Professional Documents
Culture Documents
2010
Class 0613
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Masterpact Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3
Micrologic Electronic Trip Systems . . . . . . . . . . . . . . . . . . . . . . . Page 17
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 33
Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 62
Masterpact NT Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . Page 68
Masterpact NW Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . Page 97
Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 153
Trip Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 168
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
3
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Introduction
Masterpact NT/NW Universal Power Circuit Breakers are designed to
protect electrical systems from damage caused by overloads, short
circuits and equipment ground faults. All Masterpact circuit breakers
are designed to open and close a circuit manually, and to open the
circuit automatically at a predetermined overcurrent setting.
Masterpact circuit breakers can also:
8001600 A Masterpact NT
Drawout Circuit Breaker
06133469
06133468
Figure 1:
NX 08
HA10 12kV
Uimp
Ui 1000V
Ue (V)
690
50kA/1
s
50/60Hz
AS
947-2
UNE
IEC
BS CEI
EN 60947-2
VDE
UTE
NBMA
Insulated Case
Circuit Breaker
IEC Rated
Circuit Breaker
ANSI C37.13
IEC 68-2-1: Dry cold at 55C
ANSI C37.16
ANSI C37.17
NEMA AB1
IEC 60947-2
ANSI C37.50
IEC 60947-3
NMX J-266-ANCE
NEMA SG3
NOTE: Throughout this document, the phrase ANSI Certified means the product meets the requirements
of UL 1066 and ANSI C37. When UL Listed appears, the product meets the requirements of UL 489.
The 8002000 A ANSI Low Voltage Power Circuit Breakers type L1F and Insulated Case Circuit
Breaker type LF are tested to show the arc flash hazard risk category as referenced by NFPA 70E.
Circuit breakers should be applied according to guidelines detailed in the National Electrical Code
(NEC) and other local wiring codes.
Masterpact circuit breakers are available in Square D or Schneider Electric brands.
UL File Numbers:
4
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
5
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Figure 2:
Door Escutcheon
06133341
06133339
T TEST
Racking Mechanism
Disconnected
Position
Drawout Mechanism: The drawout assembly mechanism allows the circuit breaker to be racked in
four positions (connected, test, disconnected, or withdrawn), as shown in the figure below.
NOTE: For UL/ANSI circuit breakers, the clusters are mounted on the circuit breaker; for IEC circuit
breakers, the clusters are mounted on the cradle.
Figure 3:
Racking Positions
06133830
Secondary
Contacts
Stabs (IEC)
Clusters (UL/ANSI)
Clusters (IEC)
Stabs (UL/ANSI)
T TEST
Connected Position
TTEST
06133339
Test Position
TTEST
Disconnected Position
Withdrawn Position
6
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
06133470
Arc Chamber
06133185a
Good
Contacts
Worn
Contacts
Operating Conditions
Masterpact circuit breakers are suited for use:
Masterpact circuit breakers have been tested for operation in industrial atmospheres. It is
recommended that the equipment be cooled or heated to the proper operating temperature and kept
free of excessive vibration and dust. Operation at temperatures above 104F (40C) may require
derating or overbussing the circuit breaker. See the appropriate instruction bulletin and page 15 of this
catalog for additional information.
Masterpact circuit breakers meet IEC 68-2-6 Standards for vibration.
The materials used in Masterpact NT and NW circuit breakers will not support the growth of fungus and
mold.
Masterpact circuit breakers have been tested to the following:
Storage Temperature
Circuit breakers with trip units without LCD displays may be stored in the original packaging at
temperatures between -58F (-50C) and 185F (85C). For circuit breakers with trip units with LCD
displays, this range is -40F (-40C) to 185F (85C).
7
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Auxiliary Control
Connection
Lifting Tab
Cluster
Circuit Breaker
Communication Module
Accessory Cover
Operation Counter
Overcurrent Trip
Switch (SDE1)
Trip Unit
Open/Close Push
Button Cover
(lockable with padlock)
Electrical Close
Push Button (BPFE)
ET
RES
Padlock Attachment
Faceplate
Key Interlock
Charged/Discharged
Indicator
Open/Close
Indicator
8
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Racking Handle
9
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Padlock Provision
Position Indicator
Racking Handle Insertion Opening
Stop Release Button
Racking Handle Storage Space
Accessory Cover
Charging Handle
Extension Rail Handle
Lifting Tab
NT Cradle
Fault Trip
Reset Button
"Push-to-close" Button
"Push-to-open" Button
Trip Unit
Faceplate
Accessory Cover
Charging Handle
Lifting Tab
"Push-to-close" Button
Fault Trip
Reset Button
"Push-to-open" Button
Trip Unit
Faceplate
10
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Ratings
Table 1:
Frame Rating
800/1600 A
N1
H1
H2
H3
65
85
100 200
200
65
85
100 200
65
85
85
65
85
42
3200/4000 A1
2000 A
L12, 3 L1F3 H1
L12, 3 L1F3 H1
H3
L12, 3 H2
H3
L12, 3
65
85
100
200
85
100
200
200
65
85
100
200
85
100
200
130
130
65
85
85
130
85
85
130
85
30
22
65
85
85
100
85
85
100
85
35
24
85
117
117
65
40
40
25
22
65
40
40
40
85
75
40
Yes
H3
65
85
100 200
200
200
65
85
100 200
130
130
65
85
85
85
30
22
65
85
85
354
24
65
40
40
25
22
Yes
Breaking Time
Closing Time
70 ms
100800 A
Sensor Rating
8001600 A
4000/5000/6000 A
H2
H2
10002000 A
16004000 A
20004000 A
25005000 A
30006000 A
Mechanical
12,500
10,000
10,000
5000
5000
Electrical
2800
1000
1000
1000
1000
4000 A standard width circuit breaker is not available in L1 interrupting rating code or drawout construction (fixed mounting only) (see dimensions on page 109).
Interrupting ratings (kAIR) at 50 Hz: 200 kA (254 Vac), 150 kA (508 Vac), 100 kA (635 Vac).
The interrupting ratings L1 and L1F are available only in 3P, drawout construction.
24 kA for 800 A circuit breaker frame with 100 A or 250 A sensor.
Table 2:
Frame Rating
800 A
1600 A
2000 A
3200 A
4000 A
5000 A
HA
HA
HA
HA
HA
HA
254 Vac
65
65
65
65
85
85
508 Vac
65
65
65
65
85
85
635 Vac
65
65
65
65
85
85
65
65
65
65
85
85
Table 3:
Frame Rating
800 A
HF
HC
HF
HC
HF
HC
HF
HC
HF
HC
HF
HC
254 Vac
100
200
100
200
100
200
100
200
100
200
100
200
508 Vac
100
200
100
200
100
200
100
200
100
200
100
200
635 Vac
85
130
85
130
85
130
85
130
85
130
85
130
85
30
85
30
85
30
85
100
85
100
85
100
1600 A
2000 A
3200 A
4000 A
5000 A
11
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Frame Rating
800/1200/1600/2000 A
2500/3000 A
4000/5000/6000 A
LF
100
200
200
100
200
100
200
100
150
150
100
150
100
150
85
100
100
85
100
85
100
421
651
301, 2
22
65
65
85
100
40
40
351, 2
24
65
65
75
75
ac 50/60 Hz, 1 s
40
40
253
22
40
40
40
40
Yes
Breaking Time
Closing Time
70 ms
Sensor Rating
ac 50/60 Hz
12002500 A /
16003000 A
20004000 A /
25005000 A /
30006000 A
Mechanical
12,5004
12,5004
12,5004
12,5004
10,000
10,000
5000
5000
(with no maintenance)
Electrical
28004
28004
28004
28004
1000
1000
1000
1000
65 kA for 2000 A.
40 kA for 2000 A.
The endurance rating for 2000 A, N/H/L/LF is 10,000 for mechanical and 1000 for electrical.
Table 5:
Frame Rating
800 A
1200 A
1600 A
2000 A
2500 A
3000 A
4000 A
5000 A
6000 A
HF
HB
HF
HB
HF
HB
HF
HB
HF
HB
HF
HB
HF
HB
HF
HB
HF
HB
240
100
200
100
200
100
200
100
200
100
200
100
200
100
200
100
200
100
200
480
100
150
100
150
100
150
100
150
100
150
100
150
100
150
100
150
100
150
600
85
100
85
100
85
100
85
100
85
100
85
100
85
100
85
100
85
100
40
35
40
35
40
35
40
35
65
65
65
65
75
75
75
75
75
75
Withstand Ratings1
(kA) Vac, 50/60 Hz
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit breaker with an equal continuous
current rating.
12
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Frame Rating
800/1000/1250/1600 A
N1
H1
H2
L1
H10
H1
H2
H3
L1
H10
H1
H2
H3
H10
H1
H2
220/415 Vac
42
65
100
150
65
100
150
150
65
100
150
100
150
440 Vac
42
65
100
150
65
100
150
150
65
100
150
100
150
525 Vac
42
65
85
130
65
85
130
130
65
85
130
100
130
690 Vac
42
65
85
100
65
85
100
100
65
85
100
100
100
1150 Vac
50
50
50
%Icu
100
100% 100% 100% 100% 100% 100% 100% 100%
%
100
%
100
%
100
%
100
%
100
%
100%
100%
Ultimate
Breaking
Capacity (kA)
50/60 Hz
Icu
Service Breaking
Ics
Capacity
Short-Time
Withstand
Current
(kA)
2000 A
2500/3200/4000 A
4000B/5000/6300 A
65
85
30
50
65
85
65
30
50
65
85
65
50
100
100
36
50
30
50
36
75
65
30
50
65
75
65
50
100
100
851
351
85
65
35
85
65
117
220/415 Vac
38
62
96
143
62
96
143
143
62
96
143
96
143
440 Vac
38
62
96
143
62
96
143
143
62
96
143
96
143
525 Vac
38
62
81
124
62
81
124
124
62
81
124
81
124
690 Vac
38
62
81
96
62
81
96
96
62
81
96
81
96
1150 Vac
46
46
46
Break Time
ms
25
25
25
25
Closing Time
ms
< 70
< 70
< 70
< 80
Mechanical
12.5
10
10
Electrical 440 V
10
10
10
1.25
1.5
1.5
Electrical 1150 V
0.5
0.5
0.5
Icw
Endurance Rating
(with no maint.)
C/O Cycles x 1000
1
Table 7:
Frame Rating
800/1000/1250/1600 A
2500/3200/4000 A
4000B/5000/6300 A
NA
HA
HF
HA10
HA
HF
HA10
HA
HF
HA10
HA
46
81
46
81
53
81
81
38
46
81
46
81
53
81
81
46
81
46
81
53
81
81
46
46
53
46
Icw
42
50
85
50
50
85
50
50
85
50
85
Icu
42
50
85
50
50
85
50
50
85
50
85
Icm
2000 A
13
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Frame Rating
800 A
N1
254 Vac 60 Hz
42
508 Vac 60 Hz
42
635 Vac 60 Hz
N/A
ac 60 Hz, 0.5 s
42
ac 60 Hz
40
Breaking Time
25 to 30 ms (with no
intentional time delay)
Closing Time
< 50 ms
Sensor Rating
Mechanical
12,500
(with no maintenance)
Electrical
2800
Table 9:
Frame Rating
800 A
NA
42
254/508/635 Vac, 60 Hz
42/42/NA
Table 10:
Frame Rating
800 A
L1
LF
L1
LF
L1
240 Vac, 60 Hz
50
65
100
200
200
50
65
100
200
200
50
65
100
200
480 Vac, 60 Hz
50
50
65
100
100
50
50
65
100
100
50
50
65
100
600 Vac, 60 Hz
35
50
N/A
N/A
N/A
35
50
N/A
N/A
N/A
35
50
N/A
N/A
ac 60 Hz, 0.5 s
35
35
10
10
10
35
35
10
10
10
35
35
10
10
40
40
10
10
10
40
40
10
10
10
40
40
10
10
25
25
10
10
10
25
25
10
10
10
25
25
10
10
Yes
Yes
ac 60 Hz
1200 A
Breaking Time
9 ms for L and LF
Closing Time
< 50 ms
Sensor Rating
100250 A / 400800 A
Mechanical
(with no maintenance)
Electrical
6001200 A
8001600 A
12,500
2800
Fixed-mounted only. 1600 A UL489 drawout circuit breakers are not available.
Table 11:
Frame Rating
800 A
HF
HB
HF
HB
HF
HB
240
65
200
65
200
65
200
480
50
100
50
100
50
100
600
50
NA
50
NA
50
NA
40
10
40
10
40
10
1200 A
1600 A
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected by a circuit breaker with an equal continuous
current rating.
14
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Frame Rating
800/1000 A
H1
H2
L1
H1
H2
42
50
150
42
50
42
50
130
42
50
42
42
100
42
42
42
42
25
42
42
Icu
1250/1600 A
Ics
%Icu
100%
100%
100%
100%
100%
Icw
42
36
101
42
36
102
38
45
143
38
45
38
45
124
38
45
38
38
96
38
38
38
38
23
38
38
Break Time
ms
25
25
25
25
Closing Time
ms
50
50
50
50
50
Mechanical
12,500
12,500
12,500
12,500
12,500
Electrical 440 V
6000
6000
3000
60003
60003
Electrical 1000 V
Icm
SELLIM system
Table 13:
Frame Rating
800/1000 A
HA
HA
33
33
33
33
33
33
Icw
42
42
Icu
35
35
Icm
1250/1600 A
Correction Factors
Table 14:
140
122
104
86
77
68
50
32
14
22
60
50
40
30
25
20
10
10
20
30
Current
0.83
0.92
1.00
1.07
1.11
1.14
1.21
1.27
1.33
1.39
1.44
Table 15:
Altitude Correction Factors per ANSI C37.20.1 par. 7.1.4.1 (Table 10)
< 6600 ft. (2000 m)
8500 ft (2600 m)
Voltage
1.00
0.95
0.80
Current
1.00
0.99
0.96
15
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Shipping Weights
Table 16:
1
Circuit Breaker Rating Circuit Breaker (lb/kg) Cradle (lb/kg)
(A)
3P
4P
3P
4P
3P
4P
800
FCF
42/19
55/25
17/8
265/121
320/151
FCT
84/38
109/50
17/8
307/140
384/176
2000
RCTH or RCTV
17/8
22/10
17/8
240/110
297/136
2500
FCT
80/36
104/47
17/8
348/159
435/198
RCTH or RCTV
26/12
34/15
17/8
294/135
365/166
RCOV
100/46
130/59
368/169
461/210
1600
109/50
3000
142/65
97/44
116/53
127/58
165/75
124/57
149/68
127/58
165/75
124/57
149/68
227/103
4000
295/134
278/126
334/152
5000
227/103
295/134
278/126
334/152
6000
227/103
295/134
278/126
334/152
17/8
RCOV (special)
115/52
145/66
259/118
327/149
FCF
84/38
109/50
39/18
628/285
777/354
FCT
168/77
218/99
39/18
712/324
886/403
RCTH or RCTV
52/24
68/31
39/18
596/271
736/335
FCT
168/77
218/99
39/18
712/324
886/403
RCTH or RCTV
52/24
68/31
39/18
596/271
736/335
RCTH or RCTV
396/180
528/240
39/18
940/427
1196/544
Table 17:
Circuit Breaker
Rating (A)
800
1000, 1250, 1600, 2000
2500
3200
3P
Type
3P
4P
FCF
42/19
55/25
17/8
265/121
320/145
RCTH or RCTV
17/8
22/10
17/8
240/110
287/131
FCF
42/19
55/25
17/8
310/142
386/175
RCTH or RCTV
17/8
22/10
17/8
285/131
353/161
4P
3P
4P
109/50
132/60
97/44
116/53
127/58
165/75
124/57
149/68
Pallet
(lb/kg)
4P
4000
127/58
165/75
124/57
149/68
RCTH or RCTV
42/19
55/25
17/8
310/142
386/176
5000, 6300
227/103
295/134
278/126
334/152
RCTH or RCTV
52/24
68/31
39/18
596/271
736/335
Table 18:
Circuit Breaker
Rating (A)
800
1200
16002
Cradle (lb/kg)
3P
3P
Type
3P
4P
FCF
15/7
20/9
10/5
101/46
125/58
RCTH or RCTV
6/3
8/4
10/5
92/42
113/53
RCTV
18/8
20/9
10/5
68/31
82/38
Pallet
(lb/kg)
4P
40/18
52/24
36/16
43/20
40/18
52/24
N/A
N/A
Table 19:
4P
4P
1
Circuit Breaker Circuit Breaker (lb/kg) Cradle (lb/kg)
Rating (A)
3P
4P
3P
4P
800
1000, 1250, 1600
1
Pallet
(lb/kg)
35/16
46/21
31/14
37/17
3P
FCF
15/7
4P
3P
4P
20/9
10/5
91/41
113/52
8/4
10/5
82/38
101/47
16
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
17
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Model
LS0
LI
LSI
LSIG
Long-Time +
Short-Time +
Zero Delay
Long-Time +
Instantaneous
Protection
Long-Time + Short-Time
Long-Time + Short-Time
+ Instantaneous
+ Instantaneous
Protection + Equipment
Protection
Ground-Fault Protection
(IEC Rated)
2.0
2.0A
3.0
3.0A
5.0
5.0A
5.0P
5.0H
6.0A
6.0P
6.0H
All Masterpact circuit breakers are equipped with the Micrologic trip system to protect power circuits
and loads. Micrologic trip systems use a set of current transformers (called CTs or sensors) to sense
current, a trip unit to evaluate the current, and a tripping solenoid to trip the circuit breaker. Adjustable
rotary switches on the trip unit allow the user to set the proper overcurrent or equipment ground-fault
current protection required in the electrical system. If current exceeds a set value for longer than its set
time delay, the trip system opens the circuit breaker. Alarms may be programmed for remote
indications. Measurements of current, voltage, frequency, power, and power quality optimize continuity
of service and energy management. Micrologic trip units can be changed on-site.
