You are on page 1of 67

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

399A4822

SH

Page 1 of 67
REV

REVISION HISTORY
REV

ZONE

DATE

DESCRIPTION

APPROVED

YYYY-MM-DD

DEVICE SUMMARY SYSTEM 4027


UPDATED PER ISS-0034683.
REFER ISSUE NOTES IN DEVICE
SUMMARY FOR DETAILS OF
CHANGE. ECO0090698 SELVAM
VELUSAMY.

2013-02-06

AS PER ISS0050596 RM THE


FOLLOWING DEVICES WERE
ADDED:
20TW-7,96WW-4,VA16-4.
AS PER ISS0050596 RM THE
FOLLOWING DEVICE IS
MODIFIED:
PI-WW-13

2013-07-22

DRAWN
SV
ENGINEER
MLL
DRAWN
502209130
ENGINEER
502036044

THIS DOCUMENT SHALL BE REVISED


IN ITS ENTIRETY. ALL SHEETS OF
THIS DOCUMENT ARE THE SAME
REVISION LEVEL AS INDICATED.

REVISION DESCRIPTION IS FULLY


STATED ON FIRST SHEET OF
DOCUMENT
COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)


DRAWING TYPE
SIGNATURES
DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

CHECKED

LUBBERT, MARK

GE Energy

GENERAL ELECTRIC COMPANY

CHECKED DATE
ENGRG

BALLA, SANKAR

Device Summary

ENGRG DATE
APPLIED PRACTICES

ADDITIONAL APPROVALS
SEE PLM FOR APPROVAL
INFORMATION

SIM TO:

FIRST MADE FOR ML: DM:720103 CC:0414


SIZE

CAGE CODE

DWG NO

399A4822
SHEET

1 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

Page 2 of 67

REV

System

Title

0415
0416
0417
0419
0420
0422
0426
0432
0434
0436
0440
0442
0471
0474
0477
0492
4027
4035

CONTROL DEVICES -TURBINE


LUBE OIL SYSTEM
COOL & SEAL AIR SYSTEM
CONTROL AIR
COOLING WATER SYSTEM
GAS FUEL SYSTEM
FIRE PROTECTION SYSTEM
INLET AIR HEATING
HYDRAULIC SUPPLY SYSTEM
HEAT & VENT SYSTEM
LOAD EQUIPMENT
TURBINE & COMPRESSOR WASH
INLET AND EXHAUST
HAZARDOUS GAS DETECTION
FUEL PURGE
PERFORMANCE MONITOR
H2 ACCESSORIES (Ref. G2FA)
FUEL GAS CHROMATOGRAPGH

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

2 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

Page 3 of 67

REV

NOTES
Rev "B"
Device

System Operation

20TW-7
96WW-4
VA16-4
PI-WW-13

0442
0442
0442
0442

Added
Added
Added
Modified

Sivasubramaniam
22JUL13
----------------------------------------Rev "A"
Device

System Operation

PSL-2950

4027

Deleted

Selvam Velusamy
06FEB13

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

3 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

Page 4 of 67

SH

399A4822

REV

SWITCH SETTINGS

Contact Condition

NO-

Normally open

NC-

Normally closed

()-

Parenthesis indicates sets of


contacts

Additional Contacts
CEC Additional contact:
Normally closed
Electrically common
CES Additional contact:
Normally closed
Electrically separate
OEC Additional contact:
Normally open
Electrically common
OES Additional contact:
Normally open
Electrically separate

Example: NORM=(2) NO-CEC

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

4 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

Device
20-TQ2-2

System
0417

20-TQ2-4

0417

20AP-1

0419

20CB-1

0417

20CB-2

0417

20CM-1

0417

20FGC-1

0422

20FGC-2

0422

20FGC-3

0422

20FGS-1

0422

20PG-1

0477

Page 5 of 67

REV

Settings
SOLENOID VALVE
DE-ENERGIZED:3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC;
DE-ENERGIZED TO TRIP OPEN VA7-2
SOLENOID VALVE
DE-ENERGIZED : 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED : 1 TO 2 OPEN; 3 PLUGGED
125 VDC;
DE-ENERGIZED TO TRIP CLOSED VA7-3
APU SHUTOFF VALVE.
DE-ENERGIZED: 1 TO 2 CLOSED
ENERGIZED: 1 TO 2 OPEN
230 VAC; 50 HZ; SINGLE PHASE
PROTECTS DESSICANT FROM OVER TEMPERATURE. CONTROL SIGNAL NAME
IS L20AP1, APU TROUBLE RELAY (SHUT-OFF VALVE CLOSE RELAY). WIRE TO
MKV / MARKVI.
COMPRESSOR BLEED SOL VALVE
NORM=B TO C OPEN; A CLOSED
COMPRESSOR BLEED SOL VALVE
NORM B TO C OPEN; A CLOSED
CASE TEMP. MANAGEMENT FLOW CONTROL DAMPER
FAILED POSITION = CLOSED
FUEL GAS CONTROL VALVE SOLENOID VALVE
DE-ENERGIZED: 1 TO 2 OPEN
ENERGIZED: 1 TO 2 CLOSED
125 VDC;
FUEL GAS CONTROL VALVE SOLENOID VALVE
DE-ENERGIZED: 1 TO 2 OPEN
ENERGIZED: 1 TO 2 CLOSED
125 VDC;
FUEL GAS CONTROL VALVE SOLENOID VALVE
DE-ENERGIZED: 1 TO 2 OPEN
ENERGIZED: 1 TO 2 CLOSED
125 VDC;
FUEL GAS STOP VALVE SOLENOID VALVE
DE-ENERGIZED: 1 TO 2 OPEN
ENERGIZED: 1 TO 2 CLOSED
125 VDC;
GAS FUEL SYSTEM PURGE SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC;

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

5 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

Device
20PG-2

System
0477

20PG-5

0477

20PG-6

0477

20QB-1

0434

20TH-1

0432

20TV-1

0434

20TW-4

0442

20TW-6

0442

20TW-7

0442

Page 6 of 67

REV

Settings
GAS FUEL SYSTEM PURGE SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC;
GAS FUEL SYSTEM PURGE SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC;
PART OF VA13-5
GAS FUEL SYSTEM PURGE AIR SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC;
PART OF VA13-6
LIFT OIL SUPPLY ISOLATION VALVE
DE-ENERGIZED: 1 TO 2 CLOSED
ENERGIZED: 1 TO 2 OPEN
230 VAC; 50 HZ;
1 PH
INLET HEATING CONTROL VALVE TRIP SOLENOID VALVE
125 VDC;
DE-ENERGIZE TO TRIP VA20-1
ENERGIZE TO OPERATE VA20-1
AREA CLASSIFICATION : NON-RATED
PROTECTION METHOD : D-FLAMEPROOF
TURBINE COMPRESSOR IGV SOLENOID VALVE
125 VDC;
OFF-LINE COMPRESSOR WASH WATER INJ SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC; 20.60 W; 0.1600 A;
PART OF VA16-1
ON-LINE COMPRESSOR WASH WATER INJ SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC; 20.60 W; 0.1600 A;
PART OF VA16-3
GFC WATER INJ SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC; 20.60 W; 0.1600 A;
PART OF VA16-4

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

6 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

Device
20VG-1

System
0422

20VG-2

0477

20VG-4

0477

20VG-8

0422

20VS4-1
20VS4-4
20WDET

0422
0422
0442

23BL-1

0436

23BL-2

0436

23BN-1

0417

23BN-2

0417

23BT-1

0436

Page 7 of 67

REV

Settings
FUEL GAS VENT SOLENOID VALVE TEST
DE-ENERGIZED: 1 TO 3 OPEN; 2 PLUGGED
ENERGIZED: 2 TO 1 OPEN; 3 PLUGGED
125 VDC;
FUEL GAS VENT SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC; 10.60 W; 0.0800 A;
PART OF VA13-8
GAS FUEL VENT SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC; 10.60 W; 0.0800 A;
PART OF VA13-13
FUEL GAS VENT SOLENOID VALVE
DE-ENERGIZED: 1 TO 3 OPEN; 2 PLUGGED
ENERGIZED: 2 TO 1 OPEN; 3 PLUGGED
125 VDC;
FUEL GAS AUXILIARY STOP VALVE
FUEL GAS SAFETY SHUTOFF VALVE-SOLENOID VALVE
SOLENOID, 2 WAY VALVE TO RECIRCULATE WATER BACK TO TANK.
230 VAC; 50 HZ;
1 PH;
DE-ENERGIZED: 1 TO 2 CLOSED
ENERGIZED: 1 TO 2 OPEN
CONTROL SIGNAL NAME IS L20WDET. WIRE TO MK V / MK VI. MK V / MK VI
OUTPUT SIGNAL IS DRY CONTACT.
FAN MOTOR HEATER FOR 88BL-1
60.00 W; 230 VAC; 1 PH; 50 HZ;
FAN MOTOR HEATER FOR 88BL-2
60.00 W; 230 VAC; 1 PH; 50 HZ;
SPACE HEATER
100.0 W; 230 VAC; 1 PH; 50 HZ;
MAX WATTAGE
FOR MOTOR 88BN-1
SPACE HEATER
100.0 W; 230 VAC; 1 PH; 50 HZ;
MAX WATTAGE
FOR MOTOR 88BN-2
HEATER-TURBINE COMPT FAN MOTOR
200.0 W; 230 VAC; 1 PH; 50 HZ;
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAMEPROOF

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

7 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

Device
23BT-2

System
0436

23CM-1

0417

23HG-1

0440

23HG-2

0440

23HL-1

0436

23HL-3

0436

23HQ-1

0434

23HQ-2

0434

23HT-1A

0436

23HT-1B

0436

23HT-3A

0436

23HT-3B

0436

23IC-1

0471

23KE-1

0440

23QA-1

0416

23QA-2

0416

23QS-1

0416

Page 8 of 67

REV

Settings
HEATER-TURBINE COMPT FAN MOTOR
200.0 W; 230 VAC; 1 PH; 50 HZ;
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAMEPROOF
CASE TEMP. MANAGEMENT BLOWER MOTOR SPACE HEATER
120.0 W; 230 VAC; 1 PH; 50 HZ;
FOR MOTOR 88CM-1
SPACE HEATER-GENERATOR
2.250 KW; 400 VAC; 3 PH; 50 HZ;
SPACE HEATER-GENERATOR
2.250 KW; 400 VAC; 3 PH; 50 HZ;
SPACE HEATER-LUBE OIL SKID
20.00 KW; 400 VAC; 3 PH; 50 HZ;
HEATING FOR FREEZE PROTECTION
SPACE HEATER-ACCESSORY COMPT, LUBE OIL REGION
3.600 KW; 400 VAC; 1 PH; 50 HZ;
USED FOR HUMIDITY CONTROL
HEATER-HYDRAULIC OIL PUMP MOTOR
60.00 W; 230 VAC; 1 PH; 50 HZ;
SPACE HEATER-HYDRAULIC PUMP MOTOR
60.00 W; 230 VAC; 1 PH; 50 HZ;
SPACE HEATER-TURBINE COMPARTMENT
30.00 KW; 400 VAC; 3 PH; 50 HZ;
HEATING FOR FREEZE PROTECTION
SPACE HEATER-TURBINE COMPARTMENT
30.00 KW; 400 VAC; 3 PH; 50 HZ;
HEATING FOR FREEZE PROTECTION
SPACE HEATER-TURBINE COMPARTMENT
3.600 KW; 400 VAC; 1 PH; 50 HZ;
HEATING FOR HUMIDITY CONTROL
SPACE HEATER-TURBINE COMPARTMENT
3.600 KW; 400 VAC; 1 PH; 50 HZ;
HEATING FOR HUMIDITY CONTROL
MOTOR HEATER FOR DEVICE 88IC-1
35.00 W; 230/480 VAC; 1 PH; 50 HZ;
HEATER-GENERATOR COLLECTOR ENCLOSURE
150.0 W; 230 VAC; 1 PH; 50 HZ;
HEATER-AUX LUBE OIL PUMP MOTOR
100.0 W; 230 VAC; 1 PH; 50 HZ;
SPACE HEATER-AUX LUBE OIL PUMP MOTOR
100.0 W; 230 VAC; 1 PH; 50 HZ;
HEATER-SEAL OIL PUMP MOTOR
60.00 W; 230 VAC; 1 PH; 50 HZ;

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

8 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

Device
23QT-1

System
0416

23QT-2

0416

23QT-3

0416

23QV-2A

0416

23QV-2B

0416

23TG-1

0416

23TK-1

0417

23TK-2

0417

23TW-1

0442

23VG-1

0436

23VG-2

0436

23VS-1

0436

23VS-3

0436

23WK-1

0442

23WK-2

0442

23WS-1

0442

26TG-1

0416

Page 9 of 67

REV

Settings
IMMERSION HEATER-LUBE OIL TANK
12.00 KW; 400 VAC; 3 PH; 50 HZ;
IMMERSION HEATER-LUBE OIL TANK
12.00 KW; 400 VAC; 3 PH; 50 HZ;
IMMERSION HEATER-LUBE OIL TANK
12.00 KW; 400 VAC; 3 PH; 50 HZ;
SPACE HEATER-FOR 88QV-1A
60.00 W; 230 VAC; 1 PH; 50 HZ;
SPACE HEATER-FOR 88QV-1B
60.00 W; 230 VAC; 1 PH; 50 HZ;
TURNING GEAR MOTOR HEATER
75.00 W; 230 VAC; 1 PH; 50 HZ;
TURBINE SHELL & EXHAUST FRAME BLOWER MOTOR HEATER
225.0 W; 230 VAC; 1 PH; 50 HZ;
MAX WATTAGE
FOR MOTOR 88TK-1
TURBINE SHELL & EXHAUST FRAME BLOWER MOTOR HEATER
225.0 W; 230 VAC; 1 PH; 50 HZ;
MAX WATTAGE
FOR MOTOR 88TK-2
HEATER-WATER WASH PUMP MOTOR
60.00 W; 230 VAC; 1 PH; 50 HZ;
(PART OF 88TW-1)
HEATER-VENTILATION FAN MOTOR (LOAD COMPT)
60.00 W; 230 VAC; 1 PH; 50 HZ;
HEATER-VENTILATION FAN MOTOR (LOAD COMPT)
60.00 W; 230 VAC; 1 PH; 50 HZ;
SPACE HEATER-VALVE COMPARTMENT
20.00 KW; 400 VAC; 3 PH; 50 HZ;
HEATING FOR FREEZE PROTECTION
SPACE HEATER-ACCESSORY COMPT, GAS FUEL MOD REGION
3.600 KW; 400 VAC; 1 PH; 50 HZ;
USED FOR HUMIDITY CONTROL
IMMERSION HEATER WATER WASH
45.00 KW; 400 VAC; 3 PH; 50 HZ;
IMMERSION HEATER WATER WASH
45.00 KW; 400 VAC; 3 PH; 50 HZ;
WATER WASH SKID SPACE HEATER
10.00 KW; 400 VAC; 3 PH; 50 HZ;
THERMOSTAT, TURNING GEAR MOTOR WINDING

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

9 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

10

Device
26TW-4

System
0442

26VW-3

0442

27AD-1

0419

27TF-1

0471

27WD-1

0442

28FD-15
28FD-16
28FD-17
28FD-18
2FP-1A

0415
0415
0415
0415
0426

2FP-1AE

0426

2FP-2A

0426

2FP-2AE

0426

2FP-3A

0426

Page 10 of 67

REV

Settings
-5 TO 50 MV, TEMPERATURE ELEMENT FOR TANK TEMPERATURE.
TYPE J THERMOCOUPLE
1 ELEMENT;
INCREASING: 180.0 +/- 5.0 F OR 82.22 +/- 2.778 C
DECREASING: 52.0 +/- 2.0 F OR 11.11 +/- 1.111 C
THIRD SET-POINT 75.0 +/- 2 F INCREASING
TEMP. ELEMENT FOR COMPT. SPACE HEATER AND VENT FAN.
TYPE J THERMOCOUPLE
1 ELEMENT;
OPERATE VENT FAN AT 95 DEGREES F INCREASING.
OPERATE SPACE HEATER AT 65 DEGREES F DECREASING.
ALARM AT 43 DEGREES F DECREASING.
ALARM AT 130 DEGREES F INCREASING.
APU LOSS OF POWER ALARM
CONTROL SIGNAL NAME IS L27AD1. WIRE TO MK V / MK VI.
GT AIR FILTER GENERAL ALARM DISPATCHING
1 PH, 2A RESISTIVE, 125VDC, 0.2A INDUCTIVE
NORM=(1) NO;
WATER WASH SKID LOSS OF POWER ALARM RELAY
WIRE TO MKV / MK VI
FLAME DETECTOR COMBUSTION CHAMBER #15
FLAME DETECTOR COMBUSTION CHAMBER #16
FLAME DETECTOR COMBUSTION CHAMBER #17
FLAME DETECTOR COMBUSTION CHAMBER #18
FIRE PROTECTION-INITIAL DISCHARGE TIMER (ZONE 1)
(ZONE 1)
INITIAL DISCHARGE
FIRE PROTECTION-EXTENDED DISCHARGE TIMER (ZONE 1)
(ZONE 1)
EXTENDED DISCHARGE
FIRE PROTECTION-INITIAL DISCHARGE TIMER (ZONE 2)
(ZONE 2)
INITIAL DISCHARGE
FIRE PROTECTION-EXTENDED DISCHARGE TIMER (ZONE 2)
(ZONE 2)
EXTENDED DISCHARGE
FIRE PROTECTION-INITIAL DISCHARGE TIMER (ZONE 3)
(ZONE 3)
INITIAL DISCHARGE

