marina
Dubai Marina
Dubai Marina
Jumeira Lake Towers
Jumeira Lake Towers
Jumeira Lake Towers
Jumeira Lake Towers
Jumeira Lake Towers
Jumeira Lake Towers
Nakheel Harbor & Tower
Nakheel Harbor & Tower
Nakheel Harbor & Tower
Ibn Battuta
Ibn Battuta
Energy
Energy
Energy
Jebel Ali Industrial
Jebel Ali Industrial
Jebel Ali Industrial
Jebel Ali
Jebel Ali
Jebel Ali

1
2
R22A-1
R22C-1
1
2
R23A-1
R23B-1
R23C-1
R23C-2
1
2
R24B-1
1
R25A-1
1
2
R26A-1
1
2
R27A-1
1
R28A-1
R28A-2

R40.1
R40.2
R41
R41
R40.1
R40.2
R41
R41
R41
R41.1
R40.1
R40.2,40.3
Missing
R40.3
R41
R40.1
R40.2,40.3
R41
R40.1
R40.2,40.3
R41
R40
R41
R41.1

40

32
32
100
100
32
32
100
100
100
32
32
32
NA
32
32
32
32
100
32
32
100
63
32
100