Integration of protection functions in the Application Specific Integrated Circuit (ASIC) electronic
component used in all Micrologic trip units guarantees a high degree of reliability and immunity to
conducted or radiated disturbances. On Micrologic P and H trip units, advanced functions are
managed by an independent microprocessor.
Masterpact circuit breakers are shipped with the long-time pickup switch set at 1.0 and all other trip unit
adjustments set at their lowest settings. Actual settings required for a specific application must be
determined by a qualified consultant or plant engineer. A coordination study is recommended to
provide coordination between all circuit breakers in the distribution system.
Figure 5:
Thermal Imaging
The thermal imaging function protects the cables or bus bars from overheating in case of low
amplitude repetitive faults. Such overheating can be due to repetitive motor starting, fluctuating load,
intermittent ground faults, or subsequent closing after a fault.
Traditional electronic protection does not protect against repetitive faults because the duration of each
overload above the pickup setting is too short to achieve effective tripping. Nevertheless, each
overload involves a temperature rise in the installation, the cumulative effect of which could lead to
overheating of the system.
The thermal imaging function remembers and integrates the thermal heating caused by each pickup
setting overrun. Before tripping, the integrated heating value will reduce the associated time delay and,
therefore, the reaction of the trip unit will be closer to the real heating of the power network system.
After tripping, the function will also reduce the time delay when closing the circuit breaker on an
overload.
18
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Sensor Plug
Value (In)
Minimum
GroundFault
Pickup
100250 A
30% of
sensor
rating
4001200 A
20% of
sensor
rating
16006300 A
500 A
Ground-fault push-to-trip button works for testing ground fault with current flow on one phase
greater than or equal to the values shown in the following table.
Ammeter and bar graph displays are functional with or without current flowing through the circuit
breaker
Trip settings and (Max) current readings can be accessed on the display by pressing navigation
button with or without current flowing through the circuit breaker
Ground-fault push-to-trip button works for testing ground fault with or without current flowing
through the circuit breaker
Optional Modbus communicationsAlso requires a separate 24 Vdc power supply for the circuit
breaker communications module
NOTE: Ground-fault push-to-trip button will also be functional if a hand-held test kit or full-function test
kit is powering the trip unit.
Power (P) and Harmonic (H) Trip Unit Without 24 Vdc Power Supply at F1 and F2
The P and H trip units were designed to be used with the external 24 Vdc power supply. The large LCD
display requires too much current to be powered by current flow through the circuit breaker. The P and
H trip units do have a voltage power supply which will power the trip unit with 100 Vac or more between
two phases or phase to neutral. The standard configuration for the voltage probes inside the circuit
breaker is at the bottom connections. If the circuit breaker was open in a top fed application, there
would be no voltage at the bottom of the circuit breaker and the trip unit would not be powered.
NOTE: Ground-fault push-to-trip button works for testing ground fault if the trip unit is powered by the
voltage power supply. The ground-fault push-to-trip is also functional if a hand-held test kit or fullfunction test kit is powering the trip unit.
Power (P) and Harmonic (H) Trip Unit With 24 Vdc Power Supply at F1 and F2
Modbus communicationsAlso requires a separate 24 Vdc power supply for the circuit breaker
communications module.
NOTE: Ground-fault push-to-trip button will also be functional if hand-held test kit or full-function test kit
is powering the trip unit.
19
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Micrologic 3.0A
t= In=
tsd= tr=
Isd=
Ii= Ir=
Ig=
tg=
Micrologic 5.0A
t= In=
tsd= tr=
Isd=
Ii= Ir=
Ig=
tg=
MAX
s
kA
Ir
.7
.6
.5
.4
.8
x In
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
Ir
.7
.6
.5
.4
@6 Ir
instantaneous
x In
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
3 4 5
2.5
6
2
8
1.5
10
x Ir
40 %
40 %
40 %
.7
.6
.5
.4
@ 6 Ir
instantaneous
test
setting
tsd
(s)
.
.
Ii
. . .
on
.
.
I2t
0
off
4
3
6 8 10
12
15
2
off
x In
delay
test
s
kA
100 %
Ir
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
short
Ii
setting
.8
t= In=
tsd= tr=
Isd=
Ii= Ir=
Ig=
tg=
MAX
100 %
.8
x In
Ir
alarm
.7
.6
.5
.4
@ 6 Ir
x In
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
3 4 5
2.5
6
2
8
1.5
10
x Ir
test
setting
Ir
alarm
.7
.6
.5
.4
@ 6 Ir
instantaneous
short
instantaneous
Im
setting
.8
s
kA
long time
long time
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
MAX
menu
menu
long time
long time
alarm
Micrologic 6.0A
100 %
menu
long time
06133481
Micrologic 5.0
06133478
Micrologic 3.0
06133477
06133787
06133332
tsd
(s)
.
.
. . .
on
.
.
0
I2t off
delay
Ii
4
5
3
2.5
6
2
8
1.5
10
x In
.8
x In
@ 6 Ir
instantaneous
short
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
tsd
.4 .4 .3
.2
.3
.1
.2
0
.1
Ig
D
C
B
A
Ii
(s)
on
setting
test
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
I2t
off
delay
4
3
6 8 10
12
15
off
x In
test
tg
.4 .4 .3
.2
.3
.1
.2
0
.1
(s)
G
H
J
on
I2t
off
ground fault
20
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Feature
2.0
Ammeter
3.0
LI
5.0
2.0A
LS0
Power
3.0A
5.0A
6.0A
Harmonics
5.0P
6.0P
5.0H
6.0H
LSI
LSIG/Ground-Fault Trip1
Digital Ammeter
Neutral Protection1
Power Measurement
Waveform Capture
UL Listed
Thermal Imaging
Phase-Loading Bar Graph
LED for Long-Time Pick-Up
Zone-Selective Interlocking3
Communications
Micrologic 5.0P
Micrologic 6.0P
I(A)
I(A)
Trip
Trip
5000A
24s
5000A
24s
30kA
0.4s
85kA
30kA
0.4s
85kA
long time
Ir
.7
.6
.5
.4
.8
x In
alarm
Ir
.7
.6
.5
.4
@ 6 Ir
instantaneous
short
setting
Micrologic 5.0H
tsd
(s)
.
.
Ii
. . .3
on
.
.
0
I2t off
delay
4
3
6 8 10
12
15
off
2
x In
x In
tsd
(s)
.
.
D
C
B
A
Ii
. .4 .
on
setting
Ig
.7
.6
.5
.4
instantaneous
short
test
Ir
alarm
@ 6 Ir
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
.
.
0
I2t off
delay
tg
(s)
G
H
J
(A)
I
(V)
V
(kW)
P
E (kWh)
Harmonics
long time
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
Micrologic 6.0H
(A)
I
(V)
V
(kW)
P
E (kWh)
Harmonics
long time
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
06133479
06133483
06133480
06133482
.
.
on
x In
long time
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
setting
Ir
.7
.6
.5
.4
@ 6 Ir
instantaneous
short
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
alarm
tsd
.4 .4 .3
.2
.3
.1
.2
0
.1
Ii
(s)
on
I2t
delay
off
4
3
6 8 10
12
15
off
2
x In
0
off
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
@ 6 Ir
instantaneous
short
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
tsd
.4 .4 .3
.2
.3
.1
.2
0
.1
(s)
on
setting
test
Ig
.
.
I2t
6 8 10
12
15
off
2
x In
test
. . .3
ground fault
4
3
.8
D
C
B
A
I2t
off
delay
Ii
4
3
6 8 10
12
15
off
2
x In
test
tg
.4 .4 .3
.2
.3
.1
.2
0
.1
(s)
G
H
J
on
I2t
off
ground fault
21
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Protection Settings
long time
Ir
x In
tr
(s) 4
.9
.95 2
.98 1
1
.5
@6 Ir
alarm
12
16
20
24
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
setting
Protection thresholds and delays are set using the rotary switches.
A full-range of long-time settings are available via field-installable
adjustable rating plugs.
Overload protection
instantan
short time
4Instantaneous pickup
.7
.6
.5
.4
.8
tsd
(s)
Ii
. 4 . 4 .3
.2
.1
.3
.2
.1
4
3
0 2
off
I t
on
6 8 1
o
x In
delay
Short-circuit protection.
Short-time RMS
6Test connector
Instantaneous protection.
Neutral protection on four-pole circuit breakers.
06133322
Table 21:
t
Ir
tr
Ii
0
Ir = ln x...
2.0:
0.40
0.50
0.60
0.70
0.80
0.90
0.95
0.98
1.00
3.0:
0.40
0.45
0.50
0.60
0.63
0.70
0.80
0.90
1.00
12.5
25
50
100
200
300
400
500
tr at 6 x Ir
0.5
12
16
20
24
tr at 7.2 x Ir
0.34
0.69
1.38
2.7
5.5
8.3
11
13.8
16.6
Thermal Imaging
600
Accuracy: 10%
Isd = Ir x...
2.0:
1.5
2.5
10
Ii = In x...
3.0:
1.5
10
12
No Delay
Instantaneous Current Setting (A)
Protection
Accuracy: 10%
06133323
Table 22:
t
Ir
tr
Long-Time
Protection
lsd
tsd
li
0.40
0.50
0.60
0.70
0.80
0.90
0.95
0.98
1.00
UL/ANSI: 0.40
0.45
0.50
0.60
0.63
0.70
0.80
0.90
1.00
12.5
25
50
100
200
300
400
500
tr at 6 x Ir
0.5
12
16
20
24
tr at 7.2 x Ir
0.34
0.69
1.38
2.7
5.5
8.3
11
13.8
16.6
10
10
12
15
off
Thermal Imaging
Ir = ln x...
600
tsd
Ii = In x...
1.5
I2t OFF
2.5
0.1
0.2
0.3
0.4
I2t ON
0.1
0.2
0.3
0.4
Min. trip
20
time (ms)
80
140
230
350
Max. trip
80
time (ms)
140
200
320
500
22
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Micrologic 2.0A, 3.0A, 5.0A, & 6.0A Trip Units with Ammeter
Micrologic A trip units protect power circuits and provide current measurements, overload protection,
and short-circuit protection. In addition, the 6.0A trip units also provide ground-fault protection for
equipment.
06133254
Protection Settings
Micrologic 6.0 A
6
2Indication of tripping
cause
t= In=
tsd= tr=
Isd=
Ii= Ir=
Ig=
tg=
3Digital display
MAX
s
kA
7
Protection thresholds and delays are set using the rotary switches. The
selected values are momentarily displayed in amperes and in seconds.
A full-range of long-time settings are available via field-installable rating
plug.
100 %
40 %
menu
Instantaneous protection.
Ir
10Instantaneous pickup
3
11Electronic push-to-trip
.7
.6
.5
.4
tr
.8
.9
.95
.98
1
x In
(s) 4
2
1
.5
12
16
20
24
Isd
4
5
3
2.5
6
2
8
1.5 10
x Ir
instantaneous
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
Ig
D
C
B
A
Ii
(s)
on I t off
setting
13Test connector
4
3
6 8 10
12
15
off
2
x In
delay
tg
F
G
H
J
11
12
.2
.1
0
on I t off
13
.3
.2
.1
test
.4 .4 .3
(s)
10
@ 6 Ir
short time
alarm
ground fault
Ammeter Measurements
Micrologic A trip units measure the true RMS value of currents. They provide continuous current
measurement from 0.2 to 20 x In with an accuracy of 1.5% (including sensors). No auxiliary source is
needed where I > 0.2 x In. The optional external power supply (24 Vdc) makes it possible to display
currents where I < 0.2 x In and to store values of the interrupted current. A digital LCD screen
continuously displays the most heavily loaded phase (Imax) or displays the Ia, Ib, Ic, Ig, and (on 4P circuit
breakers only) In stored current and setting values by successively pressing the navigation button.
Communication Network
Four wire Modbus, RTU, RS485
In conjunction with an optional communication network, the trip unit transmits the following parameters:
Setting values.
All ammeter measurements.
Tripping causes.
NOTE: Current-based protection functions require no auxiliary power source. When an external power
supply is added, the value of the interrupted current is stored by the trip unit. The reset button resets
alarms, and stored interrupted current indications.
23
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
06133324
Table 23:
t
Ir
Long-Time
Protection
tr
Ii
Short-Time
Protection
06133325
Table 24:
Ir
tr
Long-Time
Protection
lsd
tsd
li
Short-Time
Protection
0.70
0.80
0.90
0.95
0.98
1.00
0.50
0.60
0.63
0.70
0.80
0.90
1.00
12.5
25
50
100
200
300
400
500
tr at 6 x Ir
0.5
12
16
20
24
tr at 7.2 x Ir
0.34
0.69
1.38
2.7
5.5
8.3
11
13.8
16.6
Table 25:
Isd = Ir x...
2.0A: 1.5
2.5
10
Ii = In x...
3.0A: 1.5
10
12
IEC:
Ir = ln x...