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

10 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

11

Device
2FP-3AE

System
0426

30FP-10A

0426

30FP-1A

0426

30FP-1B

0426

30FP-20A

0426

30FP-2A

0426

30FP-30A

0426

30FP-3A

0426

30GCX-1

4035

30GCX-2

4035

30GCX-3

4035

30GCX-4

4035

Page 11 of 67

REV

Settings
FIRE PROTECTION-EXTENDED DISCHARGE TIMER (ZONE 3)
(ZONE 3)
EXTENDED DISCHARGE
FIRE PROTECTION TRIP CONTACT
ZONE 1 PRE-DISCHARGE CONTACT
NORM=(1) NO-CEC;
CONTACT IS AVAILABLE FOR CUSTOMER USE. CLOSES UPON START OF PREDISCHARGE TIMER. CONTACT RATED FOR 5A@24VDC OR 120VAC.
TROUBLE ANNUNCIATOR CONTACT
NORM=(1) NC; 125VDC CONTACT;
CONTACT WIRED TO TCP AND OPENS TO INDICATE A FAULT IN THE FIRE
PROTECTION SYSTEM
SUPERVISORY ANNUNCIATOR CONTACT
NORM=(1) NC; 125VDC CONTACT;
CONTACT WIRED TO TCP AND OPENS TO INDICATE THE FIRE PROTECTION
FLUID HAS BEEN ISOLATED FROM THE PROTECTED SPACES
FIRE PROTECTION TRIP CONTACT (ZONE 2)
ZONE 2 PRE-DISCHARGE CONTACT
NORM=(1) NO-CEC;
CONTACT IS AVAILABLE FOR CUSTOMER USE. CLOSES UPON START OF PREDISCHARGE TIMER. CONTACT RATED FOR 5A@24VDC OR 120VAC.
TROUBLE ANNUNCIATOR CONTACT
NORM=(1) NC;
CUSTOMER CONTACT. OPENS TO INDICATE A TROUBLE CONDITION WITH THE
FP SYSTEM. CONTACT RATED FOR 5A@24VDC OR 120VAC
FIRE PROTECTION TRIP CONTACT (ZONE 3)
ZONE 3 PRE-DISCHARGE CONTACT
NORM=(1) NO-CEC;
CONTACT IS AVAILABLE FOR CUSTOMER USE. CLOSES UPON START OF PREDISCHARGE TIMER. CONTACT RATED FOR 5A@24VDC OR 120VAC.
SUPERVISORY ANNUNCIATOR CONTACT
NORM=(1) NC;
CUSTOMER CONTACT. OPENS TO INDICATE A SUPERVISORY FAULT
CONDITION WITH THE FP SYSTEM. CONTACT RATED FOR 5A@24VDC OR
120VAC
FG CHROMATOGRAPH - GC A- TROUBLE ALARM
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
FG CHROMATOGRAPH - GC B - TROUBLE ALARM
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
FG CHROMATOGRAPH - GC A - CALIBRATION GAS ERROR ALARM
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
FG CHROMATOGRAPH - GC B - CALIBRATION GAS ERROR ALARM
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

11 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

12

Device
30SG-1

System
0415

33-TQ2-2

0417

33-TQ2-3

0417

33-TQ2-4

0417

33-TQ2-5A

0417

33-TQ2-5B

0417

33-TQ2-5C

0417

33CB-1

0417

33CB-2

0417

33CB-3

0417

33CB-4

0417

33CB-5

0417

33CB-6

0417

Page 12 of 67

REV

Settings
DIAGNOSTIC IGNITION EXCITER SWITCH
NORM=NO; CLOSE ON EXCITER FAILURE;
LIMIT SWITCH
LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACTS CLOSE TO INDICATE VALVE VA7-2 OPEN
LIMIT SWITCH
LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACTS CLOSE TO INDICATE VALVE VA7-2 CLOSED
LIMIT SWITCH
LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACTS CLOSE TO INDICATE VALVE VA7-3 OPEN
LIMIT SWITCH
LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACTS CLOSE TO INDICATE VALVE VA7-3 CLOSED
LIMIT SWITCH
LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACTS CLOSE TO INDICATE VALVE VA7-3 CLOSED
LIMIT SWITCH
LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACTS CLOSE TO INDICATE VALVE VA7-3 CLOSED
COMPRESSOR BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-1 VALVE IS OPEN
COMPRESSOR BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-2 VALVE IS OPEN
COMP BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-3 VALVE IS OPEN
COMP BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-4 VALVE IS OPEN
COMPRESSOR BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-1 VALVE IS CLOSED
COMPRESSOR BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-2 VALVE IS CLOSED

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

12 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

13

Device
33CB-7

System
0417

33CB-8

0417

33FP-31

0426

33FP-31E

0426

33FP-32

0426

33FP-32E

0426

33FP-33

0426

33FP-33E

0426

33PG-1

0477

33PG-10

0477

33PG-11

0477

33PG-12

0477

Page 13 of 67

REV

Settings
COMPRESSOR BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-3 VALVE IS CLOSED
COMPRESSOR BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-4 VALVE IS CLOSED
FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCH
NORM=(2) NC-OEC;
SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN
VALVE IS OPEN
FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCH
NORM=(2) NC-OEC;
SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN
VALVE IS OPEN
FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCH
NORM=(2) NC-OEC;
SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN
VALVE IS OPEN
FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCH
NORM=(2) NC-OEC;
SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN
VALVE IS OPEN
FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCH
NORM=(2) NC-OEC;
SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN
VALVE IS OPEN
FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCH
NORM=(2) NC-OEC;
SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN
VALVE IS OPEN
FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES;
FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES;
CLOSED WITH VALVE OPEN
PART OF VA13-5
FUEL GAS PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES;
CLOSED WITH VALVE CLOSED
PART OF VA13-6
FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES;
CLOSED WITH VALVE OPEN
PART OF VA13-6

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

13 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

14

Device
33PG-15

System
0477

33PG-16

0477

33PG-2

0477

33PG-3

0477

33PG-4

0477

33PG-9

0477

33TH-3

0432

33VG-4

0422

33VG-8

0422

33VG-9

0422

33VS4-1

0422

33VS4-2

0422

33VS4-4

0422

33VS4-5

0422

Page 14 of 67

REV

Settings
FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES; CLOSED WITH VALVE 55% OPEN;
PART OF VA13-2
FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES; CLOSED WITH VALVE CLOSED;
SPARE
PART OF VA13-2
FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES; CLOSED WITH VALVE OPEN;
FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES; CLOSED WITH VALVE CLOSED;
FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES; CLOSED WITH VALVE 17% OPEN;
PART OF VA13-2
FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES; CLOSED WITH VALVE CLOSED;
PART OF VA13-5
INLET HEATING ISOLATION VALVE LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACT CLOSED WITH VM15-1 FULL OPEN
AREA CLASSIFICATION : NON-RATED
PROTECTION METHOD : D-FLAMEPROOF
GAS FUEL VENT VALVE-LIMIT SWITCH
NORM=(1) NO-CEC;
SWITCH CLOSES WHEN VALVE CLOSES
GAS FUEL VENT VALVE-LIMIT SWITCH
NORM=(1) NO-CEC;
SWITCH CLOSES WHEN VALVE OPENS
GAS FUEL VENT VALVE-LIMIT SWITCH
NORM=(1) NO-CEC;
SWITCH CLOSES WHEN VALVE CLOSES
FUEL GAS STOP VALVE-LIMIT SWITCH
SWITCH CLOSES WHEN VALVE OPENS
NORM=(1) NO-CEC;
FUEL GAS STOP VALVE-LIMIT SWITCH
SWITCH CLOSES WHEN VALVE CLOSES
NORM=(1) NO-CEC;
FUEL GAS STOP VALVE-LIMIT SWITCH
SWITCH CLOSES WHEN VALVE OPENS
NORM=(1) NO-CEC;
FUEL GAS STOP VALVE-LIMIT SWITCH
SWITCH CLOSES WHEN VALVE CLOSES
NORM=(1) NO-CEC;

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

14 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

15

Device
34AD-1

System
0419

34TF-1

0471

39V-1A

0415

39V-1B

0415

39V-2A

0415

39V-2B

0415

39V-4A

0440

39V-4B

0440

39V-5A

0440

39VS-101

0440

39VS-102

0440

39VS-11

0415

39VS-12

0415

39VS-21

0415

39VS-22

0415

Page 15 of 67

REV

Settings
AIR DRYER
100.0 W; 230 VAC; 1 PH; 50 HZ;
HEATLESS DRYER
TURBINE INLET AIR FILTER-SELF CLEANING SEQUENCER
1 PH
230 VAC; 50 HZ;
VIBRATION SENSOR TURBINE
OUTPUT AT 1``/SEC = 150.0 MV
VIBRATION SENSOR TURBINE
OUTPUT AT 1``/SEC = 150.0 MV
VIBRATION SENSOR TURBINE
OUTPUT AT 1``/SEC = 150.0 MV
VIBRATION SENSOR TURBINE
OUTPUT AT 1``/SEC = 150.0 MV
VIBRATION SENSOR GENERATOR
OUTPUT AT 1``/SEC = 150.0 MV
LOCATED ON TURBINE END BEARING CAP
VIBRATION SENSOR GENERATOR
OUTPUT AT 1``/SEC = 150.0 MV
LOCATED ON TURBINE END BEARING CAP
VIBRATION SENSOR GENERATOR
OUTPUT AT 1``/SEC = 150.0 MV
LOCATED ON COLLECTOR END BEARING CAP
VIBRATION SENSOR (NON-CONT) GEN COLLECTOR END
BENTLEY NEVADA, 3300 SERIES
PROXIMITY PROBE FOR GENERATOR SHAFT
RANGE:200 MV PER MILLIINCH
ALARM @ 0.006``
VIBRATION SENSOR (NON-CONT) GEN COLLECTOR END
BENTLEY NEVADA, 3300 SERIES
PROXIMITY PROBE FOR GENERATOR SHAFT
RANGE:200 MV PER MILLIINCH
ALARM @ 0.006``
VIBRATION SENSOR (NON-CONTACTING)
OUTPUT AT 1 MIL = 200.0 MV
VIBRATION SENSOR (NON-CONTACTING)
OUTPUT AT 1 MIL = 200.0 MV
VIBRATION SENSOR (NON-CONTACTING)
OUTPUT AT 1 MIL = 200.0 MV
VIBRATION SENSOR (NON-CONTACTING)
OUTPUT AT 1 MIL = 200.0 MV

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

15 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

16

Device
39VS-91

System
0440

39VS-92

0440

43MRA-1C

0426

43MRA-3A

0426

43MRA-3B

0426

43MRFP-1A

0426

43MRFP-2A

0426

43MRFP-3A

0426

43MRT-1A

0426

43MRT-1B

0426

43WK-1
43WK-2
45FA-30A

0442
0442
0426

Page 16 of 67

REV

Settings
VIBRATION SENSOR (NON-CONT) GEN COUPLING END
BENTLEY NEVADA, 3300 SERIES
PROXIMITY PROBE FOR GENERATOR SHAFT
RANGE:200 MV PER MILLIINCH
ALARM @ 0.006``
VIBRATION SENSOR (NON-CONT) GEN COUPLING END
BENTLEY NEVADA, 3300 SERIES
PROXIMITY PROBE FOR GENERATOR SHAFT
RANGE:200 MV PER MILLIINCH
ALARM @ 0.006``
MANUAL DISCHARGE SWITCH (ACCESSORY COMPT)
LOCATED OUTSIDE NEXT TO ACCESSORY COMPARTMENT DOOR (ZONE 1)
MANUAL DISCHARGE SWITCH (ACCESSORY MODULE)
LOCATED OUTSIDE NEXT TO ACCESSORY COMPARTMENT DOOR (ZONE 3)
MANUAL DISCHARGE SWITCH (ACCESSORY MODULE)
LOCATED OUTSIDE NEXT TO ACCESSORY COMPARTMENT DOOR (ZONE 3)
FIRE PROTECTION-MANUAL DISCHARGE SWITCH (ZONE 1)
NORM=(2) NC-OEC;
LOCATED ON ELECTRICAL CONTROL CABINET DOOR ON CO2 SKID. SWITCH
HELD OPEN WITH PIN.
FIRE PROTECTION-MANUAL DISCHARGE SWITCH (ZONE 2)
NORM=(2) NC-OEC;
LOCATED ON ELECTRICAL CONTROL CABINET DOOR ON CO2 SKID. SWITCH
HELD OPEN WITH PIN.
FIRE PROTECTION-MANUAL DISCHARGE SWITCH (ZONE 3)
NORM=(2) NC-OEC;
LOCATED ON ELECTRICAL CONTROL CABINET DOOR ON CO2 SKID. SWITCH
HELD OPEN WITH PIN.
MANUAL DISCHARGE SWITCH (TURBINE COMPT)
(ZONE1)
LOCATED ON COMPARTMENT WALL OUTSIDE NEXT TO DOOR
MANUAL DISCHARGE SWITCH (TURBINE COMPT)
(ZONE1)
LOCATED ON COMPARTMENT WALL OUTSIDE NEXT TO DOOR
WATER TEMP SETPOINT SWITCH (HOT-COLD)
OPERATION SETPOINT SWITCH (AUTO-MANUAL)
FIRE DETECTOR-LUBE/HYDRAULIC COMPARTMENT
INCREASING: 325.0 F OR 162.8 C
NORM=(1) NO-SPST;
(LUBE/HYDRAULIC COMP.-ACCESS.MOD-ZONE 3)

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

16 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

17

Device
45FA-30B

System
0426

45FA-31A

0426

45FA-31B

0426

45FA-6A

0426

45FA-6B

0426

45FA-7A

0426

45FA-7B

0426

45FT-1A

0426

45FT-1B

0426

45FT-20A

0426

45FT-20B

0426

Page 17 of 67

REV

Settings
FIRE DETECTOR-LUBE/HYDRAULIC COMPARTMENT
INCREASING: 325.0 F OR 162.8 C
NORM=(1) NO-SPST;
(LUBE/HYDRAULIC COMP.-ACCESS.MOD-ZONE 3)
FIRE DETECTOR-LUBE/HYDRAULIC COMPARTMENT
INCREASING: 325.0 F OR 162.8 C
NORM=(1) NO-SPST;
(LUBE/HYDRAULIC COMP.-ACCESS.MOD-ZONE 3)
FIRE DETECTOR-LUBE/HYDRAULIC COMPARTMENT
INCREASING: 325.0 F OR 162.8 C
NORM=(1) NO-SPST;
(LUBE/HYDRAULIC COMP.-ACCESS.MOD-ZONE 3)
FIRE DETECTOR-FUEL GAS COMPARTMENT
INCREASING: 425.0 F OR 218.3 C
NORM=(1) NO-SPST;
FUEL GAS COMP.-ACCESS.MODULE (ZONE 1)
FIRE DETECTOR-FUEL GAS COMPARTMENT
INCREASING: 425.0 F OR 218.3 C
NORM=(1) NO-SPST;
FUEL GAS COMP.-ACCESS.MODULE (ZONE 1)
FIRE DETECTOR-FUEL GAS COMPARTMENT
INCREASING: 425.0 F OR 218.3 C
NORM=(1) NO-SPST;
FUEL GAS COMP.-ACCESS.MODULE (ZONE 1)
FIRE DETECTOR-FUEL GAS COMPARTMENT
INCREASING: 425.0 F OR 218.3 C
NORM=(1) NO-SPST;
FUEL GAS COMP.-ACCESS.MODULE (ZONE 1)
FIRE DETECTOR-TURBINE COMPARTMENT
INCREASING: 600.0 F OR 315.6 C
NORM=(1) NO-SPST;
TURBINE COMPARTMENT ZONE 1
FIRE DETECTOR-TURBINE COMPARTMENT
INCREASING: 600.0 F OR 315.6 C
NORM=(1) NO-SPST;
TURBINE COMPARTMENT ZONE 1
FIRE DETECTOR-#2 BEARING AREA (ZONE 2)
INCREASING: 725.0 F OR 385.0 C
NORM=(1) NO-SPST;
#2 BEARING TUNNEL - ZONE 2
FIRE DETECTOR-#2 BEARING AREA (ZONE 2)
INCREASING: 725.0 F OR 385.0 C
NORM=(1) NO-SPST;
#2 BEARING TUNNEL - ZONE 2

