You are on page 1of 2

PB-18 Input Data

Project Name: BANYU_URIP_PROJECT_REV


Prepared by: wen

11/13/2014
03:43PM

1. General Details:
Air System Name ...................................................................................... PB-18
Equipment Type ........................................................ Packaged Rooftop Units
Air System Type ........................................................................ Dual Duct CAV
Number of zones ............................................................................................... 2
2. System Components:
Ventilation Air Data:
Airflow Control .................................................... Constant Ventilation Airflow
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Unocc. Damper Position ......................................................................... Closed
Damper Leak Rate ............................................................................................ 0 %
Outdoor Air CO2 Level .................................................................................. 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................... 14.4 C
Coil Bypass Factor ..................................................................................... 0.100
Cooling Source ........................................................................... Air-Cooled DX
Schedule ............................................................................... JFMAMJJASOND
Capacity Control ........................................... Constant Temperature - Fan On
Central Heating Data:
Supply Temperature ..................................................................................... 24.0 C
Heating Source .................................................................. Electric Resistance
Schedule ............................................................................... JFMAMJJASOND
Capacity Control ........................................... Constant Temperature - Fan On
Supply Fan Data:
Fan Type ................................................................................. Forward Curved
Configuration ...................................................................................... Blow-thru
Fan Performance .......................................................................................... 700 Pa
Overall Efficiency ............................................................................................ 65 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................. 2 %
Duct Leakage .................................................................................................... 3 %
Return Duct or Plenum Data:
Return Air Via ............................................................................. Ducted Return
3. Zone Components:
Space Assignments:
Zone 1: Zone 1-LER
SUBSTATTION_PB_18
Zone 2: Zone 2-LIR
SUBSTATTION_PB_18_LIR

x1
x1

Thermostats and Zone Data:

Zone

Cooling T-Stat
Occ.
(C)

Cooling T-Stat
Unocc.
(C)

Heating T-Stat
Occ.
(C)

Heating T-Stat T-Stat Throttling


Unocc.
Range
(C)
(C)

Diversity
Factor
(%)

Direct
Exhaust
Airflow
(L/s)

Direct Exhaust
Fan
(kW)

24.0

27.0

21.1

15.6

1.70

100

0.0

0.0

24.0

27.0

19.0

15.6

1.70

100

0.0

0.0

Thermostat Schedule ............................................................................... PB-18


Unoccupied Cooling is ........................................................................ Available
Supply Terminals Data:
Zone
1
2

Terminal Type
CAV mix box
CAV mix box

Hourly Analysis Program v4.50

Min. Airflow
Fan Performance Fan Efficiency
6.00 ACH
6.00 ACH

Design Supply
Temperature
-

Page 1 of 2

PB-18 Input Data


Project Name: BANYU_URIP_PROJECT_REV
Prepared by: wen

11/13/2014
03:43PM

Zone Heating Units:


Zone ............................................................................................................... All
Zone Heating Unit Type ............................................................................. None
Zone Unit Heat Source ...................................................... Electric Resistance
Zone Heating Unit Schedule ................................................. JFMAMJJASOND
4. Sizing Data (Computer-Generated):
System Sizing Data:
Cold Deck Supply Temperature ................................................................... 14.4
Supply Fan Airflow ................................................................................... 5095.2
Ventilation Airflow ....................................................................................... 725.0
Hot Deck Supply Temperature ..................................................................... 24.0

C
L/s
L/s
C

Hydronic Sizing Specifications:


Chilled Water Delta-T ..................................................................................... 5.6 K
Hot Water Delta-T ........................................................................................ 11.1 K
Safety Factors:
Cooling Sensible ............................................................................................. 10 %
Cooling Latent ................................................................................................. 10 %
Heating .............................................................................................................. 0 %
Zone Sizing Data:
Zone Airflow Sizing Method .................................. Sum of space airflow rates
Space Airflow Sizing Method .............................. Individual peak space loads

Zone

Supply Airflow
(L/s)

Zone Htg Unit


(kW)

Reheat Coil
(kW)

4313.6

628.7

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ......................................................................... 102.0
Design OAT .................................................................................................. 35.0
Equipment Sizing ............................................................................. Auto-Sized
Capacity Oversizing Factor ............................................................................... 0
ARI Performance Rating .............................................................................. 2.96
Conventional Cutoff OAT ............................................................................. 12.8
Low Temperature Operation ................................................................ Not used

Hourly Analysis Program v4.50

kW
C
%
EER
C

Page 2 of 2