0.40
0.50
0.60
0.70
0.80
0.90
0.95
0.98
1.00
UL/ANSI: 0.40
0.45
0.50
0.60
0.63
0.70
0.80
0.90
1.00
12.5
25
50
100
200
300
400
500
600
tr at 6 x Ir
0.5
12
16
20
24
tr at 7.2 x Ir
0.34
0.69
1.38
2.7
5.5
8.3
11
13.8
16.6
10
10
12
15
off
lg
I2t off
Settings
Time Delay (s)
at 10 x Ir
tsd
1.5
I2t OFF
2.5
0.1
0.2
0.3
0.4
I2t ON
0.1
0.2
0.3
0.4
Min. trip
20
time (ms)
80
140
230
350
Max. trip
80
time (ms)
140
200
320
500
Ii = In x...
t
I2t on
600
Settings
06133326
0.60
0.45
Thermal Imaging
0.50
3.0A: 0.40
tg
2.0A: 0.40
Thermal Imaging
Ir = ln x...
tg
Ig = ln x...
ln d 400 A
0.3
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
ln > 1200 A
500
640
720
800
880
960
I2t OFF
I2t ON
Minimum Trip Time (ms)
20
0.1
0.2
0.3
0.4
0.1
0.2
0.3
0.4
80
140
230
350
140
200
320
500
24
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
06133255
Micrologic 6.0 P
1
2
I(A)
4Measurement display
Trip
5Maintenance indicators
5000A
24s
6Protection settings
30kA
0.4s
85kA
7Navigation buttons
The adjustable protection functions of the 5.0P and 6.0P trip units
are identical to those of Micrologic A trip unit (overloads, short
circuits, equipment ground-fault protection); see page 23.
4
5
10Long-time current
setting and tripping delay
6
7
long time
Ir
.7
.6
.5
.4
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
@ 6 Ir
instantaneous
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
14Electronic push-to-trip
15Ground-fault pickup and
tripping delay
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
Ig
D
C
B
A
16Test connector
Ii
(s)
on
setting
I t
off
delay
4
3
6 8 10
12
15
off
2
x In
test
tg
F
G
H
J
. 4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
I t
OFF
9
10
off
11
12
13
14
15
16
ground fault
Maintenance Record
The maintenance record can be consulted using the full-function test kit or remotely via the
communication network. It can be used as an aid in troubleshooting and to assist scheduling for device
maintenance operations.
Recorded indications include:
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
06133327
Table 26:
t
Ir
tr
Long-Time
(RMS)
Protection
Isd
IDMTL
tsd
Ir
Isd
Ii
IDMTL Setting
IEC:
UL/ANSI:
Ii
0
Ir = ln x...
Ir = ln x...
tr at 1.5 x Ir
12.5 25
50
100
200
300
400
500
600
tr at 6 x Ir
0.5
12
16
20
24
tr at 7.2 x Ir
5.5
8.3
11
13.8 16.6
Curve
slope
SIT
EIT
Thermal Imaging
lsd = Ir x...
Settings
Time Delay (s)
at 10 x Ir
tsd
06133326
Table 27:
I2t on
2
tg
I t off
Settings
tg
Table 28:
Current
Power
Frequency
Phase
1.5
I2t OFF
I2t ON
2.5
0.1
0.2
0.3
0.4
0.1
0.2
0.3
0.4
80
140
230
350
140
200
320
500
Ii = In x...
DT
10
10
12
15
off
Ig = ln x...
ln d 400 A
0.3
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
960
ln > 1200 A
500
640
720
800
880
I2t OFF
0.1
0.2
0.3
0.4
0.4
I2t ON
0.1
0.2
0.3
20
80
140
230
350
80
140
200
320
500
Settings for Alarms for Other Protection Functions for Micrologic 5.0P and 6.0P
Trip Units
Current Imbalance
Maximum Current
Voltage Imbalance
Voltage
HV Fuse
t
lg
VIT
Threshold
Time Delay
1 to 40 s
0.2 to 1.0 x In
15 to 1500 s
0.02 to 0.3 x Vn
1 to 40 s
0.25 to 0.5 s
Minimum Voltage
Vmin
Maximum Voltage
Vmax
0.20 to 5.0 s
Maximum Power
Pmax
5 to 500 kW
0.2 to 20 s
Reverse Power
Pr
0.02 to 0.2 x Pn
0.5 to 20 s
Minimum Frequency
Fmin
45 to 65 Hz
0.2 to 5 s
Maximum Frequency
Fmax
45 to 540 Hz
0.2 to 5 s
Sequence
'
A-B-C or A-C-B
Instantaneous
26
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Load-Shedding Settings for Current and Power Metering for Micrologic 5.0P and
6.0P Trip Units
Pick-Up
Threshold
Drop-Out
Time Delay
Threshold
Time Delay
Current
Power
200 kW to 10 MW
100 kW to 10 MW
10 to 3600 s
10 to 3600 s
Type of fault
Date and time of fault
Interrupted current
Contact wear
Trip
history
Ii
05 / 20 / 00
Ii
04 / 28 / 00
Vmin
04 / 28 / 00
Alarm History
Type of alarm
Date and time of the alarm
Values measured at the time of the
alarm
Alarm
history
Al
05 / 20 / 00
Trip
05 / 20 / 00
10:23:42 am
Ii 7200 A
Ia =
Ib =
Ic =
In =
7800 A
7800 A
7800 A
7800 A
Trip
05 / 20 / 00
Al
996A
Al
04 / 28 / 00
Al
02 / 28 / 00
27
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
06133258
Metering
4260A
N 1 2 3
100
Current
Metering
The Micrologic P trip unit calculates in real time all electrical values V, A, W, VAR, VA, Wh, VARh,
VAh, Hz, power factor, and crest factor. The Micrologic P trip unit also calculates demand current and
demand power over an adjustable time period.
Real-Time Metering: The value displayed on the screen is refreshed every second. Minimum and
maximum measurement values are stored in memory.
Unit of Measurement
Measurement Source
IRMS
A, B, C or N
IAVERAGE
(A + B + C)/3
IPEAK2
A, B, C or N
VRMS
VRMS
IA = 4800 A
VIMBALANCE
VRMS
IB = 4600 A
IC = 4000 A
P, Q and S
W, VAR, VA
Total
EP, EQ and ES
Total
50
Type of Measurement
Current
Iinstant.
max
Voltage
IN = 200 A
Maximum
I = 13 A
Current
Vinst.
VAB = 460 V
VBC = 464 V
VCA = 461 V
VAN = 270 V
VBN = 279 V
Voltage
V
VCN = 273 Metering
Power
Power factor
Frequency
Total
Hz
50/60
Demand Metering: The demand is calculated over a fixed or sliding time window that can be
programmed from five to 60 minutes. Depending on the contract signed with the power supplier,
specific programming makes it possible to avoid or minimize the cost of overrunning the subscribed
power. Maximum demand values are systematically stored and time stamped.
Type of Measurement
Current
IDEMAND
A, B, C or N
Power
P, Q and SDEMAND
W, VAR, VA
Total
Communication Network
Pinst.
P
(kW)
2180
(kVAR)
- 650
Power
(kVA)
Metering
2280
Four wire Modbus, RTU, RS485The communication network may be used to:
In addition, an event log of the last 100 events and a maintenance record, which is stored in the trip
unit memory but not available locally, may be accessed via the communication network.
F (Hz)
60.0
Frequency
Pdemand
P
(kW)
2180
(kVAR)
- 650
(kVA)
Power
2280
Demand
The Modbus communication system is compatible with Powerlogic System ManagerTM (SMS) software.
Event Log
The event log may be accessed by a remote computer via the communication network. All events are
time stamped and include:
Trips
Beginning and end of alarms
Modifications to settings and parameters
Loss of time
Overrun of wear indicators
Test kit connections.
Counter resets.
System faults (thermal self-protection, major fault and minor fault alarms).
28
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
(A)
I
(V)
V
(kW)
P
E (kWh)
Harmonics
x In
Harmonic components (amplitude and phase) up to the 31st current and voltage harmonic.
.4 .4 .3
.2
.3
.1
.2
.1 2 0
Ii
(s)
on
I t
off
delay
4
3
6 8 10
12
15
off
2
x In
Current
test
lg
F
G
H
J
Unit of Measurement
Measurement Source
instantaneous
tsd
setting
D
C
B
A
Type of Measurement
@ 6 Ir
Ig
alarm
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
Real-Time Metering: The value displayed on the screen is refreshed every second. The table below
shows what is measured in real-time metering.
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
Customized alarm programming to analyze and track down a disturbance on the ac power system.
The Micrologic H trip unit offers all the measurements carried out by the Micrologic P trip unit, with the
addition of phase-by-phase measurements of power and energy as well as calculation of:
long time
.7
.6
.5
.4
Metering
Ir
In-depth analysis of power quality including calculation of harmonics and the fundamentals.
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
I t
off
IRMS
A, B, C or N
IAVERAGE
(A + B + C) / 3
IPEAK/2
A, B, C or N
IIMBALANCE
A, B, C or N
VRMS
VRMS
VIMBALANCE
VRMS
P, Q and S
W, VAR, VA
Total
EP, EQ and ES
Total
ground fault
Voltage
Micrologic 6.0H Trip Unit
Power
Power factor
Frequency
Power Quality
Indicators
Total
Hz
A, B, or C
Fundamentals
50/60 Hz component
V, I, P, Q, and S
THD
V/I
V and I harmonics
Amplitude to phase
1, 2, 3, 4...50
Demand Metering: Similar to the Micrologic P trip unit, demand values are calculated over a fixed or
sliding time window that can be set from five to 60 minutes.
Type of Measurement
Unit of Measurement
Measurement Source
Current
IDEMAND
A, B, C or N
Power
P, Q and SDEMAND
W, VAR, VA
Total
Waveform Capture
Micrologic H trip units can capture and store current and voltage waveforms using digital sampling
techniques similar to those used in oscilloscopes. Using the information available in the captured
waveform, it is possible to determine the level of harmonics as well as the direction and amplitude of
the flow of harmonic power.
Users of Micrologic H trip units can record manually via the keypad the following waveforms:
29
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Event Logs
Each event is recorded with:
Setting the display language: System messages can be displayed in six different languages:
English - US
English - UK
French
German
Spanish
Italian
Protection functions: All current-based protection functions require no auxiliary source. Voltagebased protection functions are connected to AC power via a voltage measurement input built into
the circuit breaker on the bottom side. (Optional external voltage measurement is available.)
Stored information: The fine setting adjustments, the last 100 events and the maintenance record
remain in the trip unit memory even when power is lost.
Reset: An individual reset, via the keypad or remotely, will reset alarms, minimum and maximum
data, peak values, counters and the indicators.
30
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Long-Time
Pickup
Long-Time
Delay
long time
Ir
.7
.6
.5
.4
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
@ 6 Ir
instantaneous
short time
tsd
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
on
6 8 10
12
3
2
Alarm
Indicator
15
off
x In
test
tg
D
C
B
A
I2t off
delay
setting
Ig
Ii
.4 .4 .3
.2
.3
.1
.2
0
.1
(s)
.4 .4 .3
.2
.3
.1
.2
0
.1
(s)
F
G
H
J
on
I2t
off
ground fault
The trip unit includes an alarm indicator that will be lit continuously when the
current is above 100% of the pickup setting.
alarm
Short-Time
Pickup
instantaneous
Short-Time
Delay
long time
Ir
.7
.6
.5
.4
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
@ 6 Ir
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
tsd
on
setting
Ig
D
C
B
A
Ii
.4 .4 .3
.2
.3
.1
.2
0
.1
6 8 10
12
15
3
2
off
x In
(s)
I2t
delay
off
test
tg
Instantaneous Pickup
.4 .4 .3
.2
.3
.1
.2
0
.1
(s)
F
G
H
J
on
I2t
off
ground fault
Short-Time and
Instantaneous Trip
Functions
long time
Ir
.7
.6
.5
.4
@ 6 Ir
instantaneous
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
tsd
.4 .4 .3
.2
.3
.1
.2
0
.1
D
C
B
A
on
I2t off
delay
tg
F
G
H
J
Ii
(s)
setting
Ig
The ground-fault delay switch sets the length of time the circuit breaker will
carry ground-fault current which exceeds the ground-fault pickup level before
tripping. The delay (based on the sensor plug amperage (In) can be adjusted
to four positions of I2t ramp operation (I2t ON) or five positions of fixed time
delays (I2t OFF). I2t ON delay is an inverse time characteristic in that the
delay time decreases as the current increases.
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
.4 .4 .3
.2
.3
.1
.2
0
.1
(s)
on
I2t
4
3
6 8 10
12
2
15
off
x In
test
GroundFault
Pickup
GroundFault
Delay
off
ground fault
Ground-Fault Trip
Functions
31
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Communication Network
Masterpact NW/NT circuit breaker, and Micrologic trip unit information is available via a Modbus network to
Powerlogic System ManagerTM software (SMS) or other applications for reporting and recording.
Four wire Modbus, RTU, RS485Types of information available via Modbus communication network:
Trip indication.
Alarm reporting.
Historical files and maintenance records.
Real-time readings.
The Modbus circuit breaker communication feature, standard on the Micrologic P and H trip units and
available for the Micrologic A trip unit, is made up of:
A Modbus circuit breaker communication module (BCM) installed on the circuit breaker and
supplied with a kit for optional connection to the XF shunt close and MX shunt trip.
An optional Modbus cradle communication module (CCM) installed adjacent to the breaker cradle.
Cradle position switches are required for breaker position status (connected, test, or disconnected).
Screens including real-time readings, breaker status and remote control operation.
Tables displaying real-time readings, maintenance information and date and time of last operation.
Waveform captures including harmonic content.
Tabular displays of event logs and data logs.
Alarm annunciation and recording.