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

17 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

18

Device
45FT-21A

System
0426

45FT-21B

0426

45FT-2A

0426

45FT-2B

0426

45FT-3A

0426

45FT-3B

0426

45HA-IR-7

0474

45HA-IR-9A

0474

45HA-IR-9B

0474

Page 18 of 67

REV

Settings
FIRE DETECTOR-#2 BEARING AREA (ZONE 2)
INCREASING: 725.0 F OR 385.0 C
NORM=(1) NO-SPST;
#2 BEARING TUNNEL - ZONE 2
FIRE DETECTOR-#2 BEARING AREA (ZONE 2)
INCREASING: 725.0 F OR 385.0 C
NORM=(1) NO-SPST;
#2 BEARING TUNNEL - ZONE 2
FIRE DETECTOR-TURBINE COMPARTMENT
INCREASING: 600.0 F OR 315.6 C
NORM=(1) NO-SPST;
TURBINE COMPARTMENT ZONE 1
FIRE DETECTOR-TURBINE COMPARTMENT
INCREASING: 600.0 F OR 315.6 C
NORM=(1) NO-SPST;
TURBINE COMPARTMENT ZONE 1
FIRE DETECTOR-TURBINE COMPARTMENT
INCREASING: 600.0 F OR 315.6 C
NORM=(1) NO-SPST;
TURBINE COMPARTMENT ZONE 1
FIRE DETECTOR-TURBINE COMPARTMENT
INCREASING: 600.0 F OR 315.6 C
NORM=(1) NO-SPST;
TURBINE COMPARTMENT ZONE 1
IR COMBUSTIBLE GAS DETECTOR
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
IR COMBUSTIBLE GAS DETECTOR ACCESSORY MODULE - LOCAL
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
IR COMBUSTIBLE GAS DETECTOR - ACCESSORY COMPARTMENT
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
IR COMBUSTIBLE GAS DETECTOR ACCESSORY MODULE - DUCT
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
IR COMBUSTIBLE GAS DETECTOR - ACCESSORY COMPARTMENT
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
IR COMBUSTIBLE GAS DETECTOR ACCESSORY MODULE - DUCT
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

18 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

19

Device
45HA-IR-9C

System
0474

45HGT-1

0474

45HGT-2

0474

45HGT-7A

0474

45HGT-7B

0474

45HGT-7C

0474

Page 19 of 67

REV

Settings
IR COMBUSTIBLE GAS DETECTOR - ACCESSORY COMPARTMENT
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
IR COMBUSTIBLE GAS DETECTOR ACCESSORY MODULE - DUCT
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
HAZARDOUS ATM DETECTOR-GEN TERMINAL ENCLOSURE
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
IR COMBUSTIBLE GAS DETECTOR - GTE LOCAL SENSOR
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3 MS
HAZARDOUS ATM DETECTOR-GEN TERMINAL ENCLOSURE
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
IR COMBUSTIBLE GAS DETECTOR - GTE LOCAL SENSOR
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3 MS
COMBUSTIBLE GAS DETECTOR - GEN COLLECTOR COMPARTMENT
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
COMBUSTIBLE GAS DETECTOR - GCC EXTRACT DUCT SENSOR
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL, INRUSH CURRENT
DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3MS
DURATION
COMBUSTIBLE GAS DETECTOR - GEN COLLECTOR COMPARTMENT
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
COMBUSTIBLE GAS DETECTOR - GCC EXTRACT DUCT SENSOR
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL, INRUSH CURRENT
DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3MS
DURATION
COMBUSTIBLE GAS DETECTOR - GEN COLLECTOR COMPARTMENT
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
COMBUSTIBLE GAS DETECTOR - GCC EXTRACT DUCT SENSOR
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL, INRUSH CURRENT
DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3MS
DURATION

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

19 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

20

Device
45HT-IR-1A

System
0474

45HT-IR-1B

0474

45HT-IR-1C

0474

45HT-IR-1D

0474

45HT-IR-2A

0474

45HT-IR-2B

0474

Page 20 of 67

REV

Settings
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT (OUTDOOR UNITS)
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT (OUTDOOR UNITS)
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

20 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

21

Device
45HT-IR-2C

System
0474

45HT-IR-2D

0474

49IC-1

0471

49WS-1

0442

4WW

0442

62FP-1A

0426

62FP-2A

0426

62FP-3A

0426

63AD-4

0419

63AG-1A

0436

63AG-1B

0436

Page 21 of 67

REV

Settings
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT (OUTDOOR UNITS)
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT (OUTDOOR UNITS)
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
INLET AIR SCREW AUGER MOTOR OVERLOAD
RATING: 15.00 A; 230 VAC; 1 PH; 50 HZ; PROTECTS 88IC-1
NORM=(1) NC-CEC; AUXILIARY CONTACTS;;
NORMALLY CLOSED-OPEN ON OVERLOAD
WATER WASH SKID HEATER OVERLOAD
(INTEGRAL PART OF 23WS-1)
WATER WASH MASTER CONTROL RELAY
CONTROL SIGNAL NAME IS L4WWX. WIRE TO MK V / MK VI. MK V / MK VI
OUTPUT SIGNAL IS DRY CONTACT.
FIRE PROTECTION-TIMER RESET SWITCH (FOR ALL ZONES)
NORM=(1) NO;
SWITCH TO RESET SYSTEM AFTER CO2 DISCHARGE IN ZONE 1
FIRE PROTECTION-CO2 TIMER RESET SWITCH (ZONE 2)
NORM=(1) NO;
SWITCH TO RESET SYSTEM AFTER CO2 DISCHARGE IN ZONE 2
FIRE PROTECTION-CO2 TIMER RESET SWITCH (ZONE 3)
NORM=(1) NO;
SWITCH TO RESET SYSTEM AFTER CO2 DISCHARGE IN ZONE 3
APU LOW PRESSURE SWITCH
DECREASING: 85.00+-5.000 PSIG OR 586.1+-34.47 KPAG
APU LOW PRESSURE ALARM. INDICATES INSUFFICIENT
AIR AVAILABLE FOR NORMAL DEVICE OPERATION. OPENS TO ALARM. SIGNAL
NAME IS L63AD4. WIRE TO MKV / MK VI.
GEAR/LOAD COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
GEAR/LOAD COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

21 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

22

Device
63AG-1C

System
0436

63AG-2A

0436

63AG-2B

0436

63AG-2C

0436

63AT-1A

0436

63AT-1B

0436

63AT-1C

0436

63AT-2A

0436

63AT-2B

0436

63AT-2C

0436

63AT-3

0436

63AT-4

0436

63BN-1

0417

63BN-2

0417

Page 22 of 67

REV

Settings
GEAR/LOAD COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
GEAR/LOAD COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
GEAR/LOAD COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
GEAR/LOAD COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
DIFFERENTIAL PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
DIFFERENTIAL PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
DIFFERENTIAL PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
DIFFERENTIAL PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
DIFFERENTIAL PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
DIFFERENTIAL PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
DIFFERENTIAL PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
DIFFERENTIAL PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
VENT AIR PRESSURE SWITCH-#2 BEARING AREA
DECREASING: 4.500+-0.1000 INH2O OR 1.120+-0.0249 KPA
(INCREASING: 6.000+-0.3000 INH2O OR 1.493+-0.0747 KPA)
NORM=(1) NO;
VENT AIR PRESSURE SWITCH-#2 BEARING AREA
DECREASING: 4.500+-0.1000 INH2O OR 1.120+-0.0249 KPA
(INCREASING: 6.000+-0.3000 INH2O OR 1.493+-0.0747 KPA)
NORM=(1) NO;

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

22 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

23

Device
63CA-1

System
0471

63FGD-1

0422

63FP-11A

0426

63FP-12A

0426

63FP-13A

0426

63GCX-1

4035

63GCX-2

4035

63HF-1

0434

63HF-2

0434

63HQ-1A

0434

Page 23 of 67

REV

Settings
INLET AIR FILTER COMPRESSED AIR PRESSURE SWITCH
DECREASING: 60.00+-5.000 PSIG OR 413.7+-34.47 KPAG
NORM=(2) NO-CEC; CLOSED WHEN PRESSURIZED;
0.5A, 125VDC
FUEL GAS STRAINER DP SWITCH
INCREASING: 15.00+-1.000 PSID OR 103.4+-6.895 KPAD
(DECREASING: 13.75+-1.250 PSID OR 94.80+-8.618 KPAD)
NORM=(1) NC-OEC; SPDT;
FIRE PROTECTION-CO2 SELECTOR VLV ACTUATION PRESS SWITCH
INCREASING: 90.00+-20.00 PSIG OR 620.5+-137.9 KPAG
NORM=(2) NO; MANUAL RESET REQUIRED;
CONTACT CLOSES WHEN CO2 PRESSURE IN ZONE 1 ACTUATION LINE RISES
ABOVE PRIMARY SETTING. WIRES TO 45FTX-1 AUX RELAY PANEL.
FIRE PROTECTION-CO2 SELECTOR VLV ACTUATION PRESS SWITCH
INCREASING: 90.00+-20.00 PSIG OR 620.5+-137.9 KPAG
NORM=(2) NO; MANUAL RESET REQUIRED;
CONTACT CLOSES WHEN CO2 PRESSURE IN ZONE 2 ACTUATION LINE RISES
ABOVE PRIMARY SETTING. WIRES TO 45FTX-1 AUX RELAY PANEL.
FIRE PROTECTION-CO2 SELECTOR VLV ACTUATION PRESS SWITCH
INCREASING: 90.00+-20.00 PSIG OR 620.5+-137.9 KPAG
NORM=(2) NO; MANUAL RESET REQUIRED;
CONTACT CLOSES WHEN CO2 PRESSURE IN ZONE 3 ACTUATION LINE RISES
ABOVE PRIMARY SETTING. WIRES TO 45FTX-1 AUX RELAY PANEL.
CARRIER GAS - LOW PRESSURE ALARM
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
SET TO VENDOR REQUIREMENTS
REFER TO SERVICE MANUAL
CALIBRATION GAS - LOW PRESSURE ALARM
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
SET TO VENDOR REQUIREMENTS
REFER TO SERVICE MANUAL
HYDRAULIC OIL FILTER DIFF PRESSURE ALARM
INCREASING: 100.0+-3.000 PSID OR 689.5+-20.68 KPAD
(DECREASING: 80.00+-10.00 PSID OR 551.6+-68.95 KPAD)
NORM=(1) NC-OEC;
HYDRAULIC FILTER DIFF PRESSURE ALARM
INCREASING: 100.0+-3.000 PSID OR 689.5+-20.68 KPAD
(DECREASING: 80.00+-10.00 PSID OR 551.6+-68.95 KPAD)
NORM=(1) NC-OEC;
HYDRAULIC OIL SUPPLY PRESSURE SWITCH
DECREASING: 1450+-25.00 PSIG OR 9997+-172.4 KPAG
(INCREASING: 1550+-25.00 PSIG OR 10687+-172.4 KPAG)
NORM=(1) NO-CEC;

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

23 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

24

Device
63HQ-1B

System
0434

63HQ-6A

0434

63HQ-6B

0434

63PG-1A

0477

63PG-1B

0477

63PG-1C

0477

63PG-3A

0477

63PG-3B

0477

63PG-3C

0477

63QA-1A

0416

63QA-1B

0416

Page 24 of 67

REV

Settings
HYDRAULIC OIL SUPPLY PRESSURE SWITCH
DECREASING: 1450+-25.00 PSIG OR 9997+-172.4 KPAG
(INCREASING: 1550+-25.00 PSIG OR 10687+-172.4 KPAG)
NORM=(1) NO-CEC;
LOW HYDRAULIC OIL PUMP PH1-1 INLET PRESSURE
DECREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG
(INCREASING: 12.00+-1.000 PSIG OR 82.74+-6.895 KPAG)
NORM=(1) NO-CEC;
LOW HYDRAULIC OIL PUMP PH2-1 INLET PRESSURE
DECREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG
(INCREASING: 12.00+-1.000 PSIG OR 82.74+-6.895 KPAG)
NORM=(1) NO-CEC;
PRIMARY GAS FUEL SYSTEM PURGE PRESSURE SWITCH
INCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG
(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)
NORM=(1) NC-OEC;
PRIMARY GAS FUEL SYSTEM PURGE PRESSURE SWITCH
INCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG
(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)
NORM=(1) NC-OEC;
PRIMARY GAS FUEL SYSTEM PURGE PRESSURE SWITCH
INCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG
(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)
NORM=(1) NC-OEC;
GAS FUEL SYSTEM PURGE PRESSURE SWITCH
INCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG
(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)
NORM=(1) NC-OEC;
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: ``D`` - FLAME-PROOF
GAS FUEL SYSTEM PURGE PRESSURE SWITCH
INCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG
(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)
NORM=(1) NC-OEC;
GAS FUEL SYSTEM PURGE PRESSURE SWITCH
INCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG
(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)
NORM=(1) NC-OEC;
LUBE OIL BEARING HEADER PRESSURE SWITCH-AUX PUMP START
DECREASING: 83.00+-2.000 PSIG OR 572.3+-13.79 KPAG
(INCREASING: 91.00+-2.000 PSIG OR 627.4+-13.79 KPAG)
NORM=(1) NO-CEC;
LUBE OIL BEARING HEADER PRESSURE SWITCH
DECREASING: 83.00+-2.000 PSIG OR 572.3+-13.79 KPAG
(INCREASING: 91.00+-2.000 PSIG OR 627.4+-13.79 KPAG)
NORM=(1) NO-CEC;

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

24 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

25

Device
63QB-1

System
0434

63QE-1

0416

63QQ-21

0416

63QQ-22

0416

63QQ-25

0416

63QT-2A

0416

63QT-2B

0416

63TK-1

0417

63TK-2

0417

63TW-1

0442

63TW-2

0442

65CM-1

0417

Page 25 of 67

REV

Settings
BEARING LIFT OIL SUPPLY PRESSURE
DECREASING: 2350+-40.00 PSIG OR 16203+-275.8 KPAG
(INCREASING: 2500+-40.00 PSIG OR 17237+-275.8 KPAG)
NORM=(1) NO-CEC;
EMERGENCY LUBE OIL PUMP RUNNING
INCREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG
(DECREASING: 8.000+-1.000 PSIG OR 55.16+-6.895 KPAG)
NORM=(1) NO-CEC;
MAIN LUBE OIL FILTER DIFFERENTIAL PRESSURE-ALARM
INCREASING: 15.00+-1.000 PSID OR 103.4+-6.895 KPAD
(DECREASING: 12.00+-2.000 PSID OR 82.74+-13.79 KPAD)
NORM=(1) NC-OEC;
MAIN LUBE OIL FILTER DIFFERENTIAL PRESSURE-ALARM
INCREASING: 15.00+-1.000 PSID OR 103.4+-6.895 KPAD
(DECREASING: 12.00+-2.000 PSID OR 82.74+-13.79 KPAD)
NORM=(1) NC-OEC;
SEAL OIL FILTER DIFFERENTIAL PRESSURE SWITCH
INCREASING: 13.00+-1.000 PSID OR 89.63+-6.895 KPAD
(DECREASING: 11.75+-1.250 PSID OR 81.01+-8.618 KPAD)
NORM=(1) NC; SPDT;
LOW LUBE OIL PRESSURE
DECREASING: 8.000+-1.000 PSIG OR 55.16+-6.895 KPAG
(INCREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG)
LOW LUBE OIL PRESSURE
DECREASING: 8.000+-1.000 PSIG OR 55.16+-6.895 KPAG
(INCREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG)
TURBINE SHELL & EXHAUST FRAME BLOWER DSCH PRESSURE SW
DECREASING: 25.00+-0.8000 INH2O OR 6.221+-0.1991 KPA
(INCREASING: 28.00+-0.8000 INH2O OR 6.968+-0.1991 KPA)
NORM=(1) NO;
TURBINE SHELL & EXHAUST FRAME BLOWER DSCH PRESSURE SW
DECREASING: 25.00+-0.8000 INH2O OR 6.221+-0.1991 KPA
(INCREASING: 28.00+-0.8000 INH2O OR 6.968+-0.1991 KPA)
NORM=(1) NO;
TURBINE/COMPRESSOR WASH WATER PRESSURE
DECREASING: 93.00+-2.000 PSIG OR 641.2+-13.79 KPAG
NORM=(2) NO-CEC;
TURBINE/COMPRESSOR WASH WATER PRESSURE-PUMP TRIP
INCREASING: 4.000 INHG OR 13.55 KPA
NORM=NC-OEC;
OPENS ON INCREASING VACUUM 4 INHGV (DEC PRESS)
CLOSED AT ATMOSPHERIC PRESSURE.
CASE TEMP. MANAGEMENT FLOW CONTROL DAMPER POSITIONER
4.0MA = 0% = 20CM-1 FULL CLOSED
20.0MA = 100% = 20CM-1 FULL OPEN

