Professional Documents
Culture Documents
U(t)
or
ct
Ve hift
S
1. Introduction
The problem of islanding happens when a part of the
distribution network is disconnected from the rest of the
system but the distributed generators keep feeding the
islanded part of the network. This situation involves
several problems, for the equipment and for the personnel
safety also, so, it is common practice to disconnect all
distributed generators to minimize the risks associated to
the islanding situation.
The methods to detect the islanding situation can be
classified into active and passive [1]. The paper deals
with one of the most popular passive methods used to
determinate that the islanding has happened, the so called
vector shift, vector jump or vector surge relay.
The principle of operation of the vector shift relay is
quite simple [2]. During normal operation, the terminal
voltage of an embedded synchronous generator lags the
synchronous electromotive force by an angle . If the
grid supply is suddenly disconnected from the section of
the network partially supplied by the embedded
generator, the load on the generator increases or
decreases and this causes a shift in the rotor displacement
angle. The terminal voltage jumps to a new value and the
phase position changes as shown in figure 1.
T
T
T
Fig 1- Vector Shift and variation in the wave period
T 'T
T
(1)
T2
VS2
U(t)
R
or
ct 2
Ve ift
Sh
U(t)
VS1
or
ct 1
Ve ift
Sh
T3
T1
360
T 'Taverage
Taverage
4. Simulated model.
22
20
VS
Relay
2MVA
0.69kV
Yg/
0.69/13,8kV
230kV
100MVA
Yg/
13,8/230kV
Line
GS
18
16
14
Perfect Island
12
10
8
6
4
2
0
0
wref
Pref
Vabc (pu)
Pm
we
Pm
Pe0
gate
dw
Vf _
HTG
1
A
1
Iabc (pu)
v ref
Vabc
a
Synchronous Machine
2 MVA 0.69 kV
vd
100MVA, 230 kV
source
A
Vf
vq
v stab
Excitation
System
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1.3
1.4
1.5
1.6
1.7
1.8
1.9
0.1
Discrete,
Ts = 2.083e-006 s.
Potencia
(MW/Scc)
-20/28
-10/28
-5/28
-2/28
+2/28
+5/28
+10/28
+20/28
Potencia(pu Scc
PCC)
-20%
-10%
-5%
-2%
+2%
+5%
+10%
+20%
Salto Vector
22.69
14.45
7.77
3.20
3.22
7.81
14.54
23.91
7. Conclusions.
The designed algorithm for vector shift, measures with
precision the pure vector shifts and the zero crossing
ones. Also measures the value of the vector shift to
enable changes in the settings if needed, with criteria of
the vector shift measured by the unit. In the other hand,
the unit is relaying as it does not act against faults and
trips properly in the openings of the breakers caused by
faults. The effect of the connection and disconnection of
the loads and the inaccurate tripping in the abrupt
changes in the loads in weak systems and for loads that
are next to the source is not sorted out, but this is a
problem inherent to the philosophy of operation of the
vector shift.
8. Acknowledgements
This study has been done as a part of the PROINVER
project which is financed by Spanish Ministry of Science
and Innovation (INNPACTO program).
9. References.
[1] "The Impact of Renewable Energy Sources and
Distributed Generation on Substation Protection
and Automation". CIGRE WG B5.34. August
2010.
[2] N. Jenkins, R. Allan, P. Crossley, D. Kirschen, and
G. Strbac, "Embedded Generation", 1st ed.
London, U.K.: Inst. Elect. Eng., 2000.
[3] Crompton Instruments, "Vector Shift and ROCOF
Relay Instruction Manual".
[4] AREVA, "MICOM P341 Relay Instruction Manual
P341"