32
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Section 3Accessories
OPTIONS FOR REMOTE OPERATION ...................................................................................................... 34
REMOTE OPERATION ACCESSORIES ..................................................................................................... 34
Terminals ................................................................................................................................................ 35
Spring-Charging Motor (MCH) ............................................................................................................... 35
Shunt Trip (MX1) and Shunt Close (XF) ................................................................................................ 36
Additional Shunt Trip (MX2) or Undervoltage Trip (MN) ........................................................................ 37
Time-Delay Module for Undervoltage Trip ............................................................................................. 38
Ready-to-Close Switch (PF) ................................................................................................................... 38
Electrical Closing Push Button (BPFE) .................................................................................................. 39
Remote Reset (RES) and Automatic Reset After Fault Trip .................................................................. 39
SWITCHES AND SWITCH ACCESSORIES ................................................................................................ 39
Auxiliary Switch (OF) .............................................................................................................................. 39
Overcurrent Trip Switch (SDE) ............................................................................................................... 40
Connected/Closed Switch (EF) .............................................................................................................. 40
Cradle Position Switch ........................................................................................................................... 41
COMMUNICATION NETWORK ACCESSORIES ........................................................................................ 42
Modbus Circuit Breaker Communication Module (BCM) ........................................................................ 42
Modbus Cradle Communication Module (CCM) ..................................................................................... 43
MICROLOGIC TRIP UNIT ACCESSORIES ................................................................................................. 44
External Neutral Current Transformer (CT) ............................................................................................ 44
External Sensor for (SGR) and (MDGF) ................................................................................................ 44
Metering Current Transformers (CTs) .................................................................................................... 44
Voltage Measurement Inputs ................................................................................................................. 44
Sensor Plugs .......................................................................................................................................... 44
Adjustable Rating Plugs ......................................................................................................................... 44
External Power Supply Module .............................................................................................................. 45
External Battery Backup Module ............................................................................................................ 45
M2C/M6C Programmable Contact Modules ........................................................................................... 46
Zone-Selective Interlocking (ZSI) ........................................................................................................... 46
Restraint Interface Module (RIM) ........................................................................................................... 47
CRADLE CONNECTIONS ........................................................................................................................... 48
TEST EQUIPMENT ...................................................................................................................................... 56
Hand-Held Test Kit ................................................................................................................................. 56
Full-Function Test Kit ............................................................................................................................. 56
CIRCUIT BREAKER LOCKING AND INTERLOCKING ............................................................................... 57
Push Button Lock ................................................................................................................................... 57
Open Position Padlock and Key Lock Provisions ................................................................................... 57
Cradle Locking and Interlocking ............................................................................................................. 58
Disconnected Position Locking .............................................................................................................. 58
Door Interlock ......................................................................................................................................... 58
Racking Interlock Between Racking Handle and Off Position ................................................................ 58
Cable Door Interlock Kit ......................................................................................................................... 58
Source Changeover Interlocks ............................................................................................................... 59
Open Door Racking Interlock ................................................................................................................. 59
Automatic Spring Discharge Mechanism ............................................................................................... 59
Cradle Rejection Kits .............................................................................................................................. 59
Rail Padlocking ....................................................................................................................................... 59
MISCELLANEOUS ACCESSORIES ............................................................................................................ 60
Mechanical Operation Counter (CDM) ................................................................................................... 60
Shutter and Shutter Lock ........................................................................................................................ 60
Door Escutcheon (CDP) ......................................................................................................................... 60
Transparent Cover (CCP) for Door Escutcheon ..................................................................................... 60
33
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
06133264
B3
Closing
Order
Opening
Order
Spring
Charged
Ready to
Close
Fault
Closed
14
Open
B2
C2
252
A2
254
82
84
12
MCH
MX
XF
SDE
PF
OF1
CH
C1
B1
251
A1
81
11
06133832
Figure 7:
Spring
Charged
Opening
Order
B2
Closing
Order
C2
06133265
B3
MCH
CH
OF
C3
10 ft
[3 m]
MX
B1
A2
A3
10 ft
[3 m]
XF
C1
A1
PF
SDE
CH
COM
Supervisor
34
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Characteristics
Standards
UL 486E
Termination Capacity
Current
Nominal
Minimum
10 A
100mA at 24 V
Terminal
Spring-Charging
Motor (NW)
Spring-Charging
Motor (NT)
Characteristics
Voltage Ratings (Vn)
MCH
Vac 50/60 Hz
Vdc
Operating Threshold
0.85 to 1.1 Vn
Power Consumption
180 VA
Motor Overcurrent
23 x In for 0.1 s
Charging Time
Duty Cycle
Endurance
CH Contact
35
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Percent of
Source Voltage
Device
12 Vdc
24 Vdc
16 AWG
(1.31 mm2)
14 AWG
(2.08 mm2)
16 AWG
(1.31 mm2)
14 AWG
(2.08 mm2)
16 AWG
(1.31 mm2)
100%
159 ft
(48.5 m)
100 ft
(30.5 m)
765 ft
(233.2 m)
472 ft
(143.9 m)
85%
44 ft
(13.4 m)
29 ft
(8.8 m)
205 ft
(62.5 m)
129 ft
(39.3 m)
100%
57 ft
(17.4 m)
34 ft
(10.4 m)
314 ft
(95.7 m)
200 ft
(61.0 m)
1503 ft
(457.8 m)
944 ft
(287.7 m)
85%
27 ft
(8.2 m)
17 ft
(5.2 m)
205 ft
(62.5 m)
126 ft
(38.4 m)
957 ft
(291.7 m)
601 ft
(183.2 m)
Wire Size
UVR (MN)
48 Vdc
14 AWG
(2.08 mm2)
The length shown in the table is for each of the two supply wires.
Shunt Close (XF): Remotely closes the circuit breaker if the spring
mechanism is charged. The shunt close may be energized
continuously or intermittently.
Communication versions of the MX1 and XF are available for direct
connection via the circuit breaker communication module (BCM).
Table 33:
Characteristics
MX1
Vac
50/60 Hz
Vdc
Operating Threshold
Power Consumption (VA or W)
0.7 to 1.1 Vn
Steady-State/Inrush
Min
Max
24 Vac
XF
17 Vac
26 Vac
48 Vac
34 Vac
52 Vac
120 Vac
60 Vac
132 Vac
240 Vac
168 Vac
264 Vac
277 Vac
194 Vac
304 Vac
380 Vac
266 Vac
418 Vac
480 Vac
336 Vac
528 Vac
12 Vdc
8 Vdc
13 Vdc
24 Vdc
17 Vdc
26 Vdc
48 Vdc
34 Vdc
52 Vdc
125 Vdc
88 Vdc
137 Vdc
250 Vdc
175 Vdc
275 Vdc
0.85 to 1.1 Vn
4.5/200
70 ms 10 (NW d 4000 A)
50 ms 10
(NW and NT)
Shunt trip (MX1) and shunt close (XF) circuits must be energized for minimum of 200 ms.
36
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
As shown in the wiring diagram for the remote tripping function below, the delay unit (installed outside
the circuit breaker) may be disabled by an emergency off button to obtain non-delayed opening of the
circuit breaker.
When energized, the shunt trip (MX1) instantaneously opens the circuit breaker. A continuous supply
of power to the second shunt trip (MX2) locks the circuit breaker in the off position.
The undervoltage trip (MN) instantaneously opens the circuit breaker when its supply voltage drops to
a value between 35% and 70% of its rated voltage.
If the undervoltage trip is not energized, it is impossible to close the circuit breaker, either manually or
electrically. An attempt to close the circuit breaker produces no movement of the main contacts.
Closing is allowed when the supply voltage of the undervoltage trip reaches 85% of rated voltage.
Table 34:
Characteristics
Vac
50/60 Hz
Vdc
Constant/Inrush
Min
Max
24 Vac
17 Vac
26 Vac
48 Vac
34 Vac
52 Vac
120 Vac
60 Vac
132 Vac
240 Vac
168 Vac
264 Vac
277 Vac
194 Vac
304 Vac
380 Vac
266 Vac
418 Vac
480 Vac
336 Vac
528 Vac
12 Vdc
8 Vdc
13 Vdc
24 Vdc
17 Vdc
26 Vdc
48 Vdc
34 Vdc
52 Vdc
125 Vdc
88 Vdc
137 Vdc
250 Vdc
175 Vdc
275 Vdc
4.5/200
Figure 8:
MX2
50 ms 10
Opening
Order
C12
MX2
or
Delayed
Opening
Order
D2
Delayed
Unit
MN
Instantaneous Opening
Order
MN
C1 1
D1
10
12
D2
D1
37
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Adjustable
Voltage Ratings of Time-Delay Module
Non-Adjustable
Operating Threshold
Vac 50/60 Hz
Vdc
Vac 50/60 Hz
Vdc
Vac 50/60 Hz
100/130, 200/250
Vdc
100/130, 200/250
Opening
0.35 to 0.7 Vn
Closing
Power Consumption
0.85 Vn
4.5 VA/W (Holding), 200 VA/W (Inrush)
Time-Delay Settings
Adjustable
Non-Adjustable
0.25 s
Ready-to-Close
Switch (PF)
Table 36:
Type of Contact
Maximum Number of Contacts
1a/1b Form C
1
Standard: 100 mA/24V minimum load
Breaking Capacity at a
Power Factor (p.f.) of 0.3
240/380 Vac
5A
24/48 Vac
3A
480 Vac
5A
240 Vac
3A
600/690 Vac
3A
380 Vac
3A
24/48 Vdc
3A
24/48 Vdc
3A
240 Vdc
0.3 A
125 Vdc
0.3 A
380 Vdc
0.15 A
250 Vdc
0.15 A
38
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
06133804
A2
A3
XF
Electrical Closing
Push Button (BPFE)
BPFE
A1
Following tripping, the remote reset (RES) resets the overcurrent trip switch (SDE) and the
mechanical indicator. (Voltage rating: 110/130 Vac and 200/240 Vac.) RES is not compatible with
an additional overcurrent trip switch (SDE2).
Automatic reset after fault-trip: Following tripping, a reset of the mechanical indicator (reset button)
is no longer required to enable circuit breaker closing (factory adjustable only).
Table 37:
NT
NW
4
12
Vac
Vdc
Breaking Capacity at a
Power Factor (p.f.) of 0.3
240/380
6A
10 A
480
6A
10 A
6A
600/690
6A
24/48
2.5 A
10 A
240
0.5 A
10 A
380
0.3 A
3A
Low-Level (1 mA/4 V minimum load with a maximum current and voltage of 100 mA/10 V.
Note: If the maximum voltage and current is exceeded, the low-level function of the switch will be lost
but the switch will continue to function as a standard switch with the following specifications.
Vac
Vdc
24/48 Vac
5A
6A
240 Vac
5A
6A
380 Vac
5A
3A
24/48 Vdc
5/2.5 A
6A
125 Vdc
0.5 A
6A
250 Vdc
0.3 A
3A
39
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Overcurrent
Trip Switch
(SDE)
Supplied as Standard
1a/1b Form C
2
Standard: 100 mA/24 V Minimum Load Low-Level: 2 mA/15 V Minimum Load
240/380 Vac
5A
24/48 Vac
3A
480 Vac
5A
240 Vac
3A
3A
380 Vac
3A
24/48 Vdc
3A
24/48 Vdc
3A
240 Vdc
0.3 A
125 Vdc
0.3 A
380 Vdc
0.15 A
250 Vdc
0.15 A
Breaking Capacity at a
Power Factor (p.f.) of 0.3
240/380 Vac
6A
24/48 Vac
5A
480 Vac
6A
240 Vac
5A
600/690 Vac
6A
380 Vac
5A
24/48 Vdc
2.5 A
24/48 Vdc
2.5 A
125 Vdc
0.8 A
125 Vdc
0.8 A
250 Vdc
0.3 A
250 Vdc
0.3 A
Connected/Closed
Switch (EF) NW only
40
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Cradle position switches (CT) to indicate the test position. In this position, the
power circuits are disconnected and the auxiliary circuits are connected.
Table 40:
Cradle Position
Switch (CE, CD, CT)
NW
1Possible
CE CD CT
CE CD CT
CE
CD
1b
1a
1b
1a, 1b
1b
Ring-Terminal Combinations
31
31
31
1b
1a, 2b
1a, 2b
1a
1a, 2b
2a, 1b
1b
2a, 1b
1a, 2b
1b
1a
1a
1a
3a
3a
1a
3b
3b
1b
Vac
Breaking
Capacity at a
Power Factor
(p.f) of 0.3
Vdc
Vdc
Figure 9:
240
8A
8A
380
8A
8A
480
8A
8A
600/690
6A
6A
24/48
2.5 A
2.5 A
125
0.8 A
0.8 A
250
0.3 A
0.3 A
Vac
CT
24/48
5A
5A
240
5A
5A
380
5A
5A
24/48
2.5 A
2.5 A
125
0.8 A
0.8 A
250
0.3 A
0.3 A
41
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Modbus Communication
Network without CCM
CCM
(optional)
2
Terminal
Block
Modbus Communication
Network with CCM
CT
CE
CD
OF
SDE
PF
CH
MX1
XF
6
BCM
Circuit Breaker
Communication
Module (BCM)
42
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Table 41:
Cradle
Communication
Module (CCM)
Characteristics
Status Indication
z ON/OFF Indication
z Connected/Disconnected/Test Pos.
z Ready-to-Close
z Fault Trip
Controls
z Opening/Closing
Circuit
Breaker and
Trip Unit
Settings
z Reading of Settings on Rotary Switches
Standard
Set
Customized
Current
Reading of Measurements
X
X
Indicators
1
X
X
X
X
X
Maintenance record
X
X
43
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Toroidal Current
Transformers
(CTs) for W-Frame
Circuit Breakers
Sensor Plugs
Sensor plugs (standard) are used to set the sensor rating (In) of the
circuit breaker, are field replaceable and are offered at 50100% of
frame rating. For a complete list of available sensor plugs see
selection information in Section 7.
Sensor Plug
44
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Rating Plug
IEC Rated
A1
0.4
0.45
0.5
0.6
0.63
0.7
0.8
0.9
Type B
0.4
0.44
0.5
0.56
0.63
0.75
0.88
0.95
Type C
0.42
0.50
0.53
0.58
0.67
0.75
0.83
0.95
Type D
0.4
0.48
0.64
0.7
0.8
0.9
0.93
0.95
Type E
0.6
0.7
0.75
0.8
0.85
0.9
0.93
0.95
Type F
0.84
0.86
0.88
0.9
0.92
0.94
0.96
0.98
Type G
0.66
0.68
0.7
0.72
0.74
0.76
0.78
0.8
0.82
Type H
0.48
0.5
0.52
0.54
0.56
0.58
0.6
0.62
0.64
Type R1
0.4
0.5
0.6
0.7
0.8
0.9
0.95
0.98
Type S
0.4
0.45
0.5
0.55
0.6
0.65
0.7
0.75
0.8
Type T
0.8
0.82
0.85
0.88
0.9
0.92
0.95
0.98
Type P
(off plug)
No long-time protection.
Type
UL
Listed/ANSI
Certified
Adjustable
Rating Plug
Standard
Store the value of the interrupted current (P and H trip units only).
External Power
Supply Module
External Battery
Backup Module
45
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Table 43:
M2C Programmable
Contact Module
Minimum Load
100 mA/24 V
240 Vac
5A
380 Vac
3A
24 Vdc
1.8 A
48 Vdc
1.5 A
125 Vdc
0.4 A
250 Vdc
0.15 A
Z1
Z2
Z3
Z4
Z5
Fault 1
06133801
Z1
Z2
Z3
Z4
Z5
Fault 2
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
Downstream
Circuit
Breakers
Fault 1The upstream circuit breaker (A) will clear the fault
with no intentional delay, regardless of its time-delay setting.
Fault 2Circuit breaker (B) will inform upstream circuit
breaker (A) that it is clearing the fault. This will prevent circuit
breaker (A) from tripping instantaneously. Circuit breaker (A)
will trip at the end of its time delay setting if the fault is not
cleared during this time.
46
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Merlin Gerin
STR58 Trip Units
Square D
GC-200 Relay
Square D
GC-100 Relay
Downstream Device
(sends output to RIM)
Micrologic
Series B Trip Unit
Upstream Device
(receives output to RIM)
RIM Requirements
Table 44:
Restraint Interface
Module (RIM)
152
15
15
26
15
R
15
15
15
15
15
15
15
15
15
15
15
Includes 2.0A (as a downstream trip unit only), 5.0A, 5.0P, 5.0P, 5.0H, 6.0A, 6.0P, and 6.0H trip units.
Number denotes maximum number of upstream circuit breakers that can be restrained without requiring a RIM.
