Professional Documents
Culture Documents
Introduction: -
7.
Analogue Inputs
(Secondary for of currents and Voltages)
Binary Inputs
(Off/On conditions of the equipments)
Signaling Inputs
(Trigger pulse after satisfying the conditional
approaches)
INPUTS
Logic Control
following tasks
equations
perform
the
1.
DISP. UNIT
OUT PUTS
Input
Functio
Assignt
Out
put
Fun
Intermittent
Logic
Equations
Event
Report,
Self Sup.
Others
3. Application of GMR
1.
2.
3.
4.
5.
Setting
Option
OFF
ON
1100
V
Default
Setting
ON
Balance
Factor V
Balance I
limit
0.580.90
0.55.00A
0.75
Balance
Factor I
I
threshold
I Factor
0.10.90
0.2510.00A
0.000.95
50 V
2.5 A
0.50
0.50
0.10
Comments
Measured value
Monitor
Symmetry
Uph(threshold
Value)
Symmetry
Uph(Characteristic)
Symmetry
Iph(threshold
Value)
Symmetry
Iph(Characteristic)
Sum I threshold
Value
Sum I
Characteristic
3.1.3.c Trip-Coil Supervision Circuit:By the use of binary input relays (Optocoupler Relays in the GMR) and the logic functions,
the trip coil circuit is monitored/supervised. The
control voltage to the trip coil is tracked and declares
healthy of the coil circuit till to the end of the coil
terminals. The message (Trip coil faulty) is issued as
the annunciation tag for the break of control voltage
across the coil.
Moreover the logic circuit and equation used
for the supervision circuit provide the necessary
diagnosis regarding the faulty part of the circuit.
Every part (Contact) is generally coded with some
nominal value w.r.t the reference and during
normal/healthy condition the values remain within
the limitation. But on fault condition the value goes
beyond the limit and issues the message as Trip coil
faulty.
3.1.3.d. Interlock Supervision Circuit
Interlock between the equipments is always
explained as the conditional operation of the
components in the system. Suppose an isolator is to
be operated in series to the breaker in the system,
then this isolator must not be operated when circuit
breaker is in closed condition i.e. the power
interruption or reconnection should not be done
through isolator. Because this equipment is
considered as a switch, that operated in air medium.
Switching action in air medium may result severe
spark/arc and damage to the equipment with
interruption of power supply to the consumers.
By considering the above factors, the
available contacts are brought to the relay and
simulated for the software design, as per the
requirement of the systems. To design the scheme
only single pair of N/O and N/C contact from the
involved equipments in the total system is brought
for the relay design instead of the multi number of
contacts. The logic equations as per the scheme are
written for the software design. For any operation of
the equipment, the relay studies the logic of the
operation circuit and extends the permissive out put
contact for the operation.
Self supervision of the relay elements,
contacts and other associated circuits are done by the
pre- defined logic equations. For the case of any
abnormality in the self supervision circuits, warning
command is extended to the display unit with detail
faults in the circuit
2.
3.
4.
5.
6.
29M
29B1
52L
52B
29L
29B2
29T
Fig A
Sequential Operation
1.
2.
3.
Conclusion:-