CARBON FILTER & SAND FILTER TEST RECORD


Ref No :

Form No:
SYSTEM INFORMATION
System: WATER TREATMENT

Location: B1 Floor

DEPTH FILTER(SAND FILTER)

ACTIVE CARBON FILTER

Manufacturer: CULLIGAN/USA

Manufacturer: CULLIGAN/USA

Model:

HIFLO 50- HD544

Model: HIFLO 50 - HR 604

Type:

Vertical

Automatic backwashing

Type: Vertical - Automatic backwashing

17.5 l/s

Normal flow rate :

Normal flow rate :

277.8 (GPM)

Hydraulic Control valve

4"

17.5 l/s

277.8 (GPM)

Hydraulic control valve : 4"

GBE CONTROLLER SETTING AND OPERATION


VISUAL CHECK
Item

Description

Test result

LED on GBE is green and no flashing

Yes

No

N/A

All manual valves are open

Yes

No

N/A

All hydralic pipings to control valve are not leakage

Yes

No

N/A

Auto back washing with right position on pilot valve-

Yes

No

N/A

Finished back washing, automatic transfer to servicing cycle

Yes

No

N/A

There is no filtration media leakage out drainage when backwashing.

Yes

No

N/A

GBE is put on dry and clean place , not wet and dirty place.

Yes

No

N/A

All connection points at inlet and outlet of filter tank are not leakage.

Yes

No

N/A

Yes

No

N/A

9
FIELD MEASUREMENTS
Item

Description

Design

Working pressure

Measurement

Test result

30-120 psi

Yes

No

N/A

Monday , 9:00AM

Yes

No

N/A

Depth Backwashing time

10 min.

Yes

No

N/A

Filter

Fast rinse time

3 min.

Yes

No

N/A

Slow rinse time

3 min.

Yes

No

N/A

Monday , 10:30AM

Yes

No

N/A

Backwashing on weekly

Carbon

Backwashing on weekly

Filter

Backwashing time

10 min.

Yes

No

N/A

Fast rinse time

3 min.

Yes

No

N/A

Slow rinse time

3 min.

Yes

No

N/A

Comments (nhn xt):

NSC (THANG LONG)

KUMHO

SCQC

NORAH (MEP)

Name:

Name:

Name:

Name:

Signature:

Signature:

Signature:

Signature:

Date:

Date:

Date:

Date:

TIMES SQUARE PROJECT


22-36 Nguyen Hue Street, District 1,
HCMC, Vietnam

SOFTENER TEST RECORD


SYSTEM INFORMATION
System: WATER TREATMENT

Location: B1 Floor

SOFTENER

Pipe size: 1.5"

Manufacturer: CULLIGAN/USA

Pressure : 20-100 psi

Model:

HIFLO 22- WS120

Power: 24VAC/50Hz

Type:

Vertical

Automatic regeneration

Temperature: 0-48 C

1.4 l/s

Turbidity : 5 NTU max

Normal flow rate :

22.2 (GPM)

Hydraulic Control valve with water meter.

Chlorine : 1.0 ppm max; Iron : 5.0 ppm max

GBE CONTROLLER SETTING AND OPERATION


VISUAL CHECK
Item

Description

Test result

LED on GBE is green and no flashing

Yes

No

N/A

All manual valves are open

Yes

No

N/A

All hydralic pipings to control valve are not leakage

Yes

No

N/A

Auto back washing with right position on pilot valve-

Yes

No

N/A

Auto regeneration and auto drawing brine-

Yes

No

N/A

Auto stop drawing brine and transfer to next step-

Yes

No

N/A

Finished regeneration cycle, automatic transfer to servicing cycle-

Yes

No

N/A

No resin media leakage to drainage when back washing.

Yes

No

N/A

Controller is putted at dry and clean place , not wet and dirty place.

Yes

No

N/A

FIELD MEASUREMENTS
Item

Description

Design

Regeneration by water volume setting (The water


volume is calculated basing on the Harness Value
of Raw Water)

Back wash time

Measurement

Test result
Yes

No

N/A

10 min.

Yes

No

N/A

Brine draw Rinse

60 min.

Yes

No

N/A

Fast Rinse Time

10 min.

Yes

No

N/A

Refill Time

12 min.

Yes

No

N/A

Brine used

18 kg

Yes

No

N/A

Comments (nhn xt):

NSC (THANG LONG)

KUMHO

SCQC

NORAH (MEP)

Name:

Name:

Name:

Name:

Signature:

Signature:

Signature:

Signature:

Date:

Date:

Date:

Date:

TIMES SQUARE PROJECT


22-36 Nguyen Hue Street, District 1,
HCMC, Vietnam

CHEMICAL DOSING TEST RECORD


Ref No :

Form No:
CHEMICAL DOSING SYSTEM RECORD
System: WATER TREATMENT

Location: B1 Floor

DOSING PUMP

CHEMICAL TANK

Manufacturer: MILTON ROY-LMI-US

Manufacturer: Culligan/USA

Model: P753

Volume : 500 lit

Power: 230V/1pH

Stirrer 0.08 kW

Capacity: 3.8 l/h max


Requested Capacity: 0.63 l/h correlative with Raw Water Pump to be 35 l/s
VISUAL CHECK
Item

Test result

No leakage at suction pipe and discharge pipe of dosing pump

Yes

No

N/A

Stroke and speed knob are right in position of setting

Yes

No

N/A

Chemical tank is labled clearly.

