You are on page 1of 14

Section 5

Fire Safety
Overview

Section content

This section contains the following topics.


Topic

Page

General Information

5-1

Fire Prevention

5-2

Fire Response and Training

5-3

Firefighting Equipment

5-6

Flammables and Combustibles

5-11

Offshore Operating Guidelines

5-12

Smoking and Smoking Materials

5-13

General Information

General rules

This section provides guidelines regarding fires on Company property. Fires, no


matter how small, must be reported to in-country management immediately. A formal
report should include all known or reasonably surmised details, as additional reports
may be required by governmental agencies.
Fire doors, such as doors to an interior stairwell, should remain closed.

Definitions

Flammable liquids
A liquid having a flash point below 100F and a vapor pressure exceeding 40 psi
absolute at 100F.

Combustible liquids
A liquid having a flash point at or above 100F but less than 200F.
Continued on next page

March 1999

Fire Safety

5-1

General Information, Continued

For more
information

For more information, refer to the ECI OIMS Standard Systems:

Work management

Operating Procedures

Personnel Safety Management

Fire Prevention

Housekeeping

Good housekeeping and equipment maintenance must be followed to minimize fire


hazards.
The area immediately adjacent to a lease, well equipment and storage areas must
be kept free of combustible debris and dry weeds.

Furniture

Furniture must be arranged to avoid contact with heaters.

Space heaters

Open-type space heaters should not be used in gas plant or compressor facilities.

Automotive
equipment and
other ignition
sources

Unless properly permitted, automotive equipment and other ignition sources are
prohibited within the firewall or fenced enclosure of a tank battery or other facilities
designated by field management.

Burning
combustible
materials

Oil and gasoline from leaks should not be burned unless it is being done in
accordance with both the local regulatory requirements and the Esso Waste
Management Guidelines .

In the absence of firewalls or enclosures, automotive equipment and other ignition


sources must be kept a safe distance (generally 50 feet) from these facilities. If it is
not possible or necessary to maintain this 50-foot distance, then a safe distance
must be determined considering wind, weather, terrain, and other conditions.

The burning of waste oil, grass, brush, rubbish, or other combustible material is
prohibited without supervisory authorization and required permits. Extreme care
must be taken when working in dry woods, brush, marshes, and prairies.
Continued on next page

5-2

Fire Safety

March 1999

Fire Prevention, Continued

Ice and paraffin


plugs

Lines containing hydrocarbons or combustible materials under pressure must not be


fired to remove ice or paraffin plugs.

Reporting and
repairing
hydrocarbon
leaks

All hydrocarbon leaks must be reported and, if practical, repaired immediately. If


immediate repair is not possible, adequate warning signs must be posted, and extra
precautions against fires must be instituted.

Testing for gas


leaks

When testing for gas leaks, use soapsuds, an approved leak detector fluid, or an
approved combustible gas meter. Open flames must not be used.

Iron sulfide

Dry iron sulfide will spontaneously ignite when it comes in contact with air, so it must
be kept wet to prevent this problem.

In the event of a significant, unexpected release of hydrocarbons, ignition sources in


the affected area must be shut down immediately.

REFERENCE: Section 3, Chemical and Product Safety

Fire Response and Training

Personnel
requirements

Fighting fires is a dangerous operation. Personnel fighting fires must be properly


trained and equipped. They should understand their responsibilities and limitations.

Basic rules

Personnel expected to respond to initial fires must be trained in the use of portable
extinguishers and other designated equipment.
Fire drills must be held at regular intervals to familiarize personnel with their
responsibilities in the event of a fire.
Personnel assigned to enclosed buildings where automatic extinguishing systems
are employed should be instructed to vacate the building in the event of extinguisher
discharge.
Only designated and trained personnel should attempt to extinguish a fire that has
advanced beyond the initial stage.
Continued on next page

March 1999

Fire Safety

5-3

Fire Response and Training, Continued

Fire response
procedure: Initial
stage

Listed below are the actions for responding to a fire in the initial stage.

Step

Action

Activate an alarm if possible.

Attempt to extinguish Use a portable hand extinguisher or other


designated equipment to control and extinguish the fire.
NOTE: If the fire is not controlled within the first minute, back out and either
get help, or evacuate.

