AGC-300
AGC-300
(144144109.5mm/approx.1.0kg)
USE
This product is multi-function generator controller to control synchronizing, load
distribution, constant power factor, constant voltage, constant frequency and operating unit
number in parallel operation between commercial and generator and between generators.
This product can be used for wide range, such as normal power generation and emergency
power generation, congeneration, etc.
FEATURES
Small-sized thin type, panel mounting controller (DIN144144).
Generator operating unit number is up to 8 units.
It is most suitable for system which is possible for expansion (1 unit for each).
Stable operation in line with system can be realized with easy setting/switching of
operational requirements (Setting of start, separation and switching of day/night are
possible).
Safe controller with synchronizing check relay to consider incoming reverse power
prevention and generator overload prevention.
Products List
AGC-300
STANDARD SPECIFICATION
Parallel operation of incoming and
generator
1
Operating
method
Single operation (generator only)
2
3
4
Generator
3-phase input
Bus
voltage input
AC110V 5A 3
AC110V 1
DC input
Input for
control
(8 circuits)
Control output
(10 circuits)
Communication
Control
power
SW
input
Control start
Incoming start
Synchronizing start
Distribution start
Cut-in start
Forced separation
Designation of preceding generator
Control changeover
Governor increase signal (65R)
Governor decrease signal (65L)
AVR increase signal (90R)
AVR decrease signal (90L)
Start command signal
Separation command signal
Light fault
Closing command (25)
Synchronizing check signal
Alarm
Communication among controllers
10
Display
Products List
Products List
50/60Hz 0.5VA
Push switch
Slide switch
AGC-300
PERFORMANCE
Item
Synchronizing
Voltage difference
Frequency difference
Measured phase difference
Closing phase difference
Power detection
Tolerance
Distribution
control
Common
Excess voltage
strength
AC power
DC power
Excess current
strength
Strength
Insulation
resistance
AC input
DC input
30M or more at
DC 500Vmegger
5kV 1.2/50S
Vibration
False operation
Impact
durability
Products List
specification
0.5%
0.03Hz
1
5
1.0% % against rated power
( at 1/2 to F/S of T/D full scale)
3(when load current is 10% or more,
power factor is LEAD0.5-1-LAG0.5)
1.0% % against rated reactive power
1.0% % against rated current
0.1% % against rated frequency
1.0% % against rated voltage
10%0.1s % against setting value
10%0.1s % against setting value
2 times (10sec.) of rated voltage
1.2 times continuation
1.5 times (10sec.) of rated voltage
1.2 times continuation
1.5 times (10sec.) of rated voltage
1.3 times continuation
40 times (1sec.) of rated current
1.2 times continuation
2 times (10sec.) of rated current
1.2 times continuation
Between electric circuit and outer case
(earth); between each other of bus voltage
input, generator voltage input, generator
current input, power input, for-control
input, T/D input, for-control output,
governor control output, voltage control
output and communication line.
Between electric circuit and outer case
(earth); between each other of bus voltage
input, generator voltage input, generator
current input, power input, DC input,
for-control input and communication line.
Governor control output, AVR control
output and other control output
Between electric circuit and outer case
(earth) 5kV 12/50S
16.7Hz, peak-to-peak 1mm,
10mins for X.Y.Z direction each
294m/S2 (30G),
3 times for X.Y.Z direction each
-10+55,
3085%RH (no condensation)
-2570
Munsell N1.5(black), approx. 1.3kg.
AGC-300
Products List
AGC-300
CONTROL FUNCTION
Synchronizing control
1.
2.
3.
Synchronizing control starts with synchronizing start input after establishing voltage and frequency
of generator. LED bar of phase angle validation is ON in compliance with phase difference.
( marking in center is synchronizing point.)
When voltage is within V and frequency is within F, 25 closing command is outputted before
progress time from synchronous point after control. Contact ON time is progress time 200ms
When phase difference exceeds 10or progress time +200ms with synchronous point being passed in
spite of 25 closing command output, 25 closing command can be OFF. Reset of alarm is executed by
start signal being OFF.
Distribution control
Power distribution control/rated frequency control/generator power factor constant control/reactive
power distribution control/rated voltage control are selected by each start input.
Incoming + Generator
incoming constant value=WMI
power distribution (proportional distribution)
Load for each generator =
start
Common: When total load exceeds WHI and continues for
TS sec. continuously, 1st generator starts to operate.
Heavy load OFF: Following generator starts to operate when
total load exceeds WMI+WHG operating generator
unit number (no timer)
Heavy load ON: Following generator starts to operate when
total load exceeds WHI+WHG operating generator
unit number and continues for TS sec.
separation
Heavy load OFF: Last generator separates when total load
is below WMI+WMG remaining generator unit
number and continues for TB sec. after separation.
Heavy Load ON: Last generator separates when total load is
below (WHI-M)+WMG remaining generator unit
number after separation.
Common: Last generator separates when total load is below
WHI-M and continues for TB sec.
Products List
Products List
Generator only
incoming constant =0,
incoming measured value = 0
power distribution (proportional distribution)
Load for each generator =
Total load
Generator rated total
AGC-300
Generator only
Rated frequency control is executed on all unites almost
simultaneously after power distribution
Generator only
Reactive power distribution (proportional distribution)
Each generator
reactive power load =
Generator only
Rated voltage control is executed on all units almost
simultaneously after reactive power distribution.
Products List
AGC-300
OTHER FUNCTIONS
Synchronizing check function (synchronizing control)
When phase difference between bus and closing generator is within 15 in F/V,
synchronizing check relay signal is outputted.