47
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Cradle Connections
Table 45:
Ampere
Rating
3P Layout (Back/Side/Top)
4P Layout (Back/Side/Top)
06134039
06133669
Connector
Type
06134028
06133683
800 to 2000 A
2500 to 3000 A
06134050
3200 A (L1)
06133680
Rear-Connected
T Vertical
(RCTV)
06134045
06133698
4000 to 5000 A
06134038
06133675
6000 A
06134027
06134049
3200 A (L1)
06133681
Rear-Connected
T Horizontal
2500 to 3000 A
(RCTH)
06133684
800 to 2000 A
Rear-Connected 3200 A
Offset Vertical
2000 A (L1/L1F)
(RCOV)
06133575
06133574
4000 to 5000 A
48
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
3P Layout (Back/Side/Top)
06133670
Connector
Type
4P Layout (Back/Side/Top)
06134037
Table 46:
800 to 2000 A
06134072
3200 A (L1)
06133685
Front-Connected
Flat (FCF)
06133671
06134026
06133682
06134047
4000 A
800 to 3000 A
Front-Connected
T (FCT)
3200 A (L1)
4000 to 5000 A
49
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Connector
Type
06134068
06133690
800 to 2000 A
4P Layout (Back/Side/Top)
06134408
Table 47:
06133700
06134417
4000 to 5000 A
06134415
Rear-Connected
T Vertical
(RCTV)
06133691
2500 to 3000 A
Rear-Connected
T Horizontal
(RCTH)
06133700
2500 to 3000 A
06134069
800 to 2000 A
06134070
06133686
6000 A
3200 A
Rear-Connected
Offset Vertical
4000 A (B)
(Special)
06133575
06135504
Rear-Connected
Offset Vertical
(RCOV)
06135503
06133574
4000 to 5000 A
(W-Frame)
50
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Front-Connected
Flat (FCF)
800 to 2000 A
Front-Connected
T (FCT)
800 to 3000 A
4P Layout (Front/Side/Top)
06133689
06134409
06133688
Connector
Type
06134405
Table 48:
51
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
4P Layout
06134464
3P Layout
06134462
Ampere
Rating
06134457
Connector
Type
06134455
Table 49:
Front-Connected
800 to 3200 A
Flat (FCF)
06134465
06134458
800 to 3200 A
06134843
5000 A
06134844
06134460
Rear-Connected
T Vertical
(RCTV)
06134467
4000 A
06134463
06134456
6300 A
06134461
06134466
Rear-Connected
4000 A
T Horizontal
(RCTH)
06134468
06134459
800 to 3200 A
5000 A
52
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Ampere
Rating
3P Layout
06134475
Connector
Type
06134478
Table 50:
06134477
06134474
Front-Connected
800 to 3200 A
Flat (FCF)
06134481
06134479
800 to 3200 A
06134483
06134485
06134846
Rear-Connected
T Vertical
(RCTV)
06134845
4000 A
5000 A
06134480
06134482
06134486
Rear-Connected
T Horizontal
(RCTH)
06134484
800 to 3200 A
06134476
06134473
6300 A
4000
5000 A
53
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Connector Type
Table 51:
06135263
06135264
06135265
06135266
800 to 1200 A
Rear-Connected T Vertical
(RCTV)
800 to 1200 A
Rear-Connected T Horizontal
(RCTH)
06135502
800 to 1200 A
Rear-Connected Vertical
1600 A
N/A
54
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Connector Type
Rear-Connected T Vertical
(RCTV)
800 to 1600 A
Rear-Connected T Horizontal
(RCTH)
800 to 1600 A
55
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Test Equipment
Hand-Held Test Kit
The hand held test kit may be used to:
Supply control power to the trip unit for settings via the
keypad when the circuit breaker is open
(Micrologic type A, P or H trip units).
Full-Function
Optional
Test Kit
56
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A lead seal.
push OFF
push ON
06133462
06133463
Two screws.
Two different key locks mounted on the circuit breaker for double locking.
One key lock mounted on the device plus one identical key lock supplied separately for interlocking
with another device.
A locking kit for installation of one or two key locks may be ordered separately.
Table 53:
Type of Locking
Pushbutton Locking
Open Position Locking
Three padlocks
57
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Key Interlock
06133464
Padlock Hasp
Test
Disconnected
Position Locking
Provisions
Door Interlock
06133789
The door interlock prevents the compartment door from being opened
when the circuit breaker is in the connected or test position. If the circuit
breaker is put into the connected position with the door open, the door can
be closed without disconnecting the circuit breaker. For greater protection,
this interlock can be used in conjunction with the open door racking
interlock.
06134189
C
Kit Contents
(A) Panel Interlocking Plate
(B) Circuit Breaker Interlocking Plate
(C) Interlocking Cables
(D) Bolts with Washers
G
F
58
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
06133956
The racking interlock prevents racking in the circuit breaker when the door is
open. (Insertion of the circuit breaker racking handle is not possible when the
compartment door is open.)
06133802
Automatic Spring
Discharge Mechanism (NW)
Rail Padlocking
Rail padlocking is standard for UL, ANSI, and IEC cradles. When used in combination with the
disconnected position locking device, rail padlocking prevents the movement of the circuit breaker from
the disconnected position to the fully withdrawn position when the padlock hasp is pulled out and locked.
59
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Miscellaneous Accessories
Mechanical Operation Counter (CDM)
Mechanical
Operation
Counter (CDM)
06133798
0039
06133174
Shutter Lock
(NW)
Door Escutcheons
06134065
06133818
Seal
Seal
Escutcheon
Escutcheon
06133819
Transparent
Cover (CCP)
60
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
06135976
61
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
62
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Downstream
Upstream
Charged
Z2
N A
Remote Operation
Fault
Trip Unit
Z3
Z4, Z5
Z1
06133796
Power
Fault
Figure 15:
B3
B2
252
254
A3
A2
C3
C2
C12
D2
84
K2
82
184
182
Q3
Q2
484
Q1
474
Z5
Z4
Z1
Z2
Z3
V2
V3
VN
V1
M6C
MCH
S1
S2
SDE2
Trip Unit
M2C
SDE1
MN
MX2
MX1
XF
CH
PF
RES
M6C
or
or
or
24 Vdc
B1
251
A1
C1
C11
D1
81
K1
181
471
F2+
T4
F1
T3
T4
T3
T2
T1
T2
M3
M2
T1
M1
NOTE: All diagrams show circuit breaker open, connected and charged.
ADo not remove factory-installed jumpers between Z3, Z4 and Z5 unless ZSI is connected.
BDo not remove factory-installed jumper between T1 and T2 unless neutral CT is connected. Do not install jumper between T3 and T4.
CFor proper wiring of neutral CT, refer to Instrucion Bulletin 48041-082-01 shipped with it.
D24 Vdc power supply for trip unit must be separate and isolated from 24 Vdc power supply for communication modules.
EWhen remote operation features are used, make sure there is a minimum of four seconds for the spring charging motor (MCH) to completely charge the circuit
breaker closing springs prior to actuating the shunt close (XF) device.
Table 54:
Cell Switches
CD3 CD2 CD1
COM
UC1
UC2
UC3
Trip Unit
UC4 M2C/M6C SDE2/RES SDE1
Cell Switches
CE3 CE2 CE1
Remote Operation
MN/MX2 MX1
XF
PF
MCH
834
824
814
E5 E6 Z5 M1 M2 M3
F2+
V3
484/Q3
184/K2
84
334
324
314
D2/C12
C2
A2
254
B2
832
822
812
E3 E4 Z3 Z4 T3 T4
VN
V2
474/Q2
182
82
332
322
312
C13
C3
A3
252
B3
831
821
811
E1 E2 Z1 Z2 T1 T2
F1
V1
471/Q1
181/K1
81
331
321
311
D1/C11
C1
A1
251
B1
CE6
or
CE5
CE4
364
354
344
362
352
342
361
351
341
Table 55:
Cell Switches
CD3
CD2
CD1
834/832 824/822 814/812
831
821
811
COM
UC1
UC2
UC3
E5 E6 Z5 M1 M2 M3
F2 +
E3 E4 Z3 Z4 T3 T4
F1
Trip Unit
UC3a M2C/M6C SDE2/RES SDE2a
VN
484/Q3
184/K2
471/Q1
181/K1
182
SDE1
SDE1a
84
82
81
Remote Operation
MN/MX2 MX1 MX1a XF
F
D2/C12
C2
D1/C11
C1
C3
A2
XFa
A3
A1
E1 E2 Z1 Z2 T1 T2
63
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Connected
914
912
934
CE1
932
924
922
CE2
Test Position
314
324
312
332
812
814
832
834
822
824
Disconnected
EF
(OF.. + CE)
OF . .
OF . .
OF1
..6
..8
..2
Closed
..4
12
22
OF2
Connected
Closed
334
322
OF3
24
32
Closed
34
42
OF4
44
Open
14
06133794
Not Connected
or Connected
and Open
06133795
Auxiliary Contacts
CD3
CD2
CD1
CE3
CT3
CT2
CT1
or
Table 56:
911
921
931
311
321
331
811
821
831
..5
..1
11
21
31
41
CE
Auxiliary Contacts
OF24
OF23
OF22
OF21
OF14
OF13
OF12
OF11
OF4
OF3
OF2
OF1
CT3
CT2
CT1
244
234
224
214
144
134
124
114
44
34
24
14
934
924
914
242
232
222
212
142
132
122
112
42
32
22
12
932
922
912
241
231
221
211
141
131
121
111
41
31
21
11
931
921
911
or
or
or
or
EF24
EF23
EF22
EF21
EF14
EF13
EF12
EF11
CD6
CD5
CD4
CE9
CE8
C7
248
238
228
218
148
138
128
118
864
854
844
394
384
374
246
236
226
216
146
136
126
116
862
852
842
392
382
372
245
235
225
215
145
135
125
115
861
851
841
391
381
371
Fixed-mounted circuit breaker does not have cell switches (CE, CD, CT).
Table 57:
Alarm Switches
Cell Switches1
Auxiliary Contacts
PF
CT1
MCH
MCHa
OF14
OF13
OF12
OF11
OF4
OF3
OF2
OF1
252
914/912
B2
B3
144
134
122
112
44
34
22
12
251
911
B1
141
131
121
111
41
31
21
11
CE3
CE2
CE1
331
321
311
Fixed-mounted circuit breaker does not have cell switches (CE, CD, CT).
64
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B3
B2
252
254
A3
A2
C12
D2
C3
Charged
Fault
84
K2
82
184
Q3
Q2
Q1
484
474
Z5
Z4
Z3
Z2
Z1
V3
V2
V1
VN
182
M6C
C2
Z5
Z4
Z1
Z5
Z3
Downstream
Circuit Breaker
Upstream
Circuit Breaker
L3
Z4
L2
Z3
L1
Z2
Z1
06134061
Power
Remote Operation
06134062
Trip Unit
Z2
Power
Fault
Figure 16:
A
E
MCH
SDE2
Q
I
S1
MN
SDE1
MX2
MX1
XF
CH
PF
RES
S2
Micrologic
or
or
T4
24 Vdc
B1
251
A1
C1
C11
81
181
NOTE: All diagrams show circuit breaker open, connected and charged.
471
F2+
F1
T4
T3
T2
T3
T1
T2
M3
T1
M2
M1
D1
M6C
or
K1
M2C
ADo not remove factory-installed jumpers between Z3, Z4 and Z5 unless ZSI is connected.
BDo not remove factory-installed jumper between T1 and T2 unless neutral CT is connected. Do not install jumper between T3 and T4.
CFor proper wiring of neutral CT, refer to Instrucion Bulletin 48041-082-01 shipped with it.
D24 Vdc power supply for trip unit must be separate and isolated from 24 Vdc power supply for communication modules.
EWhen remote operation features are used, make sure there is a minimum of four seconds for the spring charging motor (MCH) to completely charge the circuit
breaker closing springs prior to actuating the shunt close (XF) device.
Table 58:
Cell Switches
Trip Unit
CD2
CD1
COM
UC1
UC2
UC3
SDE2 / RES
SDE1
824
814
E5 E6
Z5 M1
M2 M3
F2+
V3 / 484 / Q3
184 / K2
84
822
812
E3 E4
Z3 Z4
T3 T4
VN
V2 / 474 / Q2
182
82
821
811
E1 E2
Z1 Z2
T1 T2
F1
V1 / 471 / Q1
181 / K1
81
Remote Operation
MN / MX2
MX1
XF
PF
MCH
D2 / C12
C2
A2
254
B2
C13
C3
A3
252
B3
D1/C11
C1
A1
251
B1
65
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Open
06134064
06134063
Cell Switches
Closed
Test Position
Disconnected
914
912
314
312
324
334
CT1
911
CE1
311
CE2
321
CE3
331
821
11
21
31
41
CD1
Auxiliary Switches
Cell Switches
OF4
OF3
OF2
OF1
CE3
CE2
CE1
CT1
44
34
24
14
334
324
314
914
42
32
22
12
332
322
312
912
41
31
21
11
331
321
311
911
Figure 17:
06135267
322
OF1
CD2
Table 59:
332
822
824
812
814
12
14
22
OF2
811
OF3
24
32
34
42
OF4
44
Connected
Spring-Charging Motor
CN1
- 440/480 V
9
Spring
Charged
Light
440/480 V
11
R
B3 B2
CH
MCH
380V
B1
CN2
- 440/480 V
66
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
OF3
OF2
OF1
Cradle Contacts
CD3
or
CD2
CD1
OF23 or EF23
or
OF22 or EF22
CE6
OF21 or EF21
CE5
OF14 or EF14
CE4
CE3
Disconnected
Position Contacts
Connected
CE2 Position
Contacts
CE1
Test Position
Contacts
CT1
CE9
Connected
Position Contacts
Connected
CE8 Position
Contacts
CE7
OF13 or EF13
or
OF12 or EF12
CD6
Disconnected
CD5 Position
CD4 Contacts
OF11 or EF11
Trip Unit
Remote Operation
SDE2 or RES
Remote Reset
SDE1
Z1 = ZSI OUT
MX1
XF
PF
Ready-to-Close Contact
MCH
Spring-Charging Motor
UC4
NOTE: When communication version of the MX1 or XF coils are used, terminals (C3,
A3) must be connected to line even if the communications module is not installed.
M2C
or
M6C
The bypass circuit through terminal C2/A2 is only momentary duty for 0.5 sec. For
continuous duty, use the communications command.
812
314
CT1
CD1
CE1
911
811
311
24 V
471
M1
M2
M3
T1
T2
T3
T4
F1F2+
or
M6C
CT
CD
CE
Cradle
Communication
Module (CCM)
+24 Vdc
+24 Vdc A
Common
Common
Shield
Out Out +
In In +
24 Vdc
Common
Out Out +
In In +
M2C
VN
V1
V2
V3
Z1
Z2
Z3
Z4
Z5
S1 S2
Trip Unit
M6C
MODBUS
Downstream
E1
E2
E3
E4
E5
E6
Upstream
Q1
Q2
Q3
N A B C
UC3:
MN or MX2
474
484
Figure 18:
UC1:
Z3
Z4 Z5
Z1
Z3
06134898
CT2
or
OF22 or EF22
Basic
CT3
T1
T2
T3
T4
MX1
com
OF
Microswitches SDE
Circuit Breaker
XF
Communications
A24 Vdc power supply for trip unit must be connected to
com
PF
BCM
Module (BCM)
separate and isolated from 24 Vdc power
CH
supply for communications module.
BRefer to instruction bulletin 48041-082
NOTE: Fixed-mounted circuit breaker does not have
included with neutral CT for the proper wiring.
cell switches (CE, CD, CT).
B
67
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Number of
Circuit Breaker Rating
Poles
(H x W x D)
in.
Ventilation Area
Top
mm
in.2
mm2
Bottom
in.2
mm2
18.25 x 13 x 9.5
5806
5806
62.25 x 23 x 14.75
16.5
10645
16.5
10645
5806
5806
16.5
10645
16.5
10645
Dimensions:
in.
mm
69
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 21:
in.
mm
Dimensions:
in.
mm
70
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 23:
in.
mm
Dimensions:
in.
mm
71
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DRAWOUT
FIXED
Dimensions:
in.
mm
72
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
73
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Figure 27:
Dimensions:
in.
mm
Dimensions:
in.
mm
74
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
75
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 30:
in.
mm
Dimensions:
in.
mm
76
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
DRAWOUT
FIXED
Dimensions:
in.
mm
77
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 33:
in.
mm
Dimensions:
in.
mm
78
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 35:
in.
mm
Dimensions:
in.
mm
79
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 37:
in.
mm
Dimensions:
in.
mm
80
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 39:
in.
mm
Dimensions:
in.
mm
81
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 41:
in.
mm
Dimensions:
in.
mm
82
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 43:
in.
mm
Dimensions:
in.
mm
83
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 45:
in.
mm
Dimensions:
in.
mm
84
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 47:
in.
mm
Dimensions:
in.
mm
85
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
86
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 50:
in.
mm
Dimensions:
in.
mm
87
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 52:
in.
mm
Dimensions:
in.
mm
88
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
89
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 55:
in.
mm
Dimensions:
in.
mm
90
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 57:
in.
mm
Dimensions:
in.
mm
91
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
92
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 60:
in.
mm
Dimensions:
in.
mm
93
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Figure 62:
Dimensions:
in.
mm
Dimensions:
in.
mm
94
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
95
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 66:
in.
mm
Dimensions:
in.
mm
96
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
97
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
98
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Enclosure Information
Table 61:
Number
of Poles
(H x W x D)
in.
3P
4P
Top
mm
in.2
Bottom
mm2
in.2
Front Face
mm2
in.2
mm2
59.62
38 460
35.62
22 980
16.62
10 720
16.62
10 720
59.62
38 460
93.6 60 390
130.5 84 190
40006000 A, UL 489
16.62
10 720
16.62
10 720
59.62
38 460
35.62
22 980
16.62
10 720
16.62
10 720
59.62
38 460
93.6 60 390
130.5 84 190
16.62
10 720
40006000 A, UL 489
10 720
Dimensions:
in.
mm
99
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Figure 69:
Dimensions:
in.
mm
Dimensions:
in.
mm
100
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 71:
in.
mm
Dimensions:
in.
mm
101
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 73:
in.
mm
Dimensions:
in.
mm
102
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 75:
in.
mm
Dimensions:
in.
mm
103
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 77:
in.
mm
Dimensions:
in.
mm
104
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 79:
in.
mm
Dimensions:
in.
mm
105
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 81:
in.
mm
Dimensions:
in.
mm
106
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 83:
in.
mm
Dimensions:
in.
mm
107
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
108
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
109
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 87:
in.
mm
Dimensions:
in.
mm
110
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Figure 89:
Dimensions:
in.
mm
Dimensions:
in.
mm
111
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 91:
in.
mm
Dimensions:
in.
mm
112
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 93:
in.
mm
Dimensions:
in.
mm
113
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 95:
in.
mm
Dimensions:
in.
mm
114
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Figure 97:
Dimensions:
in.
mm
Dimensions:
in.
mm
115
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
Figure 99:
in.
mm
Dimensions:
in.
mm
116
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
117
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
118
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
119
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
120
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
121
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
122
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
123
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
124
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
125
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
126
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
127
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
128
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
129
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
130
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
131
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
Dimensions:
in.
mm
132
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
133
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
134
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
135
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
136
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
137
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
138
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
139
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
140
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
141
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
142
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
143
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
144
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
145
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
146
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
147
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
148
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
149
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
150
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
Dimensions:
in.
mm
151
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Dimensions:
in.
mm
152
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Section 7Selection
INTRODUCTION ........................................................................................................................................ 154
Overview of Selection Procedure ......................................................................................................... 154
FACTORY-ASSEMBLED CIRCUIT BREAKERS AND SWITCHES .......................................................... 156
T-Frame Circuit Breaker Selection ........................................................................................................ 156
T-Frame Switch Selection ..................................................................................................................... 157
W-Frame Circuit Breaker Selection....................................................................................................... 158
W-Frame Switch Selection .................................................................................................................... 161
Y-Frame Circuit Breaker Selection ....................................................................................................... 163
Y-Frame Switch Selection .................................................................................................................... 164
153
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Introduction
Masterpact circuit breakers are available in three frame sizes:
T-frame circuit breakers: rated up to 800 A (ANSI Certified), up to 1600 A (UL Listed), and up to
1600 A (IEC Rated).
W-frame circuit breakers: rated up to 4000 A (ANSI Certified), up to 3000 A (UL Listed), and up to
4000 A (IEC Rated).
Y-frame circuit breakers: rated up to 5000 A (ANSI Certified), up to 6000 A (UL Listed), and up to
6300 A (IEC Rated).
Within each range, several sensor plugs are available to determine the maximum trip rating of each
circuit breaker. In addition to a sensor plug, an adjustable rating plug is available to get lower ampacity
than that available with the sensor plug.
Masterpact circuit breakers can be equipped with a variety of Micrologic electronic trip unit
configurations, ranging from basic circuit protection to more advanced relay protection and power
metering capabilities. Additionally all electronic trip units within the new Micrologic family are field
interchangeable and upgradeable. Each control unit is also equipped with an interchangeable and
upgradeable adjustable rating plug which is used to select the long-time pickup setting of the circuit
breaker.
NOTE: Masterpact circuit breakers are ordered by sensor plug rating, not ampere trip rating. The trip
rating of the circuit breaker is determined by the setting of the adjustable rating plug. Sensor plugs and
rating plugs are field replaceable.
154
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Model Number
NT
Frame type
NW
NW
Y (wide-construction)
ANSI
UL
UL
IEC
ANSI
ANSI
UL
IEC
ANSI
UL
IEC
800 A
1200 A
1600 A
1600 A
3200 A
4000 A
3000 A
4000 A
5000 A
6000 A
6300 A
254 V
240 V
240 V
240 V
254 V
254 V
240 V
240 V
254 V
240 V
240 V
42 kA
200 kA
200 kA
150 kA
200 kA
100 kA
200 kA
150 kA
200 kA
200 kA
150 kA
508 V
480 V
480 V
440 V
508 V
508 V
480 V
440 V
508 V
480 V
440 V
AC rating
42 kA
100 kA
100 kA
130 kA
200 kA
100 kA
150 kA
150 kA
200 kA
150 kA
150 kA
635 V
600 V
600 V
690 V
635 V
635 V
600 V
690 V
635 V
600 V
690 V
N/A
50 kA
50 kA
42 kA
130 kA
85 kA
100 kA
100 kA
130 kA
100 kA
100 kA
Construction
Drawout
Front-connected terminals
Termination
Ready-to-close contact
Door interlock
Shunt trip
Operations counter
Undervoltage trip
Rack in interlock
Safety Shutter
Rail Padlocking
Spring-charging motor
Mechanical interlocks
LSI
Neutral protection
Contact wear indication
Communications
Ground-fault trip
Power measurement
Expanded memory
Thermal imaging
Table 63:
Feature Type
Basic
Protection
Model Number
2.0
3.0
LSI
5.0
2.0A
3.0A
LSI
5.0A
LSIG
6.0A
LSI
5.0P
LSIG
6.0P
LSI
5.0H
LSIG
6.0H
155
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Table 65:
Frame Rating
800 A
1200 A
1600 A2
Interrupting Rating
254 V
508 V
635 V
NT08N1
42 kA
42 kA
Interrupting Rating
240 V
480 V
600 V
NT08N
50 kA
50 kA
35 kA
NT08H
65 kA
50 kA
50 kA
NT08L11
100 kA
65 kA
NT08L1
200 kA
100 kA
200 kA
100 kA
NT12N
50 kA
50 kA
35 kA
NT12H
65 kA
50 kA
50 kA
NT12L11
100 kA
65 kA
NT12L1
200 kA
100 kA
NT12LF1
200 kA
5100 kA
NT16N
50 kA
50 kA
35 kA
NT16H
65 kA
50 kA
50 kA
NT16L11
100 kA
65 kA
NT16L1
200 kA
100 kA
NT16LF1
200 kA
5100 kA
Fixed-mount only. 1600A UL 489 drawout circuit breakers are not available.
Frame Rating
800 A
1000 A
NT08LF1
Table 66:
440 V
690 V
1000 V
NT08H1
42 kA
42 kA
42 kA
NT08L1
150 kA
130 kA
25 kA
NT10H1
42 kA
42 kA
42 kA
NT10L1
150 kA
130 kA
25 kA
1250 A
NT12H1
42 kA
42 kA
42 kA
1600 A
NT16H1
42 kA
42 kA
42 kA
NOTE: L1F and LF circuit breakers are tested to show the arc flash hazard risk category as referenced
by NFPA 70E.
156
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
800 A
1
Model
Number
254 V
508 V
635 V
NT08NA
42 kA
42 kA
NA
42 kA
NT08HA
42 kA
42 kA
22 kA
42 kA
Table 68:
Frame Rating
800 A
1200 A
1600 A3
Withstand Rating 1
Instantaneous Override
240 V
480 V
600 V
NT08HF
65 kA
50 kA
50 kA
NT08HB2
200 kA
100 kA
N/A
40 kA
10 kA
NT12HF
65 kA
50 kA
50 kA
40 kA
NT12HB2
200 kA
100 kA
N/A
10 kA
NT16HF
65 kA
50 kA
50 kA
40 kA
NT16HB2
200 kA
100 kA
N/A
10 kA
The withstand rating is the fault current (at rated voltage) that the switch will withstand without damage when protected
by a circuit breaker with an equal continuous current rating.
Table 69:
Frame Rating
Interrupting Rating 1
Short-Time (0.5 s) Rating
240 V
440 V
690 V
1000 V
800 A
NT08HA
42 kA
42 kA
42 kA
42 kA
1000 A
NT10HA
42 kA
42 kA
42 kA
42 kA
1250 A
NT12HA
42 kA
42 kA
42 kA
42 kA
1600 A
NT16HA
42 kA
42 kA
42 kA
42 kA
157
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Interrupting Rating
254 V
508 V
635 V
NW08N1
42 kA
42 kA
42 kA
NW08H1
65 kA
65 kA
65 kA
NW08H2
85 kA
85 kA
85 kA
NW08H3
100 kA
100 kA
85 kA
NW08L11
200 kA
200 kA
130 kA
NW08L1F1
200 kA
200 kA
130 kA
NW16N1
42 kA
42 kA
42 kA
NW16H1
65 kA
65 kA
65 kA
NW16H2
85 kA
85 kA
85 kA
NW16H3
100 kA
100 kA
85 kA
NW16L11
200 kA
200 kA
130 kA
NW16L1F1
200 kA
200 kA
130 kA
NW20H1
65 kA
65 kA
65 kA
NW20H2
85 kA
85 kA
85 kA
NW20H3
100 kA
100 kA
85 kA
NW20L11
100 kA
200 kA
130 kA
NW20L1F1
200 kA
200 kA
130 kA
NW32H1
65 kA
65 kA
65 kA
NW32H2
85 kA
85 kA
85 kA
NW32H3
100 kA
100 kA
85 kA
NW40BH1
65 kA
65 kA
65 kA
85 kA
85 kA
85 kA
100 kA
100 kA
85 kA
Frame Rating
800 A
1600 A
2000 A
3200 A
NW40BH3
NOTE: L1F circuit breakers are tested to show the arc flash hazard risk category as referenced by
NFPA 70E.
158
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
800 A
1200 A
1600 A
2000 A
2500 A
3000 A
1
Interrupting Rating
Sensor Plug Rating
240 V
480 V
600 V
NW08N
65 kA
65 kA
50 kA
NW08H
100 kA
100 kA
85 kA
NW08L1
200 kA
150 kA
100 kA
NW08LF1
200 kA
150 kA
100 kA
NW12N
65 kA
65 kA
50 kA
NW12H
100 kA
100 kA
85 kA
NW12L1
200 kA
150 kA
100 kA
NW12LF1
200 kA
150 kA
100 kA
NW16N
65 kA
65 kA
50 kA
NW16H
100 kA
100 kA
85 kA
NW16L1
200 kA
150 kA
100 kA
NW16LF1
200 kA
150 kA
100 kA
NW20N
65 kA
65 kA
50 kA
NW20H
100 kA
100 kA
85 kA
NW20L1
200 kA
150 kA
100 kA
NW20LF1
200 kA
150 kA
100 kA
NW25H
100 kA
100 kA
85 kA
NW25L1
200 kA
150 kA
100 kA
NW30H
100 kA
100 kA
85 kA
NW30L1
200 kA
150 kA
100 kA
NOTE: LF circuit breakers are tested to show the arc flash hazard risk category as referenced by
NFPA 70E.
159
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
800 A
1000 A
1250 A
1600 A
2000 A
2500 A
3200 A
4000 A
Interrupting Rating
Sensor Plug Rating
240 V
440 V
690 V
1150 V
NW08N1
42 kA
42 kA
42 kA
NW08H1
65 kA
65 kA
65 kA
NW08H2
100 kA
100 kA
85 kA
NW08L11
150 kA
150 kA
100 kA
NW08H101
50 kA
NW10N1
42 kA
42 kA
42 kA
NW10H1
65 kA
65 kA
65 kA
NW10H2
100 kA
100 kA
85 kA
NW10L11
150 kA
150 kA
100 kA
NW10H101
50 kA
NW12N1
42 kA
42 kA
42 kA
NW12H1
65 kA
65 kA
65 kA
NW12H2
100 kA
100 kA
85 kA
NW12L11
150 kA
150 kA
100 kA
NW12H101
50 kA
NW16N1
42 kA
42 kA
42 kA
NW16H1
65 kA
65 kA
65 kA
NW16H2
100 kA
100 kA
85 kA
NW16L11
150 kA
150 kA
100 kA
NW16H101
50 kA
NW20H1
65 kA
65 kA
65 kA
NW20H2
100 kA
100 kA
85 kA
NW20H3 1
150 kA
150 kA
100 kA
NW20L11
150 kA
150 kA
100 kA
NW20H101
50 kA
NW25H1
65 kA
65 kA
65
NW25H2
100 kA
100 kA
85
NW25H31
150 kA
150 kA
100
NW25H101
50 kA
NW32H1
65 kA
65 kA
65 kA
NW32H2
100 kA
100 kA
85 kA
NW32H31
150 kA
150 kA
100 kA
NW32H101
50 kA
NW40H1
65 kA
65 kA
65 kA
NW40H2
100 kA
100 kA
85 kA
NW40H31
150 kA
150 kA
100 kA
NW40H101
50 kA
160
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Interrupting Rating 1
254 V
508 V
635 V
Short-Time (1s)
Rating
800 A
NW08HA
65 kA
65 kA
65 kA
65 kA
1600 A
NW16HA
65 kA
65 kA
65 kA
65 kA
2000 A
NW20HA
65 kA
65 kA
65 kA
65 kA
3200 A
NW32HA
65 kA
65 kA
65 kA
65 kA
Table 74:
Frame Rating
(W-Frame)
800 A
1600 A
2000 A
3200 A
Interrupting Rating 1
254 V
508 V
635 V
Short-Time (1s)
Rating
85 kA
NW08HF
100 kA
100 kA
85 kA
NW08HC2
200 kA
200 kA
130 kA
30 kA
NW16HF
100 kA
100 kA
85 kA
85 kA
NW16HC2
200 kA
200 kA
130 kA
30 kA
NW20HF
100 kA
100 kA
85 kA
85 kA
NW20HC2
200 kA
200 kA
130 kA
30 kA
NW32HF
100 kA
100 kA
85 kA
85 kA
Table 75:
Frame Rating
(W-Frame)
Model
Number
254 V
508 V
635 V
800 A
NW08HF
100 kA
100 kA
85 kA
85 kA
1600 A
NW16HF
100 kA
100 kA
85 kA
85 kA
2000 A
NW20HF
100 kA
100 kA
85 kA
85 kA
3200 A
NW32HF
100 kA
100 kA
85 kA
85 kA
Short-Time (1s)
Rating
Table 76:
Frame Rating
Model
Number
240 V
480 V
800 A
NW08HF
100 kA
100 kA
85 kA
40 kA
1200 A
NW12HF
100 kA
100 kA
85 kA
40 kA
1600 A
NW16HF
100 kA
100 kA
85 kA
40 kA
2000 A
NW20HF
100 kA
100 kA
85 kA
40 kA
2500 A
NW25HF
100 kA
100 kA
85 kA
65 kA
3000 A
NW30HF
100 kA
100 kA
85 kA
65 kA
600 V
Instantaneous
Override
The withstand rating is the fault current (at rated voltage) that the switch will withstand without
damage when protected by a circuit breaker with an equal continuous current rating.
161
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
800 A
1200 A
1600 A
2000 A
2500 A
3000 A
Instantaneous
Override
Model
Number
240 V
480 V
NW08HF
100 kA
100 kA
85 kA
40 kA
NW08HB2
200 kA
150 kA
100 kA
35 kA
600 V
NW12HF
100 kA
100 kA
85 kA
40 kA
NW12HB2
200 kA
150 kA
100 kA
35 kA
NW16HF
100 kA
100 kA
85 kA
40 kA
NW16HB2
200 kA
150 kA
100 kA
35 kA
NW20HF
100 kA
100 kA
85 kA
40 kA
NW20HB2
200 kA
150 kA
100 kA
35 kA
NW25HF
100 kA
100 kA
85 kA
65 kA
NW25HB2
200 kA
150 kA
100 kA
65 kA
NW30HF
100 kA
100 kA
85 kA
65 kA
NW30HB2
200 kA
150 kA
100 kA
65 kA
The withstand rating is the fault current (at rated voltage) that the switch will withstand without
damage when protected by a circuit breaker with an equal continuous current rating.
Table 78:
Frame Rating
Withstand Rating 1
240 V
440 V
690 V
Instantaneous
Override
800 A
NW08HF
85 kA
85 kA
85 kA
85 kA
1000 A
NW10HF
85 kA
85 kA
85 kA
85 kA
1250 A
NW12HF
85 kA
85 kA
85 kA
85 kA
1600 A
NW16HF
85 kA
85 kA
85 kA
85 kA
2000 A
NW20HF
85 kA
85 kA
85 kA
85 kA
2500 A
NW25HF
85 kA
85 kA
85 kA
85 kA
3200 A
NW32HF
85 kA
85 kA
85 kA
85 kA
4000 A
NW40HF
85 kA
85 kA
85 kA
85 kA
The withstand rating is the fault current (at rated voltage) that the switch will withstand without
damage when protected by a circuit breaker with an equal continuous current rating.
162
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Frame Rating
800 A
1000 A
1250 A
1600 A
2000 A
2500 A
3200 A
4000 A
Interrupting Rating 1
Model
Number
240 V
440 V
690 V
Short-Time (1s)
1150 V Rating
NW08NA
42 kA
42 kA
42 kA
42 kA
NW08HA
50 kA
50 kA
50 kA
50 kA
NW08HA102
50 kA
50 kA
NW10NA
42 kA
42 kA
42 kA
42 kA
NW10HA
50 kA
50 kA
50 kA
50 kA
NW10HA102
50 kA
50 kA
NW12NA
42 kA
42 kA
42 kA
42 kA
NW12HA
50 kA
50 kA
50 kA
50 kA
NW12HA102
50 kA
50 kA
NW16NA
42 kA
42 kA
42 kA
42 kA
NW16HA
50 kA
50 kA
50 kA
50 kA
NW16HA102
50 kA
50 kA
NW20HA
50 kA
50 kA
50 kA
50 kA
NW20HA102
50 kA
50 kA
NW25HA
50 kA
50 kA
50 kA
50 kA
NW25HA102
50 kA
50 kA
NW32HA
50 kA
50 kA
50 kA
50 kA
NW32HA102
50 kA
50 kA
NW40HA
50 kA
50 kA
50 kA
50 kA
NW40HA102
50 kA
50 kA
Frame Rating
3200 A to 4000 A
5000 A
508 V
635 V
NW32L11
200 kA
200 kA
130 kA
NW40H2
85 kA
85 kA
85 kA
NW40H3
100 kA
100 kA
85 kA
NW40L11
200 kA
200 kA
130 kA
NW50H2
85 kA
85 kA
85 kA
NW50H3
100 kA
100 kA
85 kA
NW50L11
200 kA
200 kA
130 kA
Table 81:
Frame Rating
4000 A
5000 A
6000 A
1
Interrupting Rating
Sensor Plug Rating
240 V
480 V
600 V
NW40H
100 kA
100 kA
85 kA
NW40L1
200 kA
150 kA
100 kA
NW50H
100 kA
100 kA
85 kA
NW50L1
200 kA
150 kA
100 kA
NW60H
100 kA
100 kA
85 kA
NW60L1
200 kA
150 kA
100 kA
163
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
4000 A
5000 A
6300 A
Interrupting Rating
Sensor Plug Rating
240 V
440 V
690 V
NW40BH1
100 kA
100 kA
100 kA
NW40BH2
150 kA
150 kA
100 kA
NW50H1
100 kA
100 kA
100 kA
NW50H2
150 kA
150 kA
100 kA
NW63H1
100 kA
100 kA
100 kA
NW63H2
150 kA
150 kA
100 kA
Frame Rating
Model
Number
254 V
508 V
635 V
Short-Time (1s)
Rating
4000 A
NW40HA
85 kA
85 kA
85 kA
85 kA
5000 A
NW50HA
85 kA
85 kA
85 kA
85 kA
Table 84:
Frame Rating
(Y-Frame)
Model
Number
3200 A
NW32HC2
200 kA
200 kA
130 kA
100 kA
NW40HF
100 kA
100 kA
85 kA
85 kA
4000 A
5000 A
1
2
508 V
635 V
Short-Time (1s)
Rating
NW40HC2
200 kA
200 kA
130 kA
100 kA
NW50HF
100 kA
100 kA
85 kA
85 kA
NW50HC2
200 kA
200 kA
130 kA
100 kA
Table 85:
Frame Rating
(Y-Frame)
Model
Number
4000 A
5000 A
1
254 V
Interrupting Rating 1
Short-Time (1s)
Rating
254 V
508 V
635 V
NW40HF
100 kA
100 kA
85 kA
85 kA
NW50HF
100 kA
100 kA
85 kA
85 kA
Table 86:
Frame Rating
Model
Number
240 V
480 V
600 V
Instantaneous
Override
4000 A
NW40HF
100 kA
100 kA
85 kA
75 kA
5000 A
NW50HF
100 kA
100 kA
85 kA
75 kA
6000 A
NW60HF
100 kA
100 kA
85 kA
75 kA
The withstand rating is the fault current (at rated voltage) that the switch will withstand without
damage when protected by a circuit breaker with an equal continuous current rating.
164
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
4000 A
5000 A
6000 A
Withstand Rating1
240 V
480 V
600 V
Instantaneous
Override
NW40HF
100 kA
100 kA
85 kA
75 kA
NW40HB2
1200 kA
150 kA
100 kA
75 kA
75 kA
NW50HF
100 kA
100 kA
85 kA
NW50HB2
200 kA
150 kA
100 kA
75 kA
NW60HF
100 kA
100 kA
85 kA
75 kA
NW60HB2
200 kA
150 kA
100 kA
75 kA
The withstand rating is the fault current (at rated voltage) that the switch will withstand without
damage when protected by a circuit breaker with an equal continuous current rating.
Table 88:
Frame Rating
Interrupting Rating 1
240 V
440 V
690 V
Short-Time (1s)
Rating
4000 A
NW40BHA
85 kA
85 kA
85 kA
85 kA
5000 A
NW50HA
85 kA
85 kA
85 kA
85 kA
6300 A
NW63HA
85 kA
85 kA
85 kA
85 kA
165
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 1 of 2
For faster quote processing, please use the following request for quotation form. For each section, check the applicable box or enter value
corresponding to your choice. Note: this request for quotation form does not take into account incompatibilities. Orders to be placed on CSSS.
Customer Name:
Date
From
Phone No.
Messages
Location
Fax No.
Quantity:
Square D
Schneider Electric
Standard
ANSI
Type
Number of Poles
UL
IEC
NT
NW
Phone No.:
Fax No.:
Vac
Vdc
Amperes:
Frame rating
Amperes:
Sensor plug rating
Interrupting/Withstand rating: N, N1, NA, L, LF, L1,
L1F, H, H2, H3, H10, HA, HA10, HF, HB, HC
Cradle options:
RFQ No.:
Q2C No.:
Account No.:
Contact Name:
Location:
or Communication
Vac
Vdc
or Communication
Vac
Vdc
Vac
Vdc
Instantaneous
Vac
Vdc
Fixed-time delayed
Vac
Vdc
Vac
Vdc
Adjustable-time delayed
3.0
5.0
3.0A
5.0A
6.0A
(BPFE)
110130 Vac
200240 Vac
Wiring for Cradle (Complete only if ordering cradle without circuit breaker)
Circuit breaker communication module (BCM) wiring
5.0P
6.0P
5.0H
6.0H
Wiring for additional overcurrent trip switch (SDE2) or electrical reset (RES)
Wiring for undervoltage trip (MN) or additional shunt trip (MX2)
Wiring for shunt trip (MX), shunt close (XF) and spring-charging motor (MCH)
Wiring for ready-to-close contact (PF)
Wiring for four additional form C auxiliary switches (push-in terminals) or
2a+2b auxiliary switches (ring terminals) (OF)
Wiring for eight additional form C auxiliary switches (push-in terminals) (OF)
166
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 2 of 2
Cradle Connections
Std
Front-connected
Qty.
(CE)
Qty.
(low-level EF)
4000 A
Front-connected flat
(FCF)
40005000 A
Front-connected "T"
(FCT)
8003200 A
(RCTV)
(RCTH)
2000 A L1/L
3200 A (ANSI)
(RCOV)
(RCOV)
40006300 A
(RCTV)
(RCTH)
Door interlock
(FCF)
(FCT)
(CT)
(CD)
Choose one:
Connected/Closed switch (max. qty.: 8)
Front-connected flat
Front-connected "T"
Rear-connected
low-level
8003200 A
standard
Terminal shield
qty/type
qty/type
Rail padlocking
qty/type
Cradle
Miscellaneous Accessories
Brkr
Shutter
(Set of 2)
(long)
(short)
Test Equipment
Castell
Cradle:
Total $
Delivery Schedule
Circuit breaker and cradle to be shipped together
Cradle to be shipped prior to circuit breaker
167
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
168
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
8
9
10
1.5
.8
.9
1
.7
.6
.5
.4
.3
.2
.15
.07
.08
.09
.1
.06
.05
B48095-613-01.eps
10000
9000
8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
2000
2000
1500
1500
1000
900
800
1000
900
800
700
700
600
600
500
500
400
400
300
300
200
200
GROUND-FAULT
PICKUP
x In
150
150
100
90
80
100
90
80
70
70
60
60
50
50
40
40
30
30
0.5
0.3
0.7 0.9
20
20
15
15
0.4
10
9
8
TIME IN SECONDS
10
9
8
1.5
1.5
ON
0.4
1
.9
.8
DELAY
SECONDS AT 1 x In
0.1
0.2
0.3
0.4
.7
0.3
.6
1
.9
.8
.7
.6
ON
O
0.1
.3
0.4 OFF
ON
GROUND-FAULT
DELAY BANDS
I2t ON
.4
.5
0.2
.5
.3
0.3 OFF
MAXIMUM
UNRESTRAINED
GROUND-FAULT
DELAY
.2
.15
.4
.2
0.2 OFF
0.1 OFF
.1
.09
.08
.07
.15
.1
.09
.08
.07
.06
.06
.05
.05
GROUND-FAULT
DELAY BANDS
I2t OFF
(FIXED DELAY)
.04
.03
.04
.03
0
.02
.02
1 CYCLE
.015
.015
.01
.009
.008
.01
.009
.008
2 CYCLE
8
9
10
1.5
.8
.9
1
.7
.6
.5
.4
.3
.2
.15
.08
.09
.1
.005
.07
.006
.005
.06
.007
.006
.05
.007
169
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
10000
9000
8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
2000
2000
1500
1500
1000
900
800
1000
900
800
700
700
600
600
500
500
400
400
300
300
200
200
150
150
100
90
80
60
100
90
80
GROUND-FAULT
PICKUP
x In
70
70
60
50
50
40
40
0.2
30
0.3
0.5
0.7 0.9
30
20
20
15
15
10
9
8
10
9
8
0.4
0.6
0.8 1.0
0.4
ON
0.2
ON
TIME IN SECONDS
8
9
10
1.5
.8
.9
1
.7
.6
.5
.4
.3
.2
.15
.08
.09
.1
.07
.06
.05
B48095-613-02.eps
1.5
1.5
DELAY
SECONDS AT 1 x In
0.1
0.2
0.3
0.4
1
.9
.8
.7
.6
1
.9
.8
.7
.6
.5
.5
ON
0.3
GROUND-FAULT
DELAY BANDS
I2t ON
.4
.3
0.3 OFF
ON
0.1
.2
.4
.3
MAXIMUM
UNRESTRAINED
GROUND-FAULT
DELAY
.15
0.4 OFF
.2
0.2 OFF
0.1 OFF
.1
.09
.08
.07
.15
.1
.09
.08
.07
.06
.06
.05
.05
GROUND-FAULT
DELAY BANDS
I2t OFF
(FIXED DELAY)
.04
.03
.04
.03
0
.02
.02
1 CYCLE
.015
.015
.01
.009
.008
.01
.009
.008
2 CYCLE
8
9
10
1.5
.8
.9
1
.7
.6
.5
.4
.3
.2
.15
.08
.09
.1
.005
.07
.006
.005
.06
.007
.006
.05
.007
170
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
10000
9000
8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
2000
2000
1500
1500
1000
900
800
1000
900
800
700
700
600
600
500
500
400
400
300
300
200
200
800 A
100
90
80
150
100
90
80
70
960 A
70
GROUND-FAULT
PICKUP
x In
1120 A
150
60
60
50
640 A
50
40
40
30
20
20
880 A
30
15
15
10
9
8
1040 A
10
9
8
6
5
720 A
6
5
4
1200 A
TIME IN SECONDS
8
9
10
1.5
.8
.9
1
.7
.6
.5
.4
.3
.2
.15
.07
.08
.09
.1
.06
.05
AMPERES x 103
500 A
1.5
0.4
1
.9
.8
1.5
DELAY
SECONDS AT 1 x In
0.1
0.2
0.3
0.4
ON
O
0.2
.7
.6
1
.9
.8
.7
.6
0.1
.3
0.4 OFF
ON
GROUND-FAULT
DELAY BANDS
I2t ON
.4
.5
0.3
.5
ON
0.3 OFF
MAXIMUM
UNRESTRAINED
GROUND-FAULT
DELAY
.2
.15
.4
.3
.2
0.2 OFF
0.1 OFF
.1
.09
.08
.07
.15
.1
.09
.08
.07
.06
.06
.05
.05
GROUND-FAULT
DELAY BANDS
I2t OFF
(FIXED DELAY)
.04
.03
.04
.03
0
.02
.02
1 CYCLE
.015
.015
.01
.009
.008
.01
.009
.008
2 CYCLE
.007
.007
.006
.006
.005
8
9
10
1.5
.8
.9
1
.7
.6
.5
.4
.3
.2
.15
.08
.09
.1
.07
.06
.05
.005
AMPERES x 103
171
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B48095-613-04.eps
Figure 166: Micrologic 5.0/6.0 A/P/H Trip Units: Long-Time Pickup and Delay, Short-Time Pickup, and I2t OFF Delay
Micrologic 5.0/6.0 A/P/H Trip Units
80
90
100
70
60
50
40
30
20
15
8
9
10
1.5
.8
.9
1
.7
.6
.5
10000
9000
8000
7000
7000
6000
6000
5000
5000
LONG-TIME PICKUP
x In = Ir
3000
3000
2000
2000
1500
1500
1000
900
800
1000
900
800
700
700
600
600
24
16
500
400
300
300
200
200
150
150
100
90
80
100
90
80
20
70
70
12
60
60
50
50
40
40
30
30
1
.5
20
20
24
15
15
16
10
9
8
TIME IN SECONDS
10
9
8
LONG-TIME
DELAY BANDS
SECONDS AT 6 x Ir
7
6
7
6
1.5
1.5
8
1
.9
.8
SHORT-TIME
PICKUP
x Ir
.7
1.5
500
400
2 2.5
1
.9
.8
SHORT-TIME
DELAY I2t OFF
(FIXED-TIME DELAY)
SECONDS AT 10 x Ir
10
.6
.6
.5
.4
0.4 OFF
.4
.3
.3
0.3 OFF
MAXIMUM
UNRESTRAINED
SHORT-TIME
DELAY
.2
0.2 OFF
0.1 OFF
.1
.09
.08
NOTE:
1. There is a thermal-imaging effect that can act to
shorten the long-time delay. The thermal-imaging
effect comes into play if a current above the longtime delay pickup value exists for a time and then is
cleared by the tripping of a downstream device or
the circuit breaker itself. A subsequent overload will
cause the circuit breaker to trip in a shorter time than
normal. The amount of time delay reduction is
inverse to the amount of time that has elapsed since
the previous overload. Approximately twenty
minutes is required between overloads to completely
reset thermal-imaging.
2. The end of the curve is determined by the
interrupting rating of the circuit breaker.
3. With zone-selective interlocking ON, short-time
delay utilized, and no restraining signal, the
maximum unrestrained short-time delay time band
applies regardless of the setting.
.7
.5
.2
4000
4000
.15
.15
.1
.09
.08
.07
.07
.06
.06
.05
.05
.04
.04
.03
.03
0
.02
.02
1 CYCLE
.015
.015
.01
.009
.008
.01
.009
.008
2 CYCLE
CURRENT IN MULTIPLES OF Ir
(Ir = LONG-TIME SETTING x In)
80
90
100
70
60
50
40
30
20
15
8
9
10
1.5
.8
.9
1
.005
.7
.006
.005
.6
.007
.006
.5
.007
172
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
70
60
50
40
30
20
15
8
9
10
1.5
.7
.8
.9
1
.6
.5
10000
9000
8000
7000
7000
6000
6000
5000
5000
4000
4000
3000
3000
2000
2000
1500
1500
1000
900
800
1000
900
800
700
700
600
600
500
500
400
400
300
300
200
200
150
150
SHORT-TIME
PICKUP
x Ir
100
90
80
1.5
70
2.5
100
90
80
8 10
70
60
60
50
50
40
40
30
30
20
20
15
15
10
9
8
10
9
8
0.4
ON
4
3
4
3
0.2
ON
0.1
TIME IN SECONDS
1.5
1.5
0.3
ON
ON
1
.9
.8
1
.9
.8
.7
.7
.6
.6
.5
.5
0.4 ON
.4
SHORT-TIME
DELAY I2t ON
SECONDS AT 10 x Ir
.3
.15
.3
.2
0.2 ON
0.1 ON
.1
.09
.08
.15
.1
.09
.08
.07
.07
.06
.06
.05
.05
.04
.04
.03
.03
.02
.4
0.3 ON
MAXIMUM
UNRESTRAINED
SHORT-TIME
DELAY
.2
NOTE:
.02
1 CYCLE
.015
.015
.01
.009
.008
.01
.009
.008
2 CYCLE
CURRENT IN MULTIPLES OF Ir
(Ir = LONG-TIME SETTING x In)
80
90
100
70
60
50
40
30
20
15
8
9
10
1.5
.8
.9
1
.005
.7
.006
.005
.6
.007
.006
.5
.007
173
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
"
#
10 x
2x
3x 4x
6x 8x
12 x 15 x
!
!
174
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
70
60
50
40
30
20
15
8
9
10
1.5
.8
.9
1
.7
.6
.5
10000
9000
8000
7000
7000
6000
6000
5000
5000
LONG-TIME PICKUP
x In = Ir
4000
3000
2000
2000
1500
1500
1000
900
800
1000
900
800
700
700
600
600
500
500
400
400
24
300
16
200
200
150
150
100
90
80
100
90
80
70
70
60
60
50
50
LONG-TIME DELAY
SECONDS AT 6 x Ir
40
30
40
30
20
12
20
20
8
4
15
15
TIME IN SECONDS
24
10
9
8
4000
3000
300
10
9
8
16
.5
1.5
1.5
1
.9
.8
1
.9
.8
.7
.7
.6
.6
.5
.5
.4
.4
.3
.3
.2
.2
.15
.15
.1
.09
.08
.1
.09
.08
.07
.07
.06
.06
.05
.05
.04
.04
.03
.03
.02
.02
1 CYCLE
.015
.015
.01
.009
.008
.01
.009
.008
2 CYCLE
CURRENT IN MULTIPLES OF Ir
(Ir = LONG-TIME SETTING x In)
80
90
100
70
60
50
40
30
20
15
8
9
10
1.5
.8
.9
1
.005
.7
.006
.005
.6
.007
.006
.5
.007
175
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
"
#
5x
10 x
1.5 x 2 x
3x 4x
6x 8x
12 x
!
!
176
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
70
60
50
40
30
20
15
8
9
10
1.5
.7
.8
.9
1
.6
.5
B48095-613-09.eps
10000
9000
8000
7000
7000
6000
6000
5000
5000
4000
4000
LONG-TIME PICKUP
x In = Ir
3000
3000
2000
2000
1500
1500
1000
900
800
1000
900
800
700
700
600
600
24
16
500
500
400
400
300
300
200
200
150
150
100
90
80
100
90
80
20
70
70
12
60
60
50
50
40
40
30
30
1
.5
20
20
24
15
15
16
10
9
8
10
9
8
LONG-TIME
DELAY BANDS
SECONDS AT 6 x Ir
TIME IN SECONDS
7
6
1.5
1.5
NOTE:
1. There is a thermal-imaging effect that can act to
shorten the long-time delay. The thermal-imaging
effect comes into play if a current above the long-time
delay pickup value exists for a time and then is cleared
by the tripping of a downstream device or the circuit
breaker itself. A subsequent overload will cause the
circuit breaker to trip in a shorter time than normal. The
amount of time delay reduction is inverse to the
amount of time that has elapsed since the previous
overload. Approximately twenty minutes is required
between overloads to completely reset thermalimaging.
2. The end of the curve is determined by the short-time
setting.
3. Total clearing times shown include the response times
of the trip unit, the circuit breaker opening, and the
extinction of current.
4. Overload indicator illuminates at 100%.
8
1
.9
.8
SHORT-TIME
PICKUP
x Ir
.7
1.5
1
.9
.8
10
6
2 2.5
.7
.6
.6
.5
.5
.4
.4
.3
.3
.2
.2
.15
.15
.1
.09
.08
.1
.09
.08
.07
.07
.06
.06
.05
.05
.04
.04
.03
.03
.02
.02
1 CYCLE
.015
.015
.01
.009
.008
.01
.009
.008
2 CYCLE
CURRENT IN MULTIPLES OF Ir
(Ir = LONG-TIME SETTING x In)
80
90
100
70
60
50
40
30
20
15
8
9
10
1.5
.8
.9
1
.005
.7
.006
.005
.6
.007
.006
.5
.007
177
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Inst.
Override
(kA RMS)
+/- 10%
24
None
None
24
None
None
None
None
24
None
None
None
None
None
None
24
85
85
85
85
85
85
24
35
24
35
24
35
24
117
117
117
None
None
None
None
None
None
85
85
85
85
85
85
35
35
35
117
117
117
24
None
24
None
10
None
Inst.
Override
(kA RMS)
+/- 10%
NW08N a
24
NW08N
40
NW12N
40
NW16N
40
NW20N
40
NW08H a
24
NW08H
40
NW12H
40
NW16H
40
NW20H
40
NW25H
65
NW30H
65
NW40H
75
NW50H
75
NW60H
75
NW08L a
24
NW08L
35
NW08LF
24
NW12L
35
NW12LF
24
NW16L
35
NW16LF
24
NW20L
65
NW20LF
24
NW25L
65
NW30L
65
NW40L
75
NW50L
75
NW60L
75
NW08HF
40
NW12HF
40
NW16HF
40
NW20HF
40
NW25HF
65
NW30HF
65
NW40HF
75
NW50HF
75
NW60HF
75
NW08HB
35
NW12HB
35
NW16HB
35
NW20HB
65
NW25HB
65
NW30HB
65
NW40HB
75
NW50HB
75
NW60HB
75
NT08N a
24
NT08N
40
NT12N
40
NT16N
40
NT08H a
24
NT08H
40
NT12H
40
NT16H
40
NT08L1
10
NT12L1
10
NT16L1
10
NT08L
10
NT08LF
10
NT12L
10
NT16L
10
NT12LF
10
NT08HF
40
NT12HF
40
a Maximum sensor plug 250 A
UL CB
Model No.
Note:
Faults at or above instantaneous override value
will be cleared at 25 msec or less.
IEC CB
Model No.
NW08N1
NW10N1
NW12N1
NW16N1
NW08H1
NW10H1
NW12H1
NW16H1
NW20H1
NW25H1
NW32H1
NW40H1
NW50H1
NW63H1
NW08H2 a
NW08H2
NW10H2
NW16H2
NW20H2
NW25H2
NW32H2
NW40H2
NW50H2
NW63H2
NW20H3
NW25H3
NW32H3
NW40H3
NW08L1 a
NW08L1
NW10L1
NW12L1
NW16L1
NW20L1
NW08H10
NW10H10
NW12H10
NW16H10
NW20H10
NW25H10
NW32H10
NW40H10
NW08NA
NW10NA
NW16NA
NW08HA
NW10HA
NW12HA
NW16HA
NW20HA
NW25HA
NW32HA
NW40HA
NW50HA
NW63HA
NW08HF
NW10HF
NW12HF
NW16HF
NW20HF
NW25HF
NW32HF
NW40HF
NW08HA10
NW10HA10
NW12HA10
NW16HA10
NW20HA10
NW25HA10
NW32HA10
NW40HA10
NT08H1
NT10H1
NT12H1
NT16H1
NT08L1
NT08H10
NT10H10
NT12H10
NT16H10
NT08HA
NT10HA
NT12HA
NT16HA
NT08HA10
NT10HA10
NT12HA10
NT16HA10
Inst.
Override
(kA RMS)
+/- 10%
None
None
None
None
None
None
None
None
None
None
None
None
None
None
24
85
85
85
85
85
85
85
117
117
65
65
65
65
24
35
35
35
35
35
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
85
85
85
85
85
85
85
85
None
None
None
None
None
None
None
None
None
None
None
None
10
None
None
None
None
None
None
None
None
None
None
None
None
POWERPACT / HORIZON /
SELECT / COMPACT
UL-IEC CB
Model No.
RG 600
RG 800
RG 1000
RG 1200
RG 1600
RG 2000
RG 2500
RJ 600
RJ 800
RJ 1000
RJ 1200
RJ 1600
RJ 2000
RJ 2500
RK 600
RK 800
RK 1000
RK 1200
RK 1600
RK 2000
RK 2500
RL 600
RL 800
RL 1000
RL 1200
RL 1600
RL 2000
RL 2500
PG 250
PG 400
PG 600
PG 800
PG 1000
PG 1200
PJ 250
PJ 400
PJ 600
PJ 800
PJ 1000
PJ 1200
PK 250
PK 400
PK 600
PK 800
PK 1000
PK 1200
PL 250
PL 400
PL 600
PL 800
PL 1000
PL 1200
IEC CB
Model No.
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
NS
800b N
1000b N
1250b N
1600b N
2000 N
2500 N
3200 N
800b H
1000b H
1250b H
1600b H
2000 H
2500 H
3200 H
630b N
800 N
1000 N
1250 N
1600 N
630b H
800 H
1000 H
1250 H
1600 H
630b L
800 L
1000 L
1250 L
1600 L
Inst.
Override
(kA RMS)
+/- 10%
57
57
57
57
57
57
57
48 q
48 q
48 q
48 q
48 q
48 q
48 q
57
57
57
57
57
57
57
48 q
48 q
48 q
48 q
48 q
48 q
48 q
24
24
24
24
24
24
7
10
10
10
10
10
24
24
24
24
24
24
7
10
10
10
10
10
Inst.
Override
(kA RMS)
+/- 10%
57
57
57
57
57
57
57
48 q
48 q
48 q
48 q
48 q
48 q
48 q
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
178
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AUTOMATIC RANGE:
NO USER CONFIGURABLE SETTINGS
.5
.4
.3
.2
TIME IN SECONDS
.15
.1
.09
.08
.07
.06
.05
.04
.03
.02
.015
.01
.009
.008
.007
.006
400
500
600
700
800
900
1000
500
600
700
800
900
1000
300
400
200
150
70
80
90
100
60
50
40
30
20
15
8
9
10
.005
2 In - NW08
Figure 174: Masterpact NT Low Arc Flash Circuit Breaker: L1F and LF
Masterpact NT Low Arc Flash Circuit Breaker
CHARACTERISTIC TRIP CURVE NO. 613-16
(LF) 8001200 A, 60 Hz
1
.9
.8
.7
.6
AUTOMATIC RANGE:
NO USER CONFIGURABLE SETTINGS
.5
.4
.3
.2
TIME IN SECONDS
.15
.1
.09
.08
.07
.06
.05
.04
.03
.02
.015
.01
.009
.008
.007
.006
2 In - NT08
300
200
150
80
90
100
70
60
50
40
30
20
15
8
9
10
.005
179
20002010 Schneider Electric
All Rights Reserved
09/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com