Notify proper personnel Contact the supervisor and provide him or her
with:

The location

The time the fire was observed

Any actions taken to contain the fire

Isolate the fuel source. If necessary and safe to do so, follow local
procedures to isolate the source of fuel to the fire area.

Continued on next page

5-4

Fire Safety

March 1999

Fire Response and Training, Continued

Fire response
procedure:
Beyond
initial stage

Listed below are the actions for responding to a fire that has developed beyond the
initial stage.

Step

Survival
techniques

Action

Activate an alarm if possible.

Notify proper personnel Contact the supervisor and communicate:

The location

The time the fire was observed

Any actions taken to contain the fire

Isolate the fuel source. If necessary and safe to do so, follow local
procedures to isolate the source of fuel to the fire area.

When applicable, assist the fire brigade or outside agencies by identifying


and communicating additional hazards in the fire area.

Fire response In some areas, the fire brigade or outside agency may
handle the response (onshore).

Personnel must be familiar with the following survival techniques if trapped by a fire:

Be aware of the location of designated fire exits.

Understand evacuation procedures at the work location.

Do not use elevators. Use designated exits.

If caught in a smoke-filled area, crawl on the floor and take short breaths through
the nose. If possible, hold a cloth in front of the face.

Before opening a door, touch it to check if it is hot. If it is hot, do not open it.

If unable to safely exit a fire or smoke-filled area:


Proceed to a room with an outside window.
Close the door to isolate the room from the smoke-filled hallway.
Move to a window.
Signal for help.

March 1999

Fire Safety

5-5

Firefighting Equipment

Basic rules

Firefighting equipment is for fire use only and must be kept in its designated place at
all times.
All fire protection equipment must be located in designated areas which are clearly
identified with appropriate markings (e.g., warehouses, canteens, offices, living
quarters, etc.). This equipment should be located near likely fire hazards and must
also be accessible to operating personnel.
Due to the probability of electrostatic charge generation, CO2 extinguishers must not
be discharged into any space containing a flammable atmosphere, unless there is a
fire.

Local standards

The number, type, and location of extinguishers must meet, as a minimum, local
guidelines and standards if guidelines and standards are more stringent than Essoestablished guidelines.

Maintenance and
inspection

A qualified person must perform maintenance and inspection of fire equipment. All
fire hoses and foam stations must be inspected annually or per regulatory and
Company requirements for that work area.

Automatic fire
protection
system

In buildings equipped with an automatic fire protection system, all doors must remain
closed. The automatic louver closure and exhaust fan shutdown system must be
operable.
NOTE: Adapters should be available to connect municipal fire equipment to existing
equipment when applicable.
Continued on next page

5-6

Fire Safety

March 1999

Firefighting Equipment, Continued

Fire extinguisher
codes and uses

The chart below describes the symbols, designation codes, and extinguishing
agents that should be used for the different types of fires.

If the type of fire is...

Then this extinguisher


symbol applies...

and it contains one of


these extinguishing
agents...

Common Combustibles
(wood, cloth, rubber, or
plastic)

Water

Dry chemical

Flammable Liquids
(flammable materials,
combustible liquids, or
gas)

Dry chemical

CO2

Electrical

Dry chemical

CO2

Burning Metals
(magnesium, titanium,
batteries)

Dry powder

Company
vehicles

All assigned Company vehicles must be equipped with an approved fire extinguisher.
The size of the extinguisher should be determined by the anticipated need; however
the minimum size is 5 pounds.

Fire extinguisher
upkeep

All fire extinguisher hose nozzles must be kept free of obstructions at all times. In
areas where insects tend to nest, the nozzle must be protected against plugging.
Welding on the outer shell of a fire extinguisher is prohibited.
Instruction labels on fire extinguishers must be maintained.
Continued on next page

March 1999

Fire Safety

5-7

Firefighting Equipment, Continued

Fire extinguisher
inspections

All portable and semi-portable extinguishers must be inspected monthly to ensure


that they:

Are in their designated places

Have not been tampered with

Have a durable tag securely attached to show the maintenance or recharge date

Have no obvious physical damage, corrosion, or other impairments.

A more thorough inspection should be performed:

Recharging and
replacing fire
extinguishers

Every six months in open buildings or outside

Yearly inside air-conditioned buildings

Fire extinguishers must be recharged, repaired, or replaced as needed.