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

25 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

26

Device
65EP-18

System
0417

65EP-19

0417

65EP-3

0432

65EP-G1P

0477

65GC-1

0422

65GC-2

0422

65GC-3

0422

71QH-1

0416

71QL-1

0416

71QL-2

0416

71TW-1

0442

77HT-1

0415

Page 26 of 67

REV

Settings
VALVE POSITIONER FOR PCV
4 MA = 3 PSIG = 100% = VA7-2 FULL OPEN
20 MA = 15 PSIG = 0% = VA7-2 FULL CLOSED
PART OF VA7-2
I/P CONTROLLER, VALVE POSITIONER
4 MA = 3 PSIG = 0% = VA7-3 FULL CLOSED
20 MA = 15 PSIG = 100% = VA7-3 FULL OPEN
PART OF VA7-3
ELECTRO-PNEUMATIC TRANSDUCER
4.0MA = 100% = VA20-1 FULL OPEN
20.0MA = 0% = VA20-1 FULL CLOSED
GAS FUEL PURGE VALVE POSITIONER
4.00 +-0.200 MA = 0% STROKE (FULLY CLOSED)
20.00 +- 0.200 MA = 100% STROKE (FULLY OPEN)
PART OF VA13-2
GAS CONTROL VALVE SERVO VALVE
RATED FLOW: 1.000 GPM AT 1000 PSID
RATED FLOW: 3.785 LPM AT 6895 KPAG
GAS CONTROL VALVE SERVO VALVE
RATED FLOW: 1.000 GPM AT 1000 PSID
RATED FLOW: 3.785 LPM AT 6895 KPAG
GAS CONTROL VALVE SERVO VALVE
RATED FLOW: 1.000 GPM AT 1000 PSID
RATED FLOW: 3.785 LPM AT 6895 KPAG
HIGH LUBE OIL LEVEL-ALARM
NORM=(1) NC-OEC;
INCREASING 3.000 +- 0.250`` (76.2 +- 6.35 MM)
DECREASING 1.500 +- 0.500`` (38.1 +- 12.7 MM)
LOW LUBE OIL LEVEL-ALARM
NORM=(1) NO-CEC;
DECREASING 2.000 +- 0.250`` (-50.8 +- 6.35 MM)
INCREASING 1.500 +- 0.500`` (-38.1 +- 12.7 MM)
LOW LUBE OIL LEVEL-ALARM
NORM=(1) NO-CEC;
DECREASING 3.000 +- 0.250`` (-76.2 +- 6.35 MM)
INCREASING 1.500 +- 0.500`` (-38.1 +- 12.7 MM)
WATER TANK WATER LEVEL CONTROL
NORM=(2) NC-OEC;
DECREASING: 15+-1 IN H20 OR 38.09 +- 2.5 CM OF WATER
MAGNETICIC LEVEL SWITCH SET 15 INCHES ABOVE THE BOTTOM OF THE
WATER TANK.
MAGNETIC PICKUP (OVERSPEED)
GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

26 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

27

Device
77HT-2

System
0415

77HT-3

0415

77NH-1

0415

77NH-2

0415

77NH-3

0415

77RP-11
80HA-FS-7

0415
0474

80HA-FS-9A

0474

80HA-FS-9B

0474

Page 27 of 67

REV

Settings
MAGNETIC PICKUP (OVERSPEED)
GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM
MAGNETIC PICKUP (OVERSPEED)
GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM
MAGNETIC PICKUP (SPEED)
GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM
MAGNETIC PICKUP (SPEED)
GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM
MAGNETIC PICKUP (SPEED)
GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM
SHAFT ANGULAR POSITION INDICATOR (KEYPHASOR) BEARING#1
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

27 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

28

Device
80HA-FS-9C

System
0474

80HGT-FS-1

0474

80HGT-FS-2

0474

80HGT-FS-7A

0474

Page 28 of 67

REV

Settings
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

28 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

29

Device
80HGT-FS-7B

System
0474

80HGT-FS-7C

0474

80HT-FS-1A

0474

80HT-FS-1B

0474

Page 29 of 67

REV

Settings
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

29 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

30

Device
80HT-FS-1C

System
0474

80HT-FS-1D

0474

80HT-FS-2A

0474

80HT-FS-2B

0474

Page 30 of 67

REV

Settings
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

30 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

31

Device
80HT-FS-2C

System
0474

80HT-FS-2D

0474

80WW-1

0442

86WWX

0442

88AD-1

0419

88BL-1

0436

88BL-2

0436

88BN-1

0417

88BN-2

0417

Page 31 of 67

REV

Settings
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
FLOW SWITCH-WATER WASH SKID
NORM=(2) NC-OEC;
CONTACT OPENS AT 2 GPM OR 0.45 M3/HR ON INCR FLOW
WATER WASH FLOW EXISTS RELAY TO TURBINE CONTROL SYSTEM AND
CONTROL SIGNAL NAME IS L80WWN. WIRE TO MK V / MK VI.
WATER WASH SKID TRIP ALARM RELAY
CONTROL SIGNAL NAME IS L86WWX. WIRE TO MK V / MK VI.
FAN MOTOR, APU HEAT EXCHANGER
2.000 HP; 1725 RPM; 230 VAC; 1 PH; 50 HZ;
COOLS APU HEAT EXCHANGER. MOTOR RATING SPECIFIED IS THE MAX HP
EXPECTED.
COOLING AIR FAN MOTOR-LUBE OIL SKID
5.000 HP; 3.728 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;
COOLING AIR FAN MOTOR-LUBE OIL SKID
5.000 HP; 3.728 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;
COOLING AIR FAN MOTOR-#2 BEARING AREA
20.00 HP; 14.91 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;
15KW
COOLING AIR FAN MOTOR-#2 BEARING AREA
20.00 HP; 14.91 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;
15KW

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

31 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

32

Device
88BT-1

System
0436

88BT-2

0436

88CM-1

0417

88ES-1

0416

88FP-1A

0426

88FP-1B

0426

88HQ-1

0434

88HQ-2

0434

88IC-1

0471

88QA-1

0416

88QA-2

0416

88QE-1

0416

88QS-1

0416

88QV-1A

0416

88QV-1B

0416

88TG-1

0416

Page 32 of 67

REV

Settings
COOLING AIR FAN MOTOR-TURBINE COMPARTMENT
50.00 HP; 37.28 KW; 1000 RPM; 400 VAC; 3 PH; 50 HZ;
LEFT HAND SIDE FAN MOTOR, LOOKING DOWNSTREAM
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAMEPROOF
COOLING AIR FAN MOTOR-TURBINE COMPARTMENT
50.00 HP; 37.28 KW; 1000 RPM; 400 VAC; 3 PH; 50 HZ;
RIGHT HAND SIDE FAN MOTOR, LOOKING DOWNSTREAM
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAMEPROOF
CASE TEMP. MANANGEMENT(CLEARANCE CONTROL)BLOWER MOTOR
50.00 HP; 37.28 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;
EMERGENCY SEAL OIL PUMP MOTOR
20.00 HP; 14.91 KW; 3000 RPM; 125 VDC;
FIRE PROTECTION-CO2 REFRIGERATION COMPRESSOR MOTOR
3.000 HP; 2.237 KW; 1425 RPM; 400 VAC; 3 PH; 50 HZ;
HP LISTED IS MAX VALUE. ACTUAL HP MAY BE LESS
REDUNDANT FP-CO2 REFRIGERATION COMPRESSOR MOTOR
3.000 HP; 2.237 KW; 1425 RPM; 400 VAC; 3 PH; 50 HZ;
HP LISTED IS MAX VALUE. ACTUAL HP MAY BE LESS
HYDRAULIC SUPPLY PUMP MOTOR
60.00 HP; 44.74 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;
HYDRAULIC SUPPLY PUMP MOTOR
60.00 HP; 44.74 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;
INLET FILTER, DUST COLLECTION SYSTEM SCREW AUGER MOTOR
2.000 HP; 1.491 KW; 400 VAC; 3 PH; 50 HZ;
SCREW AUGER MOTOR
AUXILIARY LUBE OIL PUMP MOTOR
125.0 HP; 93.21 KW; 2900 RPM; 400 VAC; 3 PH; 50 HZ;
90 KW FOR CE APPLICATIONS
AUXILIARY LUBE OIL PUMP MOTOR
125.0 HP; 93.21 KW; 2900 RPM; 400 VAC; 3 PH; 50 HZ;
90 KW FOR CE APPLICATIONS
EMERGENCY LUBE OIL PUMP MOTOR
20.00 HP; 14.91 KW; 1750 RPM; 125 VDC;
GENERATOR(AUXILIARY) SEAL OIL PUMP MOTOR
30.00 HP; 22.37 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;
LUBE MIST SEPARATOR OR ELIMINATOR MOTOR
5.000 HP; 3.728 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;
LUBE MIST SEPARATOR MOTOR
5.000 HP; 3.728 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;
TURNING GEAR MOTOR
6.400 HP; 4.772 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

32 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

33

Device
88TK-1

System
0417

88TK-2

0417

88TW-1

0442

88VG-1

0436

88VG-2

0436

88VW-1

0442

88WS-1

0442

8IC-1

0471

90LT-1

0420

90SR-1

0422

90TV-1

0434

94F-1A

0426

94F-1B

0426

94F-2A

0426

94F-2B

0426

Page 33 of 67

REV

Settings
TURBINE SHELL & EXHAUST FRAME BLOWER MOTOR
213.0 HP; 158.8 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;
160 KW
TURBINE SHELL & EXHAUST FRAME BLOWER MOTOR
213.0 HP; 158.8 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;
160 KW
TURBINE/COMPRESSOR WASH WATER PUMP MOTOR
25.00 HP; 18.64 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;
20 HP MAY BE USED BASED ON ACTUAL PUMP PERFORMANCE.
LOAD COMPT COOLING AIR FAN MOTOR
7.500 HP; 5.593 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;
LOAD COMPT COOLING AIR FAN MOTOR
7.500 HP; 5.593 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;
WATER WASH UNIT VENT FAN MOTOR
0.5000 HP; 0.3728 KW; 1725 RPM; 230 VAC; 1 PH; 50 HZ;
WATER WASH SKID SPACE HEATER BLOWER MOTOR
0.1000 HP; 0.0746 KW; 1550 RPM; 230 VAC; 1 PH; 50 HZ;
INLET AIR SCREW AUGER MOTOR DISCONNECT
15 A
NORM=(3) NC-CEC; PROTECTS 88IC-1;
ALSO DISCONNECTS 23IC-1
COOLING WATER VALVE POSITION REGULATOR - LO HX
4 +- 0.200 MA = 0% STROKE (B-L POSITION, FULL UP)
20 +- 0.200 MA = 100% STROKE (B-R POSITION, FULL DOWN)
STOP/SPEED RATIO VALVE SERVO VALVE
RATED FLOW: 15.00 GPM AT 1000 PSID
RATED FLOW: 56.8 LPM AT 6895 KPAG
INLET GUIDE VANE SERVO VALVE
RATED FLOW: 10.00 GPM AT 1000 PSIG
(38 GPM @ 6895 KPA)
FIRE PROTECTION TRIP CONTACT (ZONE 1)
NORM=(1) NO; 125VDC CONTACT;
CONTACT IS WIRED TO 45FTX-1 AUX RELAY PANEL AND CLOSES UPON START
OF PRE-DISCHARGE TIMER.
FIRE PROTECTION TRIP CONTACT (ZONE 1)
NORM=(1) NC-OEC; 125VDC CONTACT;
CONTACT IS WIRED TO TCP AND OPENS UPON START OF CO2 DISCHARGE.
FIRE PROTECTION TRIP CONTACT (ZONE 2)
NORM=(1) NO; 125VDC CONTACT;
CONTACT IS WIRED TO 45FTX-1 AUX RELAY PANEL AND CLOSES UPON START
OF PRE-DISCHARGE TIMER.
FIRE PROTECTION TRIP CONTACT (ZONE 2)
NORM=(1) NC-OEC; 125VDC CONTACT;
CONTACT IS WIRED TO TCP AND OPENS UPON START OF CO2 DISCHARGE.

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

33 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

34

Device
94F-3A

System
0426

94F-3B

0426

95FP-1
95SG-2

0440
0415

95SG-3

0415

95SP-2
95SP-3
96-TS2P-1A

0415
0415
0417

96-TS2P-1B

0417

96-TS2P-1C

0417

96-TS2QP-1A

0417

Page 34 of 67

REV

Settings
FIRE PROTECTION TRIP CONTACT (ZONE 3)
NORM=(1) NO; 125VDC CONTACT;
CONTACT IS WIRED TO 45FTX-1 AUX RELAY PANEL AND CLOSES UPON START
OF PRE-DISCHARGE TIMER.
FIRE PROTECTION TRIP CONTACT (ZONE 3)
NORM=(1) NC-OEC; 125VDC CONTACT;
CONTACT IS WIRED TO TCP AND OPENS UPON START OF CO2 DISCHARGE.
GENERATOR AIR GAP FLUX PROBE
IGNITION EXCITER FOR 95SP-2
115VAC/230 VAC, 50/60HZ, 150VA MAX INPUT
1.5 MIN ON/1.5 MIN OFF/1.5 MIN ON/25 MIN OFF
IGNITION EXCITER FOR 95SP-3
115VAC/230 VAC, 50/60HZ, 150VA MAX INPUT
1.5 MIN ON/1.5 MIN OFF/1.5 MIN ON/25 MIN OFF
COMBUSTION CHAMBER SPARK PLUG
COMBUSTION CHAMBER SPARK PLUG
TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
PRESSURE TRANSMITER
STAGE TWO NOZZLE OSWC
2-WIRE, LOOP POWERED, ANALOG
TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
PRESSURE TRANSMITER
STAGE TWO NOZZLE OSWC
2-WIRE, LOOP POWERED, ANALOG
TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
PRESSURE TRANSMITER
STAGE TWO NOZZLE OSWC
2-WIRE, LOOP POWERED, ANALOG
TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
TRANSMITTER
S13 PRESSURE
2 WIRE, LOOP POWERED, ANALOG