Yes

No

N/A

Chemical tank is stored right chemical name inside.

Yes

No

N/A

Dosing pump will OFF when chemical empty

Yes

No

N/A

Yes

No

N/A

6
FIELD MEASUREMENTS

Item

Description

Design

Measurement

Test result

Dosing pump
1

Stroke knob

25%

Yes

No

N/A

Speed knob

70%

Yes

No

N/A

Chemical name

Chorine,Javel, 10%

Yes

No

N/A

Operation

Start/ Stop
correlative with Raw
Water Treatment
Pumps

Yes

No

N/A

Comments (nhn xt):

NSC (THANG LONG)

KUMHO

NORAH (MEP)

SCQC

Name:

Name:

Name:

Name:

Signature:

Signature:

Signature:

Signature:

Date:

Date:

Date:

Date:

TIMES SQUARE PROJECT


22-36 Nguyen Hue Street, District 1,
HCMC, Vietnam

UV STERILIZER TEST RECORD


Ref No :

Form No:
SYSTEM RECORD
System: WATER TREATMENT

Location:

UV STERILIZER

UV STERILIZER

Manufacturer: AQUAFINE-US

Manufacturer: AQUAFINE-US

Model: HX 02 CDL (02 NOS)

Model: HX 08 EDL (01 NOS)

Power: 230V/1pH/50HZ

Power: 230V/1pH/50HZ

Normal flow rate : 23.04 (m3/h)

Normal flow rate :

162

(m3/h)

Maximum flow rate: 30

Maximum flow rate: 193

(m3/h)

(m3/h)

VISUAL CHECK
Item

Test result

No leakage at inlet and outlet pipe, manual valves are open

Yes

No

N/A

No leakage in quartz sleeve-important

Yes

No

N/A

Open power, becareful it must be 220-230V

Yes

No

N/A

Show parameters : UV level, Number of lamps are running, temperature,operation time

Yes

No

N/A

Endplate seal is not leakage.

Yes

No

N/A

LED indicator is Green and stable, not flashing.

Yes

No

N/A

There is remark "Do not ON/OFF 3 times/day" and "safety instruction"

Yes

No

N/A

FIELD MEASUREMENTS

Item

Description

Design

Measurement

Test result

UV system
1

UV intensity alarm setting

>60%

Yes

No

N/A

Temperature alarm setting

<49C

Yes

No

N/A

Number of lamp

2;8

Yes

No

N/A

Operation

Auto

Yes

No

N/A

Comments (nhn xt):

NSC (THANG LONG)

KUMHO

NORAH (MEP)

SCQC

Name:

Name:

Name:

Name:

Signature:

Signature:

Signature:

Signature:

Date:

Date:

Date:

Date:

SAIGON TIMES SQUARE

TEST REPORT

HCM , VIET NAM


Reference Document:
SAIGON TIMES SQUARE SPEC.
QCVN 01 2009/BYT

Method Statement For WATER TREATMENT installation


Method Statement For Testing & Commissioning

DOMESTIC WATER QUALITY CHECKING


System: WATER TREATMENT
Location: : B1 Floor

Item

Take minimum 1.5 litre water sample for each parameter


testing

Description

unit

Limit

Test by authority 3rd party.

Test result

Test by Pasteur
1.1

Odor

1.2

Colour

TCU

15

1.3

Turbidity

NTU

<2.0

1.4

PH value :

1.5

Amoni NH4+

ppm

<3.0

1.6

Chloride Cl-

ppm

<250

1.7

Maganese (Mn)

ppm

<0.3

1.8

Total Iron

ppm

<0.3

1.9

Nitrite

ppm

<3.0

1.10

Nitrate

ppm

<50.0

1.11

Sulphate

ppm

<250

1.12

Total hardness as CaCO3

ppm

<300

1.13

Total dissolved solid

ppm

<500

1.14

Residual Chlorine

ppm

0.3 - 0.5

1.15

Total Coliform

1.16

E-coli

6.5 - 8.5

Note:
Refer to QCVN 01 2009/BYT
Also should test the Raw Water with the above parameters, only one time in order to know about the quality of raw water.

Test by:

Witnessed by:

Witnessed by:

Name:
Date:

Name:
Date:

Name:
Date:

Bom loc
Tong luu luong

17.50 l/s
35.00 l/s
126,000.00 l/h

Nuoc thanh pham


Nong do chlorine du
Luong chlorine nguyen chat trong 1 gio
Dung dich chlorine , nong do
Khoi luong dung dich Chlorine can trong 1 gio

0.50 ppm
63,000.00
63.00
630.00
0.63

mg/l
mg/h
g/h
g/h
l/h