Partially-used fire extinguishers must be discharged of pressure and then recharged
or replaced immediately.
Fire extinguishers removed from the premises to be recharged must be replaced
immediately with spare extinguishers.

Hydrostatic
testing

If a portable extinguisher shows evidence of corrosion, deterioration, or mechanical


damage, hydrostatic testing at 75% of factory test pressures must be conducted.
Fire extinguisher hoses with shut-off nozzles at the discharge end must be included
in the hydrostatic test.
Nitrogen and CO2 cylinders that have been discharged must be hydrostatically tested
if more than 5 years have elapsed since the last test.
CO2 cartridges used for cartridge type extinguishers should only be filled by Original
Equipment Manufacturers (OEM) qualified personnel following manufacturers'
recommendations.
Prior to recharging portable extinguishers, a visual internal inspection by qualified
personnel should be performed.
Continued on next page

5-8

Fire Safety

March 1999

Firefighting Equipment, Continued

Hydrostatic
testing,
(continued)

The table below describes the intervals in which hydrostatic tests must be conducted.

Type of Extinguisher

Hydrostatic Test
Interval

CO2 extinguisher
Example: A General 15-pound extinguisher.
Stored pressure water/foam extinguisher
Example: An extinguisher with a stainless steel shell.
Pressurized-type, dry-chemical extinguisher
Example: An extinguisher with a mild steel shell such as
the Safety 1st 20-pound extinguisher.
Nitrogen cylinder (wheel units only).

5 years

Powder tank and hose (wheel units).

12 years

CO2 cylinder (fixed system).

12 years

Cartridge dry chemical unit with brazed-brass or mildsteel shells such as Ansul or General.

5 years

5 years
12 years

5** years

** If the retest markings include a five-point star, then the retest interval may be
extended to 10 years.
IMPORTANT: Use of Halon is prohibited.
For more information on hydrostatic testing requirements, refer to the National Fire
Protection Association, NFPA 12-A and Local Regulatory Authority regulations.
Continued on next page

March 1999

Fire Safety

5-9

Firefighting Equipment, Continued

Fixed systems

Firewater
systems

Sprinkler and foam systems must be kept in good operating condition and
periodically inspected in accordance with appropriate Company and government
standards . The following precautions apply to fixed dry-chemical and carbon dioxide
extinguishing systems:

Expellant gas containers must be inspected and checked semi-annually for


pressure and weight against the required minimums.

The complete system, including alarms, shutdowns, and other associated


equipment must be thoroughly inspected and checked for proper operation by a
qualified inspector at least annually.

Dry chemical containers must be sampled annually from the top, at the center,
and near the wall of the container to determine the existence of packing or
deterioration.

Records of inspections and tests must be maintained. The preventive


maintenance report or a similar form is typically used for this purpose. The
report should be reviewed monthly to ensure that all inspections are being made
and that defective equipment is being promptly repaired or replaced.

Firewater systems, except on some offshore platforms, should have a primary and
secondary power source. They should be remotely located from potential fire hazard
areas. These facilities must be started and operated weekly and appropriate
personnel must be familiar with starting and operating procedures.
Firewater systems must be tested after any maintenance or modifications are made
to the pump, driver, or other associated equipment.

5-10

Fire Safety

March 1999

Flammables and Combustibles

Storage of
flammables and
combustibles

The following flammables and combustibles must not be allowed near stoves,
furnaces, or gas fires:

Containers of oil, kerosene, and solvents

Oily rags

Waste

Debris and

Other combustible items.

REFERENCE: For more information, refer to the National Fire Protection Association,
NFPA 30 and Local Regulatory Authority regulations.
Storing in
buildings

Buildings in which flammables or combustible liquids are handled and stored must
be adequately ventilated. Buildings that store large quantities of flammable liquids
may need design and engineering evaluation.

Storing large
amounts

Storage of greater than 10 gallons of flammable and combustible liquids requires


use of:

Outside storage

Approved storage rooms

Approved cabinets

Warehouses

Glass containers

Gasoline, kerosene, or other flammable/combustible liquids must not be placed in


glass containers unless designated or approved for transportation or storage.