Phase difference delay detection function (synchronizing control)
Frequency difference (0.05 or less) between bus and closing generator and phase difference
becomes almost constant; governor pulse is outputted 3 sec. later in order to speed up
synchronizing control.
When closing direction is FAST or FREE, governor increase signal is outputted.
When closing direction is SLOW, governor decrease signal is outputted.
Mean value measuring control (power distribution control)
Incoming power can be measured and controlled in mean value by setting mean time TAI
second.
Incoming reverse power prevention control (power distribution control)
When incoming is below min. power value (WLI), output decrease command (65L max.
pulse output) is outputted to all generators. When reverse power continues, error display/
light fault are outputted.
Power factor neutral zone changeover current value (generator power factor constant control)
When power factor neutral zone changeover current value (CHA) is below the load current,
power factor neutral zone is .
When power factor neutral zone changeover current value (CHA) exceeds the load current,
power factor neutral zone is 2.
Power factor control cut current value (generator power factor constant control)
When generator load current is below the power factor control cut current value (CTA),
power factor control is stopped.
Governor abnormality detection/AVR abnormality detection (distribution control)
When generator does not reach the target value even though governor signal (65R/65L) or
voltage signal (90R/90L) are outputted 60 times in same detection, error display/light fault
are outputted as governor abnormality/AVR abnormality. Control continues even though
error is detected.
Products List
Products List
AGC-300
Products List
21
22
23
24
25
20
Setting description
Sign
5%
Possible
setting range
1-10%
Synchronizing control
No.
Initial
value
Parallel
w/incoming
AGC-300
Generator
only
Power
Power
distribution
distribution
control +
control +
generator
frequency,
power factor
voltage
control
control
VPW
0.5S
0.1-1.0S
0.1Hz
0.1-0.3Hz
FPW
PI1
25
0.5S
2S
50mS
0.1-1.0S
1-5S
10-310mS
Note
26
25N
1 time
0: no limit
1: 1 time
2: 2 times
3: 3 times
27
WFSI
1200kW
10-9999kW
TAI
2S
0-120S
29
30
31
VT
CT
V
60
50
110V
32
50Hz
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
WRI
WHI
WHI
WMI
WMI
WLI
WLI
M
M
WI
WI
THW
TLW
FC
THF
WRG
WRG
WHG
WHG
WMG
WMG
WLG
600kW
1-9999
1-9999
90-120V
49.0-51.0Hz
59.0-61.0Hz
10-WFSI
90%
20-95%
50%
10-87%
20%
1-50%
10%
5-70%
10%
3-30%
3.0S
0.3S
1.0%
3.0S
0.5-5.0S
0.1-1.0S
0.2-5.0%
0.5-5.0S
28
55
56
57
1500kW
10 - (VTCT)kW
MAX.9999kW
100%
70-100%
80%
50-95%
10%
1-40%
20%
1-40%
WG
WG
2%
1-30%
THQ
3.0S
0.5-5.0S
TLQ
0.3S
0.1-1.0S
60
61
VC
THV
2.0%
3.0S
0.5-5.0%
0.5-5.0S
62
QRG
750kvar
Setting value
reactive power.
58
59
Products List
Products List
50 - (VTCT)kvar
MAX.9999kvar
of
generator
rated
69
70
71
63
64
65
66
67
68
72
73
Initial
value
Sign
control +
control +
generator
frequency,
power factor
voltage
control
control
Note
CHA
30%
10-60%
CTA
10%
1-10%
TS
60S
0-120S
TB
30S
0-60S
TGDL
TADL
2S
2S
WTHI
50%
0-20S
0-20S
50% fixed
value
WTRG
50%
10-70%
WTHG
30%
10-50%
Timer setting.
10%
75
TH
60
76
VTH
10%
77
GAV
78
Parallel
unit no.
1 unit
No.
01
02
03
04
05
06
07
Power
distribution
LAG90%
FTH
Display
Power
distribution
cos
AGC-300
Generator
only
LEAD95-100LAG70%
2-10
74
79
Possible
setting range
Synchronizing control
No.
Parallel
w/incoming
TDSP
10 min.
10% fixed
value
60fixed
value
10% fixed
value
1: ON
2: OFF
1-8 units
1-10 min.
0: continuation
item list
Display description
Bus voltage
Bus frequency
Incoming power
Generator voltage
Generator current
Generator power
Generator reactive power
Unit
V
Hz
kW
V
A
kW
kvar
No.
08
09
10
11
12
13
Display description
Generator power factor
Generator frequency
Voltage difference
Frequency difference
Incoming mean power
Equipment address
Unit
%
Hz
%
Hz
kW
-
Products List
Products List
Input terminal
Bus voltage input (P1)
Bus voltage input (P2)
Generator voltage input (P1)
Generator voltage input (P2)
Generator voltage input (P3)
Generator current input (1S)
Generator current input (1L)
Generator current input (3S)
Generator current input (3L)
Incoming power T/D input (+ )
Incoming power T/D input ()
No.
12
13
14
15
16
17
18
19
20
21
22
10
AGC-300
No.
50
48
46
44
42
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
No.
DI/DO terminal
49
NC
47
Control start
45
Incoming start
43
Synchronizing start
41
Distribution start
39
Cut-in start
37
Forced separation
35
Preceding generator designation
33
Control changeover
31
COM1
29
NC
27
NC
25
NC
23
NC
21
Start command
19
Separation command
17
Light fault
15
COM2
13
AVR increase
11
AVR decrease
9
COM3
7
Governor increase
HIF3 BA-50PA-2.5DS
5
Governor decrease
(Hirose)
3
COM4
1
NC
Conformity connector: HIF3 BA-50D-2.54C
HIF3 BA-50D-2.54R
DI
DO