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

34 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

35

Device
96-TS2QP-1B

System
0417

96-TS2QP-1C

0417

96-TS3QP-1A

0417

96-TS3QP-1B

0417

96-TS3QP-1C

0417

96AP-1A

0492

96AP-1B

0492

96AP-1C

0492

96BD-1

0492

Page 35 of 67

REV

Settings
TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
TRANSMITTER
S13 PRESSURE
2 WIRE, LOOP POWERED, ANALOG
TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
TRANSMITTER
S13 PRESSURE
2 WIRE, LOOP POWERED, ANALOG
TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
TRANSMITTER
S9 PRESSURE
2 WIRE, LOOP POWERED, ANALOG
TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
TRANSMITTER
S9 PRESSURE
2 WIRE, LOOP POWERED, ANALOG
TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
TRANSMITTER
S9 PRESSURE
2 WIRE, LOOP POWERED, ANALOG
BAROMETRIC PRESSURE TRANSMITTER
4.000+-0.2000 MA= 22.00 INHG OR 74.50 KPA
20.00+-0.2000 MA= 37.00 INHG OR 125.3 KPA
BAROMETRIC PRESSURE TRANSMITTER
4.000+-0.2000 MA= 22.00 INHG OR 74.50 KPA
20.00+-0.2000 MA= 37.00 INHG OR 125.3 KPA
BAROMETRIC PRESSURE TRANSMITTER
4.000+-0.2000 MA= 22.00 INHG OR 74.50 KPA
20.00+-0.2000 MA= 37.00 INHG OR 125.3 KPA
COMPRESSOR BELLMOUTH DIFFERENTIAL PRESSURE TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 138.5 INH2O OR 34.46 KPA

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

35 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

36

Device
96BH-1

System
0432

96BH-2

0432

96CD-1

0417

96CD-1B

0417

96CD-1C

0417

96CM-1

0417

96CM-2

0417

96CS-1

0492

96EP-1

0492

96EP-2

0492

96EP-3

0492

96FG-1

0422

96FG-2A

0422

96FG-2B

0422

96FG-2C

0422

Page 36 of 67

REV

Settings
INLET HTG CV UPSTREAM PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
INLET HTG CV DOWNSTREAM PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 150.0 PSIG OR 1034 KPAG
COMPRESSOR DISCH PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
COMPRESSOR DISCH PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
COMPRESSOR DISCH PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
CASE TEMP. MANAGEMENT AIR SUPPLY PRESSURE TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 250.0 INH2O OR 62.21 KPA
CASE TEMP. MANAGE. FLOW CONTROL DAMPER POSITION FEEDBACK
4.0 MA = 0% = 20CM-1 FULL CLOSED
20.0 MA = 100% = 20CM-1 FULL OPEN
INLET DIFFERENTIAL PRESSURE TRANSMITTER
4.000+-0.2000 MA= 0.0 INH2O OR 0.0 KPA
20.00+-0.2000 MA= 11.10 INH2O OR 2.762 KPA
EXHAUST DIFFERENTIAL PRESSURE TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 27.70 INH2O OR 6.893 KPA
EXHAUST DIFFERENTIAL PRESSURE TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 27.70 INH2O OR 6.893 KPA
EXHAUST DIFFERENTIAL PRESSURE TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 27.70 INH2O OR 6.893 KPA
GAS FUEL UPSTREAM PRESSURE TRANSMITTER
4.000+-0.2000 MA= 0.0 PSIG OR 0.0 KPAG
20.00+-0.2000 MA= 600.0 PSIG OR 4137 KPAG
INTERSTAGE FUEL GAS PRESSURE TRANSMITTER
4.000+-0.2000 MA= 0.0 PSIG OR 0.0 KPAG
20.00+-0.2000 MA= 500.0 PSIG OR 3447 KPAG
INTERSTAGE FUEL GAS PRESSURE TRANSMITTER
4.000+-0.2000 MA= 0.0 PSIG OR 0.0 KPAG
20.00+-0.2000 MA= 500.0 PSIG OR 3447 KPAG
INTERSTAGE FUEL GAS PRESSURE TRANSMITTER
4.000+-0.2000 MA= 0.0 PSIG OR 0.0 KPAG
20.00+-0.2000 MA= 500.0 PSIG OR 3447 KPAG

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

36 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

37

Device
96FLW-1

System
4035

96FLW-2

4035

96FM-4

0422

96GC-1

0422

96GC-2

0422

96GC-3

0422

96GC-4

0422

96GC-5

0422

96GC-6

0422

96GC-7

0422

96GC-8

0422

96GC-9

0422

Page 37 of 67

REV

Settings
FG CHROMATOGRAPH - GC A- LOW WOBBE INDEX
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
ENG MIN = 1180
ENG MAX = 1300
FG CHROMATOGRAPH - GC B - LOW WOBBE INDEX
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
ENG MIN = 1180
ENG MAX = 1300
CORIOLIS FLOW METER TRANSMITTER
4.000 MA= 0.0 PPS OR 0.0 KG/SEC
20.00 MA= 50.00 PPS OR 22.68 KG/SEC
HAZARDOUS AREA: ZONE 2
PROTECTION METHOD: D - FLAMEPROOF
FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

37 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

38

Device
96GN-1

System
0422

96GN-2

0422

96GN-3

0422

96HF-1

0434

96HF-2

0434

96HQ-1

0434

96QH-1

0416

96QL-1

0416

96QQ-1

0416

96QQ-2

0416

96QV-2

0416

96SR-1

0422

Page 38 of 67

REV

Settings
GAS FUEL NOZZLE PRESSURE RATIO TRANSMITTER
4.000 MA= -20.00 PSID OR -137.9 KPAD
20.00 MA= 120.0 PSID OR 827.4 KPAD
COMPARING PCD TO MANIFOLD PRESSURE DIFFUSION
GAS FUEL NOZZLE PRESSURE RATIO TRANSMITTER
4.000 MA= -20.00 PSID OR -137.9 KPAD
20.00 MA= 120.0 PSID OR 827.4 KPAD
COMPARING PCD TO MANIFOLD PRESSURE DIFFUSION
GAS FUEL NOZZLE PRESSURE RATIO TRANSMITTER
4.000 MA= -20.00 PSID OR -137.9 KPAD
20.00 MA= 120.0 PSID OR 827.4 KPAD
COMPARING PCD TO MANIFOLD PRESSURE DIFFUSION
HYDRAULIC OIL FILTER DIFF PRESSURE TRANSMITTER
4.000 MA= 0.0 PSID OR 0.0 KPAD
20.00 MA= 150.0 PSID OR 1034 KPAD
ALARM AT 100 PSID INCREASING (689 KPA)
HYDRAULIC OIL FILTER DELTA P TRANSMITTER
4.000 MA= 0.0 PSID OR 0.0 KPAD
20.00 MA= 150.0 PSID OR 1034 KPAD
ALARM AT 100 PSID INCREASING (689 KPA)
HYDRAULIC OIL SUPPLY PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 2000 PSIG OR 13790 KPAG
ALARM AT 1450 PSIG DECREASING (9997 KPA)
LUBE OIL HEADER PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 100.0 PSIG OR 689.5 KPAG
LUBE OIL TANK LEVEL TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 30.00 INH2O OR 7.465 KPA
LUBE OIL FILTER DELTA P TRANSMITTER
4.000 MA= 0.0 PSID OR 0.0 KPAD
20.00 MA= 30.00 PSID OR 206.8 KPAD
CONTROL OIL FILTER DELTA P TRANSMITTER
4.000 MA= 0.0 PSID OR 0.0 KPAD
20.00 MA= 30.00 PSID OR 206.8 KPAD
LUBE OIL TANK AIR PRESSURE TRANSDUCER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 30.00 INH2O OR 7.465 KPA
ALARM IF TANK PRESSURE FALLS BELOW 3.6 INH20
STOP/SPEED RATIO VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

38 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

39

Device
96SR-2

System
0422

96TD-1A

0471

96TF-1

0471

96TF-2A

0471

96TF-2B

0471

96TH-1

0432

96TV-1

0434

96TV-2

0434

96VC-11
96VC-12
96VS-1

0415
0415
0440

96WW-3

0442

96WW-4

0442

Page 39 of 67

REV

Settings
STOP/SPEED RATIO VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
DEW POINT SENSOR/TRANSMITTER
4.000+-0.5000 MA= -49.00 F OR -45.00 C
20.00+-0.5000 MA= 167.0 F OR 75.00 C
230VAC, 4-20 MA OUTPUT SIGNAL
TURBINE INLET FILTER DIFF PRESSURE TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 10.00 INH2O OR 2.488 KPA
ALARM AT 6.00 +- 0.25 INH20 (1.49 +-0.06 KPA)
POWERED BY 24 VDC, 4-20 MA OUTPUT SIGNAL
TURBINE INLET FILTER DIFF PRESSURE TRANSMITTER
ALARM AT 6.00 +- 0.25 INH20 (1.49 +-0.06 KPA)
POWERED BY 24 VDC, 4-20 MA OUTPUT SIGNAL
TURBINE INLET FILTER DIFF PRESSURE TRANSMITTER
ALARM AT 6.00 +- 0.25 INH20 (1.49 +-0.06 KPA)
POWERED BY 24 VDC, 4-20 MA OUTPUT SIGNAL
INLET HEATING CONTROL VALVE POSITION TRANSMITTER
4.0MA = 0% = VALVE VA20-1 FULL CLOSED
20.0MA = 100% =VALVE VA20-1 FULL OPEN
INLET GUIDE VANE LVDT
LVDT POSITION SIGNAL = 0.6 +/- 0.09 VRMS AT FULL LVDT EXTENSION.
CALIBRATE TO PROVIDE SIGNAL OF 0.7 +/- 0.02 VRMS AT IGV FULL CLOSED
(ACTUATOR EXTENDED), AND BETWEEN 2.40 - 3.70 VRMS AT IGV FULL OPEN
(ACTUATOR RETRACTED).
INLET GUIDE VANE LVDT
LVDT POSITION SIGNAL = 0.6 +/- 0.09 VRMS AT FULL LVDT EXTENSION.
CALIBRATE TO PROVIDE SIGNAL OF 0.7 +/- 0.02 VRMS AT IGV FULL CLOSED
(ACTUATOR EXTENDED), AND BETWEEN 2.40 - 3.70 VRMS AT IGV FULL OPEN
(ACTUATOR RETRACTED).
SHAFT AXIAL POSN TRANSMITTER BEARING #1
SHAFT AXIAL POSN TRANSMITTER BEARING #1
SHAFT VOLTAGE TRANSDUCER
30 WATT MAX
VOLTAGE ALARM = 5 VOLTS
CURRENT ALARM = 4 AMPS
PRESS TRANS, ONLINE COMPRESSOR WASH MANIFOLD SUPPLY
4.000+-0.2000 MA= 0.0 PSIG OR 0.0 KPAG
20.00+-0.2000 MA= 150.0 PSIG OR 1034 KPAG
PRESS TRANS, GFC WATER INJ MANIFOLD SUPPLY
4.000+-0.2000 MA= 0.0 PSIG OR 0.0 KPAG
20.00+-0.2000 MA= 150.0 PSIG OR 1034 KPAG

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

39 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

40

Device
ACV1-1

System
0434

AH1-1

0434

AL-2
AL-27

0416
0471

AL-2A
AL-2B
AL-4
AL-4A
AL-4B
AL-62
AL-63
AL-81
AL-87
AL-88
APU-LIC-1

0416
0416
0416
0416
0416
0442
0442
0442
0422
0422
0419

APU-TC-1
AR-2
AR-20

0419
0416
0471

AR-2A
AR-50
ASW-10

0416
0442
0471

ASW-13
ASW-13A
ASW-31
ASW-44

0416
0416
0442
0422

Page 40 of 67

REV

Settings
IGV HYDRAULIC CYLINDER ACTUATOR
SLEW TIME: 4.5 +/-1.5 SECONDS
HYDRAULIC OIL ACCUMULATOR
PRECHARGE 800 PSI DRY NITROGEN, 5 GALLONS (5516 KPA)
AC LIGHT-ACCESSORY COMPARTMENT
AC LIGHT-INLET AIR COMPARTMENT
230VAC, 50HZ
1 PH
AC LIGHT-ACCESSORY COMPARTMENT
AC LIGHT-ACCESSORY COMPARTMENT
AC LIGHT-ACCESSORY COMPARTMENT
AC LIGHT-ACCESSORY COMPARTMENT
AC LIGHT-ACCESSORY COMPARTMENT
AC LIGHT-WATER WASH SKID
AC LIGHT-WATER WASH SKID
AC LIGHT-WATER WASH SKID
AC LIGHT-GAS FUEL MODULE
AC LIGHT-GAS FUEL MODULE
APU LOCAL INDICATOR CONTROL
INCREASING: 110.0+-5.000 F OR 43.33+-2.778 C
(DECREASING: 100.0+-5.000 F OR 37.78+-2.778 C)
CONTROLS 88AD-1
APU OVER TEMPERATURE CONTROL SETTINGS
INCREASING: 145.0+-5.000 F OR 62.78+-2.778 C
DECREASING: 142.0+-5.000 F OR 61.11+- 2.778 C
CONTROLS 20AP-1
APU TEMPERATURE ELEMENT, PROVIDES SIGNAL FOR APU-LIC-1
AC RECEPTACLE-ACCESSORY COMPARTMENT
AC RECEPTACLE-INLET FILTER COMPARTMENT
230 V, 50 HZ, 1 PH
GROUNDED
AC RECEPTACLE-ACCESSORY COMPARTMENT
AC RECEPTACLE-WATER WASH SKID
AC LIGHT SWITCH-INLET AIR COMPARTMENT
230VAC, 50 HZ,1 PH
AC SW-ACCESSORY COMPARTMENT
3 WAY EXPLOSION PROOF TUMBLER SWITCH
AC LIGHT SWITCH-WATER WASH SKID
AC LIGHT SWITCH-GAS FUEL MODULE

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

40 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

41

Device
AT-HL-1

System
0436

AT-HL-2

0436

AT-ID-1

0471

AT-ID-2

0471

AT-ID-3

0471

AT-TC-1

0436

AT-TC-2

0436

AT-TC-3

0436

AT-TC-4

0436

AT-VS-1

0436

AT-VS-2

0436

BT-GJ1-1A

0440

BT-GJ1-1B

0440

Page 41 of 67

REV

Settings
AIR TEMPERATURE - LUBE OIL COMPARTMENT
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AIR TEMPERATURE - LUBE OIL COMPARTMENT
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AMBIENT TEMPERATURE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AMBIENT TEMPERATURE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AMBIENT TEMPERATURE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AIR TEMPERATURE-TURBINE COMPARTMENT
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AIR TEMPERATURE-TURBINE COMPARTMENT
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AIR TEMPERATURE-TURBINE COMPARTMENT
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AIR TEMPERATURE-TURBINE COMPARTMENT
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AIR TEMPERATURE- GAS MODULE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AIR TEMPERATURE- GAS MODULE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
BEARING METAL TEMP-GENERATOR BEARING #1
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-1
ALARMS @ 260 F
BEARING METAL TEMP-GENERATOR BEARING #1
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-1
ALARMS @ 260 F

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

41 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

42

Device
BT-GJ1-2A

System
0440

BT-GJ1-2B

0440

BT-GJ2-1A

0440

BT-GJ2-1B

0440

BT-GJ2-2A

0440

BT-GJ2-2B

0440

BT-J1-1A

0415

BT-J1-1B

0415

BT-J1-2A

0415

BT-J1-2B

0415

Page 42 of 67

REV

Settings
BEARING METAL TEMP-GENERATOR BEARING #1
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-2
ALARMS @ 260 F
BEARING METAL TEMP-GENERATOR BEARING #1
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-2
ALARMS @ 260 F
BEARING METAL TEMP-GENERATOR BEARING #2
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-1
ALARMS @ 260 F
BEARING METAL TEMP-GENERATOR BEARING #2
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-1
ALARMS @ 260 F
BEARING METAL TEMP-GENERATOR BEARING #2
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-2
ALARMS @ 260 F
BEARING METAL TEMP-GENERATOR BEARING #2
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-2
ALARMS @ 260 F
BEARING METAL TEMP-TURBINE BEARING #1
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BEARING METAL TEMP-TURBINE BEARING #1
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP.
BEARING METAL TEMP-TURBINE BEARING #1
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BEARING METAL TEMP-TURBINE BEARING #1
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

42 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

43

Device
BT-J2-1A

System
0415

BT-J2-1B

0415

BT-J2-2A

0415

BT-J2-2B

0415

BT-TA1-12A

0415

BT-TA1-12B

0415

BT-TA1-6A

0415

BT-TA1-6B

0415

BT-TI1-12A

0415

BT-TI1-12B

0415

BT-TI1-6A

0415

BT-TI1-6B

0415

CK-1A
CK-1B
CK-2A

0434
0434
0434

Page 43 of 67

REV

Settings
BEARING METAL TEMP-TURBINE BEARING #2
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BEARING METAL TEMP-TURBINE BEARING #2
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
BEARING METAL TEMP-TURBINE BEARING #2
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BEARING METAL TEMP-TURBINE BEARING #2
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
BEARING METAL TEMP-THRUST ACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BEARING METAL TEMP-THRUST ACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
BEARING METAL TEMP-THRUST ACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BEARING METAL TEMP-THRUST ACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
BEARING METAL TEMP-THRUST INACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BEARING METAL TEMP-THRUST INACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
BEARING METAL TEMP-THRUST INACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BEARING METAL TEMP-THRUST INACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
CHECK VALVE
CHECK VALVE
CHECK VALVE

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

43 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

44

Device
CK-2B
CT-DA-1

System
0434
0415

CT-DA-2

0415

CT-DA-3

0415

CT-IF-1

0415

CT-IF-2

0415

CT-IF-3

0415

DHCP

4027

DL-2
DL-2A
DL-51
DL-52
DT-GAC-23

0416
0416
0422
0422
0440

DT-GAH-17

0440

DT-GGC-10

0440

DT-GGC-11

0440

Page 44 of 67

REV

Settings
CHECK VALVE
COMPRESSOR DISCHARGE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
COMPRESSOR DISCHARGE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
COMPRESSOR TEMP-DISCHARGE ANNULUS
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
COMPRESSOR INLET THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
COMPRESSOR INLET THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
COMPRESSOR TEMP-INLET FLANGE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
HYDROGEN CONTROL PANEL POWER SUPPLY
HYDROGEN CONTROL PANEL SUPPLY POWER TO BE 230 VAC 50 HZ AND 600
WATTS. THIS EQUIPMENT IS TO BE POWERED BY A UPS. REFER TO ML-G2B0
FOR ADDITIONAL ELECTRICAL CONNECTION INFORMATION.
DC LIGHT-ACCESSORY COMPARTMENT
DC LIGHT-ACCESSORY COMPARTMENT
DC LIGHT-GAS FUEL MODULE
DC LIGHT-GAS FUEL MODULE
GENERATOR COLLECTOR-COLD AIR
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 149 F OR 65 C
GENERATOR COLLECTOR-HOT AIR
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM @ 20 C ABOVE AMBIENT
GENERATOR TEMP-COLD GAS COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 122 F
GENERATOR TEMP-COLD GAS COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 122 F

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

44 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

45

Device
DT-GGC-12

System
0440

DT-GGC-13

0440

DT-GGH-15

0440

DT-GGH-16

0440

DT-GGH-18

0440

DT-GGH-19

0440

DT-GGK-24

0440

DT-GIF-41

0440

DT-GIF-43

0440

DT-GIF-47

0440

DT-GIF-49

0440

Page 45 of 67

REV

Settings
GENERATOR TEMP-COLD GAS COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 122 F
GENERATOR TEMP-COLD GAS COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 122 F
GENERATOR TEMP-HOT GAS COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 212 F
GENERATOR TEMP-HOT GAS COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 212 F
GENERATOR TEMP-HOT GAS COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 212 F
GENERATOR TEMP-HOT GAS COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 212 F
GENERATOR FRAME-COMMON COLD GAS
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALSO IDENTIFIED AS GTG-2
ALARM = 145 F OR 62.78 C
STATOR CORE TC COLLECTOR END
TYPE E THERMOCOUPLE
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
STATOR CORE TC COLLECTOR END
TYPE E THERMOCOUPLE
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
STATOR CORE TC COLLECTOR END
TYPE E THERMOCOUPLE
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
STATOR CORE TC COLLECTOR END
TYPE E THERMOCOUPLE
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

45 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

46

Device
DT-GIF-82

System
0440

DT-GIF-84

0440

DT-GSA-34

0440

DT-GSA-35

0440

DT-GSA-36

0440

DT-GSA-4

0440

DT-GSA-5

0440

DT-GSA-6

0440

DT-GSC-20

0440

DT-GSC-21

0440

DT-GSC-22

0440

Page 46 of 67

REV

Settings
STATOR CORE TC COLLECTOR END
TYPE E THERMOCOUPLE
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
STATOR CORE TC COLLECTOR END
TYPE E THERMOCOUPLE
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR CENTER
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR CENTER
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR CENTER
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

46 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

47

Device
DT-GSF-1

System
0440

DT-GSF-2

0440

DT-GSF-3

0440

DT-GSF-31

0440

DT-GSF-32

0440

DT-GSF-33

0440

FB1-1
FB2-1
FH2-1

0416
0416
0434

FH2-2

0434

FH6-1

0434

FH7-1

0422

FH8-1

0422

FH8-2

0422

Page 47 of 67

REV

Settings
GENERATOR TEMP-STATOR COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
KKS DESIGNATION: MKA10 CT021
GENERATOR TEMP-STATOR COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
GENERATOR TEMP-STATOR COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
FAN-LUBE OIL DEMISTER #1
FAN-LUBE OIL DEMISTER #2
HYDRAULIC OIL SUPPLY FILTER
FILTRATION: 3 MICRON
BETA 3 >= 200
HYDRAULIC OIL SUPPLY FILTER
FILTRATION: 3 MICRON
BETA 3 >= 200
IGV SERVO HYDRAULIC OIL SUPPLY FILTER
FILTRATION: 15 MICRON
FUEL GAS SERVO HYDRAULIC OIL SUPPLY FILTER
FILTRATION: 15 MICRON ABSOLUTE
WITH INTEGRAL VISUAL REPLACEMENT INDICATOR (PDI FH7-1)
GAS FUEL SERVO HYDRAULIC SUPPLY FILTER
FILTRATION: 15 MICRON ABSOLUTE
WITH INTEGRAL VISUAL REPLACEMENT INDICATOR (PDI FH8-1)
GAS FUEL SERVO HYDRAULIC SUPPLY FILTER
FILTRATION: 15 MICRON ABSOLUTE
WITH INTEGRAL VISUAL REPLACEMENT INDICATOR (PDI FH8-2)

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

47 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

48

Device
FH8-3

System
0422

FI-WW-1

0442

FLOWTOTALIZER

4027

FQIC-2950

4027

FTG-1A

0422

FTG-1B

0422

FTG-1C

0422

FV-1A

0434

FV-1B

0434

FV-2A
FV-2B
FV-3A
FV-3B
FV-4A

0434
0434
0434
0434
0434

FV-4B

0434

FY-2971

4027

Page 48 of 67

REV

Settings
GAS FUEL SERVO HYDRAULIC SUPPLY FILTER
FILTRATION: 15 MICRON ABSOLUTE
WITH INTEGRAL VISUAL REPLACEMENT INDICATOR (PDI FH8-3)
WATER WASH SKID - DETERGENT FLOW INDICATOR
0.00 GPM 0.00
POWER SUPPLY
HYDROGEN FLOW TOTALIZER
120 OR 240V, 16 W, 1PH
REFER TO MLI-G2B0 FOR ADDITIONAL ELECTRICAL CONNECTION INFORMATION
HYDROGEN GAS FLOW TOTALIZER
4.000 MA= 0.0 OR 0.0
20.00 MA= 125.0 OR 125.0
FUNCTION: MONITOR HYDROGEN MAKE-UP GAS CONSUMPTION.
4 MA = 0 SCFH (0 SCMH)
20 MA = 125 SCFH (3.54 SCMH)
FE-2950 IS THE FLOW ELEMENT
FUEL GAS TEMPERATURE SENSOR
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
FUEL GAS TEMPERATURE SENSOR
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
FUEL GAS TEMPERATURE SENSOR
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
HYDRAULIC OIL SUPPLY ISOLATION
VALVE #1
HYDRAULIC OIL SUPPLY ISOLATION
VALVE #2
HYD OIL DISCHARGE ISOLATION VLV
HYD OIL DISCHARGE ISOLATION VLV
ISOLATION VALVE
ISOLATION VALVE
ACCUMULATOR ISOLATION VALVE
VALVE #1
HYDRAULIC BYPASS VALVE
VALVE #2
TURBINE END SCAVENGING SOLENOID
230 VAC; 50 HZ;
THIS SOLENOID VALVE IS POWERED BY THE H2 PANEL UPS. SIGNAL 20SCAV1
ENERGIZES SOLENOID VALVE FY-2971 ON THE H2 CTRL PANEL TO INCREASE
SCAVENGING OF TE AT LOW PURITY.

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

48 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

49

Device
FY-2972

System
4027

FY-2973

4027

FY-2974

4027

FY-2981

4027

G023-GC

4035

LF3-1

0416

LF3-2

0416

LF3-3
LF3-5

0416
0416

LI-FP-1A

0426

LI-QH-1

0416

LOHX-1

0416

Page 49 of 67

REV

Settings
COLLECTOR END GAS SOLENOID
230 VAC; 50 HZ;
THIS SOLENOID VALVE IS POWERED BY THE H2 PANEL UPS. SIGNAL 20CASE1
ENERGIZES SOLENOID VALVE FY-2972 ON THE H2 CTRL PANEL TO DIRECT
GEN CASING
GAS TO ANALYZER 1 (QT-290A)
COLLECTOR END SCAVENGING SOLENOID
230 VAC; 50 HZ;
THIS SOLENOID VALVE IS POWERED BY THE H2 PANEL UPS. SIGNAL 20SCAV2
ENERGIZES SOLENOID VALVE FY-2973 ON THE H2 CTRL PANEL TO INCREASE
SCAVENGING OF CE AT LOW PURITY.
COLLECTOR END GAS SOLENOID.
230 VAC; 50 HZ;
THIS SOLENOID VALVE IS POWERED BY THE H2 PANEL UPS. SIGNAL 20CASE2
ENERGIZES SOLENOID VALVE FY-2974 ON THE H2 CTRL PANEL TO DIRECT
GEN CASING
GAS TO ANALYZER 2 (QT-290B)
CASE, PURGE, CALIBRATION SOLENOID.
230 VAC; 50 HZ;
DE-ENERGIZED STATE ALLOWS FLOW FROM GEN CASE TO FY-2972 AND FY2974. SIGNAL 30H2STAT3 IS A CONTROL SYSTEM CONTACT FOR CASE/CAL
PURGE STATUS
THIS SOLENOID VALVE IS POWERED BY THE H2 PANEL UPS.
GAS CHROMATOGRAPH - POWER CONSUMPTION
SOURCE POWER SUPPLIED BY CUSTOMER
1.8 KW, 7.9 AMP, 230 VAC
SINGLE UPS SOURCE REQUIRED PER SITE
230 VAC, 1PH, 50 HZ
LUBE OIL FILTER
FILTRATION: BETA 25 = 200
LUBE OIL FILTER
FILTRATION: BETA 25 = 200
MIST ELIMINATOR
SEAL OIL FILTER
FILTRATION: BETA 25 = 200
CO2 TANK LIQUID LEVEL GAUGE
0.00 PSIG 0.00
(0.0-0.0 KPAG)
LEVEL INDICATOR LUBE OIL TANK
0.00 0.00
-10 TO 6 INCHES
[-254 TO 152 MM]
MAIN LUBE OIL HEAT EXCHANGER
#1

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

49 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

50

Device
LOHX-2

System
0416

LSH-2990

4027

LSH-3401

4027

LSHH-2990

4027

LT-B1D-1

0416

LT-B2D-1

0416

LT-G1D-A

0416

LT-G1D-B

0416

LT-G2D-A

0416

LT-G2D-B

0416

LT-OT-1A

0416

Page 50 of 67

REV

Settings
MAIN LUBE OIL HEAT EXCHANGER
#2
LIQUID LEVEL DETECTOR HIGH LEVEL SWITCH
NORM=(4) NC-CEC; CONTACT OPENS ON HIGH LEVEL;
DPDT SWITCH
FUNCTION IS TO ALARM WHEN FLUID ENTERS THE LIQUID LEVEL DETECTOR
HAZARDOUS ZONE 2, PROTECTION METHOD `D`-EXPLOSION PROOF
SEAL OIL DRAIN HIGH LEVEL SWITCH
NORM=(4) NC-CEC; CONTACT OPENS ON HIGH LEVEL;
DPDT SWITCH. FUNCTION IS TO ALARM WHEN FLUID ENTERS LIQUID LEVEL
DETECTOR
HAZARDOUS ZONE 2, PROTECTION METHOD `D`- EXPLOSION PROOF
LIQUID LEVEL DETECTOR HIGH HIGH LEVEL SWITCH
NORM=(4) NC-CEC; CONTACT OPENS ON HIGH HIGH LEVEL;
DPDT SWITCH
FUNCTION IS TO ALARM WHEN FLUID ENTERS THE LIQUID LEVEL DETECTOR
HAZARDOUS ZONE 2, PROTECTION METHOD `D`-EXPLOSION PROOF
LUBE TEMPERATURE #1 BRG DRAIN
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
ALARM SETTING IS 200 F (93.3 C)
LO THERMOCOUPLE #2 BRG DRAIN
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
ALARM SETTING IS 200 F (93.3 C)
LUBE SYSTEM TEMP-GENERATOR #1 BEARING DRAIN
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
ALARM SETTING IS 200 F (93.3 C)
LUBE SYSTEM TEMP-GENERATOR #1 BEARING DRAIN
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
(SPARE)
LUBE SYSTEM TEMP-GENERATOR #2 BEARING DRAIN
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
ALARM SETTING IS 200 F (93.3 C)
LUBE SYSTEM TEMP-GENERATOR #2 BEARING DRAIN
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
(SPARE)
LUBE OIL THERMOCOUPLE LUBE OIL TANK
TYPE K THERMOCOUPLE
HIGH IMMERSION HEATER TEMPERATURE

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

50 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

51

Device
LT-OT-1B

System
0416

LT-OT-1C

0416

LT-OT-3

0416

LT-OT-4

0416

LT-TH-1

0416

LT-TH-2

0416

LT-TH-3

0416

MG1-1

0422

MG1-2

0422

MG1-3

0422

MG2-4

0422

Page 51 of 67

REV

Settings
LUBE OIL THERMOCOUPLE LUBE OIL TANK
TYPE K THERMOCOUPLE
HIGH IMMERSION HEATER TEMPERATURE
LUBE OIL THERMOCOUPLE LUBE OIL TANK
TYPE K THERMOCOUPLE
HIGH IMMERSION HEATER TEMPERATURE
LUBE OIL TANK THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
LOW LUBE OIL TANK TEMPERATURE
- IMMERSION HEATERS ON AT 79 F (26 C)
- START PERMISSIVE LOCKOUT AT OR BELOW 75 F (24 C)
LUBE OIL TANK THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
LOW LUBE OIL TANK TEMPERATURE
- IMMERSION HEATERS ON AT 79 F (26 C)
- START PERMISSIVE LOCKOUT AT OR BELOW 75 F (24 C)
LUBE SYSTEM TEMP-TURBINE HEADER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
HIGH OIL TEMPERATURE: TRIPLE REDUNDANT (LT-TH-1, 2 & 3)
- ALARM AT 165 F (73.9 C)
- TRIP AT 175F (79.4 C)
LUBE SYSTEM TEMP-TURBINE HEADER-TRIP
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
HIGH OIL TEMPERATURE: TRIPLE REDUNDANT (LT-TH-1, 2 & 3)
- ALARM AT 165 F (73.9 C)
- TRIP AT 175F (79.4 C)
LUBE SYSTEM-TURBINE HEADER TEMP-TRIP
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
HIGH OIL TEMPERATURE: TRIPLE REDUNDANT (LT-TH-1, 2 & 3)
- ALARM AT 165 F (73.9 C)
- TRIP AT 175F (79.4 C)
GAS FUEL NOZZLE
DIFFUSION
GAS FUEL NOZZLE
PM1
GAS FUEL NOZZLE
PM4
CORIOLIS GAS FUEL FLOW METER

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

51 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

52

Device
MIC-292

System
4027

PDI-FG-3

0422

PDI-HQ-4

0434

PDI-QQ-21

0416

PDI-QQ-22

0416

PDI-QQ-25

0416

PDI-TF-CF

0471

PDI-TF-OF

0471

PDI-TF-SF

0471

PDS-TF-1A

0471

PDSL-3402

4027

Page 52 of 67

REV

Settings
H2 DEW POINT SENSOR LOCATED IN H2 CONTROL PANEL
4MA=-148F OR -100C
20MA=68F OR 20 C
4MA= -148F AND 20MA= 68 F, SIGNAL TO BE INTEGRATED WITH THE TCP
HIGH ALARM AT 32 F INCREASING, HIGH-HIGH ALARM SET AT 68F INCREASING
GAS FUEL STRAINER DIFFERENTIAL PRESSURE INDICATOR
0.00 0.00
0.0 - 25.0 PSID
(0.0-172.4 KPAD)
IGV HYDRAULIC OIL FILTER DIFFERENTIAL PRESSURE INDICATOR
0.00 0.00
LUBE OIL FILTER DIFFERENTIAL PRESSURE INDICATOR
0.00 PSID 25.00
(0.0-172.4 KPAD)
LUBE OIL FILTER DIFFERENTIAL PRESSURE INDICATOR
0.00 PSID 25.00
(0.0-172.4 KPAD)
SEAL OIL FILTER DIFFERENTIAL PRESSURE INDICATOR
0.00 PSID 25.00
(0.0-172.4 KPAD)
PRESSURE DIFFERENTIAL INDICATOR
0.00 10.00
0-10 IN. W.C [0-2.49 KPA]
OVERALL FILTERHOUSE PRESSURE DROP
0.00 10.00
0-10 IN. W.C [0-2.49 KPA]
SELF CLEANING FILTER PRESSURE INDICATOR
0.00 10.00
0-10 IN. W.C [0-2.49 KPA]
PRESSURE DIFFERENTIAL SWITCH
0.00 10.00
NO INTERFACE WITH TCP
0 - 10 IN. W.C. [0-2.49 KPA]
SEAL OIL DIFFERENTIAL PRESSURE LOW SWITCH
DECREASING: 4.500 PSID OR 31.03 KPAD
NORM=(2) NC-CEC;
FUNCTION: ALARM
NOTE: SWITCH MUST BE COMPENSATED IN THE FIELD SINCE THE HGF AND
HSF-2 SENSING LINES ARE AT DIFFERENT ELEVATIONS.
DEAD BAND = .35
OPENS TO ALARM LOW DP

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

52 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

53

Device
PDSL-3406

System
4027

PDT-292

4027

PDT-3402

4027

PH1-1

0434

PH2-1

0434

PI-AP-1

0419

PI-AP-2

0419

PI-AP-3

0419

PI-CA-2

0471

PI-CW-4

0420

PI-CW-5

0420

Page 53 of 67

REV

Settings
SEAL OIL DIFF PRESSURE LOW-LOW, START DC PUMP
DECREASING: 3.500 PSID OR 24.13 KPAD
FUNCTION: START DC PUMP
NOTE: SWITCH MUST BE COMPENSATED IN THE FIELD SINCE THE HGF & HSF-2
SENSING LINES ARE AT DIFFERENT ELEVATIONS.
DEAD BAND = 0.98 TO 1.9 PSID
GENERATOR ROTOR FAN PRESSURE DIFFERENTIAL
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 30.00 INH2O OR 7.465 KPA
FUNCTION: ALARM AT 12 IN H2O (2.99 KPA)
SEAL OIL DIFFERENTIAL PRESSURE, SEAL OIL VS GAS PRESSURE
4.000 MA= 0.0 PSID OR 0.0 KPAD
20.00 MA= 15.00 PSID OR 103.4 KPAD
FUNCTION: MONITOR /ALARM
ALARM AT 3.5 TO INDICATE DC PUMPS MAY HAVE STARTED, ALARM AT 4.5 FOR
LOW DP AND ALARM AT 8.5 FOR HIGH DP.
PDCV-3401 CONTROL VALVE SET TO 5.5 PSID
MAIN HYDRAULIC OIL SUPPLY PUMP
32 GPM @ 2750 PSIG (18961 KPA)
MAX VOLUME STOP SET FOR MAXIMUM VOLUME CAPACITY
AUXILIARY HYDRAULIC OIL SUPPLY PUMP
32 GPM @ 2750 PSIG (18961 KPA)
MAX VOLUME STOP SET FOR MAXIMUM VOLUME CAPACITY
APU PRESSURE INDICATOR - PREREGULATOR
0.00 PSIG 300.00
0 - 2068 KPAG
APU PRESSURE INDICATOR - DRYER INLET
0.00 PSIG 300.00
0 - 2068 KPAG
APU PRESSURE INDICATOR - DRYER DISCHARGE
0.00 PSIG 160.00
0 - 1103 KPAG
PRESSURE INDICATOR
0.00 PSIG 150.00
(0.0-1034 KPAG)
PRESSURE INDICATOR FOR SELF CLEANING AIR SUPPLY
COOLING WATER PRESSURE INDICATOR
0.00 PSIG 60.00
(0.0-413.7 KPAG)
COOLING WATER PRESSURE INDICATOR
0.00 PSIG 60.00
(0.0-413.7 KPAG)

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

53 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

54

Device
PI-D5

System
0422

PI-FG-1

0422

PI-FG-2

0422

PI-FP-1A

0426

PI-GC-1

4035

PI-GC-2

4035

PI-HQ-1

0434

PI-HQ-2

0434

PI-HQ-3

0434

PI-HQ-6A

0434

PI-HQ-6B

0434

PI-PG-1

0477

PI-PM1

0422

PI-PM4

0422

PI-QA-1

0416

Page 54 of 67

REV

Settings
FUEL GAS PRESSURE INDICATOR
0.00 PSIG 600.00
(0.0-4137 KPAG)
GAS FUEL SUPPLY PRESSURE INDICATOR
0.00 PSIG 600.00
(0.0 - 4137 KPAG)
GAS FUEL INTERVALVE (P2) PRESSURE INDICATOR
0.00 PSIG 600.00
(0.0 - 4137 KPAG)
CO2 TANK PRESSURE INDICATOR
0.00 PSIG 0.00
(0.0-0.0 KPAG)
GAS CHROMATOGRAPH SAMPLE PRESSURE GAUGE - 1
0.00 PSIG 60.00
(0.0-413.7 KPAG)
GAS CHROMATOGRAPH SAMPLE PRESSURE GAUGE - 2
0.00 PSIG 60.00
(0.0-413.7 KPAG)
HYD PUMP #1 PRESSURE DISCHARGE INDICATOR
0.00 PSIG 6000.00
(0.0-41369 KPAG)
HYD PUMP #2 PRESSURE DISCHARGE INDICATOR
0.00 PSIG 6000.00
(0.0-41369 KPAG)
HYDRAULIC LOW PRESSURE INDICATOR
0.00 PSIG 2000.00
(0.0-13790 KPAG)
HYD PUMP #1 PRESSURE INLET INDICATOR
0.00 PSIG 160.00
(0.0-1103 KPAG)
HYD PUMP #2 PRESSURE INLET INDICATOR
0.00 PSIG 160.00
(0.0-1103 KPAG)
PRESSURE INDICATOR
0.00 PSIG 160.00
(0.0-1103 KPAG)
FUEL GAS PRESSURE INDICATOR
0.00 PSIG 600.00
(0.0 - 4137 KPAG)
FUEL GAS PRESSURE INDICATOR
0.00 PSIG 600.00
(0.0 - 4137 KPAG)
MAIN LUBE OIL PUMP PRESSURE INDICATOR
0.00 PSIG 200.00
(0.0-1379 KPAG)

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

54 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

55

Device
PI-QA-1A

System
0416

PI-QA-2

0416

PI-QB-1

0434

PI-QE-1

0416

PI-QS-1

0416

PI-QS-2

0416

PI-QT-2A

0416

PI-QT-2B

0416

PI-QV-1

0416

PI-WW-1

0442

PI-WW-10

0442

PI-WW-11

0442

PI-WW-12

0442

PI-WW-13

0442

PQ1-1

0416

Page 55 of 67

REV

Settings
LUBE OIL HEADER PRESSURE INDICATOR
0.00 PSIG 60.00
(0.0-413.7 KPAG)
LUBE OIL PUMP#2 PRESSURE INDICATOR
0.00 PSIG 200.00
(0.0-1379 KPAG)
LIFT OIL PRESSURE INDICATOR
0.00 PSIG 6000.00
(0.0-41369 KPAG)
EMERGENCY LUBE OIL PUMP PRESSURE INDICATOR
0.00 PSIG 60.00
(0.0-413.7 KPAG)
SEAL OIL PUMP PRESSURE INDICATOR
0.00 PSIG 200.00
(0.0-1379 KPAG)
SEAL OIL PUMP PRESSURE INDICATOR
0.00 PSIG 200.00
(0.0-1379 KPAG)
GENERATOR BEARING LUBE OIL PRESSURE INDICATOR
0.00 PSIG 60.00
(0.0-413.7 KPAG)
GENERATOR BEARING LUBE OIL PRESSURE INDICATOR
0.00 PSIG 60.00
(0.0-413.7 KPAG)
MIST ELIMINATOR FILTER HOUSE PRESSURE INDICATOR
0.00 0.00
0.0 - 50 INCHES H2O
[0.0 - 1270 MM H2O]
WATER WASH SKID PRESSURE INDICATOR
0.00 PSIG 200.00
(0.0-1379 KPAG)
PRESSURE GAUGE - WATER WASH
0.00 PSIG 200.00
(0.0-1379 KPAG)
PRESSURE GAUGE - WATER WASH
0.00 PSIG 100.00
(0.0-689.5 KPAG)
PRESSURE GAUGE - WATER WASH
0.00 PSIG 100.00
(0.0-689.5 KPAG)
PRESSURE GAUGE - WATER WASH
0.00 PSIG 100.00
(0.0-689.5 KPAG)
LUBE OIL MAIN PUMP
RATED FLOW: 1050 GPM AT 112 PSIG (2900 RPM)

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

55 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

56

Device
PQ1-2

System
0416

PQ2-1

0416

PQ3-1

0416

PQ3-2

0416

PS-3404

4027

PSL-2930

4027

PT-2950

4027

PT-G1-1

0422

PT-G1-2

0422

PT-G1-3

0422

QT-290A

4027

Page 56 of 67

REV

Settings
LUBE OIL MAIN PUMP
RATED FLOW: 1050 GPM AT 112 PSIG (2900 RPM)
LUBE OIL EMERGENCY PUMP
RATED FLOW: 600.0 GPM AT 30 PSIG (1750 RPM)
SEAL OIL PUMP
RATED FLOW: 118.0 GPM AT 110 PSIG (2900 RPM)
SEAL OIL PUMP
RATED FLOW: 65.00 GPM AT 90 PSIG (2900 RPM)
SEAL OIL INLET PRESS LOW, START DC PUMP
DECREASING: 90.00 PSIG OR 620.5 KPAG
FUNCTION: START DC PUMP
DEAD BAND = 0.85 TO 2.9 PSIG (0.0586 TO 0.1999 BARG)
H2 SUPPLY PRESSURE LOW
DECREASING: 110.0 PSIG OR 758.4 KPAG
(INCREASING: 125.0 PSIG OR 861.8 KPAG)
NORM=(1) NC-CEC; CONTACT OPENS ON LOW PRESSURE;
H2 SUPPLY PRESSURE LOW ALARM.
DEAD BAND = 0.2 TO 1 PSIG
HAZARDOUS ZONE 2 PROTECTION METHOD `D` FLAME PROOF
GENERATOR GAS PRESSURE
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 100.0 PSIG OR 689.5 KPAG
LOW PRESSURE ALARM AT 58 PSIG.
HIGH PRESSURE ALARM AT 64 PSIG.
HAZARDOUS ZONE 2 PROTECTION METHOD `D` FLAME PROOF
GAS FUEL PURGE THERMOCOUPLE
TYPE K THERMOCOUPLE
LOCATED ON DIFFUSION GAS MAINFOLD
GAS FUEL PURGE THERMOCOUPLE
TYPE K THERMOCOUPLE
LOCATED ON DIFFUSION GAS MAINFOLD
GAS FUEL PURGE THERMOCOUPLE
TYPE K THERMOCOUPLE
LOCATED ON DIFFUSION GAS MAINFOLD
CELL #1 TRANSMITTER SIGNAL
4 MA - 70% H2; 20 MA - 100% H2, FOR H2 IN AIR
TE LOW LOW PURITY RUNBACK SETTING - 80% H2 DEC
TE LOW PURITY INCREASE SCAV - 85% H2 DEC (87% INC)
CASE LOW LOW PURITY RUNBACK SETTING - 90% H2 DEC
CASE LOW PURITY ALARM - 95% H2 DEC (98% H2 INC)

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

56 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

57

Device
QT-290B

System
4027

RS-485-1

4035

RS-485-2

4035

SLA-1C

0426

SLA-1D

0426

SLA-3A

0426

SLA-3B

0426

SLA-3C

0426

SLA-3D

0426

SLT-1A

0426

SLT-1B

0426

Page 57 of 67

REV

Settings
CELL #2 TRANSMITTER SIGNAL
4 MA - 70% H2; 20 MA - 100% H2, FOR H2 IN AIR
CE LOW LOW PURITY RUNBACK SETTING - 80% H2 DEC
CE LOW PURITY INCREASE SCAV - 85% H2 DEC (87% INC)
CASE LOW LOW PURITY RUNBACK SETTING - 90% H2 DEC
CASE LOW PURITY ALARM - 95% H2 DEC (98% H2 INC)
SERIAL PORT
FOR CUSTOMER USE
SERIAL PORT
FOR CUSTOMER USE
FIRE ALARM STROBE & HORN (ACCESSORY COMPT)
24 VDC
EXTERNAL STROBE/HORN
(GAS COMP/ ACCESS.MODULE-ZONE 1)
FIRE ALARM STROBE & HORN (ACCESSORY COMPT)
24 VDC
INTERNAL STROBE/HORN
(GAS COMP. - ACCESS.MODULE-ZONE 1)
FIRE ALARM STROBE & HORN (ACCESSORY MODULE)
24 VDC
EXTERNAL STROBE/HORN
(LUBE/HYDRAULIC COMP.-ACCESS.MODULE-ZONE 3)
FIRE ALARM STROBE & HORN (ACCESSORY MODULE)
24 VDC
EXTERNAL STROBE/HORN
(LUBE/HYDRAULIC COMP.-ACCESS.MODULE-ZONE 3)
FIRE ALARM STROBE & HORN
24 VDC
INTERNAL STROBE/HORN
(LUBE/HYDRAULIC COMP.-ACCESS.MODULE-ZONE 3)
FIRE ALARM STROBE & HORN
24 VDC
INTERNAL STROBE/HORN
(LUBE/HYDRAULIC COMP.-ACCESS.MODULE-ZONE 3)
FIRE ALARM STROBE & HORN (TURBINE COMPT)
24 VDC
EXTERNAL STROBE/HORN
(TURBINE COMPT-ZONE 1)
FIRE ALARM STROBE & HORN (TURBINE COMPT)
24 VDC
EXTERNAL STROBE/HORN
(TURBINE COMPT-ZONE 1)

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

57 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

58

Device
TI-AP-1

System
0419

TI-QA-1

0416

TI-QL-1

0416

TI-WW-1

0442

TT-CM-1

0417

TT-IB-1

0415

TT-IB-2

0415

TT-IB-3

0415

TT-S13-1

0417

TT-S2Q-2

0417

TT-S2Q-3

0417

TT-S2Q-4

0417

Page 58 of 67

REV

Settings
APU TEMPERATURE INDICATOR
0.00 F 250.00
0 - 121.1 C
LUBE OIL HEADER TEMPERATURE INDICATOR
20.00 F 240.00
(-6.667-115.6 C)
LUBE OIL TANK TEMPERATURE INDICATOR
20.00 F 240.00
(-6.667-115.6 C)
WATER WASH TANK TEMPERATURE INDICATOR
0.00 F 250.00
CASE TEMP. MANAGEMENT AIR SUPPLY TEMP. TRANS.
100 OHM PLATINUM (MINCO PB) RTD
1 ELEMENT; UNGROUNDED;
4.0 MA = -58 F OR -50 C
20.0 MA = 302 F OR 150 C
TURBINE TEMP-INNER BARREL
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMP-INNER BARREL
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMP-INNER BARREL
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
STAGE 13 FLOW TEMPERATURE
THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EJECTOR EXIT TEMPERATURE
THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
S2N SUPPLY TEMPERATURE (WYE CONNECTION LHS)
THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
S2N SUPPLY TEMPERATURE (WYE CONNECTION RHS)

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

58 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

59

Device
TT-S9-1

System
0417

TT-TC-1

0415

TT-TC-10

0415

TT-TC-11

0415

TT-TC-12

0415

TT-TC-13

0415

TT-TC-14

0415

TT-TC-15

0415

TT-TC-16

0415

TT-TC-2

0415

TT-TC-3

0415

TT-TC-4

0415

TT-TC-5

0415

TT-TC-6

0415

Page 59 of 67

REV

Settings
THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
STAGE 9 FLOW TEMPERATURE
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

59 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

60

Device
TT-TC-7

System
0415

TT-TC-8

0415

TT-TC-9

0415

TT-WS1AO-1

0415

TT-WS1AO-2

0415

TT-WS1FI-1

0415

TT-WS1FI-2

0415

TT-WS2AO-1

0415

TT-WS2AO-2

0415

TT-WS2FO-1

0415

TT-WS2FO-2

0415

TT-WS3AO-1

0415

TT-WS3AO-2

0415

TT-WS3FO-1

0415

TT-WS3FO-2

0415

Page 60 of 67

REV

Settings
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TURBINE TEMPERATURE-WHEELSPACE 1ST STG AFT OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMPERATURE-WHEELSPACE 1ST STG AFT OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMPERATURE-WHEELSPACE 1ST STG FWD INNER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMPERATURE-WHEELSPACE 1ST STG FWD INNER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMPERATURE-WHEELSPACE 2ND STG AFT OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMPERATURE-WHEELSPACE 2ND STG AFT OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMPERATURE-WHEELSPACE 2ND STG FWD OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMPERATURE-WHEELSPACE 2ND STG FWD OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMPERATURE-WHEELSPACE 3RD STG AFT OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMPERATURE-WHEELSPACE 3RD STG AFT OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMPERATURE-WHEELSPACE 3RD STG FWD OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TURBINE TEMPERATURE-WHEELSPACE 3RD STG FWD OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

60 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

61

Device
TT-XD-1

System
0415

TT-XD-10

0415

TT-XD-11

0415

TT-XD-12

0415

TT-XD-13

0415

TT-XD-14

0415

TT-XD-15

0415

TT-XD-16

0415

TT-XD-17

0415

TT-XD-18

0415

TT-XD-19

0415

TT-XD-2

0415

TT-XD-20

0415

TT-XD-21

0415

TT-XD-22

0415

Page 61 of 67

REV

Settings
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

61 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

62

Device
TT-XD-23

System
0415

TT-XD-24

0415

TT-XD-25

0415

TT-XD-26

0415

TT-XD-27

0415

TT-XD-28

0415

TT-XD-29

0415

TT-XD-3

0415

TT-XD-30

0415

TT-XD-31

0415

TT-XD-4

0415

TT-XD-5

0415

TT-XD-6

0415

TT-XD-7

0415

TT-XD-8

0415

Page 62 of 67

REV

Settings
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

62 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

63

Device
TT-XD-9

System
0415

VA13-1

0477

VA13-13

0477

VA13-15

0422

VA13-18

0422

VA13-2

0477

VA13-5

0477

VA13-6

0477

VA13-8

0477

VA16-1

0442

VA16-3

0442

VA16-4

0442

VA2-1

0417

VA2-2

0417

VA2-3

0417

VA2-4

0417

Page 63 of 67

REV

Settings
EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
FUEL GAS SYSTEM PURGE VALVE
NORM=CLOSED; VALVE TO CLOSE IN 4 SECONDS MAX
FUEL GAS SYSTEM PURGE VALVE
NORM=OPEN
PM4 VENT VALVE
GAS FUEL VENT VALVE
NORM=NO
GAS FUEL VENT VALVE
NORM=NO
FUEL GAS SYSTEM PURGE VALVE
NORM=CLOSED; VALVE TO CLOSE IN 4 SECONDS MAX
GAS FUEL SYSTEM PURGE VALVE
NORM=CLOSED; VALVE TO CLOSE IN 4 SECONDS MAX
GAS FUEL SYSTEM PURGE VALVE
NORM=CLOSED; VALVE TO CLOSE IN 4 SECONDS MAX
FUEL GAS SYSTEM PURGE VENT VALVE
NORM=OPEN
D5 VENT VALVE
OFF-LINE COMPRESSOR WASH WATER INJ (PNEUMATIC) VALVE
NORMAL = CLOSED; ENERGIZE TO OPEN
REQUIRES 80 PSIG (MINIMUM) INSTRUMENT AIR FOR ACTUATION
ON-LINE COMPRESSOR WASH WATER INJ (PNEUMATIC) VALVE
NORMAL = CLOSED; ENERGIZE TO OPEN
REQUIRES 80 PSIG (MINIMUM) INSTRUMENT AIR FOR ACTUATION
GFC WATER INJ (PNEUMATIC) VALVE
NORMAL = CLOSED; ENERGIZE TO OPEN
REQUIRES 80 PSIG (MINIMUM) INSTRUMENT AIR FOR ACTUATION
COMPRESSOR BLEED VALVE
FAILED POSITION = OPEN
COMPRESSOR BLEED VALVE
FAILED POSITION = OPEN
COMPRESSOR BLEED VALVE
FAILED POSITION = OPEN
COMPRESSOR BLEED VALVE
FAILED POSITION = OPEN

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

63 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

64

Device
VA20-1

System
0432

VA32-1

0420

VA36-1

0477

VA36-10

0477

VA36-2

0477

VA36-9

0477

VA40-1
VA42-1
VA7-2

0432
0432
0417

VA7-3

0417

VAB1-1
VAB2-1
VAD-2

0434
0434
0419

VCK7-1
VCK7-3
VGC-1

0417
0417
0422

VGC-2

0422

Page 64 of 67

REV

Settings
INLET HEATING CONTROL VALVE
4.0 INCH STROKE
LINEAR TRIM CHARACTERISTIC
10.0 INCH ANSI FLANGE CONNECTION
FAILED POSITION = OPEN
COOLING WATER CONTROL VALVE-LUBE OIL COOLER FLOW
SET 130 +- 3.000F OR 54.44 +- 1.666C
FUEL GAS SYSTEM PURGE VALVE ACTUATOR QUICK EXH VALVE
PART OF VA13-1; VALVE TO CLOSE IN 4 SECONDS MAX
3-WAY PILOT OPERATED QUICK EXHAUST VALVE
PART OF VA13-6
VALVE TO CLOSE IN 4 SECONDS MAX
FUEL GAS SYSTEM PURGE VALVE ACTUATOR QUICK EXH VALVE
PART OF VA13-2; VALVE TO CLOSE IN 4 SECONDS MAX
FUEL GAS SYSTEM PURGE VALVE ACTUATOR QUICK EXHAUST VALVE
PART OF VA13-5
INLET HEATING CONTROL VALVE VOLUME BOOSTER
INLET BLEED HEAT QUICK EXHAUSTER VALVE
CONTROL VALVE
BYPASS FLOW CONTROL
FAILED POSITION = OPEN
CONTROL VALVE
SUCTION ISOLATION FLOW CONTROL
FAILED POSITION = CLOSED
HYDRAULIC OIL SYSTEM AIR BLEED VALVE (MAIN)
HYDRAULIC OIL SYSTEM AIR BLEED VALVE (AUX)
Air Processing Unit Drain Valve
1 PH
230 VAC; 50 HZ;
ELECTRONIC SOLENOID DRAIN VALVE OPERATED BY TIMER.
TURBINE SHELL & EXHAUST FRAME BLOWER CHECK VALVE
TURBINE SHELL COOLING AIR BLOWER CHECK VALVE
FUEL GAS CONTROL VALVE
SLEW TIME = 1.00 +/-0.150 SECONDS
3.00 IN. MAXIMUM STROKE
HYDRAULIC EFFECTIVE AREA 2.54 IN^2
D5 CIRCUIT - GAS CONTROL VALVE
FUEL GAS CONTROL VALVE
SLEW TIME = 1.000 +/-0.150 SECONDS
3.0 IN. MAXIMUM STROKE
HYDRAULIC EFFECTIVE AREA 2.54 IN^2
PM1 CIRCUIT - GAS CONTROL VALVE

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

64 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

65

Device
VGC-3

System
0422

VH3-1
VH5-1
VH5-2
VH5-3
VH5-4
VM15-1

0434
0422
0422
0422
0422
0432

VPR17-3

0417

VPR17-4

0417

VPR17-5

0417

VPR17-6

0417

VPR2-1

0416

VPR3-1

0434

VPR3-2

0434

VPR4-3

0434

VPR4-4

0434

Page 65 of 67

REV

Settings
FUEL GAS CONTROL VALVE
SLEW TIME = 1.00 +/-0.150 SECONDS
3.00 IN. MAXIMUM STROKE
HYDRAULIC EFFECTIVE AREA 2.54 IN^2
PM2 CIRCUIT - GAS CONTROL VALVE
INLET GUIDE VANE DUMP VALVE
GAS FUEL DUMP VALVE-STOP/SPEED RATIO VALVE
GAS FUEL DUMP VALVE-CONTROL VALVE
GAS FUEL DUMP VALVE-CONTROL VALVE
GAS FUEL DUMP VALVE-CONTROL VALVE
INLET HEATING ISOLATION VALVE
10.0 INCH ANSI FLANGE CONNECTION
MANUAL BUTTERFLY VALVE
NORMAL POSITION = OPEN
PRESSURE REGULATOR
SET 80.00 PSIG OR 551.6 KPAG
ACTUATION AIR
PART OF VA7-2
PRESSURE REGULATOR
SET 15.00 PSIG OR 103.4 KPAG
SIGNAL AIR
PART OF VA7-2
PRESSURE REGULATOR
SET 80.00 PSIG OR 551.6 KPAG
ACTUATION AIR
PART OF VA7-3
PRESSURE REGULATOR
SET 15.00 PSIG OR 103.4 KPAG
SIGNAL AIR
PART OF VA7-3
LUBE OIL HEADER PRESSURE REGULATOR VALVE
SET 33.00+-2.000 PSIG OR 227.5+-13.79 KPAG
COMPENSATOR-HYDRAULIC OIL SUPPLY PUMP (IN PUMP)
SET 2750+-50.00 PSIG OR 18961+-344.7 KPAG
LOW PRESSURE SETTING: 1800 PSIG
COMPENSATOR-HYDRAULIC OIL SUPPLY AUX PUMP
SET 2750+-50.00 PSIG OR 18961+-344.7 KPAG
LOW PRESSURE SETTING: 1800 PSIG
HYDRAULIC SUPPLY PRESSURE REGULATING VALVE #1
SET 1625+-25.00 PSIG OR 11204+-172.4 KPAG
HYDRAULIC SUPPLY PRESSURE REGULATING VALVE #2
SET 1625+-25.00 PSIG OR 11204+-172.4 KPAG

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

65 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

66

Device
VPR41-1

System
0432

VPR54-22

0477

VPR54-3A

0477

VPR64-2

0420

VPR67-1

0419

VPR74-1

0442

VPR76-1

4035

VPR76-2

4035

VPR77-1

4035

VPR78-1

4035

VQC-1

0434

VQC-2

0434

VQC-3

0434

VQC-4

0434

VQC-5

0434

VQC-6

0434

Page 66 of 67

REV

Settings
TURBINE IAH CONTROL VALVE I/P INST AIR PRESSURE REG
SET 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG
20TH-1 TRIP SOLENOID MUST BE ENERGIZED TO SET VPR41-1 PRESSURE
OUTPUT WITH GAGE
REGULATOR - GAS FUEL PURGE CONTROL VALVE
SET 90.00+-2.000 PSIG OR 620.5+-13.79 KPAG
PART OF VA13-2
FILTER AIR PRESSURE REGULATOR
FILTER AIR PRESSURE REGULATOR
SET AT 85 +/- 5 PSIG OR 586 +/- 34.5 KPA
PRIMARY GAS PURGE VALVES
COOLING WATER CONTROL VALVE-AIR SUPPLY REG VALVE
SET 35.00+-3.000 PSIG OR 241.3+-20.68 KPAG
AIR FILTER BLOWDOWN REGULATOR VALVE
SET 110.0+-5.000 PSIG OR 758.4+-34.47 KPAG
PRESS REGULATOR, ONLINE COMPRESSOR WASH MANIFOLD SUPPLY
80 PSIG +/- 5 PSIG
(551.58 KPAG +/- 34.473 KPAG)
FUEL GAS SAMPLE PRESSURE REGULATING VALVE
SET TO VENDOR REQUIREMENTS
REFER TO SERVICE MANUAL
FUEL GAS SAMPLE PRESSURE REGULATING VALVE
SET TO VENDOR REQUIREMENTS
REFER TO SERVICE MANUAL
CARRIER GAS - PRESSURE REGULATING VALVE
SET TO VENDOR REQUIREMENTS
REFER TO SERVICE MANUAL
CALIBRATION GAS - PRESSURE REGULATING VALVE
SET TO VENDOR REQUIREMENTS
REFER TO SERVICE MANUAL
VARIABLE FLOW CONTROL VALVE
GT #1 BRG. LIFT OIL
VARIABLE FLOW CONTROL VALVE
GT #1 BRG. LIFT OIL
VARIABLE FLOW CONTROL VALVE
GT #2 BRG. LIFT OIL
VARIABLE FLOW CONTROL VALVE
GT #2 BRG. LIFT OIL
VARIABLE FLOW CONTROL VALVE
GENERATOR BRG. LIFT OIL - TURBINE END
VARIABLE FLOW CONTROL VALVE
GENERATOR BRG. LIFT OIL - COLLECTOR END

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

66 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR

DWG Number 399A4822

SIZE

DWG NO

Rev B

Released 7/23/2013

SH

399A4822

67

Device
VR-31

System
0426

VR-31E

0426

VR-32

0426

VR-32E

0426

VR-33

0426

VR-33E

0426

VR14-1

0419

VR14-2

0419

VR21-1

0434

VR22-1

0434

VR23-2

0434

VR64-10

0420

VR64-9

0420

VS4-1
VS4-4
VSR-1

0422
0422
0422

Page 67 of 67

REV

Settings
RELIEF VALVE
SET 450.0 PSIG OR 3103 KPAG
HYDROSTATIC RELIEF VALVE FOR DISCHARGE PIPING
RELIEF VALVE
SET 450.0 PSIG OR 3103 KPAG
HYDROSTATIC RELIEF VALVE FOR DISCHARGE PIPING
RELIEF VALVE
SET 450.0 PSIG OR 3103 KPAG
HYDROSTATIC RELIEF VALVE FOR DISCHARGE PIPING
RELIEF VALVE
SET 450.0 PSIG OR 3103 KPAG
HYDROSTATIC RELIEF VALVE FOR DISCHARGE PIPING
RELIEF VALVE
SET 450.0 PSIG OR 3103 KPAG
HYDROSTATIC RELIEF VALVE FOR DISCHARGE PIPING
RELIEF VALVE
SET 450.0 PSIG OR 3103 KPAG
HYDROSTATIC RELIEF VALVE FOR DISCHARGE PIPING
APU PRESSURE RELIEF VALVE
SET 150.0+-1.000 PSIG OR 1034+-6.895 KPAG
DRYER TOWER RELIEF VALVE
APU PRESSURE RELIEF VALVE
SET 150.0+-1.000 PSIG OR 1034+-6.895 KPAG
DRYER TOWER RELIEF VALVE
MAIN HYDRAULIC OIL SUPPLY PUMP PRESSURE RELIEF VALVE
SET 3025+-100.0 PSIG OR 20857+-689.5 KPAG
AUXILIARY HYDRAULIC OIL SUPPLY PUMP PRESSURE RELIEF VALV
SET 3025+-100.0 PSIG OR 20857+-689.5 KPAG
HYDRAULIC SUPPLY LOW PRESSURE RELIEF VALVE
SET 1815+-25.00 PSIG OR 12514+-172.4 KPAG
COOLING WATER PRESSURE RELIEF VALVE- LO COOLER
SET 150.0+-5.000 PSIG OR 1034+-34.47 KPAG
COOLING WATER PRESSURE RELIEF VALVE- LO COOLER
SET 150.0+-5.000 PSIG OR 1034+-34.47 KPAG
FUEL GAS STOP VALVE
FUEL GAS STOP VALVE
STOP/SPEED RATIO VALVE
SLEW TIME = 0.500 +/- 0.250 SECONDS
90 DEGREES ROTATION MAX. STROKE 6.0 INCHES
HYDRAULIC EFFECTIVE AREA 7.67 IN^2

COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON CRITICAL)

GE Energy

GENERAL ELECTRIC COMPANY

DRAWN

BALLA, SANKAR

DRAWN DATE

2012-12-11

SIZE

CAGE CODE

DWG NO

399A4822
SHEET

67 of 67

GE Proprietary Information - Class II (Internal) US EAR - NLR