Oil-soaked
clothing

Oil-soaked clothing should be removed and properly disposed of or cleaned.

Oily waste

Oily waste must be disposed of properly because of the possibility of spontaneous


combustion. Approved metal containers must be provided for the disposal of oily
rags and other oil-soaked materials. These containers must be emptied often
enough to keep the premises in a safe, sanitary condition.
Continued on next page

March 1999

Fire Safety

5-11

Flammables and Combustibles, Continued

Flammable/
Combustible
liquids
as cleaning
agents

The use of flammable liquids as cleaning agents is prohibited.


While combustible liquids (such as kerosene, diesel and varsol) may be used in
cleaning machinery, they should not be used on hot metal surfaces or sprayed
around operating machinery where there is a source of ignition.
NOTE: Section 10, Electrical Safety, "Cleaning Electrical Apparatus"

Paint, insect
sprays and
aerosol sprays

Because paint, insect sprays, aerosol sprays and paint removers are usually
flammable, they should not be used near open flames or other sources of ignition.
NOTE: Read the labels on the containers

Offshore Operating Guidelines

Offshore
operating
guidelines

5-12

Offshore platform operations must add the following requirements to the other
guidelines contained in this chapter:

Fire and evacuation drills for each work group must be held in accordance with
governmental regulations and Esso guidelines . A written report of such drills
must be made on the appropriate forms and communicated to management.

In the absence of designated smoking areas, smoking is restricted to the


quarters area. Smoking in bed is prohibited.

Gasoline powered engines and compressors, gasoline fuel, and open fires are
prohibited on offshore platforms without special approval from appropriate
Production Organization Management.

Automatic nozzle water-spray and foam systems must be inspected and tested
at least quarterly.

A fire extinguisher of appropriate size should be located near each room of the
living quarters.

Fire Safety

March 1999

Smoking and Smoking Materials

General rules

Safety tips

The following general safety rules apply:

Cigarette lighters must not be carried onto helicopters or to offshore locations.

Cigarette, cigar, or pipe smoking must be confined to specifically designated


areas.

Attics of all buildings must be designated as "No Smoking" areas, and "No
Smoking" signs must be prominently displayed.

Matches and cigarette lighters must not be carried into an area where a
potentially explosive atmosphere exists.

Cigarette lighters must not be carried into an area where welding or open flame
burning is taking place.

On offshore platforms, smoking must only be allowed in the designated smoking


room inside the living quarters. Smoking must be strictly prohibited in all other
areas.

At drilling and workover locations, designated and posted "No Smoking" areas
must include as a minimum:

The rig floor

Cellar areas

Areas near the shale shaker, mud tanks, and fuel tanks

Never leave a burning cigarette unattended. Where smoking is allowed in buildings


or offices, place cigarettes or cigars well inside of ashtrays to prevent them from
falling out. Never lay cigarettes or cigars on desks, in wastebaskets, or on the floor.
A wastebasket is the worst substitute for an ashtray; even extinguished matches and
tobacco are often hot enough to ignite other materials. Empty the contents of
ashtrays into metal containers used only for this purpose.
Wastebaskets must not be used as ashtrays and ashtrays must not be emptied into
wastebaskets until the ashes have cooled.
Continued on next page

March 1999

Fire Safety

5-13

Smoking and Smoking Materials, Continued

No-smoking
areas

Smoking in operating areas is prohibited except where specifically designated by


management.
Lighted cigarettes, cigars, or pipes are not to be carried on elevators.
Any area subject to contamination by flammable liquids or gas must be designated a
"No Smoking" area by In-country Management. A "No Smoking" sign must be
displayed in the area.
Smoking must be prohibited in the following areas, whether or not a "No Smoking"
sign is displayed:

Formation
fracturing and
high-pressure
pumping

5-14

In records storage or filing areas

In computer rooms while handling computer tapes or paper

Around shale shakers

On or under the floors of drilling and workover rigs

Near tank batteries

Next to oil and gas wells

In any area suspected of containing flammable vapors.

During all phases of the formation fracturing and high-pressure pumping of liquid
hydrocarbons operation, smoking and smoking materials (including matches,
lighters and cigarettes) are prohibited within 100 feet of the well and related
equipment.

Fire Safety

March 